This notice provides information about an upcoming federal contract opportunity for construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 will issue an Invitation for Bid on or around July 13, 2021 via Contract Opportunities for Project 691-20-200 at the VA West Los Angeles Healthcare System campus. The project scope includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures to support Electronic Health Record Modernization Infrastructure Upgrades. The work will be performed in a functioning hospital environment. The contract will be set aside 100% for Service-Disabled Veteran-Owned Small Businesses and have a value between $20-50 million. The North American Industry Classification Code is 236220 for Commercial and Institutional Building Construction. A site visit will be scheduled for interested vendors to inspect the location and ask any questions before submitting a bid response.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2-4''C
110 BLOCK
RISER
FIRE ALARM
PANELS TO
REMAIN
SS
MM
FIRE ALARM
PANELS TO
REMAIN
SCALE: 1/4" = 1' - 0"
NORTH
220.T-401
TELECOMMUNICATIONS
ENLARGED PLAN - TR ROOM 014
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
TR ROOM
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA
RACKS WITH VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
EXISTING FIRE RATED TELEPHONE
BACKBOARD.
NOT USED.
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NEW 12''W X 1 1/ 2''H LADDER RACK.
NEW 4 POST DATA RACK 84''H. WITH
HORIZONTAL & VERTICAL WIRE MANAGERS.
EZ PATH SLEEVES. QUANTITY AS REQUIRED.
SEE T-504.
TDU (TUBE DISTRIBUTION UNIT)
SCALE: 1/4" = 1' - 0"
NORTH
TR ROOM
220.T-401A
TELECOMMUNICATIONS RACK
ELEVATION
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
RACK EQUIPMENT
CABLE INFORMATION
1 ALL CAT5E
2 ALL CAT6
WALL
RACK 1
A.F.F. A.F.F.
1 PLYWOOD BACKBOARD
2 WALL MOUNTED PHONE BLOCK
3 WALL MOUNTED 110 BLOCK
4 WALL MOUNTED SIECOR ENCLOSURE
5 WALL MOUNTED FIBER ENCLOSURE
6 1U 24 PORT PATCH PANEL
7 2U 48 PORT PATCH PANEL
8 1U WIRE MANAGER
9 1U CISCO 3850 SWITCH
4" CONDUIT
(TYP.)
WALL MOUNTED
RACK
WALL WALL WALL
WALL MOUNTED
RACK
10 UPS
4" CONDUIT
(TYP.)
RACK 1
11 WALL MOUNTED FAPP
SCALE: NONE
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
3 FIBER STRAND AS
SPECIFIED
4''C. CEILING 4''C. FLOOR
ELECTRICAL
PANEL (EX)
SINK TO BE
REMOVED
9 7
SS
MM
ELECTRICAL
PANEL (EX)
SCALE: 1/4" = 1' - 0"
NORTH
220.T-402
TELECOMMUNICATIONS
ENLARGED PLAN - TR ROOM 121
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
TR ROOM
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA
RACKS WITH VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
EXISTING FIRE RATED TELEPHONE
BACKBOARD.
NOT USED.
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NEW 12''W X 1 1/ 2''H LADDER RACK.
NEW HEAVY DUTY WALL MOUNTED RACK 84''H.
WITH HORIZONTAL & VERTICAL WIRE
MANAGERS.
EZ PATH SLEEVES. QUANTITY AS REQUIRED.
SEE T-504.
TDU (TUBE DISTRIBUTION UNIT)
SCALE: 1/4" = 1' - 0"
NORTH
220.T-402A
TELECOMMUNICATIONS RACK
ELEVATION
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
RACK EQUIPMENT
CABLE INFORMATION
1 ALL CAT5E
2 ALL CAT6
WALL
RACK 1
A.F.F. A.F.F.
1 PLYWOOD BACKBOARD
2 WALL MOUNTED ELECTRICAL PANEL
3 WALL MOUNTED 110 BLOCK
4 WALL MOUNTED FIBER PANEL
5 WALL MOUNTED 48 PORT PATCH PANEL
6 1U 24 PORT PATCH PANEL
7 2U 48 PORT PATCH PANEL
8 2U WIRE MANAGER
9 1U CISCO 3850 SWITCH
WALL MOUNTED
RACK
WALL WALL WALL
WALL WALL
RACK 1
SINKSINK
SCALE: NONE
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
2-4''C.
4''C. FLOOR
110 BLOCK
RISER
4''C. FLOOR
SPRINKLER
RISER (EX)
SS
MM
SCALE: 1/4" = 1' - 0"
NORTH
220.T-403
TELECOMMUNICATIONS
ENLARGED PLAN - TR ROOM 225
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
TR ROOM
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA
RACKS WITH VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
EXISTING FIRE RATED TELEPHONE
BACKBOARD.
EXISTING 12”W CABLE LADDER RACK MOUNTED
AT 84" AFF AND FIXED TO TOP OF EQUIPMENT
RACKS TO REMAIN (TYPICAL).
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NOT USED.
NEW HEAVY DUTY WALL MOUNTED DATA RACK
CHATSWORTH CAT # 1532-3-7-24
(23”WX73.5”HX24”D
EZ PATH SLEEVES. QUANTITY AS REQUIRED.
SEE T-504.
TDU (TUBE DISTRIBUTION UNIT)
SCALE: 1/4" = 1' - 0"
NORTH
220.T-403A
TELECOMMUNICATIONS RACK
ELEVATION
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
RACK EQUIPMENT
CABLE INFORMATION
1 ALL CAT5E
2 ALL CAT6
WALL
RACK 1
A.F.F. A.F.F.
1 WALL MOUNTED 110 BLOCK
2 WALL MOUNTED FIBER ENCLOSURE
3 1U 24 PORT PATCH PANEL
4 2U 48 PORT PATCH PANEL
5 1U CISCO 3850 SWITCH
6 UPS
4" CONDUIT
(TYP.)
WALL MOUNTED
RACK
WALLWALL WALL WALLWALL
LADDER RACK
WIRE
MANAGER
WIRE
MANAGER
WALL MOUNTED
RACK
LADDER RACK
4" CONDUIT
(TYP.)
RACK 1
SCALE: NONE
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
4''C. FLOOR
FACP (EX)
4 7
SS
MM
SCALE: 1/4" = 1' - 0"
NORTH
220.T-404
TELECOMMUNICATIONS
ENLARGED PLAN - TR ROOM 332
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
TR ROOM
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA
RACKS WITH VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
EXISTING FIRE RATED TELEPHONE
BACKBOARD.
EXISTING 12”W CABLE LADDER RACK MOUNTED
AT 84" AFF AND FIXED TO TOP OF EQUIPMENT
RACKS TO BE REMOVED (TYPICAL).
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NEW 12''W X 1 1/ 2''H LADDER RACK.
NEW 4 POST DATA RACK 84''H. WITH
HORIZONTAL & VERTICAL WIRE MANAGERS.
EZ PATH SLEEVES. QUANTITY AS REQUIRED.
SEE T-504.
TDU (TUBE DISTRIBUTION UNIT)
SCALE: 1/4" = 1' - 0"
NORTH
220.T-404A
TELECOMMUNICATIONS RACK
ELEVATION
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
RACK EQUIPMENT
CABLE INFORMATION
1 ALL CAT6
A.F.F. A.F.F.
1 PLYWOOD BACKBOARD
2 WALL MOUNTED FIBER ENCLOSURE
3 2U 48 PORT PATCH PANEL
4 2U WIRE MANAGER
5 1U FIBER LIU
6 1U CISCO 3850 SWITCH
WALL MOUNTED
RACK
A.F.F.
LADDER RACK
(TYP,)
LADDER RACK
(TYP.)
LADDER RACK
(TYP.)
WALL MOUNTED
RACK
2 POST RACK
WIRE
MANAGER
WALL
WALLWALL
WALL
WALL
WALLWALL
WALL
WIRE MANAGER
SCALE: NONE SCALE: NONE
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
MMSS
SCALE: 1/4" = 1' - 0"
NORTH
256.T-401
TELECOMMUNICATIONS
ENLARGED PLAN - TR ROOM 1
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
TR ROOM
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA
RACKS WITH VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
EXISTING FIRE RATED TELEPHONE
BACKBOARD.
EXISTING 12”W CABLE LADDER RACK MOUNTED
AT 84" AFF AND FIXED TO TOP OF EQUIPMENT
RACKS TO REMAIN (TYPICAL).
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NEW 12''W X 1 1/ 2''H LADDER RACK.
NEW 4 POST DATA RACK 84''H. WITH
HORIZONTAL & VERTICAL WIRE MANAGERS.
EZ PATH SLEEVES. QUANTITY AS REQUIRED.
SEE T-504.
TDU (TUBE DISTRIBUTION UNIT)
SCALE: 1/4" = 1' - 0"
NORTH
256.T-401A
TELECOMMUNICATIONS RACK
ELEVATION
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
RACK EQUIPMENT
CABLE INFORMATION
1 ALL CAT5E
2 ALL CAT6
WALL
RACK 1
A.F.F. A.F.F.
1 PLYWOOD BACKBOARD
2 WALL MOUNTED FIBER ENCLOSURE
3 WALL MOUNTED PHONE BLOCK
4 WALL MOUNTED 110 BLOCK
5 1U 24 PORT PATCH PANEL
6 2U 48 PORT PATCH PANEL
7 1U CISCO 3850 SWITCH
8 WALL MOUNTED SPLICE CASE
4" CONDUIT
(TYP.)
WALL MOUNTED
RACK
WALL WALL WALL
WALL MOUNTED
RACK
RACK 1
SCALE: NONE
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1 RACK 2
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
4''C. RISER
4''C. FEED
110 BLOCK
RISER
SS
MM 9
SCALE: 1/4" = 1' - 0"
NORTH
256.T-402
TELECOMMUNICATIONS
ENLARGED PLAN - TR ROOM 102
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
TR ROOM
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA
RACKS WITH VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
EXISTING FIRE RATED TELEPHONE
BACKBOARD.
EXISTING 12”W CABLE LADDER RACK MOUNTED
AT 84" AFF AND FIXED TO TOP OF EQUIPMENT
RACKS TO REMAIN (TYPICAL).
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NEW 12''W X 1 1/ 2''H LADDER RACK.
NEW 4 POST DATA RACK 84''H. WITH
HORIZONTAL & VERTICAL WIRE MANAGERS.
EZ PATH SLEEVES. QUANTITY AS REQUIRED.
SEE T-504.
TDU (TUBE DISTRIBUTION UNIT)
SCALE: 1/4" = 1' - 0"
NORTH
256.T-402A
TELECOMMUNICATIONS RACK
ELEVATION
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
RACK EQUIPMENT
CABLE INFORMATION
1 ALL CAT3
2 ALL CAT5E
WALL
RACK 1
A.F.F. A.F.F.
1 PLYWOOD BACKBOARD
2 WALL MOUNTED SIECOR ENCLOSURE
3 WALL MOUNTED 110 BLOCK
4 2U 48 PORT PATCH PANEL
5 1U CISCO 3850 SWITCH
6 UPS
WIRE
MANAGER
WALL MOUNTED
RACK
WALL WALLWALL
WALL MOUNTED
RACK
WIRE
MANAGER
STEP STEP
RACK 1
SCALE: NONE
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
226.1
4''C. CEILING/RISER 1
110 BLOCK FIBER
CR
226.1
SS
MM
SCALE: 1/4" = 1' - 0"
NORTH
256.T-403
TELECOMMUNICATIONS
ENLARGED PLAN - TR ROOM 226
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
Key Plan
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
TR ROOM
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA
RACKS WITH VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
EXISTING FIRE RATED TELEPHONE
BACKBOARD.
EXISTING 12”W CABLE LADDER RACK MOUNTED
AT 84" AFF AND FIXED TO TOP OF EQUIPMENT
RACKS TO REMAIN (TYPICAL).
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NEW 12''W X 1 1/ 2''H LADDER RACK.
NEW 4 POST DATA RACK 84''H. WITH
HORIZONTAL & VERTICAL WIRE MANAGERS.
EZ PATH SLEEVES. QUANTITY AS REQUIRED.
SEE T-504.
TDU (TUBE DISTRIBUTION UNIT)
SCALE: 1/4" = 1' - 0"
NORTH
256.T-403A
TELECOMMUNICATIONS RACK
ELEVATION TR 226
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
RACK EQUIPMENT
CABLE INFORMATION
1 ALL CAT3
2 ALL CAT5E
WALL 1 PLYWOOD BACKBOARD
2 WALL MOUNTED SIECOR ENCLOSURE
3 WALL MOUNTED 110 BLOCK
4 2U 48 PORT PATCH PANEL
5 1U WIRE MANAGER
6 1U CISCO 3850 SWITCH
7 UPSWIRE
MANAGER
(TYP.)
WALL MOUNTED
RACK
WIRE
MANAGER
WALL WALL WALL
WALL MOUNTED
RACK
WALL MOUNTED
CABINET
WALL MOUNTED
CABINET
RACK 1RACK 1
SCALE: NONE
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5…