691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part1.pdf

PDF 44 MB Posted

Attached to
Z2DA--EHRM GLA Main Campus Construction, Project 691-20-200
Solicitation number
36C26221B0009
Issued by

About this file

This notice provides details of an upcoming federal contract opportunity for construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 will issue an Invitation for Bid on or around July 13, 2021 via Contract Opportunities for Project 691-20-200 at the VA West Los Angeles Healthcare System campus. The project scope includes general construction, alterations, mechanical and electrical work, and utility systems for Electronic Health Record Modernization infrastructure upgrades. The work will be performed in a functioning hospital environment. The contract will be set aside 100% for Service-Disabled Veteran-Owned Small Businesses. The North American Industry Classification Code is 236220 for commercial and institutional building construction. The estimated value of the construction project is between $20,000,000 and $50,000,000. A pre-solicitation site visit will be held for interested vendors.

View the file

Other files

File Type Posted
S06 Amendment A003_ DWG 527_E-111.pdf PDF
S06 Amendment A003_COR RFIs_Job Walk Roster_DWGs_GLA EHRM CON_36C26221B0009.pdf PDF
S06 Amendment A003_ DWG T-001.pdf PDF
S06 Amendment A003_ DWG 527_T-111.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part2.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part6.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part3.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part7.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part4.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4 (1) 42 x 30_Part5.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4_1_ 42 x 30_Part3.pdf PDF
691-20-200 Telecommunication 100 Final Drawings Part 4_1_ 42 x 30_Part1.pdf PDF
691-20-200 Elect 100 Final Drawings Part 3_1_ 42 x 30.pdf PDF
691-20-200 Architectural 100 Final Drawings Part 1_ 42 x 30_ Part2.pdf PDF
S06 Amentment A0002_EHRM GLA Main Campus_691-20-200_36C26221B0009.docx DOCX document
691-20-200 Architectural 100 Final Drawings Part 1_ 42 x 30_ Part1.pdf PDF
691-20-200 Strut-Mech 100 Final Drawings Part 2_ 42 x 30.pdf PDF
S06 A0001_Wage Rates_36C26221B0009.pdf PDF
S02 ATTACHMENT E_ Drawings Part 1 of 5_Architectural.pdf PDF
S02 ATTACHMENT F_ Drawings Part 2 of 5_Strut-Mech.pdf PDF
S02 ATTACHMENT C_ Wage Rates 6-25-21.pdf PDF
S02 ATTACHMENT G_ Drawings Part 3 of 5_Elect.pdf PDF
S02 ATTACHMENT B_ Specifications.pdf PDF
S02 ATTACHMENT J_ Facility Map.pdf PDF
S02 ATTACHMENT A_ SOW.pdf PDF
S02 ATTACHMENT I_ Drawings Part 5 of 5_ Telecommunication_Part2.pdf PDF
S02 Solicitation 36C26221B0009_1.pdf PDF
S02 ATTACHMENT D_ GLA Safety Req_Permits_Forms.pdf PDF
S02 ATTACHMENT H_ Drawings Part 4 of 5_ Telecommunication_Part1.pdf PDF
36C26221B0009.docx DOCX document
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CONCRETE

WALK

RAMP DN

RAMP DOWN

STAIR

RAMP DOWN

A

B

C

D

E

F G

H

J

K

L

M

N

O

P

Q

R

S

FIRE PENETRATIONS NOTE

- M -

MAIN CIRCUIT BREAKER

NEUTRAL

MCB

N

- N -

PHASE

POWER

PANEL

PWR

PNL

- R -

- P -

ROOM

RECEPTACLE

RM

RECEPT

- B -

AMPERE

- A -

A

- C -

CIRCUIT

CIRCUIT BREAKER

BUILDING

CONDUIT

BLDG

CKT

C

CB

- E -

EG

- G -

GROUNDG, GND

EQUIPMENT GROUND

ABBREVIATIONS

VOLT OR VOLTAGE

VOLT AMPEREVA

V

- V -

WATTW

- W -

- J -

- K -

KILOVOLT AMPERE

KILOVOLT

JUNCTION BOX

KV

KW

KVA

JB

KILOWATT

ABOVE FINISHED FLOORAFF

UON UNLESS OTHERWISE NOTED

- U -

E1.01

AC

X

MOTOR TYPE

REVISION

RISER TAGPOINT OF CONNECTION

SCHEDULE NUMBER

# LIGHT FIXTURE TYPE

INDICATES DETAIL NUMBER

SHEET NUMBER TO FIND DETAIL

SPECIFIC NOTE/

POINT OF DISCONNECTION

REFERENCE NOTE

ANNOTATIONS

EWC ELECTRIC WATER COOLER

T-001

TELECOMMUNICATIONS

GENERAL NOTES:

ABBREVIATIONS VA

EHRM ELECTRONIC HEALTH RECORD MODERNINATION

CERNER INFORMATION TECHNOLOGY COMPANY

CEDT CERNER EHRM DEPLOYMENT TEAM

EUD END USER DEVICE

CIH CERTIFIED INDUSTRIAL HYGIENIST

LBVAMC LONG BEACH VA MEDICAL CENTER

MDF MAIN DISTRIBUTION FRAME

TR TELECOMMUNICATIONS ROOM

OIT OFFICE OF INFORMATION TECHNOLOGY

3D

3D

WALL MTD DATA OUTLET

W/3 CAT 6A DROPS

FLOOR MTD DATA OUTLET

W/3 CAT 6A DROPS

SEE DRAWING T-504

ABBREVIATIONS IT

SM

MM

SFP

ORL

OTDR

UTP

LAN

SINGLE MODE FIBER

MULTI MODE FIBER

SMALL FORM FACTOR PLUGGABLE TRANSCEIVER

OPTICAL RETURN LOSS

OPTICAL TIME DOMAIN REFLECTOMETER

UNSHIELDED TWISTED PAIR

LOCAL AREA NETWORK

EIA

TIA

OS1, OS2

OS2

ELECTRONIC INDUSTRIES ASSOCIATION

TELECOMMUNICATION INDUSTRY ASSOCIATION

TYPE OF SINGLE MODE FIBER

AIR BLOWN SINGLE MODE FIBER

1. PROVIDE EQUIPMENT SUBMITTALS AND SHOP DRAWINGS IN ACCORDANCE

WITH THE SPECIFICATIONS AND THE PROJECT SCHEDULE. NO INSTALLATION

SHALL PROCEED WITHOUT APPROVAL OF THE SHOP DRAWINGS.

2. MINIMAL STORAGE WILL BE AVAILABLE ON THE CONSTRUCTION SITE. CABLING

CONTRACTOR RESPONSIBLE FOR RECEIVING AND STORING MATERIALS AND

FOR COORDINATING MATERIALS DELIVERY TO THE JOB-SITE.

3. COMMUNICATIONS CABLES INSTALLED SHALL BE INSTALLED IN ACCORDANCE

WITH THE REQUIREMENTS DETAILED HEREIN AND SHALL BE FREE OF KINKS,

TWISTS, SHARP BENDS, UNNECESSARY LOOPS OR WORKMANSHIP DEFECT.

4. PROPERLY SEAL WALL PENETRATIONS THROUGH FIRE RATED WALL & FLOOR

USING EZ PATH DETAILED ON T-504.

5. RUN OPEN CABLE FOR EACH SYSTEM IN SLEEVES, J-HOOKS DEDICATED FOR

THE SYSTEM.

6. SEPARATE AND BUNDLE CABLE BY SYSTEM.

7. MAINTAIN EIA/ TIA RECOMMENDED SEPARATIONS BETWEEN CABLING OF

DIFFERENT SYSTEMS. 6'' FROM LIGHT FIXTURES. 24'' FROM 480V & 12'' FROM

208V.

8. MAINTAIN RECOMMENDED SEPARATIONS BETWEEN CABLING AND

INTERFERENCE PRODUCING ELECTRICAL DEVICES SUCH AS POWER CABLING,

ELECTRICAL PANELS, FLUORESCENT LIGHTS, BALLAST RELAYS, ELECTRIC

MOTORS, MOTOR CONTROLLERS, VFD, TRANSFORMERS AND OTHER

ELECTROMAGNETIC DEVICES. SEE NOTE 7.

9. WHERE CABLE IS OPEN ON J-HOOK SYSTEM, RUN PARALLEL OR

PERPENDICULAR TO WALLS AND SUPPORT A MINIMUM OF EVERY 5 FEET USING

APPROVED J-HOOKS.

10. ALL CABLE HOOKS AND OTHER CABLE SUPPORT DEVICES SHALL BE ATTACHED

TO THE BUILDING STRUCTURE IN ACCORDANCE WITH CODES AND

SPECIFICATIONS.

11. NO OPEN CABLE SHALL BE DRAPED OVER OR SUPPORTED ON PLUMBING,

ELECTRICAL, MEDICAL GAS, FIRE SUPPRESSION, OR OTHER PIPING OR

DUCTWORK.

12. ALL CABLES TO BE PLENUM RATED.

13. THE CABLE LENGTH FROM THE TERMINATION POINT IN TR TO EUD IN THE

WORK AREA SHALL NOT EXCEED 295FEET INDEPENDENT OF MEDIA TYPE.

14. THE 295FEET INCLUDES AN ALLOWANCE OF 10FEET FROM EUD TO DEVICE AND

AN ADDITIONAL 24 FEET FROM PATCH PANEL TO ACTIVE COMPONENTS IN TR.

15. VISUALLY INSPECT CONNECTIONS ON CABLE TO ENSURE PROPER COMPLIANCE

WITH EIA/TIA 568B TERMINATION.

16. INSPECT ALL EXPOSED PORTIONS OF THE CABLE TO INSURE A MINIMUM OF 4

TIMES THE CABLE DIAMETER BEND RADIUS AT ANY POINT.

17. ENSURE NO CABLE BUNDLES OR TIE POINTS DISPLAY KINKS, SHARP BENDS,

CREASING OR DEFORMATION OF OUTER SHEATH OR SIGNS OF EXCESSIVE

PULLING FORCE.

18. IN TR CABLES SHOULD BE COMBED AND DRESSED UP BEFORE BUDLING AND

USING VELCRO STRAPS. ZIP TIES OR TWIST TIES SHALL NOT BE USED. STRAPS

SHALL BE SPACED AT APPROPRIATE DISTANCE TO ENSURE CABLES ARE HELD

TOGETHER.

19. ON THE RACK THE CABLES SHOULD BE DIVIDED IN THE MIDDLE, WHERE HALF

FLOWS TO THE LEFT AND HALF FLOWS TO THE RIGHT.

20. ALL CABLING SHALL BE INSTALLED BY CABLE MANUFACTURER'S CERTIFIED

INSTALLER.

21. BEFORE ACCEPTANCE OF ANY NEWLY INSTALLED COMMUNICATIONS WIRING,

THE CABLE WILL UNDERGO SEVERAL LEVELS OF TESTING TO ENSURE THAT ALL

MATERIALS AND INSTALLATION CONFORM TO STANDARD INCLUDED IN THE

DRAWINGS AND SPECIFICATIONS. THIS WILL INCLUDE BOTH THE UTP AND FIBER

OPTICS SYSTEMS. FAILURE TO MEET THE DRAWINGS AND SPECIFICATIONS

SHALL CONSTITUTE REASON TO REJECT THE INSTALLATION UNTIL ALL

PROBLEMS ARE SOLVED.

22. ALL RECORDED TESTING RESULTS SHALL REMAIN IN THE APPROPRIATE TR.

TEST BOTH CABLES AND THEIR CORRESPONDING CONNECTING SYSTEMS AS A

WHOLE UNIT TO ENSURE SYSTEM INTEGRITY.

23. TEST ALL FIBER OPTICS CABLE AND COMPONENTS COMPRISING THE

BACKBONE SYSTEM. TEST ALL FIBER STRAND IN BOTH DIRECTION. USE OTDR

OPERATING AT BOTH 1310 AND 1550 NM WAVELENGTHS.

24. PHYSICAL LABELING FOR ALL CABLES AND RELATED COMPONENTS IS

REQUIRED COMPONENTS WILL DEPEND HEAVILY ON ADHERING TO A LOGICAL

LABELING SCHEME TO ENABLE EXPEDIENT PATCH PANEL, DATA JACK AND

SWITCH PORT IDENTIFICATION.

25. PROVIDE ALL NEW CABLING IN THE BUILDING S WITH AN AS-BUILT,

ELECTRONICALLY AND PAPER, FOR THE CABLE PLANT. EACH TR WIRING

CLOSETS CABLE PLANT AS-BUILT WILL BE INSTALLED IN A FOLDER ON THE

BACK OF THE DOOR SECURED IN A HOLDER ATTACHED TO THE DOOR.

METHOD OF PROCEDUREMOP

SPECIFIC NOTE/

REFERENCE NOTE

SECURITY SYMBOLS

A

Fi le

P at h

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

PM EW/JB

A

C

D

20-SCE-07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMPCONSULTANT

32 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333

20801.12

691-20-200

June 15, 2021

FULLY SPRINKLERED

11301 WILSHIRE BOULEVARD

WEST LOS ANGELES, CA 90073

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA

FINAL CONSTRUCTION

DOCUMENTS

FIRE PROTECTION WALL SYMBOLS

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

- D -

DEEPD

- H -

HEIGHTH

26. CABLING DIAGRAM: SUBMIT, FOR APPROVAL, A COMPLETE CABLING DIAGRAM. THE DIAGRAM SHALL BE BASED ON THE DRAWING INCLUDED IN THE CONSTRUCTION DOCUMENTS. IT SHALL BE UPDATED TO SHOW QUANTITIES AND PART NUMBERS FOR ALL COMPONENTS INCLUDING PATCH PANELS, CABLE, SERVER CABINETS AND EQUIPMENT RACKS AND ALL OTHER ASSOCIATED COMPONENTS. INCLUDE THE

FOLLOW:

1). DETAIL AND ELEVATION DRAWINGS: PROVIDE TR RACK ELEVATION, ENLARGED TR

ROOM LAYOUT.

2). BUILDING COMPOSITE FLOOR PLANS: PROVIDE BUILDING FLOOR PLANS SHOWING WORK AREA OUTLET (WAO) OUTLET LOCATIONS AND CONFIGURATION, TYPES OF JACKS, DISTANCE FOR EACH

CABLE, AND CABLE ROUTING LOCATIONS.

3). FLOOR PLANS TO INCLUDE:

a. FINAL ROOM NUMBERS AND ACTUAL BACKBONE CABLING AND PATHWAY LOCATIONS

(HORIZONTAL AND VERTICAL) AND LABELING.

b. RISER FLOOR PENETRATION / DATA POLE LOCATION AFTER SCANNING THE FLOOR FOR

REBARS.

c. INPUTS AND OUTPUTS OF EQUIPMENT IDENTIFIED ACCORDING TO LABELS INSTALLED ON

CABLES AND EQUIPMENT.

d. DEVICE LOCATIONS WITH LABELS.

e. EZ PATH SLEEVES.

f. WIRING DIAGRAM.

g. LABELING AND ADMINISTRATION DOCUMENTATION.

SCALE: NO SCALE

TR 16SA

TR 15SA

TR 14SA

TR 13SA

TR 12SA

TR 11SA

TR 10SA

TR 16IS

TR 15IS

TR 14IS

TR 13IS

TR 12IS

TR 11IS

TR 10IS

TR 16IN

TR 15IN

TR 14IN

TR 13IN

TR 12IN

TR 11IN

TR 10IN

TR 16SE

TR 15SE

TR 14SE

TR 13SE

TR 12SE

TR 11SE

TR 10SE

PATCH CORDS TABLE

27. ALL DATA & TELEPHONE CABLES THAT ARE REMOVED WILL BE RECYCLED BY VA.

PLEASE DISPOSE OFF CABLES TO VA PROVIDED DUMPSTERS.

28. THE LOCATION OF END USER DEVICES (EUD) SHOWN ON THESE DRAWINGS ARE

APPROXIMATE AND ARE SUBJECT TO VERIFICATION BY THE CONTRACTOR.

CONTRACTOR SHALL REMOVE EXISTING EUD DATA OUTLETS AND PROVIDE NEW

EUD DATA OUTLETS AT THE SAME LOCATION.

29. ALL CAT 6A CABLES TO BE PLENUM AND POE RATED.

THE CONTRACTOR TO COORDINATE WITH VA AND REMOVE ABANDONED SYSTEMS/

ITEM IDENTIFIED BY VA. EXAMPLE INCLUDE OLD FIRE ALARM PANELS, BATTERIES

AND CHARGERS, TELEPHONE EQUIPMENT NOT IN USE, OLD 110 BLOCKS NOT IN

USE, EXISTING FIBERS, EXISTING FIBER DISTRIBUTED LINE MODULE (FOLM).

31. THE CORE AREA EUD LOCATION OF FLOORS 2-6 SHALL BE SERVED WITH CAT6A BY EITHER THE NORTH (IN) OR SOUTH (IS)INTERSTITIAL TELECOM ROOM. THIS SHOULD BE CONSISTENT FOR CORE AREAS FLOORS 2-6.

WHEN RE-CABLING EXISTING SLEEVES SHALL BE REMOVED AND NEW DRY WALL MUST BE INSTALLED

AND FINISHED BEFORE INSTALLING NEW SLEEVES.

CONTRACTOR TO REMOVE ALL 66 BLOCK AND ASSOCIATED CABLING OF ALL TR ROOM. ALL REMOVED

CABLING SHALL BE PUT IN A VA FURNISHED DUMPSTER FOR RECYCLING.

IN TR WHICH REQUIRES INSTALLATION OF FIRE RATED TELEPHONE BACKBOARDS. AFTER UNUSED DEVICES, 110 BLOCK AND OTHER ITEMS ARE REMOVED CONTRACTOR WILL DEMOUNT THE REMAINING

ITEMS, SUPPORT IT TEMPORARILY, INSTALL THE BACKBOARD AND REMOUNT ITEMS ON THE

BACKBOARD.

ALL UNUSED CABLES IN UNDERGROUND CONDUIT SYSTEM INCLUDING ASSOCIATED MANHOLES SHALL

BE PULLED OUT AND REMOVED BY CONTRACTOR AND TRANSPORTED TO VA SUPPLIED DUMPSTERS

INTENDED FOR RECYCLING BY VA. CONTRACTOR SHALL COORDINATE WITH VA WHO WILL IDENTIFY UNUSED CABLES WITHIN EACH MANHOLE. THERE ARE EXISTING LEAD SHEATHED CABLES THAT WILL

REQUIRE SPECIAL HANDLING AND COORDINATION WITH VA.

32.

33.

34.

30.

35.

BLDG. 500 INTERSTITIAL LEVEL EXISTING TR WAY FINDING MAP

TELEPHONE CABLE SCHEDULE

T-002

TELECOMMUNICATIONS DRAWING

LIST

A

Fi le

P at h

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

PM EW/JB

A

C

D

20-SCE-07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMPCONSULTANT

32 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333

20801.12

691-20-200

June 15, 2021

FULLY SPRINKLERED

11301 WILSHIRE BOULEVARD

WEST LOS ANGELES, CA 90073

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA

FINAL CONSTRUCTION

DOCUMENTS

SHEET INDEX

SHEET NUMBER SHEET TITLE

T-001 TELECOMMUNICATIONS SYMBOL LIST, GENERAL NOTES,

ABBREVIATIONS AND SCOPE DESCRIPTION

T-002

TS001

TS002

158.T-101 158.T-111 206.T-101 206.T-111 206.T-121 210.T-101 210.T-111 210.T-121 213.T-101 213.T-111 213.T-121 213.T-131

214.T-111 214.T-121 214.T-131 215.T-101 215.T-111 215.T-121 215.T-131 217.T-101 217.T-111 217.T-121 217.T-131 218.T-101 218.T-102 218.T-111 218.T-121 218.T-131 220.T-101 220.T-111 220.T-121 220.T-131 256.T-101 256.T-111 256.T-121 257.T-101 257.T-111 257.T-121 258.T-111 258.T-121 258.T-131 258.T-141 304.T-101 304.T-111 304.T-121 304.T-122 345.T-111 345.T-121 401.T-111 401.T-121 402.T-111 402.T-121 500.T-1B1 500.T-1B2 500.T-1B3 500.T-1B4 500.T-101 500.T-102 500.T-103 500.T-104 500.T-10I1 500.T-10I2 500.T-10I3 500.T-10I4 500.T-111 500.T-112 500.T-113 500.T-114 500.T-11I1 500.T-11I2 500.T-11I3 500.T-11I4 500.T-121

DRAWING LIST

TELECOMMUNICATIONS SITE PLAN - FIBER & CELL TUBE DISTRIBUTION

TELECOMMUNICATIONS SITE PLAN - FIBER & CELL TUBE DISTRIBUTION

TELECOMMUNICATIONS GROUND FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS GROUND FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS GROUND FLOOR

TELECOMMUNICATIONS GROUND FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS GROUND FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS FOURTH FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS FIRST FLOOR PLAN

TELECOMMUNICATIONS SECOND FLOOR PLAN

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS GROUND FLOOR

TELECOMMUNICATIONS GROUND INTERSTITIAL FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS FIRST FLOOR

TELECOMMUNICATIONS FIRST INTERSTITIAL FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS BASEMENT FLOOR

TELECOMMUNICATIONS GROUND FLOOR

TELECOMMUNICATIONS GROUND FLOOR

TELECOMMUNICATIONS GROUND FLOOR

TELECOMMUNICATIONS GROUND INTERSTITIAL FLOOR

TELECOMMUNICATIONS GROUND INTERSTITIAL FLOOR

TELECOMMUNICATIONS GROUND INTERSTITIAL FLOOR

SHEET INDEX (CONTINUED)

SHEET NUMBER SHEET TITLE

500.T-123 500.T-124 500.T-12I1 500.T-12I2

500.T-12I3 500.T-12I4 500.T-131 500.T-132 500.T-133 500.T-134

500.T-13I4

500.T-144 500.T-14I1 500.T-14I2 500.T-14I3 500.T-14I4 500.T-151 500.T-152 500.T-153 500.T-154 500.T-15I1 500.T-15I2 500.T-15I3 500.T-15I4 500.T-161 500.T-162 500.T-163 500.T-164 500.T-16I1 500.T-16I3 500.T-16I3 500.T-16I4 500.T-174 507.T-111 527.T-111 158.T-401

158.T-402

206.T-401 206.T-401A 206.T-402

206.T-403

210.T-401 210.T-401A 210.T-402

210.T-403

213.T-401 213.T-401A 213.T-402

213.T-403

213.T-404

214.T-401

214.T-402

214.T-403

215.T-401

215.T-402

215.T-403

215.T-404

217.T-401

217.T-402

217.T-403

217.T-404

218.T-401 218.T-401A 218.T-402

218.T-402A 218.T-403

218.T-403A 218.T-404

220.T-401 220.T-401A 220.T-402

220.T-402A 220.T-403

220.T-403A

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS SECOND FLOOR

TELECOMMUNICATIONS SECOND INTERSTITIAL FLOOR

TELECOMMUNICATIONS SECOND INTERSTITIAL FLOOR

TELECOMMUNICATIONS SECOND INTERSTITIAL FLOOR

TELECOMMUNICATIONS SECOND INTERSTITIAL FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS THIRD FLOOR

TELECOMMUNICATIONS THIRD INTERSTITIAL FLOOR

TELECOMMUNICATIONS FOURTH FLOOR

TELECOMMUNICATIONS FOURTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS FIFTH FLOOR

TELECOMMUNICATIONS FIFTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS SIXTH FLOOR

TELECOMMUNICATIONS SIXTH FLOOR

TELECOMMUNICATIONS SIXTH FLOOR

TELECOMMUNICATIONS SIXTH FLOOR

TELECOMMUNICATIONS SIXTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS SIXTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS SIXTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS SIXTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS PENTHOUSE FLOOR

TELECOMMUNICATIONS FIRST FLOOR PLAN

TELECOMMUNICATIONS FIRST FLOOR PLAN

TELECOMMUNICATIONS ENLARGED PLAN - ROOM 7A-008

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 101

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 101

TELECOMMUNICATIONS RACK ELEVATIONS - TR 101

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 146

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 244

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 9

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 122C

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 221K

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM B9

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 103

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 201

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 301

220.T-404

TELECOMMUNICATIONS FIRST INTERSTITIAL FLOOR

TELECOMMUNICATIONS FIRST INTERSTITIAL FLOOR

TELECOMMUNICATIONS FIRST INTERSTITIAL FLOOR

500.T-13I1 TELECOMMUNICATIONS THIRD INTERSTITIAL FLOOR

500.T-13I2 TELECOMMUNICATIONS THIRD INTERSTITIAL FLOOR

500.T-13I3 TELECOMMUNICATIONS THIRD INTERSTITIAL FLOOR

500.T-141 TELECOMMUNICATIONS FOURTH FLOOR

500.T-142 TELECOMMUNICATIONS FOURTH FLOOR

500.T-143 TELECOMMUNICATIONS FOURTH FLOOR

TELECOMMUNICATIONS FOURTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS FOURTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS FOURTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS FIFTH FLOOR

TELECOMMUNICATIONS FIFTH FLOOR

TELECOMMUNICATIONS FIFTH FLOOR

TELECOMMUNICATIONS FIFTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS FIFTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS FIFTH INTERSTITIAL FLOOR

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 105

SHEET INDEX (CONTINUED)

SHEET NUMBER SHEET TITLE

256.T-401A 256.T-402

256.T-402A 256.T-403

256.T-403A 257.T-401

257.T-401A 257.T-402

257.T-402A

258.T-402

258.T-406

304.T-402A 304.T-403

304.T-403A 304.T-404

304.T-404A 345.T-401

345.T-401A 401.T-401

401.T-401A

500.T-401 500.T-401A 500.T-402

500.T-402A 500.T-403

500.T-403A

TELECOMMUNICATIONS RACK ELEVATIONS - TR 1

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 102

TELECOMMUNICATIONS RACK ELEVATIONS - TR 102

TELECOMMUNICATIONS RACK ELEVATIONS - TR 226

TELECOMMUNICATIONS RACK ELEVATIONS - TR 2-106B

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 10IN

TELECOMMUNICATIONS ENLARGED TR 10SJ PLAN

TELECOMMUNICATIONS ENLARGED TR 10SO PLAN

TELECOMMUNICATIONS ENLARGED TR 10SA PLAN

258.T-403

258.T-404

258.T-405

304.T-401A TELECOMMUNICATIONS RACK ELEVATIONS - TR 2-2

304.T-402

500.T-122 TELECOMMUNICATIONS SECOND FLOOR

220.T-404A 256.T-401

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 205

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 306

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM B7

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 123

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 233

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 333

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 002

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 107

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 202

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 04

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 101

TELECOMMUNICATIONS RACK ELEVATIONS - TR 9

TELECOMMUNICATIONS RACK ELEVATIONS - TR B9

TELECOMMUNICATIONS RACK ELEVATIONS - TR 04

TELECOMMUNICATIONS RACK ELEVATIONS - TR 101

TELECOMMUNICATIONS RACK ELEVATIONS - TR 201

TELECOMMUNICATIONS RACK ELEVATIONS - TR 014

TELECOMMUNICATIONS RACK ELEVATIONS - TR 121

TELECOMMUNICATIONS RACK ELEVATIONS - TR 225

TELECOMMUNICATIONS RACK ELEVATIONS - TR 332

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 226

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 7K

TELECOMMUNICATIONS RACK ELEVATIONS - TR 7K

TELECOMMUNICATIONS RACK ELEVATIONS - TR 135

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 135

257.T-403 TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 215

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 120

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 215

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 210A

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 335

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 404

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 2-106B

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 3-223A

TELECOMMUNICATIONS RACK ELEVATIONS - TR 3-223A

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 1-224

TELECOMMUNICATIONS RACK ELEVATIONS - TR 1-224

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 39A

TELECOMMUNICATIONS RACK ELEVATIONS - TR ROOM 39A

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM A100G

TELECOMMUNICATIONS RACK ELEVATIONS - TR A100G

500.T-404 500.T-404A

TELECOMMUNICATIONS ENLARGED PLAN - MCR - SERVER CABINETS,

DATA RACK AND CABLE TRAY

500.T-405

500.T-405A TELECOMMUNICATIONS ENLARGED PLAN

500.T-405B TELECOMMUNICATIONS ENLARGED PLAN

500.T-406 500.T-406A

TELECOMMUNICATIONS ENLARGED TR 10IN PLAN

500.T-407 500.T-407A

TELECOMMUNICATIONS ENLARGED TR 10IS PLAN

500.T-408 500.T-408A 500.T-409

500.T-409A

500.T-410 500.T-410A

500.T-411 500.T-411A 500.T-412

500.T-412A

500.T-413 500.T-413A 500.T-414

500.T-414A 500.T-415

500.T-415A

TELECOMMUNICATIONS ENLARGED TR 11SH PLAN

TELECOMMUNICATIONS ENLARGED TR 11SD PLAN

TELECOMMUNICATIONS ENLARGED TR 11SN PLAN

TELECOMMUNICATIONS ENLARGED TR 11SE PLAN

TELECOMMUNICATIONS ENLARGED TR 11IN PLAN

TELECOMMUNICATIONS ENLARGED TR 11IS PLAN

TELECOMMUNICATIONS ENLARGED TR 12SE PLAN

TELECOMMUNICATIONS ENLARGED TR 12SA PLAN

500.T-416 500.T-416A

TELECOMMUNICATIONS ENLARGED TR12IN PLAN

TELECOMMUNICATIONS RACK ELEVATIONS - TR 10IN

TELECOMMUNICATIONS RACK ELEVATIONS TR 10SJ

TELECOMMUNICATIONS RACK ELEVATIONS TR 10SO

TELECOMMUNICATIONS RACK ELEVATIONS TR 10IN

TELECOMMUNICATIONS RACK ELEVATIONS TR 10IS

TELECOMMUNICATIONS RACK ELEVATIONS TR 11 SH

TELECOMMUNICATIONS RACK ELEVATIONS 11SD

TELECOMMUNICATIONS RACK ELEVATIONS TR 11SN

TELECOMMUNICATIONS RACK ELEVATIONS TR 11SE

TELECOMMUNICATIONS RACK ELEVATIONS TR 11IN

TELECOMMUNICATIONS RACK ELEVATIONS TR 11IS

TELECOMMUNICATIONS RACK ELEVATIONS TR 12SE

TELECOMMUNICATIONS RACK ELEVATIONS TR 12SA

TELECOMMUNICATIONS RACK ELEVATIONS TR 12IN

TELECOMMUNICATIONS RACK ELEVATIONS TR 10SA

206.T-402A TELECOMMUNICATIONS RACK ELEVATIONS - TR 146

210.T-402A TELECOMMUNICATIONS RACK ELEVATIONS - TR 122C

206.T-403A TELECOMMUNICATIONS RACK ELEVATIONS - TR 244

210.T-403A TELECOMMUNICATIONS RACK ELEVATIONS - TR 221K

213.T-402A TELECOMMUNICATIONS RACK ELEVATIONS - TR 103

213.T-403A TELECOMMUNICATIONS RACK ELEVATIONS - TR 201

213.T-404A TELECOMMUNICATIONS RACK ELEVATIONS - TR 301

214.T-401A TELECOMMUNICATIONS RACK ELEVATIONS - TR 105

215.T-401A TELECOMMUNICATIONS RACK ELEVATIONS - TR B7

215.T-402A TELECOMMUNICATIONS RACK ELEVATIONS - TR 123

215.T-403A TELECOMMUNICATIONS RACK ELEVATIONS - TR 233

215.T-404A TELECOMMUNICATIONS RACK ELEVATIONS - TR 333

217.T-401A TELECOMMUNICATIONS RACK ELEVATIONS - TR 002

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 302

217.T-402A TELECOMMUNICATIONS RACK ELEVATIONS - TR 107

217.T-403A TELECOMMUNICATIONS RACK ELEVATIONS - TR 202

217.T-404A TELECOMMUNICATIONS RACK ELEVATIONS - TR 302

218.T-404A TELECOMMUNICATIONS RACK ELEVATIONS - TR 302

257.T-403A TELECOMMUNICATIONS RACK ELEVATIONS - TR 215

304.T-401 TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 2-2

SHEET INDEX (CONTINUED)

SHEET NUMBER SHEET TITLE

TELECOMMUNICATIONS ENLARGED TR 15SA PLAN

500.T-417 500.T-417A 500.T-418

500.T-418A 500.T-419

500.T-419A 500.T-420

500.T-420A 500.T-421

500.T-421A 500.T-422

500.T-422A 500.T-423

500.T-423A 500.T-424

500.T-424A 500.T-425

500.T-425A

TELECOMMUNICATIONS ENLARGED TR 12IS PLAN

TELECOMMUNICATIONS ENLARGED TR13SE PLAN

TELECOMMUNICATIONS ENLARGED TR13SA PLAN

TELECOMMUNICATIONS ENLARGED TR13IN PLAN

TELECOMMUNICATIONS ENLARGED TR13IS PLAN

TELECOMMUNICATIONS ENLARGED TR14SE PLAN

TELECOMMUNICATIONS ENLARGED TR 14SA PLAN

TELECOMMUNICATIONS ENLARGED TR 14IN PLAN

TELECOMMUNICATIONS ENLARGED TR 14IS PLAN

500.T-426 TELECOMMUNICATIONS ENLARGED TR 15SE PLAN

500.T-426A

TELECOMMUNICATIONS RACK ELEVATIONS TR 12IS

TELECOMMUNICATIONS RACK ELEVATIONS TR 13SE

TELECOMMUNICATIONS RACK ELEVATIONS TR 13SA

TELECOMMUNICATIONS RACK ELEVATIONS TR 13IN

TELECOMMUNICATIONS RACK ELEVATIONS TR 13IS

TELECOMMUNICATIONS RACK ELEVATIONS TR 14SE

TELECOMMUNICATIONS RACK ELEVATIONS TR 14SA

TELECOMMUNICATIONS RACK ELEVATIONS TR 14IN

TELECOMMUNICATIONS RACK ELEVATIONS TR 14IS

TELECOMMUNICATIONS RACK ELEVATIONS TR 15SE

500.T-427

500.T-427A 500.T-428

TELECOMMUNICATIONS RACK ELEVATIONS TR 15SA

500.T-429

500.T-430

500.T-430A TELECOMMUNICATIONS RACK ELEVATIONS TR 16SE

500.T-432

500.T-433

500.T-434

TELECOMMUNICATIONS ENLARGED TR 15IN PLAN

TELECOMMUNICATIONS ENLARGED TR 15IS PLAN

TELECOMMUNICATIONS ENLARGED TR 16SE PLAN

TELECOMMUNICATIONS ENLARGED TR 16IN PLAN

TELECOMMUNICATIONS ENLARGED TR 16IS PLAN

TELECOMMUNICATIONS ENLARGED TR E2 PLAN

500.T-431 TELECOMMUNICATIONS ENLARGED TR 16SA PLAN

500.T-431A TELECOMMUNICATIONS RACK ELEVATIONS TR 16SA

TELECOMMUNICATIONS ENLARGED TR E2507.T-401

507.T-401A 527.T-401

TELECOMMUNICATIONS RACK ELEVATIONS TR E2

TELECOMMUNICATIONS ENLARGED TR ROOM 22 AND 23

T-501 TELECOMMUNICATIONS DETAILS

T-502 T-503 T-504

T-505 TELECOMMUNICATIONS DETAILS

T-507 TELECOMMUNICATIONS MANHOLE FOLDOUTS

T-508 T-509 T-510 T-511 T-512 T-513

T-514 TELECOMMUNICATIONS MANHOLE FOLDOUTS

T-601 TELECOMMUNICATIONS CELL TUBE BUNDLE BACKBONE HORIZONTAL

AND VERTICAL RISER BUILDING 500

T-601A TELECOMMUNICATIONS SM AND MM AIR BLOWN FIBER BACKBONE

HORIZONTAL AND VERTICAL RISER BUILDING 500

T-602 TELECOMMUNICATIONS SINGLE MODE FIBER OPTIC BACKBONE AND

VERTICAL RISER B206, B210, B213 AND B214

T-603 TELECOMMUNICATIONS SINGLE MODE FIBER OPTIC BACKBONE AND

VERTICAL RISER B215, B217, B218 AND B220

T-604 TELECOMMUNICATIONS SINGLE MODE FIBER OPTIC BACKBONE AND

VERTICAL RISER B256, B257, B258 AND B301

TELECOMMUNICATIONS DETAILS

TELECOMMUNICATIONS DETAILS

TELECOMMUNICATIONS DETAILS

TELECOMMUNICATIONS MANHOLE FOLDOUTS

TELECOMMUNICATIONS MANHOLE FOLDOUTS

TELECOMMUNICATIONS MANHOLE FOLDOUTS

TELECOMMUNICATIONS MANHOLE FOLDOUTS

TELECOMMUNICATIONS MANHOLE FOLDOUTS

TELECOMMUNICATIONS MANHOLE FOLDOUTS

500.T-428A TELECOMMUNICATIONS RACK ELEVATIONS TR 15IN

500.T-429A TELECOMMUNICATIONS RACK ELEVATIONS TR 15IS

500.T-432A TELECOMMUNICATIONS RACK ELEVATIONS TR 16IN

500.T-433A TELECOMMUNICATIONS RACK ELEVATIONS TR 16IS

527.T-401A TELECOMMUNICATIONS RACK ELEVATIONS TR ROOM 22 AND 23

527.T-402 TELECOMMUNICATIONS ENLARGED TR ROOM 3

T-605 TELECOMMUNICATIONS SINGLE MODE FIBER OPTIC BACKBONE

HORIZONTAL AND VERTICAL

T-606 TELECOMMUNICATIONS SINGLE MODE FIBER OPTIC BACKBONE

HORIZONTAL AND VERTICAL

T-607

SHEET NUMBER SHEET TITLE

SHEET INDEX (CONTINUED)

214.T-101 TELECOMMUNICATIONS BASEMENT FLOOR

158.T-401A TELECOMMUNICATIONS RACK ELEVATIONS TR 7A-008

158.T-402A TELECOMMUNICATIONS RACK ELEVATIONS - TR 101

214.T-402A TELECOMMUNICATIONS RACK ELEVATIONS - TR 205

214.T-403A TELECOMMUNICATIONS RACK ELEVATIONS - TR 306

214.T-404 TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM

214.T-404A TELECOMMUNICATIONS RACK ELEVATIONS TR BSMT

258.T-401 TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 104A

258.T-401A TELECOMMUNICATIONS RACK ELEVATIONS - TR 104A

258.T-402A TELECOMMUNICATIONS RACK ELEVATIONS - TR 120

258.T-403A TELECOMMUNICATIONS RACK ELEVATIONS - TR 215

258.T-404A TELECOMMUNICATIONS RACK ELEVATIONS - TR 210A

258.T-405A TELECOMMUNICATIONS RACK ELEVATIONS - TR 335

258.T-406A TELECOMMUNICATIONS RACK ELEVATIONS - TR 404

401.T-402 401.T-402A

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM A239

TELECOMMUNICATIONS RACK ELEVATIONS - TR ROOM A239

402.T-401 TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 1409

402.T-401A TELECOMMUNICATIONS RACK ELEVATIONS - TR 1409

402.T-402 TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 2413

402.T-402A TELECOMMUNICATIONS RACK ELEVATIONS - TR 2413

500.T-405C TELECOMMUNICATIONS SCHEDULE

500.T-406B

500.T-406C TELECOMMUNICATIONS SCHEDULE

500.T-410B

500.T-412B 500.T-412C

T-506 TELECOMMUNICATIONS DETAILS

527.T-402A TELECOMMUNICATIONS RACK ELEVATIONS TR ROOM 3

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 1

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 332

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 225

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 121

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 014

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 302

TELECOMMUNICATIONS ENLARGED PLAN - TR ROOM 201

TELECOMMUNICATIONS SITE PLAN (REFERENCE ONLY)

SCALE: 1/128" = 1' - 0"

NORTH

TS001

TELECOMMUNICATIONS SITE PLAN

FIBER & CELL TUBE DISTRIBUTION

LEGEND

BUILDING IN SCOPE

(VA SEPULVEDA CAMPUS, NORTH HILLS)

R

EF

ER

T

O W

.T -0

F

O R

C O

N

TI

N U

AT

IO

N

A

Fi le

P at h

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

PM EW/JB

A

GENERAL NOTES

C

D

20-SCE-07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMPCONSULTANT

32 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333

20801.12

691-20-200

June 15, 2021

FULLY SPRINKLERED

11301 WILSHIRE BOULEVARD

WEST LOS ANGELES, CA 90073

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA

FINAL CONSTRUCTION

DOCUMENTS

TS-001 PROPOSED STEPS FOR INSTALLATION OF NEW

FIBERS TO ALL THE BUILDINGS FROM MCR

(WLA)

STEP 1 IN COORDINATION WITH VA IDENTIFY ALL UNUSED

COPPER CABLES IN EACH MANHOLE AND DUCT BANK

STEP 2 PULL OUT ALL EXISTING UNUSED COPPER CABLES AND

DISPOSE OFF SITE

STEP 3 MANDREL EXISTING SPARE CONDUIT AND CONDUITS

FROM WHICH COPPER HAS BEEN PULLED OUT. MANDREL

SHALL BE DONE MANHOLE TO MANHOLE.

STEP 4 BLOW PULL WIRE THROUGH THE CONDUIT DUCT BANKS

STEP 5 REPEAT STEP 1 THROUGH STEP 4 UNTIL ALL MANHOLES

ARE COMPLETE

STEP 6 PULL TUBE CELL IN ALL CONDUITS/MANHOLES AS SHOWN

ON PLANS

STEP 7 TEST TUBE CELL TO MAKE SURE THERE IS NO

OBSTRUCTION. LABEL EACH TUBE CELL “FROM - TO”

STEP 8 INSTALL AIR BLOWN FIBERS FORM MCR TO EACH BUILDING

AS SPECIFIED IN THE PLANS

STEP 9 INSTALL FIBER TO EACH TR WITHIN THE BUILDING PER

FIBER RISER DIAGRAM

STEP 10 TERMINATE FIBER ON FIBER PATCH PANEL IN EACH TR

AND MCR

STEP 11 LABEL FIBER/TUBE CELL AS PER LABELING

REQUIREMENTS

STEP 12 TEST ALL FIBERS USING OTDR EQUIPMENT

STEP 13 REPLACE ALL FIBER THAT FAILED THE TEST

EXISTING

DUCT BANK

NEW DUCT BANK

TO CONNECT

MHD43 TO MH22

EXISTING PULL BOX

IN PARKING LOT

MHW 21

MHD 22

MHD 23

MHD 21

MH 4

MHD 20

MHD 19

MHD 16

MHD 10

MHD 3

MHD 2

MHD 11

MHD 4MHD 5

MHD 6

MHD 13

MHD 14

MHD 12

MHD 25

MHD 31

MHD 32

MHD 37

MHD 26

MHD 30

MHD 8

MHD 9

MHD 41

MHD 42

MHD 43

MH 22

MHD 44

MHD 46

MH 24

MHD 30

MHD 28

MHD 27

MHN 1

MHN 2

MHN 3

MHN 4

MHN 5

MHN 14

MHN 10

MHN 6

MHN 7

MHN 8

MHN 9

MHN 11

MHN 12

1 FOR DUCT BANK DETAIL SEE E-503 DETAILS 5

AND 6 .

NUMBER OF CELL TUBE BUNDLE AS RQUIRED

PER TABLE ON TS-002.

SEE DETAIL 1 SHEET T-505.

TDU PEDESTAL.

CONTRACTOR TO SURVEY MANHOLES AND

DUCTBANK FOR TELECOM FIBER BETWEEN

MH14 TO MH21 TO MH19 TO MH18 TO MH17 TO

BUILDING 259. THIS WILL BE THE ROUTE FOR

TELECOM CELL TUBE BUNDLE TO BUILDING 259.

NEW DUCT BANK

TO CONNECT

BLDG 509 TO

PULLBOX

NEW DUCT BANK

TO CONNECT

MHD43 TO MH22

2-4"C NEW DUCT

BANK TO CONNECT

MHD20 TO MHD22

NEW DUCT BANK

SEE DRAWING T-507 TO T-514 FOR EXISTING MANHOLE

FOLDOUTS. USE EXISTING SPARE CONDUITS WHERE

AVAILABLE TO PULL IN NEW CELL TUBE/FIBER OR USE

EXISTING CONDUIT WHICH HAS FIBER AND THERE IS

ROOM TO PULL IN NEW CELL TUBE/FIBER. EXISTING

FIBER WILL BE REMOVED OFF SITE AFTER NEW FIBER

INSTALLATION IS COMMISSIONED.

ALL EXISTING SPARE CONDUITS SHALL BE MANDREL

AND CLEANED OUT BEFORE PULLING NEW CELL

TUBE/FIBER.

THE MAIN TRUNK LINES CONSISTING OF SIX (6)

NINETEEN (19) CELL TUBE (NORTH CAMPUS) AND TWO

(2) TWELVE CELL TUBE (SOUTH CAMPUS) WILL BE

INSTALLED THROUGH ALL MANHOLES. THE CELL TUBE

WILL BE AS MANUFACTURED BY FUTURE FLEX OR

EQUAL. THE MAIN TRUNK LINES ORIGINATES IN THE

NEW MCR ON GROUND LEVEL OF BUILDING 500.

INSTALL ABOVE GROUND TUBE DISTRIBUTION CABINET

(NEMA3R) PER DETAIL 2 ON DRAWING T-505 AND

EXTEND TO BUILDINGS THROUGH EXISTING CONDUIT

AFTER IT HAS BEEN CLEARED OF ALL UNUSED CABLES.

CONTRACTOR WILL THEN INSTALL AIR BLOWN FIBER

STRANDS PER TABLE, SHOWN ON THIS DRAWING,

FROM THE MCR ALL THE WAY TO THE RESPECTIVE

BUILDINGS LISTED IN THE TABLE. EACH FIBER

STRANDS WILL BE TERMINATED USING LC

CONNECTORS ON NEW FIBER PATCH PANEL AT EACH

END. FIBER WILL THEN BE TESTED AND TEST RESULTS

SUBMITTED TO VA FOR APPROVAL.

IN FEW CASES THE EXISTING SIGNAL DUCTBANK GOES

THROUGH EXISTING BUILDING TO NEXT BUILDING. IN

THESE BUILDINGS INSTALL BUILDING TDU IN TR ROOM

AND DROP OFF CELL TUBES REQUIRED FOR THE

BUILDING (SEE TABLE THIS SHEET) IN THE TDU AND

CONTINUE WITH REMAINDER OF TUBE CELLS TO NEXT

BUILDING.

IN OTHER CASES THE EXISTING SIGNAL DUCTBANK

DOES NOT GO THROUGH EXISTING BUILDING TO NEXT

BUILDING. IN THESE BUILDINGS INSTALL BUILDING

OUTDOOR TDU ON PEDESTAL AND DROP OFF CELL

TUBES REQUIRED FOR THE BUILDING (SEE TABLE THIS

SHEET) IN THE OUTDOOR TDU AND CONTINUE WITH

REMAINDER OF TUBE CELLS TO NEXT BUILDING.

KEY NOTES

1.

2.

3.

4.

5.

4 3

MHN 15

MHD 35

MHD 36

MHD 33

MHD 34

ALL NOTES MAY NOT BE APPLICABLE TO THIS SHEET.

NEW MHD22A

MHN 18

MHN 17

MHN 21

MHD 45

MHD 24

TELECOMMUNICATIONS SITE PLAN (REFERENCE ONLY)

SCALE: 1/128" = 1' - 0"

NORTH

TS002

TELECOMMUNICATIONS SITE PLAN

FIBER & CELL TUBE DISTRIBUTION

(VA SEPULVEDA CAMPUS, NORTH HILLS)

R

EF

ER

T

O W

.T -0

F

O R

C O

N

TI

N U

AT

IO

N

MHW16b MHW16c

MHW16d

MHW16a

A

Fi le

P at h

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

PM EW/JB

A

C

D

20-SCE-07

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMPCONSULTANT

32 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333

20801.12

691-20-200

June 15, 2021

FULLY SPRINKLERED

11301 WILSHIRE BOULEVARD

WEST LOS ANGELES, CA 90073

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA

FINAL CONSTRUCTION

DOCUMENTS

EXISTING DUCT

BANK

NEW CELL TUBE &

FIBER IN NEW

DUCTBANK (2-4''C)

NEW MANHOLE

CONDUIT (NIC)

VIA TUNNEL

MH

W16d

MH

W16e

MH W16f

MHW 17

MHW 18

MHW 19MHW 20

EXISTING 4-4"C TO

DEMARC

NEW DUCT BANK 2-4"C1

LEGEND

BUILDING IN SCOPE

NEW DUCT BANK

SEE DRAWING T-507 TO T-514 FOR EXISTING MANHOLE

FOLDOUTS. USE EXISTING SPARE CONDUITS WHERE

AVAILABLE TO PULL IN NEW CELL TUBE/FIBER OR USE

EXISTING CONDUIT WHICH HAS FIBER AND THERE IS

ROOM TO PULL IN NEW CELL TUBE/FIBER. EXISTING

FIBER WILL BE REMOVED OFF SITE AFTER NEW FIBER

INSTALLATION IS COMMISSIONED.

ALL EXISTING SPARE CONDUITS SHALL BE MANDREL

AND CLEANED OUT BEFORE PULLING NEW CELL

TUBE/FIBER.

THE MAIN TRUNK LINES CONSISTING OF FOUR (4)

NINETEEN (19) CELL TUBE (NORTH CAMPUS) AND TWO

(2) TWELVE CELL TUBE (SOUTH CAMPUS) WILL BE

INSTALLEDTHROUGH ALL MANHOLES. THE CELL TUBE

WILL BE AS MANUFACTURED BY FUTURE FLEX. THE

MAIN TRUNK LINES ORIGINATES IN THE NEW MCR ON

GROUND LEVEL OF BUILDING 500. INSTALL ABOVE

GROUND TUBE DISTRIBUTION CABINET (NEMA3R) PER

DETAIL 2 ON DRAWING T-505 AND EXTEND TO

BUILDINGS THROUGH EXISTING CONDUIT AFTER IT HAS

BEEN CLEARED OF ALL UNUSED CABLES.

CONTRACTOR WILL THEN INSTALL AIR BLOWN FIBER

STRANDS PER TABLE, SHOWN ON THIS DRAWING,

FROM THE MCR ALL THE WAY TO THE RESPECTIVE

BUILDINGS LISTED IN THE TABLE. EACH FIBER

STRANDS WILL BE TERMINATED USING LC

CONNECTORS ON NEW FIBER PATCH PANEL AT EACH

END. FIBER WILL THEN BE TESTED AND TEST RESULTS

SUBMITTED TO COR/IT AND VA FOR APPROVAL.

IN FEW CASES THE EXISTING SIGNAL DUCTBANK GOES

THROUGH EXISTING BUILDING TO NEXT BUILDING. IN

THESE BUILDINGS INSTALL BUILDING TDU IN TR ROOM

AND DROP OFF CELL TUBES REQUIRED FOR THE

BUILDING (SEE TABLE THIS SHEET) IN THE TDU AND

CONTINUE WITH REMAINDER OF TUBE CELLS TO NEXT

BUILDING.

IN OTHER CASES THE EXISTING SIGNAL DUCTBANK

DOES NOT GO THROUGH EXISTING BUILDING TO NEXT

BUILDING. IN THESE BUILDINGS INSTALL BUILDING

OUTDOOR TDU ON PEDESTAL AND DROP OFF CELL

TUBES REQUIRED FOR THE BUILDING (SEE TABLE THIS

SHEET) IN THE OUTDOOR TDU AND CONTINUE WITH

REMAINDER OF TUBE CELLS TO NEXT BUILDING.

1.

2.

3.

4.

5.

GENERAL NOTES

MHW 164

3 3

1 FOR DUCT BANK DETAIL SEE E-503 DETAILS 5

AND 6 .

INSTALL ONE (1) 19 CELL TUBE (FUTUREFLEX OR

EQUAL) IN EXISTING 1-4”C .

SEE DETAIL 1 SHEET T-505.

TDU PEDESTAL.

INSTALL ONE (1) 12 CELL TUBE (FUTUREFLEX OR

EQUAL) IN EXISTING CONDUIT.

INSTALL ONE (1) 7 CELL TUBE (FUTUREFLEX OR

EQUAL) IN EXISTING CONDUIT.

KEY NOTES

ALL NOTES MAY NOT BE APPLICABLE TO THIS SHEET.

SCALE: 1/8" = 1' - 0"

NORTH

158.T-101

R

EF

ER

T

O V

IE

W

B

EL

O W

F O

R C

O N

TI

N

U

AT

IO

N

A

Fi le

P at h

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

PM EW/JB

A

GENERAL NOTES

C

D

1. PROVIDE UL LISTED FIRESTOPPING AT ALL

PENETRATIONS OF FIRE RATED WALLS.

2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO

PENETRATE WALLS, W/O LIMITING ABILITY TO

ADD/REMOVE CABLES AT A LATER TIME W/O

RESEALING.

3. COORDINATE RELOCATION OF EXISTING EQUIPMENT

AND FURNITURE WITH THE VA AS INDICATED ON

PROJECT NOTE 5 ON GI001.

20-SCE-07

0' 4' 8' 16'

SCALE: 1/8" = 1'-0"

GENERAL NOTE

FIRE PROTECTION

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMPCONSULTANT

32 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333

20801.12

Key Plan

691-20-200

June 15, 2021

FULLY SPRINKLERED

11301 WILSHIRE BOULEVARD

WEST LOS ANGELES, CA 90073

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA

FINAL CONSTRUCTION

DOCUMENTS

R

EF

ER

T

O V

IE

W

A

BO

VE

F

O R

C O

N

TI

N U

AT

IO

N

FOR ENLARGED

PLAN SEE

158.T-401

SCALE: 1/8" = 1' - 0" NORTH

158.T-111

R

EF

ER

T

O V

IE

W

B

EL

O W

F O

R C

O N

TI

N

U

AT

IO

N

A

Fi le

P at h

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

PM EW/JB

A

GENERAL NOTES

C

D

1. PROVIDE UL LISTED FIRESTOPPING AT ALL

PENETRATIONS OF FIRE RATED WALLS.

2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO

PENETRATE WALLS, W/O LIMITING ABILITY TO

ADD/REMOVE CABLES AT A LATER TIME W/O

RESEALING.

3. COORDINATE RELOCATION OF EXISTING EQUIPMENT

AND FURNITURE WITH THE VA AS INDICATED ON

PROJECT NOTE 5 ON GI001.

20-SCE-07

0' 4' 8' 16'

SCALE: 1/8" = 1'-0"

GENERAL NOTE

FIRE PROTECTION

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMPCONSULTANT

32 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333

20801.12

Key Plan

691-20-200

June 15, 2021

FULLY SPRINKLERED

11301 WILSHIRE BOULEVARD

WEST LOS ANGELES, CA 90073

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA

FINAL CONSTRUCTION

DOCUMENTS

R

EF

ER

T

O V

IE

W

A

BO

VE

F

O R

C O

N

TI

N U

AT

IO

N

FOR ENLARGED

PLAN SEE

158.T-402

RA

MP

U P

RAMP UP

CHAIN LINK CAGE

RAMP UP

EXIT DOOR

STORAGE

OUT REACH

COMMUNITY CARE

ELEVATOR

LOBBY

ELEVATOR MACH

RM

ELEVATOR

MENS RESTROOM

WOMENS

RESTROOM

CORRIDOR

OFFICE OF SCREENING CLERK

CLOSET

CLINICAL

CO-ORDR

PSYCHIATRIST

WORK AREA

14A

SCREENING RM

MENS SHOWER

INTAKE RM

VESTING

OFFICE

SOCIAL WORKER OFFICE

ELIGIBILITY

CLERK OFFICE

ELIGIBILITY

CLERK OFFICE

SCREENING RM

RECEPTION

CLINICAL SUPPORT OFFICE

CLINICAL SUPPORT PGM MGR

OFFICE

STAFF KITCHEN

OFFICE

STEAM RM

COPY RM

SUPPLY RM

OFFICE

SOCIAL WORKER OFFICE

OFFICE

SOCIAL

WORKER

OFFICE

BENEFITS

COUNSELOR OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

SOCIAL

WORKER

OFFICE

SOCIAL

WORKER

OFFICE

SOCIAL

WORKER

OFFICE

OFFICE

OFFICE

34A

FE

18A

TELECOM

ROOM

A B C D E F G H

3.2

1.1

ELECTRICAL

ROOM

001A

CR

001.1

SCALE: 1/8" = 1' - 0"

206.T-101

A

Fi le

P at h

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

PM EW/JB

A

GENERAL NOTES

C

D

1. PROVIDE UL LISTED FIRESTOPPING AT ALL

PENETRATIONS OF FIRE RATED WALLS.

2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO

PENETRATE WALLS, W/O LIMITING ABILITY TO

ADD/REMOVE CABLES AT A LATER TIME W/O

RESEALING.

3. COORDINATE RELOCATION OF EXISTING EQUIPMENT

AND FURNITURE WITH THE VA AS INDICATED ON

PROJECT NOTE 5 ON GI001.

20-SCE-07

0' 4' 8' 16'

SCALE: 1/8" = 1'-0"

GENERAL NOTE

FIRE PROTECTION

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMPCONSULTANT

32 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333

20801.12

Key Plan

691-20-200

June 15, 2021

FULLY SPRINKLERED

11301 WILSHIRE BOULEVARD

WEST LOS ANGELES, CA 90073

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA

FINAL CONSTRUCTION

DOCUMENTS

EXISTING CAT 5 AND BELOW (INCLUDING UNUSED CAT

3 CABLES) SHALL BE REMOVED FROM TR ROOM

PATCH PANELS TO EACH EXISTING WAO OUTLETS.

THESE EXISTING CABLES ARE TO BE REMOVED FROM

CONDUIT DROPS FOR INSTALLATION OF NEW CAT6A

CABLES.

THE RE-CABLING OF WAO OUTLETS WILL BE DONE IN

TWO SHIFTS BY THE CABLE CONTRACTOR. THE DAY

CREW WILL INSTALL THE BUNDLE CABLES FROM TR, IN

THE CEILING ABOVE CORRIDOR, TO THE SUITE AND

COIL UP THE CABLE ABOVE CEILING AND LEAVE IT

THERE FOR THE NIGHT CREW. OIT NIGHT CREW WILL

COME IN AND UNPLUG THE USER END DEVICE. THE

CABLE CONTRACTOR NIGHT CREW WILL COME IN AND

DISCONNECT THE JACK FROM THE FACEPLATE AND

PULL OUT THE OLD CABLE FROM THE CONDUIT AND

PULL IN NEW CAT6A CABLE, TERMINATE INTO NEW

CAT6A COMPLIANT JACK AND NEW FACE PLATE.

TERMINATE THE CABLE AT 48 PORT PATCH PANEL IN

RESPECTIVE TR ROOM, TEST AND CERTIFY THE

CABLE AND LABEL THE JACK AND 48PORT PATCH

PANEL. OIT NIGHT CREW WILL COME IN AND PLUG THE

END USER DEVICE BEFORE DAY BREAK.

ALL NEW CAT6A CABLES TO BE ROUTED TO

RESPECTIVE TR ROOMS AS INDICATED. TERMINATE

NEW COLOR CODED (3 U.O.N) CAT6A (WHITE, GRAY

AND BLUE) IN NEW CAT6A COMPATIBLE JACKS ON

NEW FACEPLATE AT EACH WAO OUTLET AND LABEL IT

AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATABLE RJ45 JACKS AND NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO

WAO OUTLETS SHALL BE TESTED AND CERTIFIED BY

CABLE MANUFACTURER'S CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL

BE DONE ROOM BY ROOM AND FLOOR BY FLOOR IN

CLOSE COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE

PATCHPANEL IN EXISTING RACKS OR NEW RACKS (AS

CALLED OUT ON DRAWING) IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL

NEW CAT6A CABLES WHEN THERE IS NO EXISTING

CONDUIT DROPS.

OLD FACE PLATE WILL BE PULLED OUT AND

REPLACED WITH NEW FACEPLATE WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE.

ONCE THE NEW CABLES ARE TESTED AND CERTIFIED

THE WAO WILL BE CONNECTED TO NEW FACE PLATE

BY OIT. NEW FACEPLATE TO BE SS.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK

WITH NEW CAT6A COMPLIANT 48 PORT PATCH PANEL.

ONCE THESE NEW PATCH PANELS ARE POPULATED

REMOVE EXISTING PATCH PANEL TO MAKE ROOM FOR

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL.

BEFORE DISCONNECTING AND REMOVINF EXISTING

PATCH PANEL, RING OUT AND VERIFY THAT THE DATA

CABLES ORIGINATING IN THOSE PATCH PANELS TO

WAO HAVE BEEN SUCCESSFULLY REPLACED WITH

NEW DATA CABLE AND CAT6A COMPLIANT PATCH

PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE

SEE GENERAL NOTE 7 ON STRUCTURE DRAWING S-001

& DETAIL 18 ON S-001.

1.

2.

RECOMMENDED ROUTING OF NEW CAT6A BUNDLE

CABLE ON PENDANT MOUNTED U-HOOKS. SEE

DETAILS ON STRUCTURAL DRAWING.

EXISTING CABLE TRAY ABOVE CEILING OR

INTERSTITIAL LEVEL. BUNDLE CABLE SHALL BE

ROUTED ON NEW OR EXISTING CABLE TRAY TO TR

ROOM FROM WAO.

NEW PLENUM RATED 3 (U.O.N) CAT6A (GRAY, BLUE

WHITE) DROP IN FREE AIR WITHIN WALL CAVITY

(WHEN THERE IS NO EXISTING CONDUIT DROP) .

SUPPORT USING WALL MOUNTED J-HOOKS OR

SUSPENDED FROM STRUCTURE ABOVE. PLEASE SEE

DETAIL ON DRAWING T-501

NEW FACEPLATE (SS) WITH GRAY, BLLUE AND WHITE

CAT6A COMPLIANT RJ45 JACK.

FOR FLOOR MOUNTED DATA OUTLETS REMOVE (BY

NIGHT CREW) EXISTING CABLE FROM UNDERFLOOR

FEED AND INSTALL NEW CAT6A AND RJ45 JACKS.

AT LAB BENCHES WITH MULTIRACEWAY DATA

OUTLETS REMOVE (BY NIGHT CREW) EXISTING CABLE

FROM MULTIRACEAY FEED AND INSTALL NEW CAT6A

AND RJ45 JACKS.

FOR PRE-WIRED SYSTEM FURNITURE DATA OUTLETS

REMOVE (BY NIGHT CREW) EXISTING CABLE FROM

SYSTEM FURNITURE WHIP FEED AND INSTALL NEW

CAT6A AND RJ45 JACKS.

(NOT ALL KEY NOTES ARE APPLICABLE TO THIS SHEET)

KEY NOTES

3.

4.

5.

6.

7.

8.

9.

10.

FOR ENLARGED

PLAN SEE

206.T-401

DN

DN

UP UP

A B C D E F G H

3.2

1.1

RA

MP

D

OW

N

DN

DN

ROLL DOWN DOOR

FC

CHECK IN

135A

LOCKERS

RM

PIPE SPACE

PIPE SPACE

TOILET

158A

CLINICAL

PHARMACIST

TOILET

CORRIDOR

WAITING RM

FC

WAITING RM

FC

CORRIDOR

WHITE TEAM TRIAGE

CORRIDOR

STORAGE

RM

147A

PIPE SPACE

H/C WOMENS WASH RM &

TOILET

PIPE SPACE

EXAM RM-10

14-

CORRIDOR

STAIR-3

EMS

MEN STAFF

RESTROOM

TRIAGE CARE MGR

MENS TOILET

CORRIDOR

MENTAL HEALTH CLINICAL

PHARMACIST

STAIRSTAIR

STAIR

ELEVATOR

EMS

EMS

121A

ADMINISTRATIVE OFFICER

STAIR-2

WASH RM & TOILET

SHOWER RM

113A

ELECTRICAL

RM

ASSOCIATE OFFICE NURSE

COMM/ PRIMARY &

AMBULATORY CARE

MENS STAFF

RESTROOM

HEAD NURSE

124 WOMEN TOILET

SOCIAL SVC

ADMINISTRATIVE SUPPORT

PHYSICIAN ASST OFFICE

NURSES OFFICE

143A

CORRIDOR

MEDICATION RM

LAB

PRIMARY CARE CLINIC

HEAD NURSE

NURSES STATION

CORRIDOR

153B

NURSES OFFICE

EXAM RM-8

EXAM RM-6

149A

RNS OFFICE

153A

DOCTORS OFFICE

EXAM RM-1

DOCTORS OFFICE

CORRIDOR

MULTI PURPOSE RM

CLINICAL KITCHEN

CORRIDOR

CHIEF OF COMM CARE

QUALITY MGMT

CHIEF OF COMM CARE

CORRIDOR

PGM MGR

NURSE MGR

SOCIAL WORKER OFFICE

CHAPLAINMED RM

RECEPTION

105106

112A

CORRIDOR

108112B

CONFERENCE RM

SOCIAL WORKER

OFFICE

CORRIDOR

SOCIAL SCIENCE PGM

SPECIALIST

SOCIAL WORKER

119A

CHIEF OF MENTAL HEALTH

EXAM RM-4

PS

DEPUTY PGM

GRANT PER DIEM

HCRV

HOUSING OFFICE

MGR

SPECIALIST

NURSING LIAISON

GRANT PER DIEM

VA SUPPORT

PGM MGR

PIPE CHASE

HOUSING OFFICE

PGM

VA SUPPORT

COMPUTER

SELF

TELECOM

ROOM

WAITING RM

PTSD PGM

140.1

SCALE: 1/8" = 1' - 0"

206.T-111

A

Fi le

P at h

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

PM EW/JB

A

GENERAL NOTES

C

D

1. PROVIDE UL LISTED FIRESTOPPING AT ALL

PENETRATIONS OF FIRE RATED WALLS.

2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO

PENETRATE WALLS, W/O LIMITING ABILITY TO

ADD/REMOVE CABLES AT A LATER TIME W/O

RESEALING.

3. COORDINATE RELOCATION OF EXISTING EQUIPMENT

AND FURNITURE WITH THE VA AS INDICATED ON

PROJECT NOTE 5 ON GI001.

20-SCE-07

0' 4' 8' 16'

SCALE: 1/8" = 1'-0"

GENERAL NOTE

FIRE PROTECTION

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMPCONSULTANT

32 4 5 6 7 8 9 10

Project Director

Revisions: Date:

ARCHITECT/ENGINEER OF RECORD

17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333

20801.12

Key Plan

691-20-200

June 15, 2021

FULLY SPRINKLERED

11301 WILSHIRE BOULEVARD

WEST LOS ANGELES, CA 90073

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA

FINAL CONSTRUCTION

DOCUMENTS

EXISTING CAT 5 AND BELOW (INCLUDING UNUSED CAT

3 CABLES) SHALL BE REMOVED FROM TR ROOM

PATCH PANELS TO EACH EXISTING WAO OUTLETS.

THESE EXISTING CABLES ARE TO BE REMOVED FROM

CONDUIT DROPS FOR INSTALLATION OF NEW CAT6A

CABLES.

THE RE-CABLING OF WAO OUTLETS WILL BE DONE IN

TWO SHIFTS BY THE CABLE CONTRACTOR. THE DAY

CREW WILL INSTALL THE BUNDLE CABLES FROM TR, IN

THE CEILING ABOVE CORRIDOR, TO THE SUITE AND

COIL UP THE CABLE ABOVE CEILING AND LEAVE IT

THERE FOR THE NIGHT CREW. OIT NIGHT CREW WILL

COME IN AND UNPLUG THE USER END DEVICE. THE

CABLE CONTRACTOR NIGHT CREW WILL COME IN AND

DISCONNECT THE JACK FROM THE FACEPLATE AND

PULL OUT THE OLD CABLE FROM THE CONDUIT AND

PULL IN NEW CAT6A CABLE, TERMINATE INTO NEW

CAT6A COMPLIANT JACK AND NEW FACE PLATE.

TERMINATE THE CABLE AT 48 PORT PATCH PANEL IN

RESPECTIVE TR ROOM, TEST AND CERTIFY THE

CABLE AND LABEL THE JACK AND 48PORT PATCH

PANEL. OIT NIGHT CREW WILL COME IN AND PLUG THE

END USER DEVICE BEFORE DAY BREAK.

ALL NEW CAT6A CABLES TO BE ROUTED TO

RESPECTIVE TR ROOMS AS INDICATED. TERMINATE

NEW COLOR CODED (3 U.O.N) CAT6A (WHITE, GRAY

AND BLUE) IN NEW CAT6A COMPATIBLE JACKS ON

NEW FACEPLATE AT EACH WAO OUTLET AND LABEL IT

AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATABLE RJ45 JACKS AND NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO

WAO OUTLETS SHALL BE TESTED AND CERTIFIED BY

CABLE MANUFACTURER'S CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL

BE DONE ROOM BY ROOM AND FLOOR BY FLOOR IN

CLOSE COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE

PATCHPANEL IN EXISTING RACKS OR NEW RACKS (AS

CALLED OUT ON DRAWING) IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL

NEW CAT6A CABLES WHEN THERE IS NO EXISTING

CONDUIT DROPS.

OLD FACE PLATE WILL BE PULLED OUT AND

REPLACED WITH NEW FACEPLATE WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE.

ONCE THE NEW CABLES ARE TESTED AND CERTIFIED

THE WAO WILL BE CONNECTED TO NEW FACE PLATE

BY OIT. NEW FACEPLATE TO BE SS.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK

WITH NEW CAT6A COMPLIANT 48 PORT PATCH PANEL.

ONCE THESE NEW PATCH PANELS ARE POPULATED

REMOVE EXISTING PATCH PANEL TO MAKE ROOM FOR

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL.

BEFORE DISCONNECTING AND REMOVINF EXISTING

PATCH PANEL, RING OUT AND VERIFY THAT THE DATA

CABLES ORIGINATING IN THOSE PATCH PANELS TO

WAO HAVE BEEN SUCCESSFULLY REPLACED WITH

NEW DATA CABLE AND CAT6A COMPLIANT PATCH

PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE

SEE GENERAL NOTE 7 ON STRUCTURE DRAWING S-001

& DETAIL 18 ON S-001.

1.

2.

RECOMMENDED ROUTING OF NEW CAT6A BUNDLE

CABLE ON PENDANT MOUNTED U-HOOKS. SEE

DETAILS ON STRUCTURAL DRAWING.

EXISTING CABLE TRAY ABOVE CEILING OR

INTERSTITIAL LEVEL. BUNDLE CABLE SHALL BE

ROUTED ON NEW OR EXISTING CABLE TRAY TO TR

ROOM FROM WAO.

NEW PLENUM RATED 3 (U.O.N) CAT6A (GRAY, BLUE

WHITE) DROP IN FREE AIR WITHIN WALL CAVITY

(WHEN THERE IS NO EXISTING CONDUIT DROP) .

SUPPORT USING WALL MOUNTED J-HOOKS OR

SUSPENDED FROM STRUCTURE ABOVE. PLEASE SEE

DETAIL ON DRAWING T-501

NEW FACEPLATE (SS) WITH GRAY, BLLUE AND WHITE

CAT6A COMPLIANT RJ45 JACK.

FOR FLOOR MOUNTED DATA OUTLETS REMOVE (BY

NIGHT CREW) EXISTING CABLE FROM UNDERFLOOR

FEED AND INSTALL NEW CAT6A AND RJ45 JACKS.

AT LAB BENCHES WITH MULTIRACEWAY DATA

OUTLETS REMOVE (BY NIGHT CREW) EXISTING CABLE

FROM MULTIRACEAY FEED AND INSTALL NEW CAT6A

AND RJ45 JACKS.

FOR PRE-WIRED SYSTEM FURNITURE DATA OUTLETS

REMOVE (BY NIGHT CREW) EXISTING CABLE FROM

SYSTEM FURNITURE WHIP FEED AND INSTALL NEW

CAT6A AND RJ45 JACKS.

(NOT ALL KEY NOTES ARE APPLICABLE TO THIS SHEET)

KEY NOTES

3.

4.

5.

6.

7.

8.

9.

10.

FOR ENLARGED

PLAN SEE

206.T-402

C

DN DN

A B D E F G H

3.2

1.1

DN

UP TO ATTIC

ROLL DOWN DOORROLL DOWN DOOR

WOMENS

TOILET

TREATMENT RM

PIPE SPACE

PIPE SPACE

234B

STORAGE

234A

PIPE SPACE

WORK RM

STAIR

CORRIDOR

STAIR

DAY RM

STAFF PSYCHIATRIST

REGISTERED NURSE

STAFF PSYCHIATRIST

CORRIDOR

WAITING RM

RESEARCH ASST

CONFERENCE RM / GROUP

RM

STAFF KITCHEN

STAFF PSYCHIATRIST

NURSE PRACTITIONER

MEN WASH RM AND TOILET

PIPE SPACE

STORAGE

RM

245A

STAFF PSYCHIATRIST

R N

CORRIDOR

SOCIAL WORKER

CALL CENTER OFFICE

TEAM CARE CO-ORDR

STAFF PSYCHIATRIST

HAC

BMS

237A

STAFF LOUNGE

STAFF RESTROOM

ELEVATOR

TOILET

257A

STAFF PSYCHIATRIST

PSYCHOLOGIST

REGISTERED NURSE

SUPPLY RM

CORRIDOR

STAIR

CLINICAL OPERATIONS

OFFICE

OFFICE

ADMIN ASST

WAITING RM

SOCIAL WORKER

CORRIDOR

SOCIAL WORKER

SOCIAL SVC

WAITING RM

CLINICAL NURSE

SPECIALIST

SOCIAL WORK ASSOCIATE

SOCIAL SCIENCE

TECHNICIAN

WOMEN STAFF TOILET

STAFF OFFICE

223MEN STAFF RESTROOM

STAIR

BMS

221A

HAC

STAIR

STAFF PSYCHOLOGIST

PSYCHOLOGICAL RM

CORRIDOR

GROUP RM

STAFF PSYCHIATRIST

STAFF PSYCHOLOGIST

REGISTERED NURSE

UTILITIES

SHOWER RM

213A

PIPE CHASE

STAFF WOMEN RESTROOM

STAFF PSYCHIATRIST

SOCIAL WORKER

STAFF PSYCHIATRIST

REGISTERED NURSE

CORRIDOR

STAFF PSYCHIATRIST

CORRIDOR

GROUP RM

TOILET AND LOCKER

STORAGE

FE

FIRE ACCORDION

HEALTH

MENTAL

TELECOM

ROOM

CORRIDOR

244.1

SCALE: 1/8" = 1' - 0"

206.T-121

A

Fi le

P at h

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

PM EW/JB

A

GENERAL NOTES

C

D

1. PROVIDE UL LISTED FIRESTOPPING AT ALL

PENETRATIONS OF FIRE RATED WALLS.

2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO

PENETRATE WALLS, W/O LIMITING ABILITY TO

ADD/REMOVE CABLES AT A LATER TIME W/O

RESEALING.

3. COORDINATE RELOCATION OF EXISTING EQUIPMENT

AND FURNITURE WITH THE VA AS INDICATED ON

PROJECT NOTE 5 ON GI001.

20-SCE-07

0' 4' 8' 16'

SCALE: 1/8" = 1'-0"

GENERAL NOTE

FIRE PROTECTION

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE…