Addendum Plan SheetsPart-6.pdf
PDF 6 MB Posted
- Solicitation number
- 36C26322R0065
About this file
This solicitation package provides specifications for a construction project to build a new chiller plant at the Omaha VA Medical Center in Omaha, Nebraska. The project, numbered 636-18-304, will construct a new building to house two centrifugal chillers and relocate an existing temporary chiller. It will be designed for future expansion. Work includes demolition and removal of an existing metal storage shed. The estimated construction cost is between $10-20 million. The solicitation number 36C26322R0065 will be posted on February 8th. An organized site visit will be held thereafter. Bids are due on March 8th. The award date is to be determined. The contract is set aside for Service-Disabled Veteran-Owned Small Businesses. The successful bidder must provide performance and payment bonds within 10 days of award and work must be completed within 550 calendar days of the notice to proceed.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26322R0065 0004.docx | DOCX document | |
| 36C26322R0065 0003.docx | DOCX document | |
| Addendum Plan SheetsPart-4.pdf | ||
| Addendum specs 040822.pdf | ||
| Addendum Plan SheetsPart-2.pdf | ||
| Addendum Plan SheetsPart-1.pdf | ||
| Addendum 040822.pdf | ||
| Addendum Plan SheetsPart-7.pdf | ||
| Addendum Plan SheetsPart-3.pdf | ||
| Addendum Plan SheetsPart-8.pdf | ||
| Addendum Plan SheetsPart-5.pdf | ||
| Geotechnical Report Terracon no 05215161R01.pdf | ||
| HMS VA Omaha 103119.pdf | ||
| S02_Specs - Volume 1 revised.pdf | ||
| S02_ATTACH - Specs - Volume 2 (1376 pages).pdf | ||
| Omaha VA Chiller photos.pdf | ||
| S02_ATTACH - Drawings (132 pages).pdf | ||
| 36C26322R0065 0002.docx | DOCX document | |
| 36C26322R0065 Final.docx | DOCX document | |
| Site Vist Sign In sheet.pdf | ||
| 36C26322R0065 0001.docx | DOCX document | |
| 36C26322R0065.docx | DOCX document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A D A D D 1
WALL SECTIONS
AS-411
JFB, IAR,
JY
RM, IAR
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans
Affairs
PhasePROJECT MANAGEMENT STAMPCONSULTANT
FULLY SPRINKLERED
DESIGN
San Antonio, Texas 78217
ARCHITECTURE
8718 BOTTS LANE
Tel: (210) 881-9714
HFS COMPANY
ENGINEERING
Fax: (210) 881-6808 jbianco@hfscompany.com 11/30/21
CONSTRUCTION BID
DOCUMENTS
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
4101 WOOLWORTH AVE.
OMAHA, NE 68105
11/30/2021
636-18-304
ETS
T
TA
GE
S
R I
E T EX
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJO
SE
P
H
7 6 22 1
Revisions: Date:
WALL SECTION
SCALE: 1/2" = 1'-0"
WALL SECTION
SCALE: 1/2" = 1'-0"
WALL SECTION
SCALE: 1/2" = 1'-0"
WALL SECTION
SCALE: 1/2" = 1'-0"
WALL SECTION
SCALE: 1/2" = 1'-0"
WALL SECTION
SCALE: 1/2" = 1'-0"
EAST ELEVATION - CHILLER PLANT
SCALE: 1/4" = 1'-0"
EAST ELEVATION - CORRIODR/STAIRS
SCALE: 1/4" = 1'-0"
SOUTH ELEVATION - STAFF TOILET
SCALE: 1/4" = 1'-0"
ENLARGED FLOOR PLAN - STAFF TOILET
SCALE: 1/4" = 1'-0"
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans
Affairs
PhasePROJECT MANAGEMENT STAMPCONSULTANT
FULLY SPRINKLERED
DESIGN
San Antonio, Texas 78217
ARCHITECTURE
8718 BOTTS LANE
Tel: (210) 881-9714
HFS COMPANY
ENGINEERING
Fax: (210) 881-6808 jbianco@hfscompany.com 11/30/21
CONSTRUCTION BID
DOCUMENTS
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
4101 WOOLWORTH AVE.
OMAHA, NE 68105
11/30/2021
636-18-304
ETS
T
TA
GE
S
R I
E T EX
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJO
SE
P
H
7 6 22 1
Revisions: Date:
AS-510
INTERIOR ELEVATIONS
RACJFB, IAR,
JY
SECTION DETAIL
SCALE: 3" = 1'-0"
SECTION DETAIL
SCALE: 3" = 1'-0"
2 1
2 1
SECTION DETAIL
SCALE: 3" = 1'-0"
SECTION DETAIL
SCALE: 3" = 1'-0"
SECTION DETAIL
SCALE: 3" = 1'-0"
SECTION DETAIL
SCALE: 3" = 1'-0"
A
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans
Affairs
PhasePROJECT MANAGEMENT STAMPCONSULTANT
FULLY SPRINKLERED
DESIGN
San Antonio, Texas 78217
ARCHITECTURE
8718 BOTTS LANE
Tel: (210) 881-9714
HFS COMPANY
ENGINEERING
Fax: (210) 881-6808 jbianco@hfscompany.com 11/30/21
CONSTRUCTION BID
DOCUMENTS
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
4101 WOOLWORTH AVE.
OMAHA, NE 68105
11/30/2021
636-18-304
ETS
T
TA
GE
S
R I
E T EX
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJO
S
EP
H
7 6 22 1
Revisions: Date:
AS-600
SECTION DETAILS
JFB, IAR,
DJ, IAR
D
SECTION DETAIL
SCALE: 3' = 1'-0"
SECTION DETAIL
SCALE: 3' = 1'-0"
D
SECTION DETAIL
SCALE: 3' = 1'-0"
SECTION DETAIL
SCALE: 3' = 1'-0"
SECTION DETAIL
SCALE: 3' = 1'-0"
D
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans
Affairs
PhasePROJECT MANAGEMENT STAMPCONSULTANT
FULLY SPRINKLERED
DESIGN
San Antonio, Texas 78217
ARCHITECTURE
8718 BOTTS LANE
Tel: (210) 881-9714
HFS COMPANY
ENGINEERING
Fax: (210) 881-6808 jbianco@hfscompany.com 11/30/21
CONSTRUCTION BID
DOCUMENTS
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
4101 WOOLWORTH AVE.
OMAHA, NE 68105
11/30/2021
636-18-304
ETS
T
TA
GE
S
R I
E T EX
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJO
S
EP
H
7 6 22 1
Revisions: Date:
AS-601
SECTION DETAILS
JFB, IAR,
DJ, IAR
B I M
A
L M
V A
H
R
E N
O V
A T
E
O
R A
L M
V A
H R
E N
O V
A T
E O
R r v t
P
M
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans
Affairs
PhasePROJECT MANAGEMENT STAMPCONSULTANT
FULLY SPRINKLERED
DESIGN
San Antonio, Texas 78217
ARCHITECTURE
8718 BOTTS LANE
Tel: (210) 881-9714
HFS COMPANY
ENGINEERING
Fax: (210) 881-6808 jbianco@hfscompany.com 11/30/21
CONSTRUCTION BID
DOCUMENTS
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
4101 WOOLWORTH AVE.
OMAHA, NE 68105
11/30/2021
636-18-304
ETS
T
TA
GE
S
R I
E T EX
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJO
S
EP
H
7 6 22 1
Revisions: Date:
AS-700
SCHEDULES, DOOR TYPES, FRAME
TYPES & LOUVER TYPES
JFB, IAR,
JY
IAR, RAC
ROOM NAME
DOOR
NUMBER
DOOR FRAME
HARDWARE
GROUP
LABEL
RATING REMARKSWIDTH HEIGHT MATERIAL FINISH TYPE MATERIAL FINISH TYPE HEAD
DOOR SCHEDULE
JAMB SILL
DETAILS
ABBREVIATIONS: REMARKS:
GROUND LEVEL
ROOM NAME
DOOR
NUMBER
DOOR FRAME
HARDWARE
GROUP
LABEL
RATING REMARKSWIDTH HEIGHT MATERIAL FINISH TYPE MATERIAL FINISH TYPE HEAD JAMB SILL
DETAILS
MEZZANINE LEVEL
TYPE WIDTH HEIGHT GLAZING FRAME COMMENTSU-VALUE SHGC
WINDOW SCHEDULE
ABBREVIATIONS: REMARKS:
TYPE WIDTH HEIGHT MATERIAL FINISH
LOUVER SCHEDULE
ABBREVIATIONS: REMARKS:
WALL
RATING REMARKSHEAD JAMB SILL
DETAILS
WINDOW HEAD
SCALE: 3" = 1'-0"
WINDOW JAMB
SCALE: 3" = 1'-0"
WINDOW SILL
SCALE: 3" = 1'-0"
LOUVER HEAD
SCALE: 3" = 1'-0"
LOUVER JAMB
SCALE: 3" = 1'-0"
LOUVER SILL
SCALE: 3" = 1'-0"
A
DOOR SILL
SCALE: 3" = 1'-0"
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans
Affairs
PhasePROJECT MANAGEMENT STAMPCONSULTANT
FULLY SPRINKLERED
DESIGN
San Antonio, Texas 78217
ARCHITECTURE
8718 BOTTS LANE
Tel: (210) 881-9714
HFS COMPANY
ENGINEERING
Fax: (210) 881-6808 jbianco@hfscompany.com 11/30/21
CONSTRUCTION BID
DOCUMENTS
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
4101 WOOLWORTH AVE.
OMAHA, NE 68105
11/30/2021
636-18-304
ETS
T
TA
GE
S
R I
E T EX
FO
T
CE
TI
H
AS
DER CRA
F. BIAN
C
OJO
S
EP
H
7 6 22 1
Revisions: Date:
AS-711
WINDOW & LOUVER DETAILS
JFB, IAR,
IAR, RC
FUTURE EXPANSION
3"S-DN
3/4"CW-DN
P-802
3" VTR
3/4"CW-UP
XXX-11
CHILLER PLANT
3431 SQFT
3" VTR
3" VTR3" VTR
TO P-815 ON ROOF
XXX-XX
MEZZANINE
803 SQFT
AHU
S
3" V
3" V
A B C D
3"V-UP
4"CW-UP
3" FD-E
3" FD-S
HX
HWP
HWP
HX
ET
"C
W
1 1/2"CW
1"CW
AHU
3" FD-E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\r c o o p e r\ D o c u m e n ts
\2
-1
P
L U
M B v ry a n .c o o p e rX
T C
R S
.r v t
/5
/2
:1
:2
P M
XX-P-102
PLUMBING MEZZANINE PLAN
JES RLC
1/8" = 1'-0"
PLUMBING NEW WORK - MEZZANINE LEVEL
TRUE
NORTHPLAN
NORTH
A. REFER TO 0-P-000 FOR PLUMBING SYMBOLS AND
ABBREVIATIONS.
GENERAL SHEET NOTES
1. SEE MECHANICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
KEYED NOTES#
Revisions: Date:
ADDENDUM NO. 01 04/07/2022 04/07/2022
CWR
CWS
CWR
CWS
CWR
CWS
CWR
CWS
FS
FS
FS
FS
FS
FS
CWR
CWS
CWS
CWS
CWS
CWR
CWR
CWR
CWM
NC
BYPASS
P-16
P-17
P-14
P-15
P-6
P-7
300 GPM
120 GPM
90 GPM
FROM RESEARCH
8" FOR TEMP
CHILLER
FROM CC-3
FROM CC-1
TO CC-1
TO
RESEARCH
TO CC-3
CC-2
NO
AMBULATORY CARE
TO INDUCTION UNITS ON
FLRS 1-4
TO INDUCTION UNITS ON
FLRS 5-11
NO
NO
CV-7CV-6
FILL
VALVE
TO
FLOOR
DRAIN
DRAIN
VALVE
CWS
CWR
16" CWR
CWR
CWR
CWR
14" CWR
CWS
CWS
CWS
C W
S
3" NPCW DOWNSTREAM OF METER &
BACKFLOW PREVENTERS
ALL EXISTING PUMPS TO
REMAIN
3" DCW
24" CR
C W
R
C W
S
CH-X
CH-1 BACKUP
EXISTING TRANE
"TEMP" CHILLER
1250 TON
OUTDOOR
MODULAR
CHILLER
(ETR)
RELOCATED CHILLER
ENCLOSURE
14" CS
14" CR
ET
WCC
WCC
16" CWS
20" CWR
20" CWS
24" CS
24" CS
14" CR
CT
CT
14" CS
16" CR
16" CR
CTP
CTP
CTP
CWP
CWP
CWP
24" CS
C R
12" CWR
ROUTE DOWN
TO CAMPUS
LOOP24" CWR
FUTURE
WCC-3
FUTURE
WCC-4
VALVE AND CAP FOR
FUTURE CHILLER INSTALL
(TYP)
2" NPW
3" NPW
2" NPW
12" CWS
20" DECOUPLER
ADS-1
ADS-1
BYPASS
20" CWS/CWR24" CWS/CWR
24" CWS
PIPE TRANSITION BETWEEN
NEW CHILLER PLANT AND
UNDERGROUND
M
14" CWS/R TO
TEMP ACC'S
CWP
FUTURE
B17 BYPASS
DP
18" EQUALIZER
LINE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:5 :4
P
M
0-M-201
MECHANICAL FLOW DIAGRAMS - CHILLED
WATER MODIFICATIONS
JES MDS
NOT TO SCALE
MECHANICAL ROOM PIPING SCHEMATIC -
NEW
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
04/07/2022
ABCD
CT
CT
COOLING TOWER SUPPORT
STRUCTURE. REFER TO
STRUCTURAL PLANS.
24" CS 24" CR
C S
24" CS 24" CR
4" NPWR
4" NPWR4" NPWS
WCC
WCC
CTF
CTF
4" NPWS
4" NPWS
12" CS
10" CS
16" CR 16" CR
16" CR
16" CR
C W
R
C W
S
14" CS
14" CS
14" CR
4" NPWR
4" NPWS4" NPWS
18" CR
18" CR
16" CR
14" CS 14" CS
14" CS14" CS
6" CWR
6" CWS
20" CR
18" CR
CTP
CWP
8" CWR
6" CWR
E-2
E-2
ET
SEE SCHEDULES ON SHEET
0-M-601 FOR MAXIMUM UNIT
DIMENSIONS AND
WEIGHTS. COORDINATE
WITH STRUCTURAL
SUPPORTS AND ACCESS
PLATFORMS.
12" CWR
12" CWS
12" CWR
12" CWS
14" CR
24" CR
20" CR
14" CR
2 1
AHU
30x74 SA
34x70 RA
54x96 OA
LU-1
16850
26x50 SA
A
IR
M
IX
IN
G
S
E C
T
IO
N
C O
O L
IN
G C
O
IL
C
T
IO
N
H E
A T
IN
G
C
C T
IO
N
F A
N S
E C
T
IO
N
OA
ELECTRICAL ROOM BELOW
ACCESS
DOOR
90x106 OA SHEET
METAL PLENUM
ACCESS DOOR
(TYP.4)
STRUCTURAL BEAM
MANUFACTURER PROVIDED
MINIMUM OUTSIDE AIR AND
ECONOMIZER DAMPERS.
SEE 1/0-M-703 FOR RELATED
INFORMATION.
2 1
STRUCTURAL BEAM
AHU
LU-2
A
IR
M
IX
G
C
T
IO
N
C O
O L
IN
G C
C
T
IO
N
H E
A T
IN
G
C
C T
IO
N
F A
N S
E C
T
IO
N
OA
ELECTRICAL ROOM BELOW
ACCESS
DOOR
50x60 OA SHEET
METAL PLENUM
ACCESS DOOR
(TYP.4)
MANUFACTURER PROVIDED
MINIMUM OUTSIDE AIR AND
ECONOMIZER DAMPERS.
SEE 1/0-M-703 FOR RELATED
INFORMATION.
16x45 OA 18x46 RA14x36 SA
14x36 SA24x12 SA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:5 :4
P
M
0-M-301
MECHANICAL SECTIONS
JES MDS
1/4" = 1'-0"
COOLING TOWERS
1/4" = 1'-0"
MEZZANINE AHU-1
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
1/4" = 1'-0"
MEZZANINE AHU-2
I v
ELECTRICAL EQUIPMENT
OVERHEAD DOOR
CONTROLS
14" CRREMOVE ALL EXISTING
PUMPS AND SPECIALTIES
FROM EXISTING
OUTDOOR CHILLER
ENCLOSURE. PUMP
LOCATION SHOW IS
APPROXIMATE AND FOR
REFERNECE ONLY.
CONFIRM FINAL CONNECTION
WITH MANUFACTURER
C S
C R
C S
C R
C W
S
C W
R
12" CWR
12" CWS
14" CS
REMOVE ALL EXISTING
PUMPS AND SPECIALTIES
FROM EXISTING
OUTDOOR CHILLER
ENCLOSURE. PUMP
LOCATION SHOW IS
APPROXIMATE AND FOR
REFERNECE ONLY.
PROVIDE FLEXIBLE PIPE
CONNECTION AT
OUTDOOR CHILLER
ENCLOSURE.
(TYP 4)
3' MAN DOOR
3' MAN DOOR
COORDINATE
RELOCATION OF CHILLER
WITH EXISTING
EQUIPMENT. EXISTING
REFRIGERANT AND OIL
TO BE EVACUATED PRIOR
TO RELOCATION AND
REFILLED UPON NEW
LOCATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:5 :5
P
M
0-M-401
MECHANICAL ENLARGED PLAN - EXISTING
CHILLER
JES RLC
1/2" = 1'-0"
MECHANICAL ENLARGED DESIGN PLAN -
EXISTING CHILLER
TRUE NORTH
Revisions: Date:
ROOF INSULATION
FASTEN ANGLE IRON
SECURELY TO DUCT
AND ROOF STRUCTURE
SECURE CURB TO
ROOF WITH SCREWS,
PINS, OR BOLTS
EXTEND DUCTWORK
OVER TOP OF CURB,
SECURE DUCTWORK
TO CURB NAILER
EXHAUST FAN
WITH BIRDSCREEN
SECURE EXHAUST FAN TO
ROOF CURB
PREFABRICATED
INSULATED CURB WITH
TREATED WOOD NAILER.
COUNTER BALANCED BACKDRAFT
(UNLESS NOTED OTHERWISE)
DAMPER, SECURE TO DUCT FROM
ABOVE TO ALLOW SERVICE OR
REMOVAL OF DAMPER FROM ROOF
ROOF DECK REFER TO
ARCHITECTURAL DRAWINGS
EXHAUST DUCT UP THROUGH
ROOF. SEE PLANS FOR SIZE
AND LOCATION.
VANE
VANE
R SHALL
EQUAL OR
BE
GREATER
THAN W.
R SHALL
EQUAL OR
BE
GREATER
THAN
1/3W.
R SHALL
EQUAL OR
BE
GREATER
THAN
1/6W.
SHORT RADIUS ELBOW
WITH TWO VANES
SHORT RADIUS ELBOW
WITH ONE VANE
STANDARD RADIUS OR
LONG RADIUS ELBOW
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL
SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED, SUPPORTED
AND FASTENED AS RECOMMENDED BY SMACNA.
NOTE:
1.
2.
W
R
1/6W
/3
W
1/2W
W
/3
W
2/3W
R
R
W
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM
SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE VANE
TYPE.
NOTE:
1.
2.
3.
4.
W1
W
M
AX.
M A
X
E Q
U
IP
M E
N T
M
AX.
M A
X
M A
X
M A
X
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEWTYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
AIR
FLOW
AIR
FLOW
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
15°
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR
FLOW AIR
FLOW
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" [100mm]
MIN.
BRANCH DUCT
VD
W
FROM STRUCTURE
SAME AS DIFFUSER
INLET: 5'-0" MAX
FLEXIBLE DUCT SIZE
LENGTH.
12"
CEILING
SUPPORT SADDLE
VOLUME DAMPER W/
LOCKING QUADSADDLE
SHEET METAL
CONICAL OUTLET
BRANCH DUCT
FOR CHANGE OF
DIRECTION GREATER
USE RIGID ELBOWS
THAN 45°
[300mm]
SEE SPECIFICATIONS FOR CLAMPS
AND SEALANT (TYP.)
THERMAL INSULATION
SEE SPECIFICATIONS
TYPICAL
DIFFUSER OR
REGISTER IN
LAY-IN CLG.
NOTE:
1. THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED
FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.
D
D
NOTE:
1.
2.
3.
SEE EXPANSION TANK SYSTEM SCHEDULE FOR COMPONENT SIZES.
FOR HOT WATER SYSTEMS 2" [50mm] AND SMALLER AND CHILLED WATER SYSTEMS
USE IN-LINE AIR PURGER IN LIEU OF AIR SEPARATOR.
SET PRESSURE REDUCING VALVE SO PRESSURE AT HIGHEST POINT IN SYSTEM
HAS A MINIMUM OF 4 PSIG [28kPa].
MV CONNECTOR PIPE.
FLOOR MOUNTING BASE RING
WITH DRAIN ACCESS OPENING
SHOWN. ANGLE IRON LEGS MAY
BE USED AS AN OPTION.
COLD WATER FILL LINE.
SEE EXPANSION TANK
SCHEDULE FOR SIZE
RUN DRAIN
LINE TO
NEAREST FD
6" [150mm]
HOUSEKEEPING
PAD
AIR CHARGING
SHRAEDER VALVE
RUN DRAIN LINE TO
NEAREST FD UNLESS
INDICATED OTHERWISE
AIR
SEPARATOR
SEE NOTES 3
& 4
BUTTERFLY
OR BALL
ISOLATION
VALVE
BLADDER
EXPANSION
TANK
FROM SYSTEM
DRAIN
NC
DRAIN
HANGER
RODS (TYP)PI
TO PUMP
SUCTION
AUTO. AIR VENT TO DRAIN
REDUCED PRESSURE BACKFLOW
PREVENTER
DIRECT BURY PIPING. INSULATE
PER SPECIFICATIONS WHERE
REQUIRED.
M
IN
GRANULAR
BACKFILL OR TYPE
2 BASE MATERIAL
MIN
UNDERGROUND MARKING
TAPE 12" (MAX) BELOW GRADE
MINMIN
UNDISTURBED SOIL
AGGREGATE EMBEDMENT PER
SPECIFICATIONS. PARTICLE
SIZE SHALL NOT EXCEED 1-1/2"
FOR PIPE SIZES 18"+
CONCRETE, ASPHALT,
OR TOPSOIL.
CHWS
20"± 6"
6" 6"
CHWS
20"±
FINISHED
GRADE
WHERE TRENCH BOTTOM
CONTAINS FINE GRANULAR
MATERIAL, COMPACT VIA
MANUAL OR MECHANICAL
(PREFERRED) TAMPER
NOTE:
BOTTOM OF UNIT
BASE RAIL
PIPE FULL SIZE OF
AIR HANDLING UNIT
DRAIN CONNECTION
4" HOUSEKEEPING PAD OR ROOF CURB
REMOVABLE CAP
REMOVABLE CAP
FLOW
DRAW-THRU: 1/2 OF NOTE 2 DIMENSION BUT NOT LESS THAN 2"
BLOW-THRU: SCHEDULED E.S.P. THEN ADD 1".
DRAW-THRU: SUBTRACT SCHEDULED E.S.P. FROM T.S.P. THEN ADD
1". BLOW-THRU: 1"
LOCATE TRAPS SO AS TO BE ACCESSIBLE FOR CLEANING.
ROUTE TO NEAREST SANITARY (FLOOR) DRAIN OR ROOF DRAIN.
SLOPE AT 1/4" PER FOOT.
5 CONTRACTOR SHALL INCREASE BASE RAIL HEIGHT AND/OR
HOUSEKEEPING PAD HEIGHT IF NECESSARY TO ACHEIVE
REQUIRED TRAP DIMENSION.
4" STRUCTURAL
SUPPLEMENTAL
STEEL SUPPORT
NOTE:
1.
WALL CONSTRUCTION SYSTEM.
REFER TO ARCHITECTURAL
DRAWINGS.
EXHAUST DUCT.
SEE PLAN FOR SIZE.
BIRDSCREEN
REFER TO ARCHITECTURAL DRAWINGS FOR WALL PENETRATION DETAILS.
COORDINATE ALL PENETRATIONS WITH GENERAL CONTRACTOR.
MOUNTING BOLTS
SIDEWALL MOUNTED
CENTRIFUGAL
UPBLAST EXHAUST FAN AS
SCHEDULED
CONNECT DUCTWORK TO FAN'S FRAME
HOUSING USING FLANGE AND BOLTED
CONNECTION PER FAN
MANUFACTURER'S
INSTRUCTIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:5 :5
P
M
0-M-501
MECHANICAL DETAILS
JES MDS
NOT TO SCALE
DOWNBLAST EXHAUST FAN
NOT TO SCALE
DUCTWORK RADIUS ELBOWS
NOT TO SCALE
DUCTWORK SQUARE VANE ELBOWS
NOT TO SCALE
DUCTWORK TRANSITIONS (WITH
EQUIPMENT MOUNTED IN DUCT)
NOT TO SCALE
EXHAUST OR RETURN BRANCH
DUCTWORK
NOT TO SCALE
FLEXIBLE AIR DUCT CONNECTOR
NOT TO SCALE
FLOOR MOUNTED EXPANSION TANK -
PIPING CONNECTIONS
NTS
PPRCT PLASTIC PIPING
DIRECT BURIAL DETAIL
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
NTS
CONDENSATE DRAIN TRAP
NOT TO SCALE
SIDEWALL MOUNTED UPBLAST EXHAUST
FAN DETAIL
TO DRAIN
MV
MANUAL
AIR VENT
TO BUILDING
LOAD
INVERTED BUCKET
TRAP ASSEMBLY
WELDED
TEE
12"[300 MM]
6"[150 MM]
SCHEDULE 80 STEEL PIPE
1" GATE VALVE
CONDENSATE
STEAM PIPE
A SIZE, TRAP DISCHARGE LINE 1/2" [15mm] 3/4" [20mm]
1-1/4" [32mm]1" [25mm]SIZE, 45° WELDING NIPPLEB
C 7" [175mm] 7" [175mm]
16-1/2" [415mm]16-1/2" [415mm]
2" [50mm]2" [50mm]
LENGTH OF PERFORATED PIPED
E
RETURN MAIN SIZE UP TO 1-1/2" [40mm] 2" [50mm] 3" [75mm] & OVER
SAME SIZE2-1/2" [65mm]EXPANDED RETURN MAIN SIZE
EXPANDED RETURN MAIN
SECTION A-A
WELD CAP
EXPANDED RETURN MAIN CAP
REDUCER
INCREASER
A
B
A
A
FLOW
SECTION-EXPANDED RETURN MAIN
PERFORATED TUBE 1"x1/8" [25x6mm]
THICK GUIDE FINS WELDED TO
PERFORATED TUBE
PERFORATED
TUBE
RETURN
MAIN
LENGTH OF EXPANDED MAIN OF
FOLLOWING PERFORATED PIPE
LENGTH OF EXPANDED MAIN AHEAD
OF TRAP DISCHARGE PIPE
EDC
NOTES:
1.
2.
3.
1/2" [15mm] PERFORATED TUBE SHALL HAVE 40 - 1/8" [16mm] DIAMETER HOLES
SPACED 1-1/2" [40mm] O.C. IN 4 ROWS.
3/4" [20mm] PERFORATED TUBE SHALL HAVE 78 - 1/8" [6mm] DIAMTER HOLES
SPACED 1-1/2" [40mm] O.C. IN 6 ROWS.
HOLES IN TUBE SHALL BE SPACED EQUALLY AROUND PERIMETER.
BLOWDOWN
ELEVATION
1/2" [15mm] STEEL PIPE OR
STEEL TUBING TO SENSORS
DIFFERENTIAL PRESSURE
TRANSMITTER (FLOW, LEVEL)
PT
INSTALLATION OF SENSORS AND TRANSMITTERS SHALL CONFORM TO
RECOMMENDATIONS OF MANUFACTURERS OF TRANSMITTERS.
NOTES:
1.
BUILDING INCOMING
MAIN STEAM
TO METERING
SYSTEM
SHUTOFF VALVE
DIFFERENTIAL PRESSURE (DP) CEL
STEAM FLOW MEASUREMENT
FLOW METER
INTERFACE
WITH BACNET
SYSTEM
TEMPERATURE
TRANSMITTER
PRESSURE
TRANSMITTER
PT
TT
MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY METER MANUFACTURES
NOTE:
1.
NOTE:
1.
2.
3.
4.
SEE FLOOR PLANS FOR PIPE SIZES.
SEE EQUIPMENT SCHEDULES FOR VALVE DATA AND PIPE SIZES D1 AND D2. INSTALL
VALVES AS RECOMMENDED BY MANUFACTURER.
MAKE BYPASS VALVE DISCHARGE PIPE THE SAME SIZE AS D2 FOR THE LARGEST PRV.
PROVIDE NECESSARY UNIONS FOR THE REMOVAL OF VALVE WITH SCREWED
CONNECTIONS.
SIPHON (TYP.)
VENT TO ATMOSPHERE
PILOT CONTROL LINE
REDUCER (TYP.)
IF REQUIRED.
NOTE 1
D1
N.C.
D2
D2
NOTE 1
NOTE 3
INVERTER
BUCKET TRAP
ASSEMBLY
TYP.
PSV
V
20 D2 MIN.
4 D2 MIN.
10 D1 MIN.
D
PROVIDE UNION UNLESS SAFETY
VALVE HAS FLANGED OUTLET
SAFETY VALVE
OPEN DRAIN (NOTE 3)
CONNECTION TO PRESSURE
VESSEL OR PIPE
VENT PIPE THROUGH ROOF
SUPPORT AS INDICATED ON
DWGS. (NOTES 1, 2)
PIPE THREADED INTO ELBOW
(SAME SIZE AS ELBOW)
DRIP PAN ELBOW
(SECTIONAL VIEW)
3/4" [20mm] DRAIN TO
FLOOR DRAIN OR OPEN
SIGHT DRAIN (NOTE 4)
[2 m m
[610mm]
[76mm]
ELEVATION
FLEXIBLE
CONNECTOR
NOTES:
1.
2.
3.
4.
UNLESS OTHERWISE SHOWN ON THE DRAWINGS, SIZE THE VENT PIPE SO THAT STEAM IS NOT
BLOWN OUT AT THE VENT PIPE ENTRANCE. UTILIZE THE CALCULATION METHOD CONTAINED IN
ANSI B31.1. POWER PIPING CODE, APPENDIX II.
VENT PIPE SHALL TERMINATE 6' [1829mm] MIN. ABOVE FINISHED ROOF.
DISCHARGE OF DRAIN MUST BE DIRECTED AWAY FROM PLATFORMS OR OTHER AREAS WHICH
PERSONNEL MAY OCCUPY.
DO NOT CONNECT ANY OTHER DRAIN TO THE DRIP PAN ELBOW DRAIN PIPE.
3"
24" MAX.
M
IN
STEAM TRAP ASSEMBLY
STEAM LINE DRIP POCKET
STEAM LINE
(TYPICAL)
3/4" [20mm] DRAIN (ALTERNATE
LOCATIONS) (TYPICAL)
FROM DRIP
CONNECTION
CAP (TYPICAL)
3/4" [20mm] MIN.
[1 m m
M
IN
DRIP LEG (TYP.)
[3 m m
M
IN
NOTE:
DRIP POCKET PIPE SIZE SAME
AS STEAM MAIN UNLESS
OTHERWISE NOTED.
3/8" [10mm] TEST
CONNECTION
DRIP
RETURN
PIPE T0 STEAM
TRAP (TYPICAL)
[1 m m
M
IN
[3 m m
M
1" V
1" FILL LINE
EXHAUST LINE
RESERVOIR
INLET LIFT
CHECK VALVE
1" VENT TO
ATMOSPHERE
LPR FROM
SYSTEM
UNION
(TYP.)
TRAP
STEAM
3/4" HPS
TO FD
1/2"
3/4"
1/2"
TO FD
OUTLET LIFT
CHECK VALVE
RELIEF VALVE
SET @ 125 PSI
PUMP
DISCHARGE
PC
SHUT-OFF VALVE
(TYP), SEE SPEC
FOR TYPE
T
STRAINER WITH
BLOWDOWN VALVE,
NIPPLE, AND CAP
PRESSURE
GAGE WITH
COCK
SPCP-1
GAGE GLASS
SPCP-2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:5 :5
P
M
0-M-502
MECHANICAL DETAILS
JES MDS
NOT TO SCALE
END OF STEAM LINE DRIP TRAP
NOT TO SCALE
HIGH AND MEDIUM PRESSURE STEAM
TRAP DISCHARGE INTO PUMPED
CONDENSATE RETURN LINE
NOT TO SCALE
STEAM FLOW METER PRIMARY ELEMENT
AND FLOW TRANSMITTER INSTALLATION
NOT TO SCALE
STEAM METER
NOT TO SCALE
STEAM PRESSURE REDUCING STATION -
DOUBLE VALVE
NOT TO SCALE
STEAM SAFETY VALVE
NOT TO SCALE
STEAM TRAP ASSEMBLY AND STEAM LINE
DRIP POCKET
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
NOT TO SCALE
STEAM POWERED CONDENSATE PUMP
(SPCP) DETAIL
P & T TEST PLUG; INSTALL AT
SAME ELEVATION
PIPING SHOWN IS TYPICAL FOR EACH CELL.
ALL OUTDOOR PIPING SHALL BE HEAT TRACED
AND INSULATED PERS ECTION 230700, EXCEPT
OMIT FOR OVERFLOW LINE AND DRAIN
DOWNSTREAM OF SHUTOFF VALVE. OMIT
INSULATION ON BURIED PIPE. OMIT HEAT
TRACE ON PIPE BURIED BELOW FROST LINE.
CR MAIN
SEE PLANS
SLOPE 3% DOWN
CS MAIN
SEE PLANS
TO DRAIN D
SHUT-OFF VALVE
(TYP), SEE SPEC
FOR TYPE
CS
CR
DRAIN
UNION (TYP.)
3" OVERFLOW
NOTE:
EQUALIZATION PIPING OR FLUME TO ADJACENT
CELL TO INTERCONNECT COLD WATER BASINS.
SIZE PER MANUFACTURERS RECOMMENDATIONS.
FLEXIBLE CONNECTION (TYP).
REFER TO SPECIFICATIONS
1/2" [15mm]
PUMP
FLOOR
PRESSURE GAGE
1/2" [15mm]
DRAIN
OPTIONAL STRAINER
FIRST 3 HANGERS FOR EACH PIPE AND
BRANCH SHALL BE SPRING & NEOPRENE
TYPE. TYPE "H" FOR 4" [100mm] DIA. PIPE
& SMALLER. TYPE "H-P" FOR 5" [125mm]
DIA. PIPE & LARGER.
RIGID PIPE
HANGER
INSTALL HANGER AS CLOSE TO
PIPE ELBOW AS POSSIBLE
(TYPICAL)
MECHANICAL COUPLING
(6" MIN.[150 MM] SPACING)
(TYPICAL)
SUCTION DIFFUSER
WITH BUILT IN STRAINER.
OPTIONAL: LONG RADIUS
ELBOW AND INLET
STRAINER WITH 3XDIAM
STRAIGHT INLET TO PUMP
1" [25mm] MIN. DIA.
PIPE STAND
CONCRETE BASE
(SEE DETAIL)
BUTTERFLY OR BALL
SHUT OFF VALVE, TYP.
RIGID PIPE
HANGER
NOTES:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION
FLANGED
CONNECTION
1/4"x1 1/4"
[6.4x31.4mm]
IRON PIPE
CLAMP
1/4"x1 1/4"
[6.4x31.4mm] IRON
PIPE STRAP
[1 m m
HIGH DENSITY
POLYETHYLENE (HDPE)
SLEEVE WITH INTEGRAL
HOLLOW MOLDED WATER
STOP RING 4" [100mm]
LARGER THAN OUTSIDE
DIAMETER OF PIPE
5/8" [16mm]Ø ROD
PIPE SLEEVE
WATER STOP
EXTERIOR WALL
PIPEPIPE SLEEVE
WHERE SPECIFIED
FIRE-STOPPING
MATERIAL
BOLT
RISER
CLAMP
PIPE SLEEVE
WHERE
SPECIFIED
RISER
CLAMP
INSULATION
ELEVATION
RISER
PLAN
RISER CLAMP.
BOTTOM CLAMP
REQUIRED AT
ANCHOR POINTS
ONLY.
PROVIDE ANCHORS ONLY
WHERE SHOWN ON
DRAWINGS.
EXTEND SLEEVE ABOVE
FLOOR WHERE SPECIFIED.
BOLT
(TYPICAL)
FLOOR
SLAB
NOTES:
1.
2.
NOTE:
1. MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY METER MANUFACTURES
TE
TEMPERATURE ELEMENT
INTERFACE WITH
METERING
STATION
TEFE
SUPPLY
OUTLET
FLOW ELEMENT
BACNET
INTERFACE
EXTERIOR WALL
ROOF
GROUND
SUPPORT VENT PIPING
PER SPECIFICATIONS
DRIP LEG LENGTH
L (IN.) = (294.1) / (INSIDE Ø (IN.))²
REMOVABLE CAP TO BE
INSTALLED UPSTREAM
OF FLEX CONNECTION
CHILLER RUPTURE DISK
FLEX CONNECTION
PER SPECIFICATIONS
VENT LINE FROM PURGE
DISCHARGE
MINIMUM DISTANCES:
15' ABOVE GROUND LEVEL
20' FROM ALL BUILDING OPENINGS
1/4 IN. FL X 1/4 IN. NPT
THREADED END FOR
HOSE CONNECTION
36" MIN
TERMINATE PIPING WITH 3/16" MESH
BRASS OR STAINLESS HARDWARE
CLOTH
3/4" HOSE-END
DRAIN VALVE W/CAP
(TYP)
SHUT-OFF VALVE (TYP),
SEE SPEC FOR TYPE
PRESSURE
GAUGE (TYP)
TO FLOOR DRAIN
SAFETY RELIEF VALVE
AUTOMATIC AIR VENT
THERMOMETER (TYP)
GAUGE COCK (TYP)
FLEXIBLE CONNECTOR (TYP),
SEE SPECIFICATIONS
CONDENSATION TRAP
A
RV
CR
ROOF
CWR
CS
CWS
NOTES:
PROVIDE AIR VENTS AND DRAIN
VALVES AT ALL SUCH POINTS
PROVIDED BY CHILLER
MANUFACTURER, BOTH WATER BOXES,
BOTH ENDS, TYPICAL.
ALTERNATE LOCATION OF
CWS (3-PASS CHILLERS)
PROVIDE OFFSET IN PIPING
TO CLEAR WATER BOX (TYP)
SEE
PLANS
FOR PIPE
SIZE AND
ROUTE
PURGE VENT
(BY CHILLER MFR)
CALIBRATED BALANCING
VALVE
1.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:5 :5
P
M
0-M-503
MECHANICAL DETAILS
JES MDS
NOT TO SCALE
COOLING TOWER WITH BOTTOM SUMP
OUTLET AND INTERNAL PIPING DETAIL
NOT TO SCALE
SINGLE SUCTION FLOOR MOUNTED PUMPS
- CONNECTIONS WITH MECHANICAL
COUPLINGS
NOT TO SCALE
SUPPORT ANCHOR (CONDENSATE OR
CHILLED WATER)
NOT TO SCALE
SUPPORT ANCHOR FOR PIPE RISER
NOT TO SCALE
WATERFLOW MEASURING DEVICE
NOT TO SCALE
CHILLER REFRIGERANT VENT PIPING
DETAIL
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
NOT TO SCALE
WATER COOLED CHILLER PIPING DETAIL
6 UNIT SHALL REMOVE 80% OF THE 30 MICRON PARTICLES IN 100 CIRCULATIONS. UNIT SHALL BE CAPABLE OF 5 MICRON PARTICLE SIZE REMOVAL.
NOTES:
1 PROVIDE COALESCING TYPE SEPARATOR. CENTRIFUGAL TYPE NOT ACCEPTED.
2 VESSEL SHALL BE CERTIFIED FOR 150 LB WORKING PRESSURE AND SHALL BE FURNISHED WITH ANSI / ASME B16.5 OR B16.47 CLASS 150 STEEL WELD NECK RAISED-FACE FLANGES.
3 UNIT SHALL INCLUDE STRUCTURED COALESCING MEDIA FILLING THE ENTIRE VESSEL.
4 VESSELS WITH LOOSE OR PARTIALLY FILLED INTERNAL MEDIA NOT ACCEPTED.
5 UNIT SHALL REMOVE 100% OF FREE AND ENTRAINED AIR AND 99.6% OF DISSOLVED AIR AS TESTED BY INDEPENDENT LAB.
AIR-DIRT SEPARATOR SCHEDULE
IN GPM FT IN IN IN IN LBS
ADS-1 CHILLER ROOM CAMPUS CHILLED WATER LOOP SPIROTHERM VDN-2400FA COALESCING 24 6000 5 2 72 48 158 7240 1-6
ADS-2 CHILLER ROOM BLDG HEATING HOT WATER SPIROTHERM VDN-400FA COALESCING 4 400 5 1 21 9 31 233 1-6
MARK LOCATION SERVICE MANUFACTURERS MODEL TYPE
CONN. MAX MAX DRAIN PHYSICAL DATA
NOTESSIZE FLOW P.D. SIZE L W H WEIGHT
1 EQUIPMENT PERFORMANCE VALUES SELECTED FOR OPERATION AT AN ELEVATION OF 1100 FT ABOVE SEA LEVEL.
2 PROVIDE CONCRETE HOUSEKEEPING PAD PER SPECIFICATIONS. COORDINATE HOUSEKEEPING PAD WITH ARCHITECTURAL.
3 VARIABLE FREQUENCY DRIVE FURNISHED BY DIVISION 23 CONTRACTOR AND INSTALLED BY DIVISION 26
4 PUMP MOTOR SHALL BE NON-OVERLOADING THROUGHOUT THE FULL RANGE OF THE PUMP CURVE.
5 NPSHA IS THE NET POSITIVE SUCTION HEAD AVAILABLE TO THE PUMP. PUMP AT DESIGN CONDITIONS SHALL HAVE NPSH LESS THAN SPECIFIED VALUE.
PUMP SCHEDULE
NOTES:
CTP-1 CHILLER PLANT CONDENSER WATER SUPPLY BELL AND GOSSETT VSX 12 10 VERTICAL SPLIT-CASE BASE 4,500 70 25.7 125 94.5 1674 2885 VFD VFD 460/3 1-5
CTP-2 CHILLER PLANT CONDENSER WATER SUPPLY BELL AND GOSSETT VSX 12 10 VERTICAL SPLIT-CASE BASE 4,500 70 25.7 125 94.5 1674 2885 VFD VFD 460/3 1-5
CTP-3 CHILLER PLANT CONDENSER WATER SUPPLY BELL AND GOSSETT VSX 12 10 VERTICAL SPLIT-CASE BASE 4,500 70 25.7 125 94.5 1674 2885 VFD VFD 460/3 1-5
HWP-1 CHILLER PLANT BUILDING XX HEATING HOT WATER BELL AND GOSSETT e-80 3 3 VERTICAL INLINE INLINE 200 60 5.2 7.50 3.92 1800 280 VFD VFD 460/3 1-5
HWP-2 CHILLER PLANT BUILDING XX HEATING HOT WATER BELL AND GOSSETT e-80 3 3 VERTICAL INLINE INLINE 200 60 5.2 7.50 3.92 1800 280 VFD VFD 460/3 1-5
CWP-1 CHILLER PLANT PRIMARY CHILLED WATER RETURN BELL AND GOSSETT VSX 8 6 VERTICAL SPLIT-CASE BASE 2,000 130 16.9 100 75.9 1670 2104 VFD VFD 460/3 1-5
CWP-2 CHILLER PLANT PRIMARY CHILLED WATER RETURN BELL AND GOSSETT VSX 8 6 VERTICAL SPLIT-CASE BASE 2,000 130 16.9 100 75.9 1670 2104 VFD VFD 460/3 1-5
CWP-3 CHILLER PLANT PRIMARY CHILLED WATER RETURN BELL AND GOSSETT VSX 8 6 VERTICAL SPLIT-CASE BASE 2,000 130 16.9 100 75.9 1670 2104 VFD VFD 460/3 1-5
MARK LOCATION SERVICE MANUFACTURERS MODEL MIN. SIZE TYPE MOUNTING MAX. FLOW/HEAD NPSHA MOTOR WEIGHT ELECTRICAL NOTES
SUCTION DISCHARGE DISC. STARTER V/PH
IN. IN. GPM FTHD FT HP BHP RPM LBS TYPE TYPE
1 EQUIPMENT PERFORMANCE VALUES SELECTED FOR OPERATION AT AN ELEVATION OF 1100 FT ABOVE SEA LEVEL.
2 VARIABLE FREQUENCY DRIVE FURNISHED BY DIVISION 23 CONTRACTOR, INSTALLED BY DIVISION 26 CONTRACTOR.
3 PROVIDE SIDE OUTLET SUMP.
4 COORDINATE SIZE OF CONDUCTOR TERMINATION LUGS WITH CONDUCTOR SIZES SHOWN ON ELECTRICAL DRAWINGS.
5 PROVIDE WITH WELDED STAINLESS STEEL BASIN.
6 UNIT SHALL BE FACTORY FABRICATED AND FACTORY TESTED.
7 PROVIDE LADDER, GUARD RAIL, AND DAVIT FOR SERVICE AT THE TOP OF EACH UNIT
8 PROVIDE STANDARD MANUFACTURER CONTROL DEVICES FOR BASIN WATER LEVEL
9 PROVIDE COOLING TOWER WITH 18KW BASIN HEATER FOR FREEZE PROTECTION WITH CONTROLLER.
COOLING TOWER SCHEDULE
NOTES:
KW EA. QTY QTY HP/FAN RPM TYPE TYPE
CT-1 CHILLER PLANT ROOF CHILLER CONDENSER WATER MARLEY NC8407TAN2 22,421 4500 3750 75.0 89.9 95.0 85.0 Y 48,830 24 2 2 40.00 1800 VFD VFD 460/3 1-9
CT-2 CHILLER PLANT ROOF CHILLER CONDENSER WATER MARLEY NC8407TAN2 22,421 4500 3750 75.0 89.9 95.0 85.0 Y 48,830 24 2 2 40.00 1800 VFD VFD 460/3 1-9
MARK LOCATION SERVICE MANUFACTURERS MODEL CAP.
MBH
MAX
FLOW
GPM
DESIGN
FLOW
GPM
EAT
°F WB
LAT
°F WB
EWT
°F
LWT
°F
VFD
Y/N
WEIGHT
LBS
BASIN HEATER FAN ELECTRICAL
NOTES
FAN MOTOR DISC. STARTER V/PH
7 NOTE: CHILLER INITIAL FLOW RATE WILL OPERATE AT 10F TEMPERATURE DIFFERENTIAL (TD) TO OPERATE WITH EXISTING COILS. FINAL WILL BE 15 DEGREE TD FOLLOWING FUTURE CAMPUS HVAC UPGRADE.
8 PROVIDE REFRIGERANT DIFFERENTIAL PRESSURE HEAD CONTROL FOR OPERATION WITH WATERSIDE ECONOMIZER AND FUNCTIONAL PERFORMANCE TESTING AT LOW OR NO LOAD ON EQUIPMENT STARTUP.
VV: VA PROVIDED / VA INSTALLED
VC: VA PROVIDED / CONTRACTOR INSTALLED
6 VARIABLE FREQUENCY DRIVE FURNISHED UNIT MOUNTED WITH CHILLER BY MANUFACTURER.
1 EQUIPMENT PERFORMANCE VALUES SELECTED FOR OPERATION AT 15 DEGREE EVAPORATOR DESIGN CONDITION AT AN ELEVATION OF 1100 FT ABOVE SEA LEVEL.
2 AS DEFINED BY AHRI 550/590 - PERFORMANCE RATINGS OF WATER-CHILLING PACKAGES USING THE VAPOR COMRESSION CYCLE.
3 SOUND PRESSURE MEASURED IN ACCORDANCE WITH ANSI/AHRI STANDARD 575-1994 (A-WEIGHTED).
4 REFRIGERANT SHALL BE AS APPROVED PER CURRENT ASHRAE 15-2019.
5 PROVIDED BY / INSTALLED BY ABBREVIATIONS INDICATE THE FOLLOWING:
CC: CONTRACTOR PROVIDED / CONTRACTOR INSTALLED
CHILLER SCHEDULE (WATER COOLED)
NOTES:
WCC-1 CC BLDG XX CHILLER PLANT SITE CHILLED WATER DEMAND TRANE CVHH 1,250 0.554 0.367 R-1233zd 2 3,000 790 42 52 15.0 2000 770.00 42 57 10 2 3,750 85 95 20 58,000 1600 1093 Y VFD VFD 460/3 1-7
WCC-2 CC BLDG XX CHILLER PLANT SITE CHILLED WATER DEMAND TRANE CVHH 1,250 0.554 0.367 R-1233zd 2 3,000 790 42 52 15.0 2000 770.00 42 57 10 2 3,750 85 95 20 58,000 1600 1093 Y VFD VFD 460/3 1-7
MARK
PROVIDED BY /
INSTALLED BY
LOCATION SERVICE MANUFACTURERS MODEL
CAP
(TONS)
MAX
KW/TON
MAX
NPLV
REFR.
TYPE
EVAPORATOR (DESIGN PERFORMANCE) EVAPORATOR (OPERATING CONDITIONS) CONDENSER (DESIGN PERFORMANCE) ELECTRICAL
NOTES
PASS
DESIGN MIN. EWT LWT MAX PD OPERATING MIN. EWT LWT MAX PD PASS DESIGN EWT LWT MAX PD WEIGHT
MOCP MCA
VFD DISC. STARTER V/PH
GPM GPA °F °F FT GPM GPM °F °F FT GPM °F °F FT LBS Y/N TYPE TYPE
CH-E CH-1&2 2019 R123 SITE MODULAR CHILLER PLANT- EAST SIDE AMBULATORY CARE CENTER (ACC) TRANE CVHE0400 - CENTRIFUGAL 600 1,024 1,500 2,3
4 DEMOLISH CHILLER. SEE SHEET 17-MPD100 FOR RELATED INFORMATION.
1 CHILLED WATER CONDITIONS: EWT= 52F, LWT-42F (10F TEMPERATURE DIFFERENTIAL)
2 CHILLED WATER CONDITIONS: EWT= 56F, LWT-42F (14F TEMPERATURE DIFFERENTIAL)
3 CHILLER IS EXISTING TO REMAIN FOR REFERENCE ONLY.
EXISTING CHILLER SCHEDULE
NOTES:
DESIGN INSTALL REFRIGERANT CAPACITY CHW CW NOTES
MARK MARK YEAR TYPE LOCATION SERVES MAKE MODEL SERIAL NO. TYPE TONS GPM GPM
CH-A CH-1 1999 Lithium Bromide B-17 BASEMENT MECHANICAL ROOM MAIN CHW LOOP TRANE ABTF950 L99F02719M ABSORPTION 980 2,352 3,400 1,4
CH-B CH-1 2012 R123 B-17 TEMPORARY OUTDOOR ENCLOSURE MAIN CHW LOOP TRANE CVHF1300 L11M04637 CENTRIFUGAL 1,250 1,870 2,500 1,3
CH-C Existing 1998 HFC-134A B-1 ROOM B024A SURGERY/SPD/WAREHOUSE MCQUAY PEH087K 58C81053 CENTRIFUGAL 450 1,080 2,500 1,3
CH-D CH-1 2014 R410 B-1 ROOM B024A SURGERY/SPD/WAREHOUSE MultiStack M9070XC5A-1W2AAC-410A AE-11-080 MODULAR 450 1,080 1,350 1,3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/6
/2
:4
:4
A
M
0-M-601
MECHANICAL SCHEDULES
JES MDS
24 22 AQUATHERM SDR 17.6 PP-RT
18 15.8 AQUATHERM SDR 17.6 PP-RT
NOMINAL SIZE ID (IN) MANUFACTURER WGT MATERIAL
UNDERGROUND PIPE SCHEDULE
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
1 PROVIDE COOLING CAPACITY SCHEDULED AT 100F AMBIENT AIR TEMPERATURE
2 DISCONNECT PROVIDED WITH THE EQUIPMENT BY MANUFACTURER.
3 INDOOR FAN COIL POWERED FROM OUTDOOR CONDENSING UNIT.
7 PROVIDE CONDENSATE PUMP AND OVERFLOW SHUTOFF SWITCH WITH UNIT.
8 PROVIDE STANDARD FACTORY FURNISHED WASHABLE FILTERS.
4 TEMPERATURE CONTROL - PROVIDE COMMUNICATING WALL THERMOSTAT INTERFACE FOR COMMUNICATION WITH BAS.
5 PROVIDE NECESSARY MOUNTING BRACKET AND ACCESSORIES FOR SPECIFIED MOUNTING.
6 PROVIDE ALL MOUNTING HARDWARE REQUIRED FOR UNIT TYPE SUBJECT TO MANUFACTURERS INSTALLATION INSTRUCTIONS.
DUCTLESS SPLIT SYSTEM FAN COIL UNIT SCHEDULE
NOTES:
MARK LOCATION SERVICE MANUFACTURER MODEL MOUNTING COOLING NOTES
REFR. CFM NOMINAL TH SH EAT LAT WEIGHT MCA V/PH
TYPE TONS MBH MBH DB WB DB WB LBS
ACU-1 EMERGENCY ELECTRICAL RM EMERGENCY ELECTRICAL RM MITSUBISHI PKA-A24KA7 WALL R410A 750 2 22.5 20.3 80.0 67.0 55.0 54.2 37 1 208/1 1-8
ACU-2 IT ROOM IT ROOM MITSUBISHI PKA-A24KA7 WALL R410A 750 2 22.5 20.3 80.0 67.0 55.0 54.2 37 1 208/1 1-8
ACU-3 CONTROL ROOM CONTROL ROOM MITSUBISHI PKA-A24KA7 WALL R410A 750 2 22.5 20.3 80.0 67.0 55.0 54.2 37 1 208/1 1-8
NOTES:
1 125 PSI MAXIMUM WORKING PRESSURE.
2 HEAT EXCHANGERS PROVIDED WITH HOT WATER PUMPS AND ASSOCIATED EQUIPMENT AS PART OF A PRE-MANUFACTURERED STEAM TO HOT WATER SKID ASSEMBLY.
3 SIZE STEAM TRAP FOR A SAFETY FACTOR OF 2:1 AT OPERATING 1/2 MAXIMUM PRESSURE DIFFERENTIAL.
FLUID FLOW CAP. EWT LWT WPD MAX. NO. FLUID CAP. INLET PRESS. MIN. HEATING
TYPE GPM MBH °F °F FT PASSES TYPE MBH PSI SURFACE (SF)
HEAT EXCHANGER SCHEDULE (STEAM)
HX-1 CHILLER PLANT CHILLER PLANT HHW LOOP ARMSTRONG WS-0802-200E SHELL & TUBE 40 12 WATER 160 1571 140 160 12 2 STEAM 1571 30 14.3 1-3
HX-2 CHILLER PLANT CHILLER PLANT HHW LOOP ARMSTRONG WS-0802-200E SHELL & TUBE 40 12 WATER 160 1571 160 180 12 2 STEAM 1571 30 14.30 1-3
MARK LOCATION SERVICE MANUFACTURERS MODEL TYPE
LENGTH
(IN)
DIA.
(IN)
TUBE SIDE SHELL SIDE
NOTES
3 PROVIDE WITH BIRDSCREEN AND MOTORIZED BACKDRAFT DAMPER.
1 PROVIDE WITH MINIMUM 24" HIGH ROOF CURB, BIRDSCREEN AND BACKDRAFT DAMPER.
2 DIVISION 26 CONTRACTOR TO FURNISH AND INSTALL DISCONNECT SWITCH AND MOTOR STARTER.
EF-3 SIDEWALL EA ELECTRICAL ROOM GREENHECK SIDEWALL CUE-160-A 3780 0.75 DIRECT 2 1725 N 460/3 2, 3
FAN SCHEDULE
NOTES
EF-1 ROOF EA MECHANICAL ROOM GREENHECK ROOF G-240-VG 7100 1 DIRECT 5 1020 N 460/3 1, 2
EF-2 ROOF EA STAFF TOILET GREENHECK ROOF CUE-099-1 150 0.65 DIRECT 0.25 1433 N 120/1 1, 2
MARK LOCATION
SERVICE
MANUFACTURER MOUNTING MODEL CFM
ESP DRIVE MIN. FAN VFD ELECTRICAL
NOTES
TYPE LOCATION (IN) (BELT/DIRECT) HP RPM (Y/N) V/PH
LOUVER SCHEDULE
LU-1 CHILLER MEZZANINE AHU-1 RUSKIN L375D 106x80 16850 32.83 550 0.03
LU-2 CHILLER MEZZANINE AHU-2 RUSKIN L375D 60x50 3780 10.41 500 0.03
MARK LOCATION SERVICE MANUFACTURERS MODEL
SIZE
(W" x H")
CFM
MIN. FREE AREA
(SF)
FREE AREA
MAX. VEL.
(FPM)
MAX. P.D.
(IN. W.C.)
NOTES
NOTES:
1 PROVIDE UNIT WITH FACTORY SUPPLIED NEMA 1 MOTOR STARTER ENCLOSURE WITH SAFETY DISCONNECT AND H.O.A. SWITCH.
COOLING TOWER FILTRATION SCHEDULE
GPM FT IN. IN. GPM
CTF-1 90 150 AMIAD ASY-850PGM LH-S 850 35 6 6 850 35 15 460/3 1
CTF-2 90 150 AMIAD ASY-850PGM LH-S 850 35 6 6 850 35 15 460/3 1
MANUFACTURER MODEL
FLOW PRESS. SIZE FLOW
HEAD
FTHD
MOTOR HP
ELECTRICAL V
/ PH
RATE DROP INLET OUTLET RATE
SYSTEM
SYSTEM OPERATING
TEMP. °F
SYSTEM WORKING
PRESSURE PSIG
WATER FILTRATION UNIT PUMP
NOTES
THE ASSOCIATED REFRIGERANT TRAPS BASED ON THE ACTUAL ROUTING AND PROVIDE OTHER APPURTENANCES TO PROVIDE A FULLY FUNCTIONAL AND OPERATIONAL SYSTEM.
3 COORDINATE WITH THE MANUFACTURER LOCATIONS FOR ALL REFRIGERANT PIPING DEVICES TO MAINTAIN SERVICEABILITY AND ACCESSIBILITY.
4 PROVIDE LIQUID LINE FILTER DRYER AND SIGHT GLASS.
1 EQUIPMENT SIZED FOR 95°F AMBIENT TEMPERATURE.
2 COORDINATE WITH THE MANUFACTURER THE HORIZONTAL AND VERTICAL REFRIGERANT PIPE ROUTING TO DETERMINE PIPE SIZES FOR THE REFRIGERANT PIPING. MANUFACTURER
SHALL PROVIDE DETAILED REFRIGERANT PIPING DIAGRAMS INCLUDING DIMENSIONAL DATA FOR ALL REFRIGERANT PIPING DEVICES. THE MANUFACTURER SHALL SIZE AND LOCATE
8 PROVIDE CONDENSER COIL HAIL GUARDS.
9 PROVIDE HARD START KIT.
10 INDOOR FAN COIL POWERED FROM OUTDOOR CONDENSING UNIT
5 UNIT TO MOUNT ON ROOF MOUNTED BASE RAILS. SEE ARCHITECTURAL DRAWINGS FOR MORE INFORMATION.
6 DISCONNECT FURNISHED AND INSTALLED BY DIVISION 26 CONTRACTOR.
7 STARTERS FOR ALL MOTORS SHALL BE FURNISHED INTEGRAL WITH UNIT.
CONDENSING UNIT SCHEDULE
NOTES:
TYPE TYPE
CU-1 ROOF ACU-1 MITSUBISHI PUZ-A24NHA7 410A 24.0 21.40 4.35 180 19 26 NOTE 6 NOTE 7 208/1 1-10
CU-2 ROOF ACU-2 MITSUBISHI PUZ-A24NHA7 410A 24.0 21.40 4.35 180 19 26 NOTE 6 NOTE 7 208/1 1-10
MARK LOCATION SERVICE MANUFACTURERS MODEL
REFR. CAP. SEER COP WEIGHT ELECTRICAL
NOTESTYPE MBH @ 47°F LBS MCA MOCP DISC.
STARTER
V/PH
CU-3 ROOF ACU-3 MITSUBISHI PUZ-A24NHA7 410A 24.0 21.40 4.35 180 19 26 NOTE 6 NOTE 7 208/1 1-10
2 VARIABLE FREQUENCY DRIVES TO BE FACTORY INSTALLED SINGLE VFD PER FAN.
3 SPECIFIED FAN ESP ACCOUNTS FOR DUCT LOSSES EXTERNAL TO UNIT.
4 DIVISION 26 CONTRACTOR SHALL PROVIDE SMOKE DETECTORS IN RETURN AIR AND SUPPLY AIR DUCT(S).
5 PROVIDE CONCRETE HOUSEKEEPING PAD PER SPECIFICATIONS.
6 PROVIDE SHAFT GROUNDING SYSTEM ON MOTORS. REFER TO MOTOR SPECIFICATION FOR ADDITIONAL INFORMATION.
7 MIN. O/A IS THE MINIMUM OUTSIDE AIR CFM USING VENTILATION RESET OR DEMAND CONTROL VENTILATION.
8 PROVIDE UNIT WITH ECONOMIZER.
9 PROVIDE UNIT WITH BOTTOM DISCHARGE AND RETURN.
10 DISCONNECT SWITCH FURNISHED AND INSTALLED BY DIVISION 26 CONTRACTOR.
75 62 55 54.7 87 82 42 55 13 1.13 0.25 450 1 8 8 0.0 85.0 11 4 0.1 501 160 140 35 1.2 8 2 62 38 145 1686 VFD 460/3 5 1-9
AIR HANDLING UNIT SCHEDULE (CHILLED WATER / HOT WATER) - CONTINUED
NOTES:
1 PROVIDE FACTORY MOUNTED DISCONNECT INSTALLED ON SERVICE SIDE OF UNIT.
AIR TEMP. AIR TEMP. TOTAL SENS. ENT. LVG. FLOW WPD APD VEL. COIL FINS AIR TEMP. FINS MAX APD VEL. ENT. LVG. FLOW WPD
FT
W H L MAX. DISC. SCCR
EDB F EWB F LDB F LWB F MBH MBH EWT F LWT F GPM FT IN FPM QTY FPI EDB F LDB F FPI ROWS IN FPM EWT F LWT F GPM MERV IN IN IN IN LBS TYPE (kA)
87 72 55 54.7 957 582 42 55 147 11.30 0.53 450 1 8 8 0.0 85.0 11 4 0.1 501 160 140 155 5.7 8 2 113 68 174 5436 VFD 460/3 5 2-8, 10
COOLING COIL HEATING COIL FILTER DIMENSIONS WEIGHT ELECTRICAL
NOTES
CC ENTERING CC LEAVING CC CAPACITY CC FLUID COIL MAX. CC MAX
MAX
ROWS
HC ENTERING MAX COIL MAX. HC FLUID PRE-FILTER MAX. MAX. MAX.
V/PH
5 PROVIDE CONCRETE HOUSEKEEPING PAD PER SPECIFICATIONS.
6 PROVIDE SHAFT GROUNDING SYSTEM ON MOTORS. REFER TO MOTOR SPECIFICATION FOR ADDITIONAL INFORMATION.
7 MIN. O/A IS THE MINIMUM OUTSIDE AIR CFM USING VENTILATION RESET OR DEMAND CONTROL VENTILATION.
2 VARIABLE FREQUENCY DRIVES TO BE FACTORY INSTALLED SINGLE VFD PER FAN.
3 SPECIFIED FAN ESP ACCOUNTS FOR DUCT LOSSES EXTERNAL TO UNIT.
4 DIVISION 26 CONTRACTOR SHALL PROVIDE SMOKE DETECTORS IN RETURN AIR AND SUPPLY AIR DUCT(S).
8 PROVIDE UNIT WITH MINIMUM OUTSIDE AIR AND ECONOMIZER OUTSIDE AIR DAMPER.
9 PROVIDE UNIT WITH BOTTOM DISCHARGE.
10 DISCONNECT SWITCH FURNISHED AND INSTALLED BY DIVISION 26 CONTRACTOR.
AHU-2 CHILLER PLANT MEZZ. ELECTRICAL ROOM TRANE CSAA INDOOR PLENUM FAN ARRAY 2 3780 3780 3780 160 2040 2040 80 1.00 2.26 400.00 2.32 2838 1.50 DIRECT Y 3780 1960
AIR HANDLING UNIT SCHEDULE (CHILLED WATER / HOT WATER)
NOTES:
1 PROVIDE FACTORY MOUNTED DISCONNECT INSTALLED ON SERVICE SIDE OF UNIT.
QTY. AIRFLOW SUPPLY MAX OSA MIN OSA SUPPLY MAX OSA MIN OSA ESP TSP VELOCITY HP DRIVE VFD AIRFLOW AIRFLOW
CFM CFM CFM CFM CFM CFM CFM IN IN FPM PER FAN TYPE Y/N CFM CFM
AHU-1 CHILLER PLANT MEZZ. CHILLER PLANT TRANE CSAA INDOOR PLENUM FAN ARRAY 2 16850 16850 16850 10350 9860 9860 7100 2.00 3.68 400.00 14.52 1750 7.50 DIRECT Y 16850 2760
MARK LOCATION SERVES MANUFACTURER MODEL TYPE
SUPPLY FAN RETURN / EXHAUST
FAN TYPE
FAN DESIGN DESIGN AIRFLOW OPERATING AIRFLOW
BHP RPM
MAX. DESIGN OPERATING
VFD-CT-1 VFD-CT-1 CHILLER PLANT ROOF CT-1 FAN DIRECT ABB ACH550 2 40 MULTISTRUT 460/3 460/3 2-5
VFD-CT-2 VFD-CT-2 CHILLER PLANT ROOF CT-2 FAN DIRECT ABB ACH550 2 40 MULTISTRUT 460/3 460/3 2-5
VARIABLE SPEED DRIVE (VFD) SCHEDULE
NOTES:
1 VARIABLE FREQUENCY DRIVES TO BE FACTORY INSTALLED. COORDINATE ALL ELECTRICAL CONNECTIONS WITH DIVISION 26 CONTRACTOR.
2 VARIABLE FREQUENCY DRIVES TO BE FURNISHED AND INSTALLED BY DIVISION 23 CONTRACTOR. COORDINATE ALL ELECTRICAL CONNECTIONS WITH DIVISION 26 CONTRACTOR.
3 VARIABLE FREQUENCY DRIVE OUTPUT TO COINCIDE WITH ASSOCIATED EQUIPMENT REQUIREMENTS PER THEIR SCHEDULED OPERATING VALUES.
4 PROVIDE WITH CLEARANCES PER NEC.
5 REFER TO DETAILS 10/XX-E-501 FOR MORE INFORMATION.
MARK PLAN LOCATION SERVES EQUIPMENT EQUIPMENT MANUFACTURERS MODEL MAX MAX MOUNTING ELECTRICAL NOTES
MARK MOTOR MOTOR
TYPE DRIVE QTY. HP/FAN INPUT V/PH OUTPUT V/PH
VFD-CWP-1 VFD-CWP-1 CHILLER PLANT CWP-1 PUMP DIRECT ABB ACH550 1 100 MULTISTRUT 460/3 460/3 2-5
VFD-CWP-2 VFD-CWP-2 CHILLER PLANT CWP-2 PUMP DIRECT ABB ACH550 1 100 MULTISTRUT 460/3 460/3 2-5
VFD-CWP-3 VFD-CWP-3 CHILLER PLANT CWP-3 PUMP DIRECT ABB ACH550 1 100 MULTISTRUT 460/3 460/3 2-5
VFD-CTP-1 VFD-CTP-1 CHILLER PLANT CTP-1 PUMP DIRECT ABB ACH550 1 125 MULTISTRUT 460/3 460/3 2-5
VFD_AHU-1-SF-1 VFD-SF-1 MEZZANINE AHU-1 PLENUM FAN ARRAY DIRECT ABB ACH550 1 7.5 NOTE 1 460/3 460/3 1,3-4
VFD_AHU-1-SF-2 VFD-SF-2 MEZZANINE AHU-1 PLENUM FAN ARRAY DIRECT ABB ACH550 1 7.5 NOTE 1 460/3 460/3 1,3-4
VFD_AHU-2-SF-3 VFD-SF-3 MEZZANINE AHU-2 PLENUM FAN ARRAY DIRECT ABB ACH550 1 1.5 NOTE 1 460/3 460/3 1,3-4
VFD_AHU-2-SF-4 VFD-SF-4 MEZZANINE AHU-2 PLENUM FAN ARRAY DIRECT ABB ACH550 1 1.5 NOTE 1 460/3 460/3 1,3-4
VFD-CTP-2 VFD-CTP-2 CHILLER PLANT CTP-2 PUMP DIRECT ABB ACH550 1 125 MULTISTRUT 460/3 460/3 2-5
VFD-CTP-3 VFD-CTP-3 CHILLER PLANT CTP-3 PUMP DIRECT ABB ACH550 1 125 MULTISTRUT 460/3 460/3 2-5
VFD-HWP-1 VFD-HWP-1 MEZZANINE HWP-1 PUMP DIRECT ABB ACH550 1 7.5 MULTISTRUT 460/3 460/3 2-5
VFD-HWP-2 VFD-HWP-2 MEZZANINE HWP-2 PUMP DIRECT ABB ACH550 1 7.5 MULTISTRUT 460/3 460/3 2-5
2 FRAME TYPE TO MATCH CEILING CONSTRUCTION, COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLAN.
3 NECK SIZE SHOWN ON DRAWINGS.
4 4-WAY THROW PATTERN UNLESS OTHERWISE SHOWN ON DRAWINGS.
5 BRANCH DUCT SIZE SHALL BE SAME AS NECK SIZE UNLESS OTHERWISE SHOWN ON DRAWINGS.
6 PROVIDE NECK FOR DUCT CONNECTION.
7 FRONT BLADES PARALLEL TO LONG DIMENSION.
8 FRONT BLADES PARALLEL TO SHORT DIMENSION
9 DOUBLE DEFLECTION BARS SHALL BE ADJUSTABLE.
DIFFUSER , REGISTER AND GRILLE SCHEDULE
NOTES:
1 COORDINATE FINISH WITH ARCHITECTURAL.
MARK MOUNTING SERVICE MANUFACTURERS MODEL TYPE FACE SIZE NECK SIZE MAX. MAX. PRESS. NOTES
LOCATION (IN) (IN) NC DROP IN-WC
E-1 GYPSUM CEILING EXHAUST TITUS 350RL PARALLEL BLADE 12 x 12 10 x 6 30 0.08 1-3, 5-7
E-2 DUCT EXHAUST TITUS 350RL PARALLEL BLADE 18 x 18 18 x 18 30 0.08 1-3, 5-7
S-1 LAY-IN CEILING SUPPLY TITUS OMNI PLAQUE 24 x 24 6" 30 0.1 1-6
S-2 DUCT SUPPLY TITUS 301RL PARALLEL BLADE 12 x 8 12 x 8 30 0.1 1-7
S-3 DUCT SUPPLY TITUS 301RS PARALLEL BLADE 18 x 10 18 x 10 30 0.1 1-6, 8
S-4 DUCT SUPPLY TITUS 111RL PARALLEL BLADE 38 x 36 38 x 36 30 0.1 1-7,9
2 PROVIDE PRECHARGED BLADDER-TYPE ASME RATED TANK.
3 VERTICAL TANKS SHALL BE INSTALLED TO ACCOMMODATE BOTTOM DRAIN CONNECTION.
EXPANSION / COMPRESSION TANK SCHEDULE
NOTES:
1 PROVIDE PRECHARGED DIAPHRAGM-TYPE ASME RATED TANK.
ET-1 MEZZANINE HEATING HOT WATER BELL & GOSSET D-40 FLOOR 21.7 11.6 240 125 263 1,3-4
ET-2 CHILLER PLAN CHILLED WATER BELL & GOSSET B-1200 FLOOR 317 317 240 125 3394 2-4
4 PROVIDE CONCRETE HOUSEKEEPING PAD PER SPECIFICATIONS FOR FLOOR-MOUNTED UNITS.
MARK LOCATION SERVICE MANUFACTURERS MODEL MOUNTING
TANK SIZE
GAL.
ACCEPTANCE
GAL.
MAX. TEMP.
°F
MAX. PRESS.
PSIG
WEIGHT
LBS
NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:5 :5
P
M
0-M-602
MECHANICAL SCHEDULES
JES MDS
Revisions: Date:
ADDENDUM NO. 01 04/07/2022
4. PROVIDE ISOLATION VALVE BETWEEN RECIEVER AND PUMP.
3. PROVIDE MECHANICAL ALTERNATOR TO SWITCH LEAD/LAG PUMP OPERATION.
2. PROVIDE CONCRETE HOUSEKEEPING PAD PER SPECIFICATIONS.
1. PROVIDE WITH FLOAT SWITCH, ALTERNATOR, AND ALL CONTROLS REQUIRED FOR PUMP OPERATION.
NOTES:
CONDENSATE PUMP SCHEDULE
MARK
MFR. MODEL TYPE LOCATION SERVICE
RECEIVER
CAPACITY
(GAL)
RECEIVER
VENT SIZE
# OF
PUMPS
PRESSURE POWERED PUMP
NOTES
ID #
CAPACITY
(LB/HR)
MOTIVE INLET
PRESS (PSIG)
BACK PRESS
(PSIG)
SPCP 1 ARMSTRONG DPT-404RP STEAM POWERED MEZZANINE STEAM CONDENSATE 50 4" 2 4400 30 15 1-4
T
SP
SA
RA
TT
C W
S
C W
R C
C
RA-T
MOA-D
PF-PD
MA-T
RA-D
PHC-LAT
CC-VLV
SA-LAT
SA-SP
EOA-F
NO
SP
BLD-P
T
MA-FRZST
SMOKE DETECTOR
FURNISHED AND INSTALLED,
AND INTERLOCKED WITH FIRE
ALARM CONTROL PANEL BY
DIV. 28
SD
SUPPLY
FAN
VFD
SF-S
SF-SS
SF-DATA
SF-SPD
AFMSSA-F
DP
H W
S
H W
R
PHC-VLV
NO
P H
C
MOA-F
EOA-D
EOA-D-S
MOA-D-S
RA-D-S
T
CC-LAT
SMOKE DETECTOR
FURNISHED AND INSTALLED,
AND INTERLOCKED WITH FIRE
ALARM CONTROL PANEL BY
DIV. 28
SD
SD
SF-FAULT
SD-D
SD-D-S
SMOKE DAMPER FURNISHED
AND INSTALLED, AND
INTERLOCKED WITH FIRE
ALARM CONTROL PANEL BY
DIV. 23
O A
N C
A M
S A
M S
N C
T S
D N
O N
O 1
EF-X-S
EF-X-SSSTARTER
CT
EA OUTEA IN
BD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION BID
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
PRIME CONSULTANT STAMPCONSULTANT
321 4 5 6 7 8 9 10
636-18-304
X
CONSTRUCT COMBINED
ENERGY PLANT PHASE 1
5350 W 94TH TERRACE #102
PRAIRIE VILLAGE, KS 66207
T 913.258.5026 www.rossbar.com
4101 WOOLWORTH AVE
OMAHA, NE 68105
11/30/2021
NOT F
OR
CONSTRUCTIO
N
D U s e rs
\m s im m o n s \D o c u m e n ts
\2 -1
M
E C
H v m s im m o n s L W
R W
.r v t
/5
/2
:0 :0
P
M
0-M-703
MECHANICAL CONTROLS
JES MDS
NTS
AIR HANDLING UNIT CONTROL DIAGRAM
AIR HANDLING UNIT (AHU-X) POINTS LIST - NO HEAT RECOVERY
CONTROL
POINT TAG SYSTEM POINT DESCRIPTION
INPUTS OUTPUTS ALARM REPORTS
DI AI DO AO H
IG
H \L
O W
L
IM
IT
S A
F E
T Y
M A
IN
T
A N
E N
C E
A B
N O
R M
A L O
N /O
F F
O P
E N
/C L O
S E
A L A
R M
R U
N T
IM
E
T O
T A
L
IZ
A T
IO
N
T R
E N
D
BLD-P BUILDING PRESSURE ● ● ● ●
CC-LAT COOLING COIL LEAVING AIR TEMPERATURE ● ● ● ●
CC-VLV CHILLED WATER VALVE ● ●
EOA-D ECONOMIZER OUTSIDE AIR DAMPER ACTUATOR ● ●
EOA-D-S ECONOMIZER OUTSIDE AIR DAMPER STATUS ● ●
EOA-F ECONOMIZER OUTSIDE AIRFLOW ● ●
MA-FRZST MIXED AIR FREEZESTAT ● ● ● ●
MA-T MIXED AIR TEMPERATURE ● ● ● ●
MOA-D MINIMUM OUTSIDE AIR DAMPER ACTUATOR ● ●
MOA-D-S MINIMUM OUTSIDE AIR DAMPER STATUS ● ●
MOA-F MINIMUM OUTSIDE AIR FLOW ● ●
PF-PD PRE-FILTER PRESSURE DROP ● ● ● ●
PHC-LAT PREHEAT COIL LEAVING AIR TEMPERATURE ● ● ● ●
PHC-VLV PREHEAT COIL VALVE ACTUATOR ● ●
RA-D RETURN AIR DAMPER ● ●
RA-D-S RETURN AIR DAMPER STATUS ● ●
RA-T RETURN AIR TEMPERATURE ● ● ● ●
SA-F SUPPLY AIRFLOW ● ●
SA-LAT SUPPLY AIR TEMPERATURE ● ● ● ●
SA-SP SUPPLY AIR DUCT STATIC PRESSURE ● ● ● ●
SD SMOKE DETECTOR ● ● ● ●
SD-D SMOKE DAMPER ● ●
SD-D-S SMOKE DAMPER STATUS ● ●
SF-DATA SUPPLY FAN VFD DATA ● ● ● ● ●
SF-FAULT VFD FAULT ● ● ●
SF-S SUPPLY FAN STATUS ● ● ● ● ●
SF-SPD SUPPLY FAN VFD SPEED ● ●
SF-SS SUPPLY FAN START/STOP ● ●
SEQUENCE OF OPERATIONS
AIR HANDLING UNIT (AHU-X)
GENERAL DESCRIPTION
The air handling unit (AHU-X) described by this sequence of operations consists of the following features. These features include a variable speed supply fan array, hot water preheating coil, and chilled water cooling coil that operate to provide heating, ventilation, and air-conditioning for the conditioned space as shown on the drawings.
OPERATING MODES
SYSTEM START UP MODE
The AHU shall be in system start up mode for after the unit has been enabled. The AHU will automatically reset to Occupied Mode after a user definable amount of time.
OCCUPIED MODE
The AHU shall be in occupied mode per the project design conditions schedule shown on the control drawings.
UNOCCUPIED MODE
The AHU shall be in unoccupied mode for all periods not included in the occupied hours of operation per the project design conditions schedule shown on the control drawings. Overrides of unoccupied schedule shall be defined by zone level controls.
ECONOMIZER MODE – OUTSIDE AIR TEMPERATURE ENABLED
The unit shall be in economizer mode when:
The supply fan status is on;
AND the…
This is the start of the file's text. The full file is on GovTribe.