Bldg 10 - Narrative Report.pdf
PDF 1 MB Posted
- Solicitation number
- 36C26322Q0029
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Narrative Report.pdf | ||
| Roofing diagram.pdf | ||
| Explanation of Attachments.docx | DOCX document | |
| Bldg 40 - Narrative Report.pdf | ||
| Bldg 39 - Narrative Report.pdf | ||
| Tunnels - Narrative Report.pdf | ||
| 36C26322Q0029 0001.pdf | ||
| Volume 2.pdf | ||
| Bldg 11 - Narrative Report.pdf | ||
| Volume 1.pdf | ||
| Attachment 3 - EC-26 Confined Space.docx | DOCX document | |
| Bldg 30 - Narrative Report.pdf | ||
| Bldg 13 - Narrative Report.pdf | ||
| Bldg 12 - Narrative Report.pdf | ||
| P15 Drawings.pdf | ||
| QA.docx | DOCX document | |
| Bldg 3 - Narrative Report.pdf | ||
| C03 36C26322Q0029.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING #10
LEGEND No. 0800912
TABLE OF CONTENTS
ITEM
NARRATIVE REPORT
1.0 BUILDING INTRODUCTION
2.0 ASBESTOS SURVEY INFORMATION
2.1 SUSPECT MATERIALS IDENTIFIED AND SAMPLED
2.2 ASBESTOS CONTAINING MATERIALS
2.3 COST ESTIMATES
ACM LOCATIONS/FRIABLE MATERIALS ASSESSMENTS TABLE
ACM LOCATIONS DIAGRAMS
LABORATORY DATA
ASBESTOS BULK SAMPLE RESULTS TABLE
ASBESTOS BULK SAMPLE LOCATIONS DIAGRAM
LEGEND No. 0800912 BUILDING #10 Page 1 of 3
1.0 BUILDING INFORMATION
Building #10 was originally constructed in 1945 and a 1976 renovation extended the building to the south; limited renovations are evident in the building.
The interior floor finishes included floor tile, ceramic tile, and concrete; the interior wall finishes included gypsum wallboard, concrete block, concrete, plaster, and brick; and the interior ceiling finishes included concrete and metal. The roofing system is a flat rubber-membrane roof; the exterior of the structure is brick.
The piping systems were insulated; fiberglass insulation (without hard fittings), millboard insulation (with hard fittings), and mag block insulation (with hard fittings) are located throughout the structure. Generator breeching and boiler breeching were observed in the structure. HVAC systems located in the structure consisted of steam radiators, electric radiators, and a forced air furnace equipped with heating coils.
2.0 ASBESTOS SURVEY INFORMATION
Building #10 was surveyed as part of a larger project for the VA. This report is part of “Volume 2” of a two volume series. This report includes building specific information only; please refer to the opening section of “Volume 2” for methodologies, definitions, and other pertinent supporting information.
A total of 48 samples were collected from suspect asbestos-containing materials (ACM) on October 15, 2008 and an additional 11 samples were collected on November 12, 2008.
Laboratory analysis results indicate 16 of these samples tested positive for asbestos.
2.1 Suspect Materials Identified and Sampled
Floor Tile (multiple types) Floor Tile Mastic (multiple types) Adhesive (multiple types) Ceiling Tile (multiple types) Gypsum Wallboard Joint Compound Plaster- Skimcoat Plaster- Basecoat CMU Coating Foundation Coating (multiple types) Hard Fittings on Mag Block Pipe Insulation Mag Block Pipe Insulation Window Glazing (multiple type) Sink Undercoating HVAC Canvas Connector Tank Insulation (multiple types) Generator Breeching Boiler Breeching Encapsulant on Fiberglass Insulation (multiple types) Gasket (on boiler) Building Seam Caulk (multiple types) Door Caulk (multiple types) Window Caulk (multiple types) Penetration Putty Air Vent Caulk (multiple types) Flashing Hard Fitting on Millboard Pipe Insulation Millboard Pipe Insulation
The Asbestos Bulk Sample Results Table includes asbestos sampling data.
LEGEND No. 0800912 BUILDING #10 Page 2 of 3
2.2 Asbestos Containing Materials
Mastic for 12” Gray/White Mottled Floor Tile Mastic for 12” Cream w/ Tan/Gray Clouds Floor Tile Hard Fitting on Mag Block Pipe Insulation Window Glazing (multiple type) Black Sink Undercoating White HVAC Canvas Connector Blow-Down Tank Insulation Boiler Breeching Door Caulk (1 type) Window Caulk (1 type) Hard Fitting on Millboard Pipe Insulation Millboard Pipe Insulation
The ACM Locations/ Friable Materials Assessments Table includes ACM locations data.
2.3 Cost Estimates
Legend Technical Services Inc. estimates abatement costs (removal & disposal) of ACM as follows:
ACM QUANTITY UNIT COST TOTAL COST
Asbestos Floor Tile Mastic (all types) 261 ft2 $10.00/ft2 $2,610.00 Asbestos Pipe Insulation (all types) 38 ft
127 fittings $25.00/ft
$60.00/fitting $8,570.00 Asbestos Window Glazing (all types) 39 ea $225.00/ea $8,775.00 Asbestos Sink Undercoating 2 ea $150.00/ea $300.00 Asbestos HVAC Canvas Connector 1 ea $250.00/ea $250.00 Asbestos Tank Insulation 1 ea $2,500.00/ea $2,500.00 Asbestos Boiler Breeching 3 ea $5,000.00/ea $15,000.00 Asbestos Door/Window Caulk 3 ea $125.00/ea $375.00
Total Estimated Abatement Costs: $38,380.00
2.4 Survey Notes
LEGEND identified and sampled tank insulation on the blow-down tank in the mechanical room;
a review of the data indicates the insulation contains asbestos. The tank is approximately 7’ tall and 4’ in diameter (113 ft2).
LEGEND identified and sampled boiler breeching on 3 exhaust stacks, one for each boiler, in the boiler room; a review of the data indicates the breeching contains asbestos. Each exhaust stack is approximately 28’ tall and 4’ in diameter for the vertical portion and 15’ tall, 3’ wide, and 5’ long for the horizontal portion (557 ft2 each).
LEGEND identified and sampled Mag Block Pipe Insulation and Hard Fittings in the building; a review of the data indicates all samples of the Mag Block Pipe Insulation and two samples (#54, #57) of the Hard Fittings did not contain asbestos. However, one sample (#19) of the Hard
LEGEND No. 0800912 BUILDING #10 Page 3 of 3
Fittings on Mag Block Pipe Insulation tested positive for asbestos; all the Hard Fittings on Mag Block Pipe Insulation appear identical (homogeneous). A review of available records indicates the piping in the building was abated in the earlier 1980s and re-insulated. LEGEND believes the pipes were re-insulated with non-ACM Mag Block Pipe Insulation and a mix of non-ACM/ACM Hard Fittings at that time; which would be consistent with the tunnel system which was abated/re-insulated at the same time. Due to this, all Hard Fittings on Mag Block Pipe Insulation (including elbows and T-fittings) must be treated as ACM.
LEGEND TECHNICAL SERVICES, INC.
LEGEND No. 0800912 (VA)
ROOM/
ACM
ACM TYPE
(SAMPLE #)
EST.
QUANTITY
MATERIAL
CONDITION
DAMAGE
POTENTIAL
HIGH
M
OD
LOW
ASSESS.
CAT.1 NOTES ABATEMENT INFORMATION
* = Non-Friable materials were not assessed Page 1 of 3
Bathroom (2nd Floor) Mastic for 12” Cream w/ Tan/Gray Clouds Floor Tile
Non-Friable Miscellaneous (4)
42 ft2 N/A* N/A* N/A* The mastic contains asbestos; the floor tile is negative.
LEGEND #: ____________________
Date: ________________________
Boiler Room
White HVAC Canvas Connector
Non-Friable Miscellaneous (22)
1 ea N/A* N/A* N/A* The canvas connector is on the AHU in the southwest corner of the room, upper level.
Boiler Breeching
Friable
TSI
(29,30,31)
3 ea
Damaged Physical
Air Erosion Vibration
1 The boiler breeching is on the exhaust stacks for all 3 boilers (Boiler #2 is partially abated).
Millboard Pipe Insulation
Friable
TSI
(52)
1 feet Significantly Damaged
Physical Air Erosion Vibration
1 The millboard insulation is on a domestic water pipe penetrating the north wall (residual).
Hard Fittings on Mag Block Pipe Insulation
Friable
TSI
(19)
115 ea Good Physical Air Erosion Vibration
6 The hard fittings are throughout the boiler room, both levels.
Entry
Door Caulk Non-Friable Miscellaneous (36)
1 ea N/A* N/A* N/A* The door caulk is around the door on the east end of the room.
Mechanical Room
Blow-Down Tank Insulation
Friable
TSI
(23)
1 ea
Significantly Damaged
Physical Air Erosion Vibration
1 The tank is in the southeast corner of the room.
Insulation and Hard Fittings
Friable
TSI
(50,52)
27 feet 3 fittings
Significantly Damaged
Physical Air Erosion Vibration
1 The millboard insulation and hard fittings are at ceiling level along the east and south walls.
ACM TYPE
(SAMPLE #)
EST.
QUANTITY
MATERIAL
CONDITION
DAMAGE
POTENTIAL
HIGH
M
* = Non-Friable materials were not assessed Page 2 of 3
Block Pipe Insulation
Friable
TSI
(19)
6 ea Good Physical Air Erosion Vibration
6 The hard fittings are on the west end of the room by the stairs.
Office (1st Floor)
Gray/White Mottled Floor Tile
Non-Friable Miscellaneous (2)
125 ft2 N/A* N/A* N/A* The mastic contains asbestos; the
Black Sink Undercoating
Non-Friable Miscellaneous (21)
1 ea N/A* N/A* N/A* The undercoating is on the sink in the southeast corner of the room.
Window Glazing Non-Friable
Miscellaneous (20)
1 ea N/A* N/A* N/A* The glazing is around the window on the north end of the room (window to boiler room).
Office (2nd Floor)
Cream w/ Tan/Gray Clouds Floor Tile
Non-Friable Miscellaneous (4)
74 ft2 N/A* N/A* N/A* The mastic contains asbestos; the
Work Room (1st Floor)
Mastic for 12” Gray/White Mottled Floor Tile
Non-Friable Miscellaneous (2)
20 ft2 N/A* N/A* N/A* The mastic contains asbestos; the floor tile is negative. It is located by the entry to the office.
Black Sink Undercoating
Non-Friable Miscellaneous (21)
1 ea N/A* N/A* N/A* The undercoating is on the sink in the northwest corner of the room.
Block Pipe Insulation
Friable
TSI
(19)
2 ea Good Physical Air Erosion Vibration
6 The hard fittings are by the unit heater along the east wall (they are T-fittings).
ACM TYPE
(SAMPLE #)
EST.
QUANTITY
MATERIAL
CONDITION
DAMAGE
POTENTIAL
HIGH
M
* = Non-Friable materials were not assessed Page 3 of 3
Work Room (2nd Floor)
Insulation and Hard Fittings
Friable
TSI
(50,52)
10 feet 1 fitting
Good Physical Air Erosion Vibration
6 The millboard insulation is along the south wall.
Exterior
Door Caulk Non-Friable Miscellaneous (36)
1 ea N/A* N/A* N/A* The door caulk is around the door to the entry on the west end of the building.
Window Caulk Non-Friable
Miscellaneous (39)
1 ea N/A* N/A* N/A* The window caulk is around the window to the entry on the west end of the building.
Window Glazing Non-Friable
Miscellaneous (40,41)
38 ea N/A* N/A* N/A* Refer to the ACM Locations Diagram for exact locations.
1Assessment Categories:
1) Damaged or Significantly Damaged TSI ACM 5) ACM with Potential for Damage
2) Damaged Friable Surfacing ACM 6) ACM with Potential for Significant Damage
3) Significantly Damaged Friable Surfacing ACM 7) Any Remaining Friable ACM or Friable Suspected ACM
4) Damaged or Significantly Damaged Friable Miscellaneous ACM
End
LABORATORY DATA
MATERIAL/
SAMPLE NO. LAB NO. LOCATION PHYSICAL DESCRIPTION ASBESTOS CONTENT BALANCE OF MATERIAL
< = Less than the number shown Page 1 of 7
1 0800912-NV 1st Floor Office North End
12” Gray/White Mottled Floor Tile Gray, Cementitious Homogeneous
None Detected <1% Cellulose 99% Nonfibrous
2 0800912-NW 1st Floor Office North End
Mastic for Sample #1 Black, Cementitious Homogeneous
5% Chrysotile 3% Cellulose 92% Nonfibrous
3 0800912-NX 2nd Floor Bathroom West End
12” Cream w/ Tan/Gray Clouds Floor Tile Gray, Cementitious Homogeneous
None Detected 100% Nonfibrous
4 0800912-NY 2nd Floor Bathroom West End
Mastic for Sample #3 Black, Cementitious Homogeneous
5% Chrysotile 95% Nonfibrous
5 0800912-NZ 1st Floor Office Southeast Corner
Adhesive (for baseboard) Brown, Cementitious Homogeneous
None Detected 3% Cellulose 97% Nonfibrous
6 0800912-OA 2nd Floor Bathroom West End
Adhesive (for baseboard) Brown, Cementitious Homogeneous
None Detected 100% Nonfibrous
7 0800912-OB 1st Floor office South End
2’x4’ White w/ Craters and Pinholes CT Gray, Fibrous Homogeneous
None Detected 60% Cellulose 30% Nonfibrous
10% Glass 8 0800912-OC 1st Floor Bathroom
South End 2’x4’ White w/ Widthwise Fissures/Pinholes CT Gray, Fibrous Homogeneous
None Detected 40% Cellulose 20% Nonfibrous
40% Glass 9 0800912-OD 1st Floor Bathroom
East End 2’x4’ White w/ Long Worms and Pinholes CT Gray, Fibrous Homogeneous
None Detected 40% Cellulose 30% Nonfibrous
30% Glass
< = Less than the number shown Page 2 of 7
10 0800912-OE 2nd Floor Office East Wall
Gypsum Wallboard White, Cementitious Homogeneous
None Detected 5% Cellulose 93% Nonfibrous
2% Glass 11 0800912-OF 2nd Floor Office
East Wall Joint Compound White, Cementitious Homogeneous
None Detected 100% Nonfibrous
12 0800912-OG 2nd Floor Office West Wall
Plaster- Skimcoat White, Cementitious Homogeneous
None Detected 100% Nonfibrous
13 0800912-OH 2nd Floor Office West Wall
Plaster- Basecoat Gray, Cementitious Homogeneous
None Detected <1% Cellulose 99% Nonfibrous
14 0800912-OI 2nd Floor Work Room East Wall
CMU Coating Gray, Cementitious Homogeneous
None Detected 100% Nonfibrous
15 0800912-OJ Mechanical Room East Wall
Foundation Coating Gray, Cementitious Homogeneous
None Detected 2% Cellulose 98% Nonfibrous
16 0800912-OK Boiler Room Feedwater Pipe (Blue)
Mag Block Pipe Insulation (straight) White, Cementitious Homogeneous
None Detected 20% Cellulose 70% Nonfibrous
10% Hair 17 0800912-OL Boiler Room
Condensate Pipe (Brown)
Mag Block Pipe Insulation (straight)
None Detected 15% Cellulose 70% Nonfibrous
15% Glass 18 0800912-OM Boiler Room
High Pressure Steam Pipe (Orange)
Mag Block Pipe Insulation (valve)
None Detected 90% Nonfibrous 10% Glass
< = Less than the number shown Page 3 of 7
19 0800912-ON Boiler Room Low Pressure Steam Pipe (Yellow)
Hard Fitting on Mag Block Pipe Insulation White/Gray, Cementitious Heterogeneous
5% Chrysotile 10% Cellulose 75% Nonfibrous
10% Glass 20 0800912-OO 1st Floor Office
North End Window Glazing Gray, Cementitious
3% Chrysotile 97% Nonfibrous
21 0800912-OP 1st Floor Work Room Northwest Corner
Black Sink Undercoating Black, Cementitious
5% Chrysotile 95% Nonfibrous
22 0800912-OQ Boiler Room Southwest Corner
White HVAC Canvas Connector White, Fibrous
80% Chrysotile 20% Cellulose
23 0800912-OR Mechanical Room Blow-Down Tank
Tank Insulation (side) White, Fibrous Homogeneous
30% Amosite 50% Nonfibrous 20% Glass
24 0800912-OS Mechanical Room Blow-Down Tank
Tank Insulation (end) White, Fibrous Homogeneous
None Detected 15% Cellulose 55% Nonfibrous
25% Glass 5% Mica
25 0800912-OT Boiler Room De-Aerator Tank
Tank Insulation (side) Gray, Fibrous Homogeneous
None Detected 35% Cellulose 45% Nonfibrous
20% Glass 26 0800912-OU Boiler Room
De-Aerator Tank Tank Insulation (end) Gray, Fibrous Homogeneous
None Detected 30% Cellulose 50% Nonfibrous
20% Glass 27 0800912-OV Generator Room
West End Generator Breeching (straight) Gray, Fibrous Homogeneous
None Detected 30% Cellulose 50% Nonfibrous
20% Glass
< = Less than the number shown Page 4 of 7
28 0800912-OW Generator Room West End
Generator Breeching (elbow) Gray, Fibrous Homogeneous
None Detected 30% Cellulose 45% Nonfibrous
20% Glass 5% Mica
29 0800912-OX Boiler Room Exhaust Stack #1 by Boiler #1
Boiler Breeching (vertical) Gray, Fibrous Homogeneous
3% Chrysotile 5% Cellulose 62% Nonfibrous
30% Glass 30 0800912-OY Boiler Room
Exhaust Stack #1
Boiler Breeching (horizontal) Gray, Fibrous Homogeneous
5% Chrysotile 75% Nonfibrous 20% Glass
31 0800912-OZ Boiler Room Exhaust Stack #1 by Boiler #1
Boiler Breeching (access hatch) Gray, Fibrous Homogeneous
5% Chrysotile 70% Nonfibrous 15% Glass 10% Mica
32 0800912-PA Mechanical Room North End
Encapsulant on Fiberglass Insulation White, Cementitious Homogeneous
None Detected 95% Nonfibrous 5% Glass
33 0800912-PB Boiler Room by Boiler #3
Encapsulant on Fiberglass Insulation White, Cementitious Homogeneous
None Detected 3% Cellulose 97% Nonfibrous
34 0800912-PC Boiler Room
Gasket (on boiler #1) Gray, Cementitious Homogeneous
None Detected 100% Nonfibrous
35 0800912-PD Boiler Room East End
Building Seam Caulk White, Cementitious Homogeneous
None Detected 100% Nonfibrous
36 0800912-PE Exterior West End
Door Caulk White, Cementitious
3% Chrysotile 97% Nonfibrous
< = Less than the number shown Page 5 of 7
37 0800912-PF Exterior East End
Door Caulk Gray, Cementitious Homogeneous
None Detected 98% Nonfibrous 2% Glass
38 0800912-PG Exterior East End
Window Caulk Gray, Cementitious Homogeneous
None Detected 95% Nonfibrous 5% Synthetic
39 0800912-PH Exterior West End by Entry
Window Caulk (small window) White, Cementitious Homogeneous
3% Chrysotile 2% Cellulose 95% Nonfibrous
40 0800912-PI Exterior by Entry
Window Glazing (small window) Gray, Cementitious Homogeneous
2% Chrysotile 97% Nonfibrous <1% Glass
41 0800912-PJ Exterior East End
Window Glazing (large windows) Gray, Cementitious Homogeneous
2% Chrysotile 97% Nonfibrous <1% Glass
42 0800912-PK Exterior West End
Penetration Putty Gray, Cementitious Homogeneous
None Detected 10% Cellulose 90% Nonfibrous
43 0800912-PL Exterior
South End Air Vent Caulk Gray, Cementitious Homogeneous
None Detected 100% Nonfibrous
44 0800912-PM Exterior South End
Air Vent Caulk Gray, Cementitious Homogeneous
None Detected 100% Nonfibrous
45 0800912-PN Exterior West End
Building Seam Caulk Gray, Cementitious
None Detected 100% Nonfibrous
< = Less than the number shown Page 6 of 7
46 0800912-PO Exterior
Building Seam Caulk White, Cementitious Homogeneous
None Detected 2% Cellulose 98% Nonfibrous
47 0800912-PP Exterior West End
Foundation Coating Gray, Cementitious Homogeneous
None Detected 99% Nonfibrous <1% Glass
48 0800912-PQ Roof South End
Flashing (on perimeter) Black, Cementitious Homogeneous
None Detected 100% Nonfibrous
49 0800912-ZF Boiler Room Feedwater Piping (Blue)
Mag Block Pipe Insulation (encapsulant) Gray, Cementitious Homogeneous
None Detected 15% Cellulose 65% Nonfibrous
20% Glass 50 0800912-ZG Mechanical Room
Domestic Water Piping Northeast Corner
Hard Fitting on Millboard Pipe Insulation White, Fibrous Homogeneous
25% Chrysotile 5% Amosite
10% Cellulose 55% Nonfibrous
5% Glass 51 0800912-ZH Mechanical Room
High Pressure Steam Piping (Orange)
Mag Block Pipe Insulation (encapsulant) Gray, Cementitious Homogeneous
None Detected 30% Cellulose 30% Nonfibrous
40% Glass 52 0800912-ZI Mechanical Room
Domestic Water Piping Northeast Corner
Millboard Pipe Insulation Tan/Gray/Black, Fibrous Layered
5% Chrysotile 80% Cellulose 15% Nonfibrous
53 0800912-ZJ Boiler Room
Low Pressure Steam Piping (Yellow)
Mag Block Pipe Insulation (straight) White, Cementitious Homogeneous
85% Nonfibrous
54 0800912-ZK Boiler Room
Condensate Piping (Brown)
Hard Fitting on Mag Block Pipe Insulation White, Cementitious Homogeneous
< = Less than the number shown Page 7 of 7
55 0800912-ZL Boiler Room High Pressure Steam Piping (Orange)
Mag Block Pipe Insulation (straight) White, Cementitious Homogeneous
56 0800912-ZM Boiler Room
Low Pressure Steam Piping (Yellow)
Mag Block Pipe Insulation (valve) Gray, Cementitious Homogeneous
None Detected 20% Cellulose 75% Nonfibrous
5% Glass 57 0800912-ZN Boiler Room
High Pressure Steam Piping (Orange)
Hard Fitting on Millboard Pipe Insulation Gray, Cementitious Homogeneous
None Detected 15% Cellulose 70% Nonfibrous
10% Glass 5% Wollastonite
58 0800912-ZO Boiler Room Northwest Corner Steam Manifold (Orange)
Mag Block Pipe Insulation (end) Gray, Cementitious Homogeneous
None Detected 15% Cellulose 82% Nonfibrous
3% Glass 59 0800912-ZP Boiler Room
Northwest Corner Steam Manifold (Orange)
Mag Block Pipe Insulation (side) Gray, Fibrous Homogeneous
None Detected 10% Cellulose 60% Nonfibrous
20% Glass 10% Wollastonite