691-20-200 Elect 100 Final Drawings Part 3_1_ 42 x 30.pdf
PDF 38 MB Posted
- Attached to
- Z2DA--EHRM GLA Main Campus Construction, Project 691-20-200 Federal contract opportunity
- Solicitation number
- 36C26221B0009
About this file
This document provides details of an upcoming federal construction contract opportunity. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 will issue an Invitation for Bid for Project 691-20-200, Electronic Health Record Modernization Infrastructure Upgrades to be performed at the VA West Los Angeles Healthcare System located in Los Angeles, California. Work includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures. The contract will be set aside 100% for Service-Disabled Veteran-Owned Small Businesses listed in the Vendor Information Pages database. The project magnitude is estimated between $20,000,000 to $50,000,000. The solicitation will be issued on or around July 13, 2021 via the System for Award Management Contract Opportunities website.
View the file
Other files for this federal contract opportunity
Show all 30
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONCRETE
WALK
RAMP DN
RAMP DOWN
STAIR
RAMP DOWN
A
B
C
D
E
F G
H
J
K
L
M
N
O
P
Q
R
S
E-001
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
C
D
20-SCE-07
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
T
FEATURES:
PENETRATION DETAIL BELOW.
FANNULAR
ON BOTH SIDES OF WALL ASSEMBLY.
MAX PIPE
OF OPENING IS 13-1/2 IN.
SPACED MAX 24 IN. OC.
SYSTEM (ITEM 3) IS 2 H. STEEL PIPES OR CONDUITS LARGER THAN NOM 4 IN. DIA
IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY
SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRESTOP SYSTEM
THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS
A MIN 1/4 IN. DIA BEAD OF CAULK APPLIED TO PERIMETER OF PIPE OR CONDUIT AT
OF ONE PIPE OR CONDUIT IS PERMITTED IN THE FIRESTOP SYSTEM. PIPE OR CONDUIT
MAY ONLY BE USED IN WALLS CONSTRUCTED USING STEEL CHANNEL STUDS. A MAX
COPPER PIPE OR FLEXIBLE STEEL CONDUIT IS USED, MAX F RATING OF FIRESTOP
COPPER TUBING OR NOM 1 IN. DIA (OR SMALLER) FLEXIBLE STEEL CONDUIT. WHEN
(OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR TYPE L OR (OR HEAVIER)
IRON PRESSURE PIPE, NOM 6 IN. DIA (OR SMALLER) STEEL CONDUIT, NOM 4 IN. DIAM
PIPE OR CONDUIT-NOM 12 IN. DIA (OR SMALLER) SERVICE WEIGHT (OR HEAVIER)
U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX. DIAM.
FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL
TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS,
WALLBOARD, GYPSUM*-NOM 1/2 OR 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OR
BRACES. STEEL STUDS TO BE MIN. 3-5/8 IN. WIDE BY 1-3/8 IN. DEEP CHANNELS
LUMBER SPACE 16 IN OC WITH NOM 2 B Y 4 IN. LUMBER END PLATES AND CROSS
ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN.
STUDS-WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED
FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION
WALL ASSEMBLY-THE 1, 2, 3, OR 4 HR FIRE-RATED GYPSUM WALLBOARD/ STUD WALL
FIRE PENETRATIONS NOTE
EACH PENETRATION WITH ALL VARIABLES DEFINED. SEE TYPICAL FIRE
DETAILS, FURNISHED BY THE MANUFACTURER OF THE FIRE STOP MATERIAL,
HORIZONTAL OFFSET. THE CONTRACTOR SHALL SUBMIT SHOP DRAWING
RECESSED IN OPPOSITE SIDES OF RATED WALLS WITH LESS THAN A 24"
APPROVED BY THE FIRE MARSHAL. THIS INCLUDES, BUT IS NOT LIMITED
PENETRATION FIRE STOP SYSTEMS, AND SHALL BE A TESTED ASSEMBLY
BE PROTECTED BY MATERIALS AND INSTALLATION DETAILS THAT CONFORM
ALL PENETRATIONS OF FIRE RESISTIVE FLOORS, WALLS OR CEILING SHALL
ARCHITECT. THESE DRAWINGS SHALL BE AVAILABLE TO
THE FIRE MARSHAL. THE SHOP DRAWINGS SHALL BE SPECIFIC FOR
WHICH SHOW COMPLETE CONFORMANCE TO THE U.L. LISTING, TO THE
TO, ALL RACEWAY PENETRATIONS AND ELECTRICAL OUTLET BOXES
TO U.L. (UNDERWRITERS LABORATORY) LISTINGS FOR THROUGH
HOUR
0+, 1 OR 2
3 OR 4
3 OR 4
1 OR 2
HOUR
3 OR 4
1 OR 2
1 OR 2
1 OR 2
INCHES
0 TO 1/4
3/16 TO 3/8
0 TO 1-1/2#
1/4 TO 1/2
1/4 TO 1/2
0 TO 3/16
COMPLY WITH THIS DETAIL.
*BEARING THE UL CLASSIFICATION MARKING
FIRE PENETRATION DETAIL
NO SCALE
+WHEN COPPER PIPE IS USED, T RATING IS 0 H.
WB+ CAULK IS USED.
DIA, INCHES
MINNESOTA MINING & MFG. CO.-TYPES CP-25 S/L, CP-25 N/S, CP-25 WB,
CP-25 WB+. (NOTE: L RATINGS APPLY ONLY WHEN TYPE CP-25 WB CAULK IS USED.)
ALL CONDUIT PENETRATIONS THROUGH WALLS SHALL
#0 TO 1-1/2 IN. ANNULAR SPACE APPLIES ONLY WHEN TYPE CP-25
OR CONDUIT SPACE RATING, RATING,
GENERAL NOTES
AFF
AC
ATS
APPLICABLE CODES
MOTOR TYPE
REVISION
RISER TAG
POINT OF CONNECTION
SCHEDULE NUMBER
LIGHT FIXTURE TYPE
INDICATES DETAIL NUMBER
SHEET NUMBER TO FIND DETAIL SPECIFIC NOTE/
POINT OF DISCONNECTION
REFERENCE NOTE
WIRING SYMBOLS
ANNOTATIONS
LIGHTING SYMBOLS
SINGLE LINE SYMBOLS
PANELBOARD
AUTOMATIC TRANSFER SWITCH (ATS)
GROUNDED TRANSFORMER
CIRCUIT BREAKER WITH AMP TRIP OVER AMP FRAME
SWITCH
FUSE
POWER SYMBOLS
NON-FUSED DISCONNECT SWITCH
EXISTING 2 X 4 FIXTURE
NEW 1 X 4 FIXTURE
LIGHT SWITCH WITH OCCUPANCY SENSOR
FIRE ALARM SYMBOLS
AUTOMATIC FIRE ALARM SMOKE DETECTOR
SPRINKLER HEAD
QUAD RECEPTACLE
FIRE PROTECTION WALL SYMBOLS
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
SPECIAL OUTLET
A. CONCEALED IN SPACE ABOVE HUNG CEILING AND WALL: EMT CONDUIT.
SIZE AS SHOWN ON DRAWINGS AND SHALL MEET NEC REQUIREMENTS. INSTALL
ALL FEEDERS AND BRANCH CIRCUITS SHALL CONSIST OF CONDUITS AND WIRES.
GREEN GROUNDING WIRE IN ALL BRANCH CIRCUIT CONDUIT.
11.
12. AC AND NM CABLES SHALL NOT BE USED.
PERPENDICULAR TO WALLS, CEILINGS AND FLOORS.
REPAIR ANY DAMAGE AS A RESULT OF THIS WORK.
UNLESS OTHERWISE NOTED FOR INTERIOR WORK, THE FOLLOWING TYPES OF
INSTALL CONDUITS IN THE MOST EFFICIENT ROUTE BETWEEN TERMINATIONS
ALL WIRE SHALL BE A MINIMUM #12 (COPPER) UNLESS OTHERWISE NOTED. ALL HOME
AND AVOIDING INTERFERENCE WITH OTHER UTILITY LINES AND FEATURES OF
RUNS 100 FT AND LONGER SHALL BE MINIMUM # 10 WIRE (120/208V SYSTEM
EXISTING UTILITIES, OBSTRUCTIONS AND/OR OTHER CONDITIONS WHICH MAY
TAKE EVERY PRECAUTION TO PREVENT DAMAGE TO EXISTING WORK AND SHALL
THE CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND EXTENT OF ALL
AFFECT THE PROPOSED WORK UNDER THE PROJECT. THE CONTRACTOR SHALL
CONDUIT RUNS SHOWN ARE DIAGRAMMATICAL. THE CONTRACTOR SHALL
EXPOSED CONDUITS ON WALLS AND CEILINGS TO RUN PARALLEL OR
CONDUITS SHALL BE USED:
10.
9.
8.
7.
4.
6.
5.
ONLY). INSULATION TYPE SHALL BE THHN.
OTHER DISCIPLINES.
ALL ELECTRICAL DRAWINGS ARE TO BE READ IN CONJUNCTION WITH THE
CLEAR, DUCTS, OPENINGS, ETC AND INCLUDING ALL STRUCTURAL FEATURES.
PROJECT SPECIFICATIONS AND ALL OTHER RELATED CONTRACT DRAWINGS.
COORDINATE WORK WITH OTHER TRADES AND INSTALL CONDUIT AND BOXES TO 3.
2.
1.
NEW WORK IS SHOWN WITH DARK LINE WEIGHT AND EXISTING IS SHOWN WITH LIGHT LINE 13.
WEIGHT U.O.N.
PANEL DIRECTORY SHALL BE TYPED WHEN UPDATED TO REFLECT NEW & EXISTING WORK.14.
ALL ELECTRICAL WORK TO BE IN ACCORDANCE WITH LATEST REQUIREMENTS OF THE
NEC AND ALL OTHER APPLICABLE CODES AND REGULATIONS OF AUTHORITIES HAVING
JURISDICTION OVER THE WORK AND VA TIL SPECIFICATION DIVISION 26
NO SET SCREW CONNECTOR SHALL BE USED AND NO POT METAL ELECTRICAL FITTINGS.15.
FLEXIBLE CONDUIT LENGTH SHALL NOT EXCEED 6'-0'' AND SHALL BE STEEL.16.
ALL ELECTRICAL FITTINGS SHALL BE STEEL AND COMPRESSION TYPE.17.
18.
ANYTHING THAT IS NOT EXISTING IS NEW WHETHER IT IS CALLED OUT OR NOT.19.
APPROVAL BEFORE PROCEEDING WITH INSTALLATION .
CONTRACTOR SHALL PREPARE SHOP DRAWINGS SHOWING ALL CONDUIT ROUTING & SUBMIT FOR 20.
ALL FIRE SYSTEM WIRING SHALL BE IN CONDUIT.21.
CONNECT TO EXISTING SYSTEM USING CONDUIT & WIRE.
ALL SMOKE DETECTORS IN TR ROOMS SHALL BE NEW & MATCH EXISTING MANUFACTURER.22.
FOR FIRE STOPPING REQUIREMENTS SEE DRAWING 20.A-121.23.
THE CONTRACTOR SHALL CAREFULLY EXAMINE ALL CONTRACT
DRAWINGS/SPECIFICATIONS AND BE RESPONSIBLE FOR THE PROPER FITTING OF
MATERIALS AND EQUIPMENT AT EACH LOCATIONS AS INDICATED, WITHOUT
SUBSTANTIAL ALTERATION. IN AS MUCH AS THE DRAWINGS ARE GENERALLY
DIAGRAMMATIC AND BECAUSE OF THE SMALL SCALE OF THE DRAWINGS IT IS NOT
POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS AND ACCESSORIES WHICH MAY BE
REQUIRED. FURNISHING SUCH FITTINGS TO MEET SUCH CONDITIONS SHALL BE AT NO
COST TO THE GOVERNMENT .
THE CONTRACTOR SHALL EXAMINE THE SITE AND OBSERVE THE CONDITIONS UNDER
WHICH THE WORK WILL BE DONE OR OTHER CIRCUMSTANCES WHICH WILL EFFECT THE
CONTEMPLATED WORK. NO ALLOWANCE WILL BE MADE SUBSEQUENTLY IN
CONNECTION WITH ANY ERROR OR NEGLIGENCE ON THE CONTRACTORS PART.
PROVIDE TWO (SYSTEM A & B) 3000VA/2700 W UPS FOR EACH TR. MATCH EXISTING UPS
TYPE "CYBERPOWER". REUSE EXISTING "CYBERPOWER" UPS'S FOR RELOCATED TR'S.
PROVIDE ADDITIONAL 3000 VA/2700W UPS UNITS AS REQUIRED DURING THE PHASING
PROCESS.ALL SYSTEMS SHALL BE PROTECTED AT ALL TIMES DURING THE PHASING
PERIOD. PROVIDE & INSTALL TWO PDU PER RACK. ONE FED FROM SYSTEM A UPS AND
OTHER FROM SYSTEM B UPS. PDU SHALL BE CYBERPOWER MODEL PDU
20MHVIEC8FNET BOTH PDU SHALL BE RACK MOUNTED. FOR COMPLETE LIST OF UPS
INVENTORY PLEASE SEE TABLE THIS SHEET.
SINCE EXACT LOCATION OF EXISTING BUILDING GROUND IS NOT AVAILABLE CONTRACTOR24.
TO ASSUME 200FT RUN FROM THE FIRST TGB TO EXISTING BUILDING GROUND.
FURNISH AND INSTALL CYBER POWER ENVIRONMENTAL (ENVIROSENSOR) SENSOR IN
TWO OF THE 3, 4, 5, OR 6 RACKS AND ONE (1) WHERE THERE IS ONLY ONE (1) RACK. THE
SENSOR WILL MEASURE THE TEMPERATURE AND HUMIDITY WITHIN THE RACK. FOR
CONNECTION PROVIDE AND INSTALL CAT6A ETHERNET CABLE FOR CONNECTION OF
THE SENOR WITHIN THE RACK TO REMOTE MANAGEMENT CARD RM CARD/PDU AT UPS.
SEE DETAILS 5 AND 6 ON SHEET E-504.
CONTRACTOR SHALL REPLACE EXISTING CORDS CONNECTED TO CISCO SWITCHES
WITH RED AND BLUE CORDS (10'-0" LENGTH) MANUFACTURED BY CYBER POWER.
25.
26.
SYMBOL
MOUNTING
LIGHTING FIXTURE SCHEDULE
LAMP
WATTSQTY. TYPE
COLOR
TEMP.
TOTAL INPUT
FIXTURE
INPUT
VOLTS WATTS
DRIVER
POWER
CATALOG NO.
MULTIPLE LED 34 4000 120/277
MULTIPLE LED 38.87 4000 277
38.87 0-10V RECESSED
LAY-IN
AXIS CAT#
BBR WALLED-24-6400-90-35-B35-VL-W-277-DP-1-TB9
SURFACE ON
UNISTRUT
LED POWER
DRIVER
PHILIPS CAT#
SM 534C LED 40S/ 940 PSD
SCALE: NO SCALE
TR 16SA
TR 15SA
TR 14SA
TR 13SA
TR 12SA
TR 11SA
TR 10SA
TR 16IS
TR 15IS
TR 14IS
TR 13IS
TR 12IS
TR 11IS
TR 10IS
TR 16IN
TR 15IN
TR 14IN
TR 13IN
TR 12IN
TR 11IN
TR 10IN
TR 16SE
TR 15SE
TR 14SE
TR 13SE
TR 12SE
TR 11SE
TR 10SE
FOR ADDITIONAL NEW TELECOMMUNICATIONS UNDERGROUND DUCTBANK
REQUIREMENTS PLEASE SEE DRAWINGS TS001 & TS002.
27.
RECEPTACLE
MOTOR RATED SWITCH
LED 5 N/A PENDANT5 EMERGENCY120 CHLORIDE CAT# CN6GCB1LC; PKIT12BMULTIPLE
RIGID CONDUIT & ASSOCIATED FITTINGS SHALL BE USED FOR OUTDOOR, WET & DAMP LOCATIONS.28.
CONTRACTOR TO PROVIDE ARC FLASH STICKERS ON ALL NEW ELECTRICAL EQUIPMENT.29.
ELECTRICAL BRANCH CIRCUIT PANEL VOLTAGE
RATING AS SHOWN
BLDG. 500 INTERSTITIAL LEVEL EXISTING TR WAY FINDING MAP
EXISTING UPS INVENTORY
RIGID CONDUIT & ASSOCIATED FITTINGS SHALL BE USED FOR OUTDOOR, WET & DAMP LOCATIONS.
CONTRACTOR TO PROVIDE ARC FLASH STICKERS ON ALL NEW ELECTRICAL EQUIPMENT.
PROVIDE 120VAC TO NEW DDC I/O PANEL FROM EXISTING 120VAC RECEPTACLE CIRCUIT IN EACH TR. COORDINATE WITH MECHANICAL
CONTRACTOR ON THE EXACT LOCATION OF DDC I/O PANEL.
30.
31.
32.
E-002
DRAWING LIST
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
C
D
20-SCE-07
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
SHEET INDEX
SHEET NUMBER SHEET TITLE
E-001
ELECTRICAL SYMBOL LIST, GENERAL NOTES, ABBREVIATIONS AND
SCOPE DESCRIPTION
E-002
158.E-101 158.E-111 206.E-101 206.E-111 206.E-121 210.E-101 210.E-111 210.E-121 213.E-101 213.E-111 213.E-121 213.E-131 213.E-1R1 214.E-111 214.E-121 214.E-131 214.E-1R1 215.E-101 215.E-111 215.E-121 215.E-131 215.E-1R1 217.E-101 217.E-111 217.E-121 217.E-131 217.E-1R1 218.E-101 218.E-111 218.E-121 218.E-131 218.E-1R1 220.E-101 220.E-111 220.E-121 220.E-131 256.E-101 256.E-111 256.E-121 257.E-101 257.E-111 257.E-121 258.E-111 258.E-121 258.E-131 258.E-141 304.E-101 304.E-111 304.E-121 304.E-122
345.E-111 401.E-111 401.E-121
402.E-111 402.E-121
500.E-1B1 500.E-1B2 500.E-1B3 500.E-1B4 500.E-101 500.E-102 500.E-103 500.E-104 500.E-10I1 500.E-10I2 500.E-10I3 500.E-10I4 500.E-111 500.E-112 500.E-113 500.E-114 500.E-11I1 500.E-11I2 500.E-11I3 500.E-11I4 500.E-121 500.E-122
DRAWING LIST
ELECTRICAL GROUND FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL BASEMENT FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL BASEMENT FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL BASEMENT FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL THIRD FLOOR
ELECTRICAL ROOF PLAN
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL THIRD FLOOR
ELECTRICAL ROOF PLAN
ELECTRICAL BASEMENT FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL THIRD FLOOR
ELECTRICAL ROOF PLAN
ELECTRICAL GROUND FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL THIRD FLOOR
ELECTRICAL ROOF PLAN
ELECTRICAL GROUND FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL THIRD FLOOR
ELECTRICAL ROOF PLAN
ELECTRICAL GROUND FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL THIRD FLOOR
ELECTRICAL BASEMENT FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL BASEMENT FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL FIRST PLAN
ELECTRICAL SECOND PLAN
ELECTRICAL THIRD PLAN
ELECTRICAL FOURTH PLAN
ELECTRICAL BASEMENT FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL FIRST FLOOR PLAN
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL BASEMENT FLOOR
ELECTRICAL GROUND FLOOR
ELECTRICAL GROUND INTERSTITIAL FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL FIRST INTERSTITIAL FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL BASEMENT FLOOR
ELECTRICAL BASEMENT FLOOR
ELECTRICAL BASEMENT FLOOR
ELECTRICAL GROUND FLOOR
ELECTRICAL GROUND FLOOR
ELECTRICAL GROUND FLOOR
ELECTRICAL GROUND INTERSTITIAL FLOOR
ELECTRICAL GROUND INTERSTITIAL FLOOR
ELECTRICAL GROUND INTERSTITIAL FLOOR
SHEET INDEX (CONTINUED)
SHEET NUMBER SHEET TITLE
500.E-123 500.E-124 500.E-12I1 500.E-12I2 500.E-12I3 500.E-12I4 500.E-131 500.E-132 500.E-133 500.E-134 500.E-13I1
500.E-141
500.E-14I1 500.E-14I2 500.E-14I3 500.E-14I4 500.E-151 500.E-152 500.E-153 500.E-154 500.E-15I1 500.E-15I2 500.E-15I3 500.E-15I4 500.E-161 500.E-162 500.E-163 500.E-164 500.E-16I1 500.E-16I2 500.E-16I3 500.E-16I4
507.E-111
527.E-111 527.E-112
158.E-401 206.E-401 210.E-401 213.E-401 214.E-401 215.E-401 217.E-401 218.E-401 220.E-401 256.E-401 257.E-401
345.E-401 401.E-401
500.E-401 500.E-402 500.E-403 500.E-404 500.E-405 500.E-406 500.E-407 500.E-408
500.E-410 500.E-411 500.E-412 500.E-413 500.E-414 500.E-415 500.E-416 507.E-401 527.E-401
E-501 E-502 E-503 E-504
E-601 E-602
ELECTRICAL SECOND FLOOR
ELECTRICAL SECOND FLOOR
ELECTRICAL SECOND INTERSTITIAL FLOOR
ELECTRICAL SECOND INTERSTITIAL FLOOR
ELECTRICAL SECOND INTERSTITIAL FLOOR
ELECTRICAL SECOND INTERSTITIAL FLOOR
ELECTRICAL THIRD FLOOR
ELECTRICAL THIRD FLOOR
ELECTRICAL THIRD FLOOR
ELECTRICAL THIRD FLOOR
ELECTRICAL THIRD INTERSTITIAL FLOOR
ELECTRICAL FOURTH FLOOR
ELECTRICAL FOURTH INTERSTITIAL FLOOR
ELECTRICAL FIFTH FLOOR
ELECTRICAL FIFTH INTERSTITIAL FLOOR
ELECTRICAL SIXTH FLOOR
ELECTRICAL SIXTH FLOOR
ELECTRICAL SIXTH FLOOR
ELECTRICAL SIXTH FLOOR
ELECTRICAL SIXTH INTERSTITIAL FLOOR
ELECTRICAL SIXTH INTERSTITIAL FLOOR
ELECTRICAL SIXTH INTERSTITIAL FLOOR
ELECTRICAL SIXTH INTERSTITIAL FLOOR
ELECTRICAL FIRST FLOOR
ELECTRICAL FIRST FLOOR PLAN - POWER
ELECTRICAL FIRST FLOOR PLAN - LIGHTING
ELECTRICAL ENLARGED PLAN
ELECTRICAL ENLARGED PLAN - TR ROOMS 101, 146 AND 244
ELECTRICAL ENLARGED PLAN - TR ROOMS 9, 122C AND 221K
ELECTRICAL ENLARGED PLAN - TR ROOMS B09, 103, 201 AND 301
ELECTRICAL ENLARGED PLAN - TR ROOMS 105, 205 ADN 305
ELECTRICAL ENLARGED PLAN - TR ROOMS B7,123, 233 AND 333
ELECTRICAL ENLARGED PLAN - TR ROOMS 002, 107, 202 AND 302
ELECTRICAL ENLARGED PLAN - TR ROOMS 04, 101, 201 AND 302
ELECTRICAL ENLARGED PLAN - TR ROOMS 014, 121, 225 AND 332
ELECTRICAL ENLARGED PLAN - TR ROOMS 1, 102 AND 226
ELECTRICAL ENLARGED PLAN - TR ROOMS B, 135 AND 215
ELECTRICAL ENLARGED PLAN - TR ROOMS 29 AND 39A
ELECTRICAL ENLARGED PLAN - TR ROOMS A100G AND A239
E-603
ELECTRICAL FIRST INTERSTITIAL FLOOR
ELECTRICAL FIRST INTERSTITIAL FLOOR
ELECTRICAL FIRST INTERSTITIAL FLOOR
500.E-13I2 ELECTRICAL THIRD INTERSTITIAL FLOOR
500.E-13I3 ELECTRICAL THIRD INTERSTITIAL FLOOR
500.E-13I4 ELECTRICAL THIRD INTERSTITIAL FLOOR
500.E-142 ELECTRICAL FOURTH FLOOR
500.E-143 ELECTRICAL FOURTH FLOOR
500.E-144 ELECTRICAL FOURTH FLOOR
ELECTRICAL FOURTH INTERSTITIAL FLOOR
ELECTRICAL FOURTH INTERSTITIAL FLOOR
ELECTRICAL FOURTH INTERSTITIAL FLOOR
ELECTRICAL FIFTH FLOOR
ELECTRICAL FIFTH FLOOR
ELECTRICAL FIFTH FLOOR
ELECTRICAL FIFTH INTERSTITIAL FLOOR
ELECTRICAL FIFTH INTERSTITIAL FLOOR
ELECTRICAL FIFTH INTERSTITIAL FLOOR
ELECTRICAL ENLARGED PLAN - ROOM MPOE
ELECTRICAL ENLARGED PLAN - ROOM 10SJ, 10SO, 10SA
ELECTRICAL ENLARGED PLAN - ROOM 10IN & 10IS
ELECTRICAL ENLARGED PLAN - ROOM 11SH, 11SO, 11SN, 11SE
ELECTRICAL ENLARGED PLAN - ROOM 11IN & 11IS
ELECTRICAL ENLARGED PLAN - ROOM 12SE, 12 SA
ELECTRICAL ENLARGED PLAN - 12IN & 12IS
ELECTRICAL ENLARGED PLAN - ROOM 13SE, 13SA
ELECTRICAL ENLARGED PLAN - ROOM 14SE, 14SA
ELECTRICAL ENLARGED PLAN - ROOM 14IN, 14IS
ELECTRICAL ENLARGED PLAN - ROOM 15SE, 15SA
ELECTRICAL ENLARGED PLAN - ROOM 15IN, 15IS
ELECTRICAL ENLARGED PLAN 16SE, 16SA
ELECTRICAL ENLARGED PLAN - ROOM 16IN, 16IS
ELECTRICAL ENLARGED PLAN - ROOM E2
ELECTRICAL ENLARGED PLAN - TR ROOM 102
ELECTRICAL ENLARGED PLAN - TR ROOMS 22 AND 3
ELECTRICAL DETAILS - GROUNDING
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ELECTRICAL DETAILS
ELECTRICAL PARTIAL SINGLE LINE BLDG. 206, 210, 213, 214, 215, 217, 218
ELECTRICAL PARTIAL SINGLE LINE BLDG. 220, 256, 257, 258, 304
ELECTRICAL PARTIAL SINGLE LINE BLDG. 345, 401, 402
SHEET INDEX (CONTINUED)
SHEET NUMBER SHEET TITLE
E-604 E-605 E-701 E-702 E-703 E-704 E-705
E-801 E-802 E-803
ELECTRICAL PARTIAL SINGLE LINE BLDG. 500
ELECTRICAL PARTIAL SINGLE LINE BLDG. 507, 525, 527
ELECTRICAL
ELECTRICAL
ELECTRICAL
ELECTRICAL
ELECTRICAL PANEL SCHEDULES BLDG. 158, 206, AND 210
ELECTRICAL PANEL SCHEDULES BLDG. 210, 213 AND 214
ELECTRICAL PANEL SCHEDULES BLDG. 214 AND 215
E-804
ELECTRICAL PANEL SCHEDULES BLDG. 220, 256 AND 257
E-805
304.E-1R1 ELECTRICAL ROOF PLAN
402.E-1R1 ELECTRICAL ROOF PLAN
507.E-1R1 ELECTRICAL ROOF PLAN
527.E-1R1 ELECTRICAL ROOF PLAN
402.E-401 ELECTRICAL ENLARGED PLAN 1409 AND 2413
E-505 ELECTRICAL DETAILS
E-806
ELECTRICAL PANEL SCHEDULES BLDG. 257, 258 AND 304
ELECTRICAL PANEL SCHEDULES BLDG. 304, 345 AND 401
258.E-401
304.E-401 ELECTRICAL ENLARGED PLAN - TR ROOMS 2,2, 2-106B, 2-223A AND 1-224
500.E-171 ELECTRICAL PENTHOUSE LEVEL
ELECTRICAL PENTHOUSE LEVEL500.E-174
401.E-1R1 ELECTRICAL ROOF PLAN
ES001
ES002
ELECTRICAL SITE PLAN
ELECTRICAL SITE PLAN
E-807 E-808
E-809 ELECTRICAL PANEL SCHEDULES BLDG. 402
ELECTRICAL PANEL SCHEDULES BLDG. 500
ELECTRICAL PANEL SCHEDULES BLDG. 500
E-810
ELECTRICAL PANEL SCHEDULES BLDG. 500
E-811 E-812
ELECTRICAL PANEL SCHEDULES BLDG. 500
E-706 ELECTRICAL GROUNDING RISER (NEW) BLDG. 507 AND 527
E-813 E-814
ELECTRICAL PANEL SCHEDULES BLDG. 217
ELECTRICAL PANEL SCHEDULES BLDG. 217, 218 AND 220
500.E-409 ELECTRICAL ENLARGED PLAN - ROOM 13IN, 13IS
ELECTRICAL PANEL SCHEDULES BLDG. 500, 507 AND 527E-815
ELECTRICAL PANEL SCHEDULES BLDG. 500
ELECTRICAL SITE PLAN (REFERENCE ONLY)
SCALE: 1/128" = 1' - 0"
NORTH
ES001
ELECTRICAL SITE PLAN
LEGEND
BUILDING IN SCOPE
(VA SEPULVEDA CAMPUS, NORTH HILLS)
R
EF
ER
T
O E
S-
FO
R C
O N
TI
N
U
AT
IO
N
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
C
D
20-SCE-07
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ELECTRICAL SITE PLAN (REFERENCE ONLY)
SCALE: 1/128" = 1' - 0"
NORTH
ES002
ELECTRICAL SITE PLAN
(VA SEPULVEDA CAMPUS, NORTH HILLS)
R
EF
ER
T
O W
.T -0
F
O R
C O
N
TI
N U
AT
IO
N
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
C
D
20-SCE-07
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
LEGEND
BUILDING IN SCOPE
SCALE: 1/8" = 1' - 0"
NORTH
158.E-101
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
M
AT
C H
L
IN
E
M
AT
C H
L
IN
E
FOR ENLARGED PLAN
SEE 158.E-401
SCALE: 1/8" = 1' - 0" NORTH
158.E-111
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
M
AT
C H
L
IN
E
M
AT
C H
L
IN
E
SEE 158.E-401
RA
MP
U P
RAMP UP
CHAIN LINK CAGE
RAMP UP
EXIT DOOR
STORAGE
OUT REACH
COMMUNITY CARE
ELEVATOR
LOBBY
ELEVATOR MACH
RM
ELEVATOR
MENS RESTROOM
WOMENS
RESTROOM
CORRIDOR
OFFICE OF SCREENING CLERK
CLOSET
CLINICAL
CO-ORDR
PSYCHIATRIST
WORK AREA
14A
SCREENING RM
MENS SHOWER
INTAKE RM
VESTING
OFFICE
SOCIAL WORKER OFFICE
ELIGIBILITY
CLERK OFFICE
ELIGIBILITY
CLERK OFFICE
SCREENING RM
RECEPTION
CLINICAL SUPPORT OFFICE
CLINICAL SUPPORT PGM MGR
OFFICE
STAFF KITCHEN
OFFICE
STEAM RM
COPY RM
SUPPLY RM
OFFICE
SOCIAL WORKER OFFICE
OFFICE
SOCIAL
WORKER
OFFICE
BENEFITS
COUNSELOR OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
SOCIAL
WORKER
OFFICE
SOCIAL
WORKER
OFFICE
SOCIAL
WORKER
OFFICE
OFFICE
OFFICE
34A
FE
18A
TELECOM
ROOM
A B C D E F G H
3.2
1.1
ELECTRICAL
ROOM
001A
001.1
CU
206-101
WP
GFI
A
A1-2,4
A1-6
SCALE: 1/8" = 1' - 0"
NORTH
206.E-101
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
SEE 206.E-401
1 NEW 30A/ 2P 208V 3R DISCONNECT.
NEW 3/4''C - 2 #12 + 1 #12EG.
NEW 3/4''C - 2 #12 + 1 #12EG TO RESPECTIVE FAN
COIL UNIT IN RESPECTIVE TR.
NEW SUB PANEL A1 60A 208/120V 3P 4W.
1''C- 4 #6 + 1 #10EG.
DN
DN
UP UP
A B C D E F G H
3.2
1.1
RA
MP
D
OW
N
DN
DN
ROLL DOWN DOOR
FC
CHECK IN
135A
LOCKERS
RM
PIPE SPACE
PIPE SPACE
TOILET
158A
CLINICAL
PHARMACIST
TOILET
CORRIDOR
WAITING RM
FC
WAITING RM
FC
CORRIDOR
WHITE TEAM TRIAGE
CORRIDOR
STORAGE
RM
147A
PIPE SPACE
H/C WOMENS WASH RM &
TOILET
PIPE SPACE
EXAM RM-10
14-
CORRIDOR
STAIR-3
EMS
MEN STAFF
RESTROOM
TRIAGE CARE MGR
MENS TOILET
CORRIDOR
MENTAL HEALTH CLINICAL
PHARMACIST
STAIRSTAIR
STAIR
ELEVATOR
EMS
EMS
121A
ADMINISTRATIVE OFFICER
STAIR-2
WASH RM & TOILET
SHOWER RM
113A
ELECTRICAL
RM
ASSOCIATE OFFICE NURSE
COMM/ PRIMARY &
AMBULATORY CARE
MENS STAFF
RESTROOM
HEAD NURSE
124 WOMEN TOILET
SOCIAL SVC
ADMINISTRATIVE SUPPORT
PHYSICIAN ASST OFFICE
NURSES OFFICE
143A
CORRIDOR
MEDICATION RM
LAB
PRIMARY CARE CLINIC
HEAD NURSE
NURSES STATION
CORRIDOR
153B
NURSES OFFICE
EXAM RM-8
EXAM RM-6
149A
RNS OFFICE
153A
DOCTORS OFFICE
EXAM RM-1
DOCTORS OFFICE
CORRIDOR
MULTI PURPOSE RM
CLINICAL KITCHEN
CORRIDOR
CHIEF OF COMM CARE
QUALITY MGMT
CHIEF OF COMM CARE
CORRIDOR
PGM MGR
NURSE MGR
SOCIAL WORKER OFFICE
CHAPLAINMED RM
RECEPTION
105106
112A
CORRIDOR
108112B
CONFERENCE RM
SOCIAL WORKER
OFFICE
CORRIDOR
SOCIAL SCIENCE PGM
SPECIALIST
SOCIAL WORKER
119A
CHIEF OF MENTAL HEALTH
EXAM RM-4
PS
DEPUTY PGM
GRANT PER DIEM
HCRV
HOUSING OFFICE
MGR
SPECIALIST
NURSING LIAISON
GRANT PER DIEM
VA SUPPORT
PGM MGR
PIPE CHASE
HOUSING OFFICE
PGM
VA SUPPORT
COMPUTER
SELF
TELECOM
ROOM
WAITING RM
PTSD PGM
140.1
CU
206-244
CU
206-146
WP
GFI
1PM2-33
1PM2-36,38
1PM2-40,42
SCALE: 1/8" = 1' - 0"
206.E-111
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
SEE 206.E-401
1 NEW 30A/ 2P 208V 3R DISCONNECT.
NEW 3/4''C - 2 #12 + 1 #12EG.
NEW 3/4''C - 2 #12 + 1 #12EG TO RESPECTIVE FAN
COIL UNIT IN RESPECTIVE TR.
EXISTING PANEL 1PM2 225A 208/120V.4
C
DN DN
A B D E F G H
3.2
1.1
DN
UP TO ATTIC
ROLL DOWN DOORROLL DOWN DOOR
WOMENS
TOILET
TREATMENT RM
PIPE SPACE
PIPE SPACE
234B
STORAGE
234A
PIPE SPACE
WORK RM
STAIR
CORRIDOR
STAIR
DAY RM
STAFF PSYCHIATRIST
REGISTERED NURSE
STAFF PSYCHIATRIST
CORRIDOR
WAITING RM
RESEARCH ASST
CONFERENCE RM / GROUP
RM
STAFF KITCHEN
STAFF PSYCHIATRIST
NURSE PRACTITIONER
MEN WASH RM AND TOILET
PIPE SPACE
STORAGE
RM
245A
STAFF PSYCHIATRIST
R N
CORRIDOR
SOCIAL WORKER
CALL CENTER OFFICE
TEAM CARE CO-ORDR
STAFF PSYCHIATRIST
HAC
BMS
237A
STAFF LOUNGE
STAFF RESTROOM
ELEVATOR
TOILET
257A
STAFF PSYCHIATRIST
PSYCHOLOGIST
REGISTERED NURSE
SUPPLY RM
CORRIDOR
STAIR
CLINICAL OPERATIONS
OFFICE
OFFICE
ADMIN ASST
WAITING RM
SOCIAL WORKER
CORRIDOR
SOCIAL WORKER
SOCIAL SVC
WAITING RM
CLINICAL NURSE
SPECIALIST
SOCIAL WORK ASSOCIATE
SOCIAL SCIENCE
TECHNICIAN
WOMEN STAFF TOILET
STAFF OFFICE
223MEN STAFF RESTROOM
STAIR
BMS
221A
HAC
STAIR
STAFF PSYCHOLOGIST
PSYCHOLOGICAL RM
CORRIDOR
GROUP RM
STAFF PSYCHIATRIST
STAFF PSYCHOLOGIST
REGISTERED NURSE
UTILITIES
SHOWER RM
213A
PIPE CHASE
STAFF WOMEN RESTROOM
STAFF PSYCHIATRIST
SOCIAL WORKER
STAFF PSYCHIATRIST
REGISTERED NURSE
CORRIDOR
STAFF PSYCHIATRIST
CORRIDOR
GROUP RM
TOILET AND LOCKER
STORAGE
FE
FIRE ACCORDION
HEALTH
MENTAL
TELECOM
ROOM
CORRIDOR
244.1
SCALE: 1/8" = 1' - 0"
206.E-121
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 8' 16'
SCALE: 1/8" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
SEE 206.E-401
1 EXISTING PANEL 1PM2 225A 208/120V.
CU
210-9
CU
210-122C
CU
210-221K
WP
GFI
WP
GFI
233 2
X
X2-10,12 X2-6,8X2-2,4
SCALE: 3/32" = 1' - 0"
210.E-101
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
SEE 210.E-401
1 NEW 30A/ 2P 208V 3R DISCONNECT.
NEW 3/4''C - 2 #12 + 1 #12EG.
NEW 3/4''C - 2 #12 + 1 #12EG TO RESPECTIVE FAN
COIL UNIT IN RESPECTIVE TR.
NEW SUB PANEL X2 60A 208/120V 3P 4W
EXISTING PANEL X 225A 208/120V
1''C- 4 #6 + 1 #10EG
E1
SCALE: 3/32" = 1' - 0"
210.E-111
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
SEE 210.E-401
1 EXISTING PANEL E1 225A 208/120V 3P 4W
F1
SCALE: 3/32" = 1' - 0"
210.E-121
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
SEE 210.E-402
1 EXISTING PANEL F1 225A 208/120V 3P 4W.
UP
BIO HAZARD DOOR
ROLL DOWN DOOR
ACCORDION DOOR
UP
VENDING
A
B
C
D
E
G
F
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 1910
UNISEX
TOILET
B43A
ELECTRICAL
CLOSET
B03
CLOSET
ELEV
MACH
RM
B02
LOCKER
B43
MENS
TOILET
B34
WOMENS
TOILET
B32
ELC
PANEL
B20A
SOILED
INSTRUMENTS
B28
LOCKER
B26B
SUPPLIES
B24A
PATIENT
RESTROOM
B17A
TELELECOM
RM
B09
CORRIDOR
EXAM RM
B41HEMODIALYSIS
B44 B36
EXIT
CORRIDOR
B35
ELC CL
B43B
KITCHEN
B42
DIALYSIS
PREPARATION
B45 TECH SUPPLIES
B46
LOCKER
B47
B48
WATER
TREATMENT
B50
NURSING
SUPPLIES
B51
SUPPLIES
B52B44A
HAC
B37
EMS
SUPPLY
RM
B39
LOCKER
B38
TOILET
B40
ELEVATOR
EQUIP
B08
TRANSFORMER RM
SOLAR PANEL
DISCONNECT
B11
B13
COMMUNITY
NURSING HOME
PGM
B14
STORAGE
B15
B16
DOCTORS OFFICE
B17C
DOCTORS OFFICE
B17D
DOCTORS OFFICE
B17
X RAY RM
B19
EXAM RM
B20
DENTAL LAB
B21
B21A
CLEAN RM
B22
SUPPLIES RM
B22A
BARBER SHOP
B07
STORAGE
B06
LAUNDRY
B05
WASTE COLLECTION
B04
PHARMACY
B33
VAULT
B33B
CLOTHING RM
B01
LOUNGE
B33A
CONFERENCE
RM
B31A
PHARMACY
B31
WAITING
B30
TREATMENT RM
B29
EXAM RM
B25
LOUNGE
B26LOCKER
B26C
TOILET
B26A
TREATMENT RM
B24
ELEVATOR
EAST
STAIR
B49
ELEVATOR
CENTRAL
STAIR
B12
WEST
STAIR
B23
EL 01
EL 02
STORAGE
ELECTRICAL RM
LOBBY
CL 01
HEMODIALYSIS SOILED
UTILITY
SUPPLIES
B36A
LAB
CR 01
SCALE: 3/32" = 1' - 0"
213.E-101
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
SEE 213.E-401
1 EXISTING PANEL EB 100A 208/120V 3P 4W
NEW SUB-PANEL EB1 60A 208/120V 3P 4W
DNUP
UP
UP
ACCORDION DOOR
ACCORDION DOOR
ACCORDION DOOR
H/C
TELECOMM
RM 103
A
B
C
D
E
G
F
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 1910
RESTROOM
120A 110
ELEC
CLO
114A
DINING HALL
ELEVATOR LOBBY
CORRIDOR
MENS
RESTROOM
OCCUPATIONAL THERAPY
CONFERENCE RM
106B
106D
TOILET
106C
TOILET
106A
TOILET
106DIETICIAN
MED
DIRECTORS
SUITE
CHIEF GRC
107A
EAST STAIRWEST STAIR CENTER STAIR
ELEVATOR
SVC
ELEVATOR
WAITING RM
COMPUTER
ASST
TIMEKEEPER
EXERCISE GYM
WOMENS
RESTROOM
SOCIAL WORK
CO-ORDR
104B
104A
COPY RM
107C
CLINICAL
DIRECTOR
107B108
GERIATRIC
NURSE
PRACTITIONER
109B
GERIATRIC
EDUCATIONAL
109A
AUDIO
SPEECH
109ADMIN
OFFICER
112A
112B112C
SWA
SOILED LINEN
OFFICE
FOOD
WARMING RM
SUPPLIES RM (FOR
RECREATION ACTIVITY)
124C
STORAGE
ELC
CL
RECREATION THERAPY
HAC
TRASH
AREA
STORAGE SHOWER
TOILET
PSYCHOLOGIST
101A
EL 02
ST 03 ST02
LOUNGE
CR 04
CORRIDOR
CR 01
OFFICE
OFFICE
OFFICE
ELEC
CL
TOILET
EXERCISE RM
ST01
ELEVATOR
SCALE: 3/32" = 1' - 0"
213.E-111
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
SEE 213.E-401
1 EXISTING EMERGENCY PANEL E1A 225A
208/120V
NEW EMERGENCY SUB-PANEL E1A1 60A
208/20V 3P 4W
DN
UP
UP
UP
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 1910
A
B
C
D
E
G
F
TELECOM
RM
CLO
TOILET
OXYGEN
STORAGE
ELECT
CLOSET
ELC
CL
ELC CL
SHOWER BATH
AND TOILET RM
CONGREGATE
BATH AND
TOILET RM
TOILET
CORRIDOR
ELEVATOR
LOBBY
TV LOUNGE/
WAITING AREA
TOILET
TOILET
2-BED
PATIENT RM
TOILET
2 BED
PATIENT RM
2 BED
PATIENT RM
TOILET
2 - BED
PATIENT RM
2 - BED
PATIENT RM
TOILET
2 - BED PATIENT
RM
4 - BED PATIENT RM
TOILET
TOILET
NURSE
STATION
2 - BED
PATIENT RM
NURSE MGR
MEDICATION
RM
SVC
ELEVATOR 224
NOURISHMENT
KITCHEN RM
SOLID LINEN RM
2-BED RM
TOILET
TOILET
DAY RM AND TOILET RM
2 - BED
PATIENT RM
TOILET
TOILET
2 - BED
PATIENT RM
2 - BED
PATIENT RM
2 - BED PATIENT
RM
TOILET
1 - BED
PATIENT RM
TOILET
TOILET
2 - BED
PATIENT RM
EAST STAIR
TOILET
207TOILET
TOILET
4 - BED PATIENT RM
TOILET
ELEVATOR
HAC
250249
WARD
SUPPLY
RM
LINEN
SUPPLY RM
CENTER STAIR
2 - BED PATIENT RM
TOILET
TOILET
4 - BED PATIENT RM
2 - BED PATIENT
RM
TOILET
COPY RM
2 - BED
PATIENT RM
TOILET
2 - BED
PATIENT RM
WEST STAIR
2 BED PATIENT RM
ST 03
240A
244A 246A
245A
ST 01
TREATMENT RM NURSE MGR
STAFF
RESTROOM
2 BED
PATIENT RM
TOILET
AND
SHOWER
202A 2 - BED
PATIENT RM
204A
206A
2 - BED PATIENT
RM
2 - BED PATIENT
RM
ST 02
209A
210A211A
213A
2 - BED PATIENT
RM
214A
217A
218A
PIPE CHASE
NURSE LOUNGE
EL 02
LAUNDRY RM
PIPE CHASE
230A
231A
234A
235A
237A238A
239A
CL 01
CORRIDOR
CR 02
CR 01
242A
203A
ELEVATOR
207A
SCALE: 3/32" = 1' - 0"
213.E-121
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
SEE 213.E-401
1 EXISTING PANEL E2A 225A 208/120V 3P 4W
NEW SUB PANEL E2A1 60A 208/120V 3P 4W2
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 1910
A
B
C
D
E
G
F
TELECOM
RM
HBPC OFFICE
TOILET &
SHOWER
TOILET
TOILET
ELC
ELC
COPY RM
ELC
CL
CLCL
CORRIDORCORRIDOR
WAITING AREA
CORRIDOR
TOILET
TOILET
OFFICE
TOILET
OFFICE
TELECARE
OFFICE
TOILET
TELECARE
OFFICE
TELECARE
OFFICE
334 TOILET
OFFICE
OFFICE
TOILET
OFFICE
NURSE STATION
328 327
ELEVATOR
WOUND CARE
PGM MGR
HPBC OFFICE
TOILET
TOILET
HBPC OFFICE
HBPC OFFICE
TOILET
HBPC OFFICE
HBPC OFFICE
TOILET
HBPC OFFICE
HBPC OFFICE
TOILET
HBPC OFFICE
TOILET
TOILET
EAST STAIR
TOILET
307306TOILET
TOILET
TOILET
HBPC OFFICE
TOILET
OFFICE
ELEVATOR
TOILET 351
350349
SUPPLY
348OFFICE
CENTRAL STAIR
CONFERENCE RM
TOILET
TOILET
OFFICE
OFFICE TELE
HEALTH
COPY
TOILET
STORAGE
OFFICE
TOILET
OFFICE
WEST STAIR
PROGRAM MGR
HBPC OFFICE
ST 03
340A
342A
344A 346A
345A
ST 01
OFFICE OFFICE
HAC
302A
303A
304A
306A
HBPC OFFICE HBPC OFFICE
ST 02
309A
310A311A
312A 314A
317A
318A
NOURISHMENT
KITCHEN
HMPC
SUPPLY/STORAGE
EL 02
STAFF OFFICE
STAFF OFFICE
SUPPLIES
STORAGE
330A
331A
332A
335A
337A 338A
339A
CR 01
ELEVATOR
STORAGE
307A
SCALE: 3/32" = 1' - 0"
213.E-131
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
SEE 213.E-401
1 EXISTING EMERGENCY PANEL E3A 225A
208/120V 3P 4W
NEW EMERGENCY SUB PANEL E3A1 60A
208/ 120V 3P 4W
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 1910
B
C
D
E
G
F
CU
213-B-9
CU
213-301
CU
213-103
CU
213-201
2 2 2
WP
GFI
E3 A1
-2 ,4
E3 A1
-6 ,8
E3 A1
-1 0,1
E3 A1
-1 4,1
E3A1-17
SCALE: 3/32" = 1' - 0"
NORTH
213.E-1R1
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
1 UNISTRUT RACK. SEE DETAIL ON E-503.
NEW 30A/ 2P 208V 3R DISCONNECT.
NEW 3/4''C - 2 #12 + 1 #12EG.
NEW 3/4''C - 2 #12 + 1 #12EG TO RESPECTIVE FAN
COIL UNIT IN RESPECTIVE TR.
COMMUNITY ROOM
FAMILY ROOM
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
LAUNDRY
RESIDENT
SOILED LINEN
RESIDENT
113 RESIDENT
OFFICE
RESIDENT
CLEAN LINEN
MEN
WOMEN
CLEAN LINEN
OFFICE
DINING
ROOM
DINING
ROOM
MEN'S
LOCKER
HAC
OFFICE
DISHWASHER
ROOM
STOR.FOOD
STORAGE
NON-FOOD
STORAGE
LOUNGE
100 OFFICE
BMS
BUILDING
MANAGEMENT
LOBBY
WOMEN'S
LOCKER
BUILDING
MGMT STOR.
SCALE: 3/32" = 1' - 0" NORTH
214.E-111
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
SEE 214.E-401
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
OFFICE
OFFICE
R221
RESIDENT
RESIDENT
RESIDENT
RESIDENT216
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
HAC
COMMUNITY ROOM
TOILET
HAC
RECYCLE STORAGE
MULTIPURPOSE RM
OFFICE
OFFICE200
LAUNDRY
ELEC
CLEAN LINEN
SCALE: 3/32" = 1' - 0"
214.E-121
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
STORAGE ROOM
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT316
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
RESIDENT
HAC
RESIDENT
MULTIPURPOSE RM.
MLU LIVING ROOM
COMMUNITY ROOM
OFFICE
LAUNDRY
OFFICE
OFFICE
MULTIPURPOSE RM.
RECYCLED STORAGE
ELEC
HAC
307A
CLEAN LINEN
SCALE: 3/32" = 1' - 0"
214.E-131
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'0' 8' 16' 32'0' 4' 8' 16'
SCALE: 1/8" = 1'-0"SCALE: 1/16" = 1'-0"SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
FOR ENLARGED PLAN
214-1
CU
214-205
CU
214-306
WP
GFI
E3 A1
-2 ,4
E3 A1
-6 ,8
E3 A1
-1 0,1
E3A1-14
SCALE: 3/32" = 1' - 0"
214.E-1R1
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
0' 4' 16' 24'2' 8'
SCALE: 3/32" = 1'-0"
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone:…