S06 Amendment A003_ DWG T-001.pdf

PDF 519 KB Posted

Attached to
Z2DA--EHRM GLA Main Campus Construction, Project 691-20-200 Federal contract opportunity
Solicitation number
36C26221B0009
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22

About this file

This solicitation notice provides details for an upcoming construction services project at the VA West Los Angeles Healthcare System located in Los Angeles, California. The project scope includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures to complete Electronic Health Record Modernization Infrastructure Upgrades. The work will be performed in a functioning hospital environment. The North American Industry Classification Code is 236220, Commercial and Institutional Building Construction with a Size Standard of $39.5M. The construction project magnitude is between $20,000,000 to $50,000,000. The solicitation will be issued as an Invitation for Bid on or around July 13, 2021 via www.sam.gov. A mandatory site visit will be scheduled to review the scope of work. This requirement is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses listed on www.vip.vetbiz.va.gov.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--EHRM GLA Main Campus Construction, Project 691-20-200, newest first.
File Type Posted
S06 Amendment A003_COR RFIs_Job Walk Roster_DWGs_GLA EHRM CON_36C26221B0009.pdf PDF
S06 Amendment A003_ DWG 527_E-111.pdf PDF
S06 Amendment A003_ DWG 527_T-111.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part2.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part4.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part3.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part1.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part5.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part6.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part7.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4_1_ 42 x 30_Part3.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4_1_ 42 x 30_Part1.pdf PDF
691-20-200 Elect 100 Final Drawings Part 3_1_ 42 x 30.pdf PDF
691-20-200 Strut-Mech 100 Final Drawings Part 2_ 42 x 30.pdf PDF
S06 Amentment A0002_EHRM GLA Main Campus_691-20-200_36C26221B0009.docx DOCX document
691-20-200 Architectural 100 Final Drawings Part 1_ 42 x 30_ Part1.pdf PDF
691-20-200 Architectural 100 Final Drawings Part 1_ 42 x 30_ Part2.pdf PDF
S06 A0001_Wage Rates_36C26221B0009.pdf PDF
S02 ATTACHMENT A_ SOW.pdf PDF
S02 ATTACHMENT E_ Drawings Part 1 of 5_Architectural.pdf PDF
S02 ATTACHMENT C_ Wage Rates 6-25-21.pdf PDF
S02 ATTACHMENT I_ Drawings Part 5 of 5_ Telecommunication_Part2.pdf PDF
S02 ATTACHMENT J_ Facility Map.pdf PDF
S02 Solicitation 36C26221B0009_1.pdf PDF
S02 ATTACHMENT D_ GLA Safety Req_Permits_Forms.pdf PDF
S02 ATTACHMENT F_ Drawings Part 2 of 5_Strut-Mech.pdf PDF
S02 ATTACHMENT H_ Drawings Part 4 of 5_ Telecommunication_Part1.pdf PDF
S02 ATTACHMENT B_ Specifications.pdf PDF
S02 ATTACHMENT G_ Drawings Part 3 of 5_Elect.pdf PDF
36C26221B0009.docx DOCX document
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONCRETE

WALK

RAMP DN

RAMP DOWN

STAIR

RAMP DOWN

A

B

C

D

E

F G

H

J

K

L

M

N

O

P

Q

R

S

FIRE PENETRATIONS NOTE

- M -

MAIN CIRCUIT BREAKER

NEUTRAL

MCB

N

- N -

PHASE

POWER

PANEL

PWR

PNL

- R -

- P -

ROOM

RECEPTACLE

RM

RECEPT

- B -

AMPERE

- A -

A

- C -

CIRCUIT

CIRCUIT BREAKER

BUILDING

CONDUIT

BLDG

CKT

C

CB

- E -

EG

- G -

GROUNDG, GND

EQUIPMENT GROUND

ABBREVIATIONS

VOLT OR VOLTAGE

VOLT AMPEREVA

V

- V -

WATTW

- W -

- J -

- K -

KILOVOLT AMPERE

KILOVOLT

JUNCTION BOX

KV

KW

KVA

JB

KILOWATT

ABOVE FINISHED FLOORAFF

UON UNLESS OTHERWISE NOTED

- U -

E1.01

AC

X

MOTOR TYPE

REVISION

RISER TAGPOINT OF CONNECTION

SCHEDULE NUMBER

# LIGHT FIXTURE TYPE

INDICATES DETAIL NUMBER

SHEET NUMBER TO FIND DETAIL

SPECIFIC NOTE/

POINT OF DISCONNECTION

REFERENCE NOTE

ANNOTATIONS

EWC ELECTRIC WATER COOLER

T-001

TELECOMMUNICATIONS

GENERAL NOTES:

ABBREVIATIONS VA

EHRM ELECTRONIC HEALTH RECORD MODERNINATION

CERNER INFORMATION TECHNOLOGY COMPANY

CEDT CERNER EHRM DEPLOYMENT TEAM

EUD END USER DEVICE

CIH CERTIFIED INDUSTRIAL HYGIENIST

LBVAMC LONG BEACH VA MEDICAL CENTER

MDF MAIN DISTRIBUTION FRAME

TR TELECOMMUNICATIONS ROOM

OIT OFFICE OF INFORMATION TECHNOLOGY

3D

3D

WALL MTD DATA OUTLET

W/3 CAT 6A DROPS

FLOOR MTD DATA OUTLET

W/3 CAT 6A DROPS

SEE DRAWING T-504

ABBREVIATIONS IT

SM

MM

SFP

ORL

OTDR

UTP

LAN

SINGLE MODE FIBER

MULTI MODE FIBER

SMALL FORM FACTOR PLUGGABLE TRANSCEIVER

OPTICAL RETURN LOSS

OPTICAL TIME DOMAIN REFLECTOMETER

UNSHIELDED TWISTED PAIR

LOCAL AREA NETWORK

EIA

TIA

OS1, OS2

OS2

ELECTRONIC INDUSTRIES ASSOCIATION

TELECOMMUNICATION INDUSTRY ASSOCIATION

TYPE OF SINGLE MODE FIBER

AIR BLOWN SINGLE MODE FIBER

1. PROVIDE EQUIPMENT SUBMITTALS AND SHOP DRAWINGS IN ACCORDANCE

WITH THE SPECIFICATIONS AND THE PROJECT SCHEDULE. NO INSTALLATION

SHALL PROCEED WITHOUT APPROVAL OF THE SHOP DRAWINGS.

2. MINIMAL STORAGE WILL BE AVAILABLE ON THE CONSTRUCTION SITE. CABLING

CONTRACTOR RESPONSIBLE FOR RECEIVING AND STORING MATERIALS AND

FOR COORDINATING MATERIALS DELIVERY TO THE JOB-SITE.

3. COMMUNICATIONS CABLES INSTALLED SHALL BE INSTALLED IN ACCORDANCE

WITH THE REQUIREMENTS DETAILED HEREIN AND SHALL BE FREE OF KINKS,

TWISTS, SHARP BENDS, UNNECESSARY LOOPS OR WORKMANSHIP DEFECT.

4. PROPERLY SEAL WALL PENETRATIONS THROUGH FIRE RATED WALL & FLOOR

USING EZ PATH DETAILED ON T-504.

5. RUN OPEN CABLE FOR EACH SYSTEM IN SLEEVES, J-HOOKS DEDICATED FOR

THE SYSTEM.

6. SEPARATE AND BUNDLE CABLE BY SYSTEM.

7. MAINTAIN EIA/ TIA RECOMMENDED SEPARATIONS BETWEEN CABLING OF

DIFFERENT SYSTEMS. 6'' FROM LIGHT FIXTURES. 24'' FROM 480V & 12'' FROM

208V.

8. MAINTAIN RECOMMENDED SEPARATIONS BETWEEN CABLING AND

INTERFERENCE PRODUCING ELECTRICAL DEVICES SUCH AS POWER CABLING,

ELECTRICAL PANELS, FLUORESCENT LIGHTS, BALLAST RELAYS, ELECTRIC

MOTORS, MOTOR CONTROLLERS, VFD, TRANSFORMERS AND OTHER

ELECTROMAGNETIC DEVICES. SEE NOTE 7.

9. WHERE CABLE IS OPEN ON J-HOOK SYSTEM, RUN PARALLEL OR

PERPENDICULAR TO WALLS AND SUPPORT A MINIMUM OF EVERY 5 FEET USING

APPROVED J-HOOKS.

10. ALL CABLE HOOKS AND OTHER CABLE SUPPORT DEVICES SHALL BE ATTACHED

TO THE BUILDING STRUCTURE IN ACCORDANCE WITH CODES AND

SPECIFICATIONS.

11. NO OPEN CABLE SHALL BE DRAPED OVER OR SUPPORTED ON PLUMBING,

ELECTRICAL, MEDICAL GAS, FIRE SUPPRESSION, OR OTHER PIPING OR

DUCTWORK.

12. ALL CABLES TO BE PLENUM RATED.

13. THE CABLE LENGTH FROM THE TERMINATION POINT IN TR TO EUD IN THE

WORK AREA SHALL NOT EXCEED 295FEET INDEPENDENT OF MEDIA TYPE.

14. THE 295FEET INCLUDES AN ALLOWANCE OF 10FEET FROM EUD TO DEVICE AND

AN ADDITIONAL 24 FEET FROM PATCH PANEL TO ACTIVE COMPONENTS IN TR.

15. VISUALLY INSPECT CONNECTIONS ON CABLE TO ENSURE PROPER COMPLIANCE

WITH EIA/TIA 568B TERMINATION.

16. INSPECT ALL EXPOSED PORTIONS OF THE CABLE TO INSURE A MINIMUM OF 4

TIMES THE CABLE DIAMETER BEND RADIUS AT ANY POINT.

17. ENSURE NO CABLE BUNDLES OR TIE POINTS DISPLAY KINKS, SHARP BENDS,

CREASING OR DEFORMATION OF OUTER SHEATH OR SIGNS OF EXCESSIVE

PULLING FORCE.

18. IN TR CABLES SHOULD BE COMBED AND DRESSED UP BEFORE BUDLING AND

USING VELCRO STRAPS. ZIP TIES OR TWIST TIES SHALL NOT BE USED. STRAPS

SHALL BE SPACED AT APPROPRIATE DISTANCE TO ENSURE CABLES ARE HELD

TOGETHER.

19. ON THE RACK THE CABLES SHOULD BE DIVIDED IN THE MIDDLE, WHERE HALF

FLOWS TO THE LEFT AND HALF FLOWS TO THE RIGHT.

20. ALL CABLING SHALL BE INSTALLED BY CABLE MANUFACTURER'S CERTIFIED

INSTALLER.

21. BEFORE ACCEPTANCE OF ANY NEWLY INSTALLED COMMUNICATIONS WIRING,

THE CABLE WILL UNDERGO SEVERAL LEVELS OF TESTING TO ENSURE THAT ALL

MATERIALS AND INSTALLATION CONFORM TO STANDARD INCLUDED IN THE

DRAWINGS AND SPECIFICATIONS. THIS WILL INCLUDE BOTH THE UTP AND FIBER

OPTICS SYSTEMS. FAILURE TO MEET THE DRAWINGS AND SPECIFICATIONS

SHALL CONSTITUTE REASON TO REJECT THE INSTALLATION UNTIL ALL

PROBLEMS ARE SOLVED.

22. ALL RECORDED TESTING RESULTS SHALL REMAIN IN THE APPROPRIATE TR.

TEST BOTH CABLES AND THEIR CORRESPONDING CONNECTING SYSTEMS AS A

WHOLE UNIT TO ENSURE SYSTEM INTEGRITY.

23. TEST ALL FIBER OPTICS CABLE AND COMPONENTS COMPRISING THE

BACKBONE SYSTEM. TEST ALL FIBER STRAND IN BOTH DIRECTION. USE OTDR

OPERATING AT BOTH 1310 AND 1550 NM WAVELENGTHS.

24. PHYSICAL LABELING FOR ALL CABLES AND RELATED COMPONENTS IS

REQUIRED COMPONENTS WILL DEPEND HEAVILY ON ADHERING TO A LOGICAL

LABELING SCHEME TO ENABLE EXPEDIENT PATCH PANEL, DATA JACK AND

SWITCH PORT IDENTIFICATION.

25. PROVIDE ALL NEW CABLING IN THE BUILDING S WITH AN AS-BUILT,

ELECTRONICALLY AND PAPER, FOR THE CABLE PLANT. EACH TR WIRING

CLOSETS CABLE PLANT AS-BUILT WILL BE INSTALLED IN A FOLDER ON THE

BACK OF THE DOOR SECURED IN A HOLDER ATTACHED TO THE DOOR.

METHOD OF PROCEDUREMOP

SPECIFIC NOTE/

REFERENCE NOTE

SECURITY SYMBOLS

A

F i l e

P a t h

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

PM EW/JB

A

C

D

20-SCE-07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMPCONSULTANT

32 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.12

691-20-200

June 15, 2021

FULLY SPRINKLERED

11301 WILSHIRE BOULEVARD

WEST LOS ANGELES, CA 90073

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA

FINAL CONSTRUCTION

DOCUMENTS

FIRE PROTECTION WALL SYMBOLS

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

- D -

DEEPD

- H -

HEIGHTH

26. CABLING DIAGRAM: SUBMIT, FOR APPROVAL, A COMPLETE CABLING DIAGRAM. THE DIAGRAM SHALL BE BASED ON THE DRAWING INCLUDED IN THE CONSTRUCTION DOCUMENTS. IT SHALL BE UPDATED TO SHOW QUANTITIES AND PART NUMBERS FOR ALL COMPONENTS INCLUDING PATCH PANELS, CABLE, SERVER CABINETS AND EQUIPMENT RACKS AND ALL OTHER ASSOCIATED COMPONENTS. INCLUDE THE

FOLLOW:

1). DETAIL AND ELEVATION DRAWINGS: PROVIDE TR RACK ELEVATION, ENLARGED TR

ROOM LAYOUT.

2). BUILDING COMPOSITE FLOOR PLANS: PROVIDE BUILDING FLOOR PLANS SHOWING WORK AREA OUTLET (WAO) OUTLET LOCATIONS AND CONFIGURATION, TYPES OF JACKS, DISTANCE FOR EACH

CABLE, AND CABLE ROUTING LOCATIONS.

3). FLOOR PLANS TO INCLUDE:

a. FINAL ROOM NUMBERS AND ACTUAL BACKBONE CABLING AND PATHWAY LOCATIONS

(HORIZONTAL AND VERTICAL) AND LABELING.

b. RISER FLOOR PENETRATION / DATA POLE LOCATION AFTER SCANNING THE FLOOR FOR

REBARS.

c. INPUTS AND OUTPUTS OF EQUIPMENT IDENTIFIED ACCORDING TO LABELS INSTALLED ON

CABLES AND EQUIPMENT.

d. DEVICE LOCATIONS WITH LABELS.

e. EZ PATH SLEEVES.

f. WIRING DIAGRAM.

g. LABELING AND ADMINISTRATION DOCUMENTATION.

SCALE: NO SCALE

TR 16SA

TR 15SA

TR 14SA

TR 13SA

TR 12SA

TR 11SA

TR 10SA

TR 16IS

TR 15IS

TR 14IS

TR 13IS

TR 12IS

TR 11IS

TR 10IS

TR 16IN

TR 15IN

TR 14IN

TR 13IN

TR 12IN

TR 11IN

TR 10IN

TR 16SE

TR 15SE

TR 14SE

TR 13SE

TR 12SE

TR 11SE

TR 10SE

PATCH CORDS TABLE

27. ALL DATA & TELEPHONE CABLES THAT ARE REMOVED WILL BE RECYCLED BY VA.

PLEASE DISPOSE OFF CABLES TO VA PROVIDED DUMPSTERS.

28. THE LOCATION OF END USER DEVICES (EUD) SHOWN ON THESE DRAWINGS ARE

APPROXIMATE AND ARE SUBJECT TO VERIFICATION BY THE CONTRACTOR.

CONTRACTOR SHALL REMOVE EXISTING EUD DATA OUTLETS AND PROVIDE NEW

EUD DATA OUTLETS AT THE SAME LOCATION.

29. ALL CAT 6A CABLES TO BE PLENUM AND POE RATED.

THE CONTRACTOR TO COORDINATE WITH VA AND REMOVE ABANDONED SYSTEMS/

ITEM IDENTIFIED BY VA. EXAMPLE INCLUDE OLD FIRE ALARM PANELS, BATTERIES

AND CHARGERS, TELEPHONE EQUIPMENT NOT IN USE, OLD 110 BLOCKS NOT IN

USE, EXISTING FIBERS, EXISTING FIBER DISTRIBUTED LINE MODULE (FOLM).

31. THE CORE AREA EUD LOCATION OF FLOORS 2-6 SHALL BE SERVED WITH CAT6A BY EITHER THE NORTH (IN) OR SOUTH (IS)INTERSTITIAL TELECOM ROOM. THIS SHOULD BE CONSISTENT FOR CORE AREAS FLOORS 2-6.

WHEN RE-CABLING EXISTING SLEEVES SHALL BE REMOVED AND NEW DRY WALL MUST BE INSTALLED

AND FINISHED BEFORE INSTALLING NEW SLEEVES.

CONTRACTOR TO REMOVE ALL 66 BLOCK AND ASSOCIATED CABLING OF ALL TR ROOM. ALL REMOVED

CABLING SHALL BE PUT IN A VA FURNISHED DUMPSTER FOR RECYCLING.

IN TR WHICH REQUIRES INSTALLATION OF FIRE RATED TELEPHONE BACKBOARDS. AFTER UNUSED DEVICES, 110 BLOCK AND OTHER ITEMS ARE REMOVED CONTRACTOR WILL DEMOUNT THE REMAINING

ITEMS, SUPPORT IT TEMPORARILY, INSTALL THE BACKBOARD AND REMOUNT ITEMS ON THE

BACKBOARD.

ALL UNUSED CABLES IN UNDERGROUND CONDUIT SYSTEM INCLUDING ASSOCIATED MANHOLES SHALL

BE PULLED OUT AND REMOVED BY CONTRACTOR AND TRANSPORTED TO VA SUPPLIED DUMPSTERS

INTENDED FOR RECYCLING BY VA. CONTRACTOR SHALL COORDINATE WITH VA WHO WILL IDENTIFY UNUSED CABLES WITHIN EACH MANHOLE. THERE ARE EXISTING LEAD SHEATHED CABLES THAT WILL

REQUIRE SPECIAL HANDLING AND COORDINATION WITH VA.

32.

33.

34.

30.

35.

BLDG. 500 INTERSTITIAL LEVEL EXISTING TR WAY FINDING MAP

TELEPHONE CABLE SCHEDULE

FIRE ALARM SYMBOLS

FIRE ALARM AUDIO/VISUAL INDICATING UNIT

AUTOMATIC FIRE ALARM SMOKE DETECTOR

ADDENDUM 08-12-2021

AUGUST 12, 2021