S02 ATTACHMENT F_ Drawings Part 2 of 5_Strut-Mech.pdf
PDF 14 MB Posted
- Solicitation number
- 36C26221B0009
About this file
This document provides details of an upcoming federal contract opportunity for construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 will issue an Invitation for Bid between July 13, 2021 and July 27, 2021 for Project 691-20-200, Electronic Health Record Modernization Infrastructure Upgrades at the VA West Los Angeles Healthcare System located in Los Angeles, California. The scope of work includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures. This requirement is valued between $20,000,000 and $50,000,000. The project is set aside 100% for Service-Disabled Veteran-Owned Small Businesses listed in the Vendor Information Pages database. A site visit will be scheduled for potential offerors prior to proposal submission.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200
BS TB
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
1.
1.
A/E:
ARCHITECT/ENGINEER OF RECORD
D
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
C
B
FINAL CONSTRUCTION
DOCUMENTS
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
June 15, 2021 S-001
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200
BS TB
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
1.
1.
A/E:
ARCHITECT/ENGINEER OF RECORD
D
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
C
B
FINAL CONSTRUCTION
DOCUMENTS
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
June 15, 2021 S-002
MECHANICAL LEGEND &
ABBREVIATIONS
M-001
ABBREVIATIONSYMBOL DESCRIPTIONABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION
MECHANICAL ABBREVIATIONS AND LEGEND
ABBREVIATIONSYMBOL DESCRIPTION
ROUND DUCT
ROUND ELBOW ( LONG RADIUS )
12 INCH DIAMETER DUCT12"Ø
STRAIGHT TEE
A
ACM ASBESTOS CONTAINING MATERIALS
A/E ARCHITECT / ENGINEER
ABV ABOVE
AMP AMPERE
B
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
CC COOLING COIL
CD CEILING DIFFUSER
CHW CHILLED WATER
CFM CUBIC FEET PER MINUTE
CG CEILING GRILLE
CP CONDENSATE PUMP
CU CONDENSING UNIT
CW COLD WATER
D
DB DRY-BULB TEMPERATURE
DB DECIBELS
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DN DOWN
DX DIRECT EXCHANGE
DWGS. DRAWINGS
E
(E) EXISTING
EHRM ELECTRONIC HEALTH RECORDS
MODERNIZATION
F
F DEGREES FAHRENHEIT
FT FEET
H
HP HORSEPOWER
HW HOT WATER
HZ HERTZ
I
I/O INPUT/OUTPUT
IN INCHES
J
JCI JOHNSON CONTROL INC.
M
MAX MAXIMUM
MBH 1,000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
N
NA NOT APPLICABLE
NAE NETWORK AUTOMATION ENGINE
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
R
RA RETURN AIR
REQ. REQUIREMENT
S
SA SUPPLY AIR
SEN SENSIBLE HEAT
SQ FT SQUARE FOOT (FEET)
SS SPLIT SYSTEM
STRUCT. STRUCTURAL
T
TAB TESTING, ADJUSTING AND BALANCING
TD TEMPERATURE DIFFERENCE
THRU THROUGH
TR TELECOMMUNICATION ROOM
TYP TYPICAL
U
UNO UNLESS OTHERWISE NOTED
UTR UP THROUGH ROOF
V
V VALVE
VA VETERAN AFFAIRS
W
W WATTS
WB WET-BULB (TEMPERATURE)
WC WATER COOLED
W/ WITH
1. THESE DRAWINGS ARE A GENERAL GRAPHIC PRESENTATION OF THE WORK. DUCTWORK,
PIPING, AND EQUIPMENT, AS SHOWN, ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS.
PROVIDE ADDITIONAL OFFSETS AND SECTIONS OF DUCTWORK AND PIPING AS REQUIRED
TO MEET THE PROJECT REQUIREMENTS.
2. COORDINATE WITH OTHER TRADES. PROVIDE A COMPLETE SET OF FABRICATION
DRAWINGS REFLECTING ACTUAL DIMENSIONS, ACCESS REQUIREMENTS, AND DETAILS
BASED UPON THE ACTUAL EQUIPMENT PROCURED. MAINTAIN AN UP TO DATE SET OF
AS-BUILT DRAWINGS AT THE JOB SITE.
3. COMPLY WITH APPLICABLE MECHANICAL CODE, PLUMBING CODE, FIRE PROTECTION
CODE, AND ALL OTHER GOVERNING CODES. THERE SHALL BE NO EXCEPTION. REPORT
DEFICIENCIES WITHIN THIRTY (30) DAYS UPON AUTHORIZATION TO PROCEED.
4. REVIEW ALL DRAWINGS AND SPECIFICATIONS INCLUDING ARCHITECTURAL, STRUCTURAL,
MECHANICAL, PLUMBING, FIRE PROTECTION, TELECOMMUNICATION S AND ELECTRICAL.
ANY QUESTIONS SHALL BE BROUGHT UP, IN WRITING, TO THE ATTENTION OF THE
ENGINEER BEFORE THE START OF CONSTRUCTION.
5. PROVIDE ACCESS AND CLEARANCE FOR MAINTENANCE OF MECHANICAL EQUIPMENT AND
COMPONENTS AS RECOMMENDED BY EQUIPMENT MANUFACTURER AND APPLICABLE
CODES, BUT NO LESS THAN 3 FEET ON ALL SIDES.
6. ALL SEALS, BEARINGS, PACKINGS, AND ACCESSORIES FOR ALL EQUIPMENT AND PIPING
SPECIALTIES SHALL BE SUITABLE FOR THE CONTINUOUS OPERATIONAL TEMPERATURES,
PRESSURES, AND CHARACTERISTICS OF THE SYSTEMS THEY SERVE.
7. HANDLE, STORE, AND INSTALL EQUIPMENT PER MANUFACTURER'S INSTRUCTIONS.
8. SUPPORT PIPING IN ACCORDANCE WITH ANSI/MSS SP-58 PIPE HANGERS AND SUPPORTS -
MATERIALS, DESIGN, MANUFACTURE, SELECTION, APPLICATION, AND INSTALLATION.
9. SUPPORT DUCTWORK IN ACCORDANCE WITH ANSI/SMACNA 006 HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE.
10. BRACE PIPING, EQUIPMENT, DUCTWORK, AND CONDUIT IN ACCORDANCE WITH ISAT
DESIGN, INSTALLATION & INSPECTION MANUAL FOR NON-STRUCTURAL SEISMIC BRACING
UNLESS THE AUTHORITY HAVING JURISDICTION HAS ADDITIONAL REQUIREMENTS.
11. COMMISSION AND START-UP THE MECHANICAL SYSTEMS TO ASSURE A COMPLETE AND
OPERATIONAL HVAC SYSTEM IN ACCORDANCE WITH ASHRAE, NEBB, OR AABC.
12. ALL PENETRATIONS THROUGH FIRE RATED CONSTRUCTION SHALL BE FIRE SEALED WITH
UL LISTED THROUGH-PENETRATION SEALING SYSTEMS SUITABLE FOR WALL/FLOOR
ASSEMBLIES AND PENETRATING MATERIAL.
13. MAINTAIN FIRE PROOFING OF STRUCTURAL BEAMS WHERE APPLICABLE.
14. LOCATE ALL ROOF MOUNTED EQUIPMENT IN ACCORDANCE WITH OSHA.
GENERAL NOTES
1. FIELD VERIFY ALL EXISTING CONDITIONS INCLUDING STRUCTURAL, MECHANICAL,
PLUMBING, ELECTRICAL, EQUIPMENT, AND ALL OTHER EXISTING SYSTEMS. MAKE
NECESSARY PROVISIONS TO MAINTAIN THE INTEGRITY OF SYSTEMS PRIOR TO THE
COMMENCEMENT OF DEMOLITION.
2. COORDINATE PHASING OF ALL DEMOLITION AND NEW WORK WITH OTHER TRADES.
REVIEW RENOVATION DRAWINGS TO VERIFY AND DETERMINE EXTENT OF, AND
SCHEDULING FOR, ALL DEMOLITION PRIOR TO PERFORMING ANY WORK.
3. FOR RENOVATION WORK, FIELD VERIFY ALL SIZES, LOCATIONS, AND ROUTING OF
EXISTING ITEMS TO REMAIN, AND OF NEW WORK INDICATED ON THE PLANS. NOTIFY THE
DESIGN AUTHORITY OF ANY DEVIATIONS WHICH MAY AFFECT RENOVATION WORK OR
SYSTEM OPERATION PRIOR TO PROCEEDING WITH THE WORK.
PROJECT NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
POINT OF CONNECTION
POINT OF DISCONNECTPOD
POC
T'STAT
RR
CD
CFM
ER
SYMBOL, SEE EQUIPMENT SCHEDULE
CUBIC FEET PER MINUTE
CEILING DIFFUSER
RETURN REGISTER
EXHAUST REGISTER
HUMIDITY LEVEL SENSOR
THERMOMETERTI
PG
CONTROL VALVE (2-WAY)CV (2W)
CAPPED LINE
VALVE IN RISE
VALVE IN DROP
PIPE UP (RISE)
PIPE DN (DROP)
CD CONDENSATE DRAIN
SHUT-OFF VALVE
UNIONU
STR
FLEXIBLE CONNECTION (PIPE)FC
SUCTION DIFFUSERS
BV
CONTROL VALVE (3-WAY)CV (3W)
BACKFLOW PREVENTERBFP
PRESSURE RELIEF VALVEPR
PRV PRESSURE REDUCING VALVE
THERMOSTAT OR TEMPERATURE SENSOR
(NUMBER INDICATES EQUIPMENT OR
ZONE SERVED)
REMOVE/DEMO EXISTING PIPING
REMOVE/DEMO EXISTING EQUIPMENT
BALANCING VALVE
STRAINER W/ BLOW
DOWN VALVE
PRESSURE GAUGE WITH
SHUTOFF VALVE
TEST WELL (PETE'S PLUG)TW
SOV
CV CHECK VALVE
CONT CONTINUATION
CD
- CFM
T
H
- PHOTO REFERENCE
1 . 1 1 1M -
BUILDING NUMBER
DISCIPLINE
A: ARCHITECTURAL
S: STRUCTURAL
M: MECHANICAL
E: ELECTRICAL
T: TELECOM
SHEET TYPE
1. GENERAL
4. ENLARGED
FLOOR NUMBER
SHEET NUMBER
EXAMPLE
DRAWING NUMBER NOMENCLATURE
TRANSITION - ROUND TO
RECTANGULAR DUCTTRANS.
EXHAUST DUCT DOWNEA
EXHAUST DUCT UPEA
SUPPLY AIR DUCT UPSA
SUPPLY AIR DUCT DOWNSA
T=3'' T
TRANS.
FLEX. CONN. FLEXIBLE DUCT CONNECTION
BD BALANCING DAMPER WITH
LOCKING DEVICE
RETURN AIR
DUCT UP
RETURN AIR
DUCT DOWN
CEILING SUPPLY DIFFUSER
SEE SCHEDULE
FLEXIBLE DUCTWORK
CEILING RETURN GRILLE
SEE SCHEDULE
SIDEWALL REGISTER
SEE SCHEDULE
MANUAL VOLUME DAMPER
RA
RA
MVD
MOTOR OPERATED DAMPERMOD
CEILING EXHAUST GRILLE
SEE SCHEDULE
REMOVE/DEMO EXISTING EQUIPMENT
REMOVE/DEMO EXISTING DUCTWORK
TRANSITION RECTANGULAR DUCT
x1
SPLITTER THROAT SIZE
D CFM
RECTANGULAR DUCT DIMENSIONS
SQUARE ELBOW
RECTANGULAR ELBOW (LONG RADIUS)
HVAC EQUIPMENT SEE SCHEDULE-
C CFM
B CFM
A CFM
1. PROVIDE MECHANICAL SHOP DRAWINGS IN ACCORDANCE WITH GI006.
MECHANICAL SHOP DRAWING NOTES
MECHANICAL SCHEDULES
M-002
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
SPLIT SYSTEM SCHEDULE (HEAT PUMP)
INDOOR
SYMBOL AREA SERVED
INDOOR FAN SECTION
OUTDOOR
SYMBOL
OUTDOOR SECTION
MAX.
CFM V Ø Hz
WEIGHT
(LBS) MCA V Ø Hz
WEIGHT
(LBS)
COOLING CAPACITY
MIN
SEER
MAX. PIPING
LENGTH (FT)NOMINAL
TONNAGE
SENS.
CAP.
(MBH)
AMB
(°F)
DETAIL REMARKSREFRIGERANT
TYPE
BLDG 206 ROOM 101 568 1 60 31 13.75 1 60 104 R410A 97.7 14 98
BLDG 206 ROOM 146 1 60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 31 13.75 1 60 R410A 97.7
60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 31 13.75 1 60 R410A 97.7
1 60 31 13.75 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 1 60 R410A 97.7 98
1 60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1.25
DESCRIPTION
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DESCRIPTION
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
BLDG 206 ROOM 244
BLDG 210 ROOM 9
BLDG 210 ROOM 122C
BLDG 210 ROOM 221K
BLDG 213 ROOM B-9
BLDG 213 ROOM 103
BLDG 213 ROOM 201
BLDG 213 ROOM 301
BLDG 214 ROOM B01
BLDG 214 ROOM 205
BLDG 214 ROOM 306
BLDG 215 ROOM B7
BLDG 215 ROOM 123
DUCTLESS SPLIT SYSTEM 1 60 1 60 R410A 97.7 98CONDENSING UNIT
REFER TO THE FOLLOWING SHEET FOR SCHEDULE NOTES.
BLDG 217 ROOM 002
BLDG 217 ROOM 107
BLDG 217 ROOM 202
BLDG 218 ROOM 4
BLDG 218 ROOM 101
BLDG 217 ROOM 302
BLDG 218 ROOM 201
BLDG 220 ROOM 014
BLDG 220 ROOM 121
BLDG 218 ROOM 302
BLDG 220 ROOM 225
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
13.75
13.75
13.75
13.75
13.75
13.75
16.4
13.75
13.75
13.75
13.75
13.75
13.75
13.75
568 1 60 31 104 9813.75 1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
2.0
1.25
1.25
1.25
1.25
1.25
1.25
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
568 31 13.75 104 981.25
568 31 13.75 104 981.25
568 31 13.75 104 981.25
568 31 13.75 104 981.25
568 31 13.75 104 981.25
568 31 13.75 104 981.25
568 31 13.75 104 981.25
98568 31 13.75 104 1.25
98568 31 13.75 104 1.25
SS
210-9
CU
210-9
SS
210-122C
CU
210-122C
SS
210-221K
CU
210-221K
SS
213-B-9
CU
213-B-9
SS
213-103
CU
213-103
SS
213-201
CU
213-201
SS
213-301
CU
213-301
SS
214-1
CU
214-1
SS
214-205
CU
214-205
SS
214-306
CU
214-306
SS
215-B7
CU
215-B7
SS
215-123
CU
215-123
SS
215-233
CU
215-233
SS
215-333
CU
215-333
SS
217-002
CU
217-002
SS
217-107
CU
217-107
SS
217-202
CU
217-202
SS
217-302
CU
217-302
SS
218-4
CU
218-4
SS
218-101
CU
218-101
SS
218-201
CU
218-201
SS
218-302
CU
218-302
SS
220-121
CU
220-121
SS
220-225
CU
220-225
SS
220-332
CU
220-332
SS
256-1
CU
256-1
SS
256-102
CU
256-102
SS
256-226
CU
256-226
SS
257-1
CU
257-1
SS
257-135
CU
257-135
SS
257-215
CU
257-215
SS
258-104A
CU
258-104A
SS
258-120
CU
258-120
SS
258-210A
CU
258-210A
SS
220-014
CU
220-014
SS
206-101
CU
206-101
SS
206-146
CU
206-146
SS
206-224
CU
206-244
10.0
9.3
7.3
7.5
7.3
7.3
12.4
4.6
6.9
7.4
6.9
4.5
4.5
4.8
4.7
2.3
4.8
4.6
7.1
7.3
7.2
5.1
7.0
7.3
7.3
9.9
11.9
9.5
9.5
10.0
15.0
9.4
9.6
10.0
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
BLDG 220 ROOM 332
BLDG 256 ROOM 1
BLDG 256 ROOM 102
1 2 3 4
1 2 3 4
1 2 3 4
13.75
13.75
13.75
1.25
1.25
1.25
5 6
5 6
5 6
B5 / M-501
B5 / M-501
B5 / M-501
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
BLDG 256 ROOM 226
BLDG 257 ROOM
BLDG 257 ROOM 135
1 2 3 4
1 2 3 4
1 2 3 4
13.75
13.75
13.75
1.25
1.25
1.25
5 6
5 6
5 6
B5 / M-501
B5 / M-501
B5 / M-501
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
BLDG 257 ROOM 215
BLDG 258 ROOM 104A
BLDG 258 ROOM 120
1 2 3 4
1 2 3 4
1 2 3 4
13.75
13.75
13.75
1.25
1.25
1.25
5 6
5 6
5 6
B5 / M-501
B5 / M-501
B5 / M-501
1 60 31DUCTLESS SPLIT SYSTEM BLDG 258 ROOM 210A 568 208 1 60 R410A 97.7 98CONDENSING UNIT 13.75 104 1.25 14208 B5 / M-501 1 2 3 4 5 6 7
BLDG 215 ROOM 233
BLDG 215 ROOM 333
7.3
4.7
4.6
4.8
MCA
M-003
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
SPLIT SYSTEM SCHEDULE (HEAT PUMP) (CONTINUED)
SYMBOL AREA SERVED
INDOOR FAN SECTION
SYMBOL
OUTDOOR SECTION
MAX.
CFM V Ø Hz
WEIGHT
(LBS) MCA V Ø Hz
WEIGHT
(LBS)
COOLING CAPACITY
MIN
SEER
MAX. PIPING
LENGTH (FT)NOMINAL
TONNAGE
SENS.
CAP.
(MBH)
AMB
(°F)
DETAIL REMARKSREFRIGERANT
TYPE
BLDG 258 ROOM 215 568 1 60 31 13.75 1 60 104 R410A 97.7 98
BLDG 258 ROOM 335 1 60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 31 13.75 1 60 R410A 97.7
60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1 60 31 13.75 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 31 1 60 R410A 97.7
1 60 1 60 R410A 97.7 98
1 60 1 60 R410A 97.7
1 60 1 60 R410A 97.7
1.25
DESCRIPTION
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DESCRIPTION
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
BLDG 258 ROOM 404
BLDG 304 ROOM 2-2
BLDG 304 ROOM 106B
BLDG 304 ROOM 2-223A
BLDG 304 ROOM 224
BLDG 345 ROOM 39A
BLDG 401 ROOM A100G
BLDG 401 ROOM A-239
BLDG 402 ROOM 2413
BLDG 507 ROOM 102
BLDG 527 ROOM 22
BLDG 527 ROOM 23
DUCTLESS SPLIT SYSTEM 1 60 1 60 R410A 97.7 164CONDENSING UNIT
PROVIDE FACTORY WIRED WALL-MOUNTED THERMOSTAT.
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3
1 2 3 4
1 2 3 4
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
DO NOT EXCEED MANUFACTURER'S LISTED MAXIMUM PIPING LENGTH REQUIREMENTS. COORDINATE SELECTION WITH ACTUAL LENGTHS FROM SHOP DRAWINGS.
PROVIDE W/ FACTORY PROVIDED FIELD INSTALLED CONDENSATE PUMP.1 2 3 4 INDOOR UNIT POWERED FROM THE OUTDOOR UNIT. REFER TO ELECTRICAL
55 PROVIDE PER APPLICABLE OSP.
31 13.75
568 1 60 31 104 9813.75 1.25
1.25
1.25
1.25
6 VERIFY AND COORDINATE CONNECTION SIDE PRIOR TO PROCUREMENT.
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
5 6
7 PROVIDE WITH INTEGRAL OVERFLOW ALARM TO SHUFT OFF THE EVAPORATOR IN CASE OF BLOCKAGE OR FAILURE.
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
B5 / M-501
568 31 13.75 104 981.25
568 31 13.75 104 981.25
568 31 13.75 104 981.25
568 31 13.75 104 981.25
568 31 13.75 104 981.25
568 31 13.75 104 981.25
98568 31 13.75 104 1.25
16431 172
2.0
7.8
9.9
10.6
7.2
11.9
8.2
1.9
13.4
16.4
18.2
7.2
4.6
4.6
SS
258-215
CU
258-215
SS
258-335
CU
258-335
SS
258-404
CU
258-404
SS
304-2-2
CU
304-2-2
SS
304-2-106B
CU
304-2-106B
SS
304-2-223A
CU
304-2-223A
SS
304-224
CU
304-224
SS
345-39A
CU
345-39A
SS
401-A100G
CU
401-A100G
SS
401-A-239
CU
401-A-239
SS
402-2413
CU
402-2413
SS
507-102
CU
507-102
SS
527-22
CU
527-22
SS
527-23
CU
527-23
10.8
12.6
SS
500-10IN
SS
500-10IS
SS
500-11IN
SS
500-11IS
SS
500-12IN
SS
500-12IS
SS
500-13IN
SS
500-13IS
SS
500-14IN
SS
500-14IS
SS
500-15IN
SS
500-15IS
SS
500-16IN
SS
500-16IS
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEM
CU
500-10IN
CU
500-10IS
CU
500-11IN
CU
500-11IS
CU
500-12IN
CU
500-12IS
CU
500-13IN
CU
500-13IS
CU
500-14IN
CU
500-14IS
CU
500-15IN
CU
500-15IS
CU
500-16IN
CU
500-16IS
13.4
13.4
13.4
13.4
13.4
13.4
13.4
13.4
13.4
13.4
13.4
13.4
13.4
1 2 3
1 2 3
1 2 3
5 6
5 6
5 6
1 60 R410A
1 60 R410A
1 60 R410A
208 172
2.0
CONDENSING UNIT
CONDENSING UNIT
CONDENSING UNIT
97.7
97.7
97.7
B5 / M-501
B5 / M-501
B5 / M-501
1 60 31
1 60
1 60 31
31 16.5
16.5
16.5
16.5
16.5
16.5
16.5
16.5
16.5
16.5
16.5
16.5
16.5
16.5
BLDG 500 ROOM 10IN
BLDG 500 ROOM 10IS
BLDG 500 ROOM 11IN
BLDG 500 ROOM 11IS
BLDG 500 ROOM 12IN
BLDG 500 ROOM 12IS
BLDG 500 ROOM 13IN
BLDG 500 ROOM 13IS
BLDG 500 ROOM 14IN
BLDG 500 ROOM 14IS
BLDG 500 ROOM 15IN
BLDG 500 ROOM 15IS
BLDG 500 ROOM 16IN
BLDG 500 ROOM 16IS
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
635 1642.017216.5
635 17216.5 1642.0
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
MCA
M-004
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
DESCRIPTIONSYMBOL
CFM
SUPPLY FAN
QTY
AREA SERVED
FC
HP
REMARKS
V PHHZ
COOLING COIL
DB WB
LAT (F°)
DB WB
GPM
MINIMUM
NOMINAL
TONNAGE
SENSIBLE
CAPACITY
(MBH)
PROVIDE SECONDARY CONDENSATE PAN AND CONDENSATE PAN OVERFLOW SWITCH BY FAN COIL MANUFACTURER.
208 60 1
WITH EC MOTOR.1 2
1 2
AMPS
FC BLDG 500 ROOM 10SD 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
FC 208 60 1 1 2
BLDG 500 ROOM 10SJ
BLDG 500 ROOM 10SA
BLDG 500 ROOM 10SH
BLDG 500 ROOM 11SE
BLDG 500 ROOM 11SO
BLDG 500 ROOM 12SE
BLDG 500 ROOM 13SA
BLDG 500 ROOM 13SE
BLDG 500 ROOM 14SE
BLDG 500 ROOM 14SA
BLDG 500 ROOM 15SA
BLDG 500 ROOM 15SE
BLDG 500 ROOM 16SA
BLDG 500 ROOM 16SE
FC 208 60 1 1 2BLDG 500 ROOM 11SN
1.25825 4 13.41.9EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
EXPOSED SUSPENDED CHW FAN COIL
(2) 1/4
MIN.
ROWS
3 70
EWT
(F°)
LWT
(F°)
BRANCH
SIZE
1.9 44
MAX.
WATER PD
(FT)
MAX.
OPER.
WEIGHT
(LBS)
MOUNTING
DETAIL
55 58 55 58 3/4 13.1 81 C8 / M-502
1.25825 4 13.41.9 (2) 1/4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25825 4 13.41.9 (2) 1/4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25825 4 13.41.9 (2) 1/4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
1.25 13.4 3 70 1.9 4455 58 55 58 3/4 13.1 81 C8 / M-502
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
825 4 1.9 (2) 1/4
EAT (F°)
FAN COIL SCHEDULE
500-10SJ
500-10SD
500-10SA
500-11SH
500-11SE
500-11SO
500-12SE
500-13SA
500-13SE
500-14SE
500-14SA
500-15SA
500-15SE
500-16SA
500-16SE
500-11SN
NON DUCTED.3 PROVIDE PER APPLICABLE OSP.4 PROVIDE FACTORY MOUNTED CONDENSATE PUMP WITH SINGLE POINT POWER.5
VERIFY AND COORDINATE CONNECTION SIDE PRIOR TO PROCUREMENT.6
SERVICE
AIR DISTRIBUTION SCHEDULE
SYMBOL
6"Ø 0-95
MOUNTING
SURFACE
T-BAR/
HARD
CEILING
DESCRIPTION
4-WAY,
MODULAR
CORE CEILING
DIFFUSER
NECK
SIZE PHOTO
NECK
SIZE
T-BAR/
HARD
CEILING
SUPPLY
AIR
RETURN
AIR
REMARKS
ALUMINUM
CONSTRUCTION
ALUMINUM
CONSTRUCTION
MATCH
EXISTING
ADJACENT
STYLE
8"Ø 95-210
10"Ø 210-370
12"Ø 370-600
14"Ø 600-900
16"Ø 900-1,290
8"Ø 190
10"Ø 340
12"Ø 560
14"Ø 890
16"Ø 1,190
18"Ø 1,610
CFM
RANGE
MAX
CFM
A CFM
B CFM
WITH BOTTOM RETURN.7
RA
MP
U P
RAMP UP
CHAIN LINK CAGE
RAMP UP
EXIT DOOR
A B C D E F G H
3.2
1.1
MEN'S
RR
WOMEN'S
RR
ELEV
LOBBY
ELEV
ELEV
MACH RM
MEN'S
SHOWER
INTAKE
RM
VESTING
OFFICE
SOCIAL WORKER
OFFICE
ELIGIBILITY
CLERK OFFICE
ELIGIBILITY
CLERK OFFICE
SCREENING
RM
RECEPTION
SCREENING
RM
WORK
AREA
014A
PSYCHIATRIST
CLINICAL
CO-ORDR
SCREENING
CLINIC
OFFICE OF
SCREENING CLERK
CL
QUIET
RM
CLINICAL SUPPORT
OFFICE
CLINICAL SUPPORT
PGM MGR OFFICE
OUTREACH
COMMUNITY CARE
STORAGE
018A
STAFF
KITCHEN
OFFICE
STAIR
SUPPLY
RM
STORAGE
OFFICE
SOCIAL
WORKER OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
034A
OFFICE
SOCIAL WORKER
OFFICE
SOCIAL WORKER
OFFICE
SOCIAL WORKER
OFFICE
SOCIAL WORKER
OFFICE
GRANT PER DIEM
LIAISON OFFICE
BENEFIT &
COUNSELOR OFFICE
COPY
RM
CLINICAL STAFF
GRANT PER DIEM
STEAM RM
STAIR
CORRIDOR
TELECOM
ROOM
ELECTRICAL
ROOM
001A
C1 206.M-401
CU
206-101
E1 206.M-401
3/4" CD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
206.M-101
MECHANICAL BASEMENT FLOOR
PLAN - BUILDING 206 BUILDING 206
MECHANICAL BASEMENT FLOOR PLAN - BUILDING 206F1 SCALE:
NORTH
SCALE: 1/8" = 1'-0"
1. DISCHARGE CONDENSATE DRAIN TO LAVATORY
TAILPIECE. SEE DETAIL F8/M-501.
2. PROVIDE CODE REQUIRED AND MANUFACTURER'S
RECOMMENDED EQUIPMENT CLEARANCE.
3. PROVIDE CONCRETE HOUSEKEEPING PAD.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1A
0' 4' 8' 16'
DN
DN
UP UP
A B C D E F G H
3.2
1.1
RA
MP
D
OW
N
DN
DN
ROLL DOWN DOOR
TELECOM
ROOM
SOCIAL WORKER
OFFICE
CHAPLAIN
MED RM
RECEPTION
VA SUPPORT
HOUSING OFFICE
VA SUPPORT
HOUSING OFFICE
PGM
MGR
CONFERENCE
RM
STAIR
CORRIDOR
GRANT PER DIEM
NURSING LIAISON
PGM
SPECIALIST
112BHCRV DEPUTY
PGM MGR
112A
PIPE SPACE
CORR
WASH RM
& TOILET
SHOWER RM
113A
ASSOC. OFFICE NURSE COMM/
PRIMARY & AMBULATORY CARE
PIPE SPACE
ELEC RM
SOCIAL
WORKER
SOCIAL
WORKER
CHIEF OF
MENTAL HEALTH
SOCIAL SCIENCE
PGM SPECIALIST
119A
GRANT PER
DIEM OFFICE
ADMIN
OFFICER
CORR
CORR
STAIR-2
STAIR-3
STAIR
WAITING
RM
MENTAL HEALTH CLINICAL
PHARMACIST
EMS
121A
EMS
MEN'S
STAFF RR
ADMIN
SUPPORT
HEAD
NURSE
COMPUTER RM
W. RR
SOCIAL
SVC
QUALITY
MGMT
PGM MGR
NURSE
MGR
130 CHIEF OF
COMM CARE
CORR
CHIEF OF
COMM CARE
CLINICAL
KITCHEN
CORR
MEN'S TOILET
CORR
P. S.
135A
LOCKERS
SELF CHECK IN
PIPE CHASE
TRIAGE
CARE MGR
MEN
STAFF RR
CORR
EMS
EXAM
RM-10
14-
ELEV
MEDICATION
RM
PRIMARY CARE
CLINIC
LAB
NURSES
OFFICE
143A
PHYSICIAN ASST
OFFICE
CORR
WAITING RM
PTSD PGM
CORR
IT/COMM RM
STORAGE RM
147A
PIPE SPACE
H/C WOMEN'S
WASH RM & TOILET
EXAM
RM-8
EXAM
RM-6
EXAM
RM-4
149A
EXAM
RM-1
MULTI PURPOSE
RM
STAIR
CORRIDOR
DOCTORS
OFFICE
DOCTORS
OFFICE
RNS
OFFICE
153A
NURSES
OFFICE
153B
NURSES
STATION
HEAD
NURSE
WAITING
RM
CLINICAL
PHARMACIST
WHITE TEAM
TRIAGE
TOILET
158A
TOILET
CORR
P. S.
STORAGE
RM 147A
CU
206-244
CU
206-146
3/4" CD
C4 206.M-401
E4 206.M-401
(TYP)
(TYP)
CD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
206.M-111
MECHANICAL FIRST FLOOR PLAN -
BUILDING 206 BUILDING 206
MECHANICAL FIRST FLOOR PLAN - BUILDING 206F1 SCALE:
NORTH
0' 4' 8' 16'SCALE: 1/8" = 1'-0"
1. CONDENSATE DRAIN DISCHARGE TO UTILITY SINK.
SEE DETAIL F5/M-501.
2. PROVIDE CODE REQUIRED AND MANUFACTURER'S
RECOMMENDED EQUIPMENT CLEARANCE.
3. PROVIDE CONCRETE HOUSEKEEPING PAD.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1B
1C
C
DN DN
A B D E F G H
3.2
1.1
DN
UP TO ATTIC
FE
TELECOM
ROOM
GROUP
RM
STAIR
STAIR-2
STAIR-3
STAIR
STAIR
STAFF
PSYCHIATRIST
SOCIAL
WORKER
REGISTERED
NURSE
CORR
STAFF
PSYCHIATRIST
STAFF
PSYCHIATRIST
CORRIDOR
WAITING
RM
ADMIN
ASST
OFFICE
CLINICAL OPERATION
OFFICE
PSYCHOLOGIST
STAFF
PSYCHIATRIST
TREATMENT
RM
RN SUPPLY
RM
ELEV STAFF
KITCHEN
CONFERENCE RM /
GROUP RM
RESEARCH
ASST
WAITING
RM
STAFF
PSYCHIATRIST
REGISTERED
NURSE
CORR
DAY
RM
STAFF
PSYCHIATRIST
STAFF
PSYCHIATRIST
NURSE
PRACTITIONER
P. S.
MEN'S WASH RM
& TOILET
P. S.
IT/COMM
RM
STORAGE
RM
245A
STAFF PSYCHIATRIST
RN
SOCIAL
WORKER
CORR
TEAM CARE
CO-ORDR
CALL CENTER
OFFICE
STAFF
PSYCHIATRIST
CORR
CORR
CORR
CORR
--- HAC
BMS
237A
STAFF
LOUNGE
STAFF
RR
MENTAL HEALTH
STORAGE
234A
P. S.
234B
TOILET & LOCKER
SOCIAL
WORKER
SOCIAL
WORKER
SOCIAL
SVC
WAITING
RM
CLINICAL NURSE
SPECIALIST
SOCIAL WORK
ASSOCIATE
SOCIAL SCIENCE
TECHNICIAN
STAFF
OFFICE
MEN
STAFF RR
HAC
BMS
221A
STAFF
PSYCHIATRIST
PSYCHOLOGICAL
RM
GROUP
RM
CORR
STAFF
PSYCHIATRIST
STAFF
PSYCHOLOGIST
REGISTERED
NURSE
SHOWER
RM
213A
UTILITIES
PIPE CHASE
STAFF
WOMEN RR
PIPE
SPACE
TOILET
257A
WOMEN'S
TOILET
STORAGE
WORK RM
W. STAFF T.
STORAGE RM
245A
C7 206.M-401
E7 206.M-401
3/4" CD
CD
TELECOM
ROOM
STORAGE RM
245A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
206.M-121
MECHANICAL SECOND FLOOR PLAN
- BUILDING 206 BUILDING 206
MECHANICAL SECOND FLOOR PLAN - BUILDING 206F1 SCALE:
NORTH
0' 4' 8' 16'SCALE: 1/8" = 1'-0"
1. CONDENSATE DRAIN DISCHARGE TO UTILITY SINK.
SEE DETAIL F5/M-501.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1D
C1 210.M-401
E1 210.M-401
3/4" CD
(TYP)
(TYP)
(E) MECHANICAL
EQUIPMENT TO REMAIN CU
210-221K
CU
210-122C
CU
210-9
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
210.M-101
MECHANICAL BASEMENT FLOOR
PLAN - BUILDING 210 BUILDING 210
MECHANICAL BASEMENT FLOOR PLAN - BUILDING 210F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. CONDENSATE DRAIN DISCHARGE INDIRECTLY TO MOP
SINK. ROUTE PIPING EXPOSED IN THE ROOM.
2. PROVIDE CODE REQUIRED AND MANUFACTURER'S
RECOMMENDED EQUIPMENT CLEARANCE.
3. PROVIDE CONCRETE HOUSEKEEPING PAD.
4. RS/RL UP TO FIRST FLOOR. REFER TO 210.M-111.
5. DEMOLISH CONDENSING UNIT, REFRIGERANT PIPES
TO/FROM THE ASSOCIATED INDOOR UNIT, AND ALL
ASSOCIATED APPURTENANCES.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1E
C4
E4 210.M-401
NEW TELECOM ROOM
3/4" CD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
210.M-111
MECHANICAL FIRST FLOOR PLAN -
BUILDING 210 BUILDING 210
MECHANICAL FIRST FLOOR PLAN - BUILDING 210F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. DISCHARGE CONDENSATE DRAIN TO UTILITY SINK. SEE
DETAIL F5/M-501.
2. NOT USED.
3. RS/RL DOWN TO BASEMENT FLOOR. REFER TO 210.M-101
FOR CONTINUATION.
4. RS/RL DOWN TO BASEMENT FLOOR AND UP TO SECOND
FLOOR. REFER TO 210.M-101 AND 210.M-121 FOR
CONTINUATION.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1F
C7
E7 210.M-401
3/4" CD
NEW TELECOM ROOM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
210.M-121
MECHANICAL SECOND FLOOR PLAN
- BUILDING 210 BUILDING 210
MECHANICAL SECOND FLOOR PLAN - BUILDING 210F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. DISCHARGE CONDENSATE DRAIN TO UTILITY SINK. SEE
DETAIL F5/M-501.
2. RS/RL DOWN TO BASEMENT AND FIRST FLOOR. REFER TO
210.M-101 AND 210.M-111 FOR CONTINUATION.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1G
UP
UP
A
B
C
D
E
G
F
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 1910
UNISEX
TOILET
B43A
ELECTRICAL
CLOSET
B03
CLOSET
ELEV
MACH
RM
B02
LOCKER
B43
MENS
TOILET
B34
WOMENS
TOILET
B32
ELC
PANEL
B20A
SOILED
INSTRUMENTS
B28
LOCKER
B26B
SUPPLIES
B24A
PATIENT
RESTROOM
B17A
TELELECOM
RM
B09
CORRIDOR
EXAM RM
B41HEMODIALYSIS
B44 B36
EXIT
CORRIDOR
B35
ELC CL
B43B
KITCHEN
B42
DIALYSIS
PREPARATION
B45 TECH SUPPLIES
B46
LOCKER
B47
B48
WATER
TREATMENT
B50
NURSING
SUPPLIES
B51
SUPPLIES
B52B44A
HAC
B37
EMS
SUPPLY
RM
B39
LOCKER
B38
TOILET
B40
ELEVATOR
EQUIP
B08
TRANSFORMER RM
SOLAR PANEL
DISCONNECT
B11
B13
COMMUNITY
NURSING HOME
PGM
B14
STORAGE
B15
B16
DOCTORS OFFICE
B17C
DOCTORS OFFICE
B17D
DOCTORS OFFICE
B17
X RAY RM
B19
EXAM RM
B20
DENTAL LAB
B21
B21A
CLEAN RM
B22
SUPPLIES RM
B22A
BARBER SHOP
B07
STORAGE
B06
LAUNDRY
B05
WASTE COLLECTION
B04
PHARMACY
B33
VAULT
B33B
CLOTHING RM
B01
LOUNGE
B33A
CONFERENCE
RM
B31A
PHARMACY
B31
WAITING
B30
TREATMENT RM
B29
EXAM RM
B25
LOUNGE
B26LOCKER
B26C
TOILET
B26A
TREATMENT RM
B24
ELEVATOR
EAST
STAIR
B49
ELEVATOR
CENTRAL
STAIR
B12
WEST
STAIR
B23
EL 01
EL 02
STORAGE
ELECTRICAL RM
LOBBY
CL 01
HEMODIALYSIS SOILED
UTILITY
SUPPLIES
B36A
LAB
CR 01
C1 213.M-401
E1 213.M-401
3/4" CD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
213.M-101
MECHANICAL BASEMENT FLOOR
PLAN - BUILDING 213 BUILDING 213
MECHANICAL BASEMENT FLOOR PLAN - BUILDING 213F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. DISCHARGE CONDENSATE DRAIN TO MOP SINK. SEE
DETAIL C5/M-502.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1H
DNUP
UP
UP
H/C
TELECOMM
RM 103
BLDG
ENTRY
A
B
C
D
E
G
F
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 1910
RESTROOM
120A 110
ELEC
CLO
114A
DINING HALL
ELEVATOR LOBBY
CORRIDOR
MENS
RESTROOM
OCCUPATIONAL THERAPY
CONFERENCE RM
106B
106D
TOILET
106C
TOILET
106A
TOILET
106DIETICIAN
MED
DIRECTORS
SUITE
CHIEF GRC
107A
EAST STAIRWEST STAIR CENTER STAIR
ELEVATOR
SVC
ELEVATOR
WAITING RM
COMPUTER
ASST
TIMEKEEPER
EXERCISE GYM
WOMENS
RESTROOM
SOCIAL WORK
CO-ORDR
104B
104A
COPY RM
107C
CLINICAL
DIRECTOR
107B108
GERIATRIC
NURSE
PRACTITIONER
109B
GERIATRIC
EDUCATIONAL
109A
AUDIO
SPEECH
109ADMIN
OFFICER
112A
112B112C
SWA
SOILED LINEN
OFFICE
FOOD
WARMING RM
SUPPLIES RM (FOR
RECREATION ACTIVITY)
124C
STORAGE
ELC
CL
RECREATION THERAPY
HAC
TRASH
AREA
STORAGE SHOWER
TOILET
PSYCHOLOGIST
101A
EL 02
ST 03 ST02
LOUNGE
CR 04
CORRIDOR
CR 01
OFFICE
OFFICE
OFFICE
ELEC
CL
TOILET
EXERCISE RM
ST01
ELEVATOR
C4 213.M-401
E4 213.M-401
3/4" CD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
213.M-111
MECHANICAL FIRST FLOOR PLAN -
BUILDING 213 BUILDING 213
MECHANICAL FIRST FLOOR PLAN - BUILDING 213F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. DISCHARGE CONDENSATE DRAIN TO MOP SINK. SEE
DETAIL C5/M-502.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1I
DN
UP
UP
UP
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 1910
A
B
C
D
E
G
F
TELECOM
RM
CLO
TOILET
OXYGEN
STORAGE
ELECT
CLOSET
ELC
CL
ELC CL
SHOWER BATH
AND TOILET RM
CONGREGATE
BATH AND
TOILET RM
TOILET
CORRIDOR
ELEVATOR
LOBBY
TV LOUNGE/
WAITING AREA
TOILET
TOILET
2-BED
PATIENT RM
TOILET
2 BED
PATIENT RM
2 BED
PATIENT RM
TOILET
2 - BED
PATIENT RM
2 - BED
PATIENT RM
TOILET
2 - BED PATIENT
RM
4 - BED PATIENT RM
TOILET
TOILET
NURSE
STATION
2 - BED
PATIENT RM
NURSE MGR
MEDICATION
RM
SVC
ELEVATOR 224
NOURISHMENT
KITCHEN RM
SOLID LINEN RM
2-BED RM
TOILET
TOILET
DAY RM AND TOILET RM
2 - BED
PATIENT RM
TOILET
TOILET
2 - BED
PATIENT RM
2 - BED
PATIENT RM
2 - BED PATIENT
RM
TOILET
1 - BED
PATIENT RM
TOILET
TOILET
2 - BED
PATIENT RM
EAST STAIR
TOILET
207TOILET
TOILET
4 - BED PATIENT RM
TOILET
ELEVATOR
HAC
250249
WARD
SUPPLY
RM
LINEN
SUPPLY RM
CENTER STAIR
2 - BED PATIENT RM
TOILET
TOILET
4 - BED PATIENT RM
2 - BED PATIENT
RM
TOILET
COPY RM
2 - BED
PATIENT RM
TOILET
2 - BED
PATIENT RM
WEST STAIR
2 BED PATIENT RM
ST 03
240A
244A 246A
245A
ST 01
TREATMENT RM NURSE MGR
STAFF
RESTROOM
2 BED
PATIENT RM
TOILET
AND
SHOWER
202A 2 - BED
PATIENT RM
204A
206A
2 - BED PATIENT
RM
2 - BED PATIENT
RM
ST 02
209A
210A211A
213A
2 - BED PATIENT
RM
214A
217A
218A
PIPE CHASE
NURSE LOUNGE
EL 02
LAUNDRY RM
PIPE CHASE
230A
231A
234A
235A
237A238A
239A
CL 01
CORRIDOR
CR 02
CR 01
242A
203A
ELEVATOR
207A
C7 213.M-401
E7 213.M-401
3/4" CD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
213.M-121
MECHANICAL SECOND FLOOR PLAN
- BUILDING 213 BUILDING 213
MECHANICAL SECOND FLOOR PLAN - BUILDING 213F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. DISCHARGE CONDENSATE DRAIN TO MOP SINK. SEE
DETAIL C5/M-502.
2. ROUTE CONDENSATE EXPOSED BELOW CEILING. PATCH
AND REPAIR CEILING AS REQUIRED.
1J
DN
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 1910
A
B
C
D
E
G
F
TELECOM
RM
HBPC OFFICE
TOILET &
SHOWER
TOILET
TOILET
ELC
ELC
COPY RM
ELC
CL
CLCL
CORRIDORCORRIDOR
WAITING AREA
CORRIDOR
TOILET
TOILET
OFFICE
TOILET
OFFICE
TELECARE
OFFICE
TOILET
TELECARE
OFFICE
TELECARE
OFFICE
334 TOILET
OFFICE
OFFICE
TOILET
OFFICE
NURSE STATION
328 327
ELEVATOR
WOUND CARE
PGM MGR
HPBC OFFICE
TOILET
TOILET
HBPC OFFICE
HBPC OFFICE
TOILET
HBPC OFFICE
HBPC OFFICE
TOILET
HBPC OFFICE
HBPC OFFICE
TOILET
HBPC OFFICE
TOILET
TOILET
EAST STAIR
TOILET
307306TOILET
TOILET
TOILET
HBPC OFFICE
TOILET
OFFICE
ELEVATOR
TOILET 351
350349
SUPPLY
348OFFICE
CENTRAL STAIR
CONFERENCE RM
TOILET
TOILET
OFFICE
OFFICE TELE
HEALTH
COPY
TOILET
STORAGE
OFFICE
TOILET
OFFICE
WEST STAIR
PROGRAM MGR
HBPC OFFICE
ST 03
340A
342A
344A 346A
345A
ST 01
OFFICE OFFICE
HAC
302A
303A
304A
306A
HBPC OFFICE HBPC OFFICE
ST 02
309A
310A311A
312A 314A
317A
318A
NOURISHMENT
KITCHEN
HMPC
SUPPLY/STORAGE
EL 02
STAFF OFFICE
STAFF OFFICE
SUPPLIES
STORAGE
330A
331A
332A
335A
337A 338A
339A
CR 01
ELEVATOR
STORAGE
307A
C1 213.M-402
E1 213.M-402
3/4" CD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
213.M-131
MECHANICAL THIRD FLOOR PLAN -
BUILDING 213 BUILDING 213
MECHANICAL THIRD FLOOR PLAN - BUILDING 213F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. DISCHARGE CONDENSATE DRAIN TO MOP SINK. SEE
DETAIL C5/M-502.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1K
1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 1910
A
B
C
D
E
G
F
CU
213-B-9
CU
213-301
CU
213-103
CU
213-201
2 1
(TYP)
(TYP)
(TYP)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
213.M-1R1
MECHANICAL ROOF PLAN -
BUILDING 213 BUILDING 213
MECHANICAL ROOF PLAN - BUILDING 213F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. PROVIDE CODE REQUIRED AND MANUFACTURER'S
RECOMMENDED EQUIPMENT CLEARANCE.
2. RS/RL DOWN TO FLOORS BELOW. REFER TO 213.M-401
AND 213.M-402 FOR CONTINUATION.
3. PROVIDE CONCRETE HOUSEKEEPING PAD.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
EX
214.M-401
E1 214.M-401
3/4" CD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
214.M-111
MECHANICAL FIRST FLOOR PLAN -
BUILDING 214 BUILDING 214
MECHANICAL FIRST FLOOR PLAN - BUILDING 214F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. DISCHARGE CONDENSATE DRAIN TO MOP SINK. SEE
DETAIL C5/M-502.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
HZ
HZ
C4 214.M-401
E4 214.M-401
3/4" CD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
214.M-121
MECHANICAL SECOND FLOOR PLAN
- BUILDING 214 BUILDING 214
MECHANICAL SECOND FLOOR PLAN - BUILDING 214F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. CONDENSATE DRAIN TO LAVATORY TAILPIECE, SEE
DETAIL. SEE DETAIL F8/M-501.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
WITH MANUFACTURER'S REQUIREMENTS.
1L
HZ
C7
214.M-401
E7 214.M-401
3/4" CD
2 (TYP)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
214.M-131
MECHANICAL THIRD FLOOR PLAN -
BUILDING 214 BUILDING 214
MECHANICAL THIRD FLOOR PLAN - BUILDING 214F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. CONDENSATE DRAIN TO LAVATORY TAILPIECE, SEE
DETAIL F8/M-501.
2. RS/RL UP TO FLOOR BELOW. REFER TO 214.M-1R1
FOR CONTINUATION.
1. RS/RL SIZED PER MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO M-80X FOR PHOTO REFERENCES ( ).
3. ROUTE CONDENSATE DRAIN PIPING CONCEALED ABOVE
CEILING, EXCEPT IN JANITORS CLOSET / HOUSEKEEPING
ROOMS WITH HARD LID CEILINGS. PATCH AND REPAIR
CEILING WHERE REQUIRED TO PENETRATE CEILING.
4. RS/RL ROUTING IS SHOWN FOR REFERENCE.
ALTERNATIVE ROUTING MAY BE USED BASED ON
COORDINATED SHOP DRAWINGS AND IN ACCORDANCE
CU
214-1
CU
214-205
CU
214-306
(TYP)
(TYP)
2(TYP)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h U.S. Department of Veterans Affairs
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
691-20-200FINAL CONSTRUCTION
DOCUMENTS
June 15, 2021 MS TS / JM
FULLY SPRINKLERED
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
D
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
20801.12
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades -
WLA, CA
C
B
214.M-1R1
MECHANICAL ROOF PLAN -
BUILDING 214 BUILDING 214
MECHANICAL ROOF PLAN - BUILDING 214F1 SCALE:
NORTH
0' 4' 16' 24'2' 8'SCALE: 3/32" = 1'-0"
1. PROVIDE CODE REQUIRED AND MANUFACTURER'S
RECOMMENDED EQUIPMENT CLEARANCE.
2. RS/RL DOWN TO FLOORS BELOW. REFER TO 214.M-103
FOR CONTINUATION.
3. PROVIDE CONCRETE…