Bldg 13 - Narrative Report.pdf

PDF 577 KB Posted

Attached to
Amendment 0001 - ACM Inspection Service Contract - Fargo
Solicitation number
36C26322Q0029
Issued by

View the file

Other files

File Type Posted
Narrative Report.pdf PDF
Roofing diagram.pdf PDF
Explanation of Attachments.docx DOCX document
Bldg 40 - Narrative Report.pdf PDF
Bldg 39 - Narrative Report.pdf PDF
Tunnels - Narrative Report.pdf PDF
36C26322Q0029 0001.pdf PDF
Volume 2.pdf PDF
Bldg 11 - Narrative Report.pdf PDF
Bldg 10 - Narrative Report.pdf PDF
Volume 1.pdf PDF
Attachment 3 - EC-26 Confined Space.docx DOCX document
Bldg 30 - Narrative Report.pdf PDF
Bldg 12 - Narrative Report.pdf PDF
P15 Drawings.pdf PDF
QA.docx DOCX document
Bldg 3 - Narrative Report.pdf PDF
C03 36C26322Q0029.pdf PDF
Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BUILDING #13

LEGEND No. 0800912

TABLE OF CONTENTS

ITEM

NARRATIVE REPORT

1.0 BUILDING INTRODUCTION

2.0 ASBESTOS SURVEY INFORMATION

2.1 SUSPECT MATERIALS IDENTIFIED AND SAMPLED

2.2 ASBESTOS CONTAINING MATERIALS

2.3 COST ESTIMATES

ACM LOCATIONS/FRIABLE MATERIALS ASSESSMENTS TABLE

ACM LOCATIONS DIAGRAMS

LABORATORY DATA

ASBESTOS BULK SAMPLE RESULTS TABLE

ASBESTOS BULK SAMPLE LOCATIONS DIAGRAM

LEGEND No. 0800912 BUILDING #13 Page 1 of 2

1.0 BUILDING INFORMATION

Building #13 was originally constructed in 1945; limited renovations are evident in the building.

The interior floor finishes included floor tile, ceramic tie, and concrete; the interior wall finishes included gypsum wallboard, concrete block, concrete, and brick; and the interior ceiling finishes included ceiling tile, concrete, and metal. The roofing system is a peaked asphalt-shingle roof;

the exterior of the structure is brick.

The piping systems were insulated; fiberglass insulation (without hard fittings) is located throughout the structure. Fireproofing was observed in the structure. HVAC systems located in the structure consisted of steam radiators and forced air furnaces equipped with heating/cooling coils.

2.0 ASBESTOS SURVEY INFORMATION

Building #13 was surveyed as part of a larger project for the VA. This report is part of “Volume 2” of a two volume series. This report includes building specific information only; please refer to the opening section of “Volume 2” for methodologies, definitions, and other pertinent supporting information.

A total of 39 samples were collected from suspect asbestos-containing materials (ACM) on October 15, 2008. Laboratory analysis results indicate 10 of these samples tested positive for asbestos.

2.1 Suspect Materials Identified and Sampled

Floor Tile (multiple types) Floor Tile Mastic (multiple types) Ceiling Tile (multiple types) Gypsum Wallboard (multiple types) Joint Compound (multiple types) CMU Coating Adhesive (for baseboard) (multiple types) Fireproofing Window Glazing (multiple types) HVAC Duct Wrap Encapsulant on Fiberglass Insulation (multiple types) Window Caulk (multiple types) Air Vent Caulk Garage Door Caulk Penetration Putty Asphalt Shingle Tarpaper

The Asbestos Bulk Sample Results Table includes asbestos sampling data.

2.2 Asbestos Containing Materials

Mastic for 12” Tan w/ Brown/Gray Marks Floor Tile Mastic for 12” Light Gray w/ Brown Marks Floor Tile Mastic for 12” Brown/Tan/Gray Mottled Floor Tile Window Glazing (3 types) Window Caulk (1 type) Air Vent Caulk (1 type) Garage Door Caulk Penetration Putty

LEGEND No. 0800912 BUILDING #13 Page 2 of 2

The ACM Locations/ Friable Materials Assessments Table includes ACM locations data.

2.3 Cost Estimates

Legend Technical Services Inc. estimates abatement costs (removal & disposal) of ACM as follows:

ACM QUANTITY UNIT COST TOTAL COST

Asbestos Floor Tile Mastic (all types) 3,130 ft2 $5.00/ft2 $15,650.00 Asbestos Air Vent Caulk 1 ea $60.00/ea $60.00 Asbestos Window Caulk 4 ea $125.00/ea $500.00 Asbestos Window Glazing (all types) 11 ea $225.00/ea $2,475.00 Asbestos Garage Door Caulk 6 ea $125.00/ea $750.00 Asbestos Penetration Putty 1 ea $60.00/ea $60.00

Total Estimated Abatement Costs: $19,495.00

LEGEND TECHNICAL SERVICES, INC.

LEGEND No. 0800912 (VA)

ROOM/

ACM

ACM TYPE

(SAMPLE #)

EST.

QUANTITY

MATERIAL

CONDITION

DAMAGE

POTENTIAL

HIGH

M

OD

LOW

ASSESS.

CAT.1 NOTES ABATEMENT INFORMATION

* = Non-Friable materials were not assessed Page 1 of 3

Cart Wash Area Mastic for 12” Tan w/ Brown/Gray Marks Floor Tile

Non-Friable Miscellaneous (2)

143 ft2 N/A* N/A* N/A* The floor tile is negative; the mastic is positive. They are below the ceramic tile.

LEGEND #: ____________________

Date: ________________________ Window Glazing (on reinforced window)

Non-Friable Miscellaneous (24)

1 ea N/A* N/A* N/A* The asbestos glazing is on the window in the north wall of the room.

Clean Linen

Mastic for 12” Tan w/ Brown/Gray Marks Floor Tile

Non-Friable Miscellaneous (2)

2,301 ft2 N/A* N/A* N/A* The floor tile is negative; the mastic is positive. Refer to the ACM drawings for exact location.

Issue

Window Glazing Non-Friable Miscellaneous (31)

1 ea N/A* N/A* N/A* The asbestos glazing is on the room above the doorway.

Garage Door Caulk Non-Friable

Miscellaneous (36)

1 ea N/A* N/A* N/A* ACM caulk is around the garage door/ window system on the north end of the room.

Lunch Room

Mastic for 12” Brown/Tan/Gray Mottled Floor Tile

Non-Friable Miscellaneous (6)

141 ft2 N/A* N/A* N/A* The floor tile is negative; the mastic is positive. It is throughout the room.

reinforced window)

Non-Friable Miscellaneous (24)

1 ea N/A* N/A* N/A* The asbestos glazing is on the

ACM TYPE

(SAMPLE #)

EST.

QUANTITY

MATERIAL

CONDITION

DAMAGE

POTENTIAL

HIGH

M

* = Non-Friable materials were not assessed Page 2 of 3

Office Mastic for 12” Brown/Tan/Gray Mottled Floor Tile

Non-Friable Miscellaneous (6)

127 ft2 N/A* N/A* N/A* The floor tile is negative; the reinforced window)

Non-Friable Miscellaneous (24)

1 ea N/A* N/A* N/A* The asbestos glazing is on the

Receiving

Window Glazing Non-Friable Miscellaneous (31)

1 ea N/A* N/A* N/A* The asbestos glazing is on the room above the doorway.

Miscellaneous (36)

1 ea N/A* N/A* N/A* ACM caulk is around the garage door/ window system on the north end of the room.

Shower Room (East)

Mastic for 12” Light Gray w/ Brown Marks Floor Tile

Non-Friable Miscellaneous (4)

112 ft2 N/A* N/A* N/A* The floor tile is negative; the

Shower Room (West)

Mastic for 12” Light Gray w/ Brown Marks Floor Tile

Non-Friable Miscellaneous (4)

108 ft2 N/A* N/A* N/A* The floor tile is negative; the

Soiled Linen

Mastic for 12” Tan w/ Brown/Gray Marks Floor Tile

Non-Friable Miscellaneous (2)

198 ft2 N/A* N/A* N/A* The floor tile is negative; the mastic is positive. They are below the equipment in the room.

ACM TYPE

(SAMPLE #)

EST.

QUANTITY

MATERIAL

CONDITION

DAMAGE

POTENTIAL

HIGH

M

* = Non-Friable materials were not assessed Page 3 of 3

Exterior Penetration Putty Non-Friable

Miscellaneous (37)

1 ea N/A* N/A* N/A* The asbestos penetration putty is on the north end of the building around an electric conduit.

Air Vent Caulk Non-Friable

Miscellaneous (34)

1 ea N/A* N/A* N/A* The asbestos caulk is around the air vent to the crawlspace on the south end of the building.

Window Glazing Non-Friable

Miscellaneous (31,33)

6 ea N/A* N/A* N/A* ACM glazing is on the 4 basement windows and the 2 windows above the south garage doors.

Miscellaneous (36)

4 ea N/A* N/A* N/A* ACM caulk is around the 2 garage doors on the west end and 2 on the south end of the building.

Window Caulk Non-Friable

Miscellaneous (32)

4 ea N/A* N/A* N/A* The ACM caulk is around the 4 basement windows on the north end of the building.

1Assessment Categories:

1) Damaged or Significantly Damaged TSI ACM 5) ACM with Potential for Damage

2) Damaged Friable Surfacing ACM 6) ACM with Potential for Significant Damage

3) Significantly Damaged Friable Surfacing ACM 7) Any Remaining Friable ACM or Friable Suspected ACM

4) Damaged or Significantly Damaged Friable Miscellaneous ACM

End

LABORATORY DATA

MATERIAL/

SAMPLE NO. LAB NO. LOCATION PHYSICAL DESCRIPTION ASBESTOS CONTENT BALANCE OF MATERIAL

< = Less than the number shown Page 1 of 5

1 0800912-RE Soiled Linen Room Southeast Corner

12” Tan w/ Brown/Gray Marks Floor Tile White, Cementitious Homogeneous

None Detected 100% Nonfibrous

2 0800912-RF Soiled Linen Room Southeast Corner

Mastic for Sample #1 Black, Cementitious Homogeneous

8% Chrysotile 2% Cellulose 90% Nonfibrous

3 0800912-RG Shower Room (east) Northeast Corner

12” Light Green w/ Brown Marks Floor Tile White, Cementitious Homogeneous

None Detected 100% Nonfibrous

4 0800912-RH Shower Room (east) Northeast Corner

Mastic for Sample #3 Black, Cementitious Homogeneous

2% Chrysotile 3% Cellulose 95% Nonfibrous

5 0800912-RI Lunch Room

South End 12’’ Brown/Tan/Gray/Mottled Floor Tile Tan, Cementitious Homogeneous

None Detected 100% Nonfibrous

6 0800912-RJ Lunch Room South End

Mastic For Sample #5 Black, Cementitious Homogeneous

5% Chrysotile 3% Cellulose 92% Nonfibrous

7 0800912-RK Soiled Linen Room

West End 2’x4’ White w/ Widthwise Fissures/Pinholes CT Gray, Fibrous Homogeneous

None Detected 70% Cellulose 25% Nonfibrous

5% Glass 8 0800912-RL Lunch Room

West End 2’x4’ White w/ Long Worms and Pinholes CT Gray, Fibrous Homogeneous

None Detected 40% Cellulose 20% Nonfibrous

40% Glass 9 0800912-RM Clean Linen Room

West End 2’x4’ White w/ Craters and Pinholes Ceiling Tile Gray, Fibrous Homogeneous

None Detected 40% Cellulose 30% Nonfibrous

30% Glass

< = Less than the number shown Page 2 of 5

10 0800912-RN Cart Wash Area North Wall

Gypsum Wallboard Tan, Cementitious Homogeneous

None Detected 3% Cellulose 95% Nonfibrous

2% Glass 11 0800912-RO Cart Wash Area

North Wall Joint Compound White, Cementitious Homogeneous

None Detected 100% Nonfibrous

12 0800912-RP Shower Room (west) West Wall

Gypsum Wallboard Tan, Cementitious Homogeneous

None Detected 5% Cellulose 90% Nonfibrous

5% Glass 13 0800912-RQ Shower Room (west)

West Wall Joint Compound White, Cementitious Homogeneous

None Detected <1% Cellulose 99% Nonfibrous

14 0800912-RR Clean Linen Room

West Wall Gypsum Wallboard Tan, Cementitious Homogeneous

None Detected 5% Cellulose 90% Nonfibrous

5% Glass 15 0800912-RS Clean Linen Room

West Wall Joint Compound White, Cementitious Homogeneous

None Detected 99% Nonfibrous <1% Glass

16 0800912-RT Back Stairway North Wall

CMU Coating Tan, Cementitious Homogeneous

None Detected 100% Nonfibrous

17 0800912-RU Basement North Wall

CMU Coating Gray, Cementitious Homogeneous

None Detected <1% Cellulose 99% Nonfibrous

18 0800912-RV Back Entrance

South Wall CMU Coating Gray, Cementitious Homogeneous

None Detected 100% Nonfibrous

< = Less than the number shown Page 3 of 5

19 0800912-RW Basement North End

Fireproofing White, Fibrous Homogeneous

None Detected 95% Cellulose 5% Nonfibrous

20 0800912-RX Basement

East End Fireproofing White, Fibrous Homogeneous

None Detected 95% Cellulose 5% Nonfibrous

21 0800912-RY Basement

West End Fireproofing White, Fibrous Homogeneous

None Detected 97% Cellulose 3% Nonfibrous

22 0800912-RZ Shower Room (west)

West Wall Adhesive (for baseboard) Tan, Cementitious Homogeneous

None Detected 98% Nonfibrous 2% Glass

23 0800912-SA Clean Linen Room West Wall

Adhesive (for baseboard) Brown, Cementitious Homogeneous

None Detected <1% Cellulose 98% Nonfibrous

<1% Hair 24 0800912-SB Lunch Room

North End Window Glazing (on reinforced window) White, Cementitious

3% Chrysotile 97% Nonfibrous

25 0800912-SC Mechanical Room

HVAC Duct Wrap Tan, Cementitious Homogeneous

None Detected 3% Cellulose 90% Nonfibrous

2% Glass 5% Talc

26 0800912-SD Basement North End

Encapsulant on Fiberglass Insulation White, Cementitious Homogeneous

None Detected 3% Cellulose 90% Nonfibrous

2% Glass

27 0800912-SE Issue Room East End

Encapsulant on Fiberglass Insulation White, Cementitious Homogeneous

None Detected 85% Nonfibrous 15% Glass

< = Less than the number shown Page 4 of 5

28 0800912-SF Exterior by Receiving

Window Caulk Gray, Cementitious Homogeneous

None Detected 3% Cellulose 97% Nonfibrous

29 0800912-SG Exterior by Receiving Window Glazing Black, Cementitious Heterogeneous

None Detected 10% Cellulose 85% Nonfibrous

5% Synthetic 30 0800912-SH Exterior by Mechanical Room Window Caulk Gray, Cementitious

31 0800912-SI Exterior by Issuing

Window Glazing Gray, Cementitious Homogeneous

3% Chrysotile 2% Cellulose 94% Nonfibrous

<1% Glass 32 0800912-SJ Exterior by Basement Window Caulk Tan, Cementitious

5% Chrysotile 95% Nonfibrous

33 0800912-SK Exterior by Basement

Window Glazing Gray, Cementitious

2% Chrysotile 98% Nonfibrous

34 0800912-SL Exterior

Air Vent Caulk Gray, Cementitious

5% Chrysotile 95% Nonfibrous

35 0800912-SM Exterior by Mechanical Room

Window Glazing (on garage door) White, Cementitious

36 0800912-SN Exterior by Back Stairway

Garage Door Caulk Gray, Cementitious Homogeneous

5% Chrysotile <1% Cellulose 94% Nonfibrous

< = Less than the number shown Page 5 of 5

37 0800912-SO Exterior North End

Penetration Putty (on electric conduit) Gray, Cementitious Homogeneous

5% Chrysotile <1% Cellulose 93% Nonfibrous

<1% Glass 38 0800912-SP Roof

North End Asphalt Shingle Back, Cementitious, Fibrous Heterogeneous

None Detected 70% Nonfibrous 30% Glass

39 0800912-SQ Roof North End

Tarpaper Black, Cementitious Homogeneous

None Detected 50% Nonfibrous 50% Glass