This notice provides details of an upcoming federal construction solicitation by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22. The solicitation will be for Project 691-20-200, Electronic Health Record Modernization Infrastructure Upgrades to be performed at the VA West Los Angeles Healthcare System located in Los Angeles, California. Work will include general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures and other items to complete the project. The project value is estimated between $20,000,000 to $50,000,000 and will be set aside 100% for Service-Disabled Veteran-Owned Small Businesses. The North American Industry Classification Code is 236220 for Commercial and Institutional Building Construction. The solicitation in the form of an Invitation for Bid will be issued on or around July 13, 2021 via the System for Award Management Contract Opportunities website. A mandatory site visit will also be held with details provided in the solicitation.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
208V L6-20R
100 PAIR
7-4'' SLEEVE TO
REMAIN
4-2'' SLEEVE
TO REMAIN
MM SS
SCALE: 1/4" = 1' - 0"
NORTH
401.T-401
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
TR ROOM
A100G
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA
RACKS WITH VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
EXISTING FIRE RATED TELEPHONE
BACKBOARD.
EXISTING 12”W CABLE LADDER RACK MOUNTED
AT 84" AFF AND FIXED TO TOP OF EQUIPMENT
RACKS TO REMAIN (TYPICAL).
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NEW 12''W X 1 1/ 2''H LADDER RACK.
NEW 4 POST DATA RACK 84''H. WITH
HORIZONTAL & VERTICAL WIRE MANAGERS.
EZ PATH SLEEVES. QUANTITY AS REQUIRED.
SEE T-504.
TDU (TUBE DISTRIBUTION UNIT)
SCALE: 1/4" = 1' - 0"
NORTH
TR ROOM
A100G
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1 RACK 2
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
SCALE: NONE SCALE: NONE
401.T-401A
TELECOMMUNICATIONS RACK
ELEVATION TR A100G
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
3 FIBER STRAND AS
SPECIFIED
SS
MM
401.T-402
SCALE: 1/4" = 1'-0"
0' 2' 4' 12'
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
SCALE: 1/4" = 1' - 0"
NORTH
TR ROOM
A239
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA
RACKS WITH VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
EXISTING FIRE RATED TELEPHONE
BACKBOARD.
EXISTING 12”W CABLE LADDER RACK MOUNTED
AT 84" AFF AND FIXED TO TOP OF EQUIPMENT
RACKS TO BE REMOVED.
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NEW 12''W X 1 1/ 2''H LADDER RACK.
NEW 4 POST DATA RACK 84''H. WITH
HORIZONTAL & VERTICAL WIRE MANAGERS.
EZ PATH SLEEVES. QUANTITY AS REQUIRED.
SEE T-504.
TDU (TUBE DISTRIBUTION UNIT)
SCALE: 1/4" = 1' - 0"
NORTH
TR ROOM
A239
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
WIRE MANAGER (TYP.)
RACK 1
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
SCALE: NONE SCALE: NONE
401.T-402A
TELECOMMUNICATIONS RACK
ELEVATION TR A239
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
MM SS
402.T-401
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1' - 0"
NORTH
TR ROOM
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1 EXISTING EQUIPMENT DATA RACKS WITH
VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
NOT USED.
NOT USED.
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NEW 12''W X 1 1/ 2''H LADDER RACK.
NEW HEAVY DUTY DATA RACK 72''H. WITH
HORIZONTAL & VERTICAL WIRE MANAGERS.
NOT USED.
TDU (TUBE DISTRIBUTION UNIT)
SCALE: 1/4" = 1' - 0"
NORTH
TR ROOM
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE
402.T-401A
TELECOMMUNICATIONS RACK
ELEVATION
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.SCALE: NONE SCALE: NONE
RACK EQUIPMENT
CABLE INFORMATION
1 ALL CAT5E
2 ALL CAT6
1 1U 24 PORT PATCH PANEL
2 2U 48 PORT PATCH PANEL
3 1U WIRE MANAGER
4 2U WIRE MANAGER
5 1U CISCO 3850 SWITCH
6 1U PDU
7 2U FIBER LIU
8 4U 110 BLOCK
A.F.F. A.F.F.
4 POST RACK
4 POST RACK
A.F.F.
LADDER
RACK
(TYP.)
4 POST RACK
WIRE
MANAGER
(TYP.)
RACK 1
(REAR)
RACK 1
4 POST RACK
LADDER RACK
(TYP.)LADDER RACK
(TYP.)
4" CONDUIT
(TYP.)
4" CONDUIT
(TYP.)
4" CONDUIT
(TYP.)
4 POST RACK
WIRE
MANAGER
(TYP.)
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
3 FIBER 12 STRAND
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
SSMM
402.T-402
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = 1' - 0"
NORTH
TR ROOM 2413
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE
SCALE: 1/4" = 1' - 0"
NORTH
TR ROOM 2413
SCALE: NONE
SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
1 EXISTING EQUIPMENT DATA RACKS WITH
VERTICAL AND HORIZONTAL CABLE
MANAGEMENT TO BE REMOVED AFTER NEW
DATA RACK IS IN PLACE & COMMISSIONED.
NOT USED.
NOT USED.
INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT
PAINT.
NEW TGB GROUND BUS. SEE RISER ON E-701.
NEW 12''W X 1 1/ 2''H LADDER RACK.
NEW HEAVY DUTY DATA RACK 72''H. WITH
HORIZONTAL & VERTICAL WIRE MANAGERS.
NOT USED.
TDU (TUBE DISTRIBUTION UNIT)
402.T-402A
TELECOMMUNICATIONS RACK
ELEVATION
SCALE: NONE
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
SCALE: NONE SCALE: NONE
RACK EQUIPMENT
CABLE INFORMATION
1 ALL CAT5E
2 ALL CAT6
A.F.F.
1 WALL MOUNTED HIRSCH PANEL
2 1U FIBER LIU
3 1U 24 PORT PATCH PANEL
4 2U 48 PORT PATCH PANEL
5 2U WIRE MANAGER
6 1U CISCO 3850 SWITCH
7 1U PDU
8 7U DVR
9 UPS
4" CONDUIT
(TYP.)
LADDER RACK
WALL
A.F.F.
4" CONDUIT
(TYP.)
4" CONDUIT
(TYP.)
4 POST RACK
4 POST RACK
WIRE
MANAGER
(TYP.)
RACK 1
(REAR)
RACK 1
(FRONT)
LADDER RACK
(TYP.)LADDER RACK
(TYP.)
4" CONDUIT
(TYP.)
4 POST RACK
WIRE
MANAGER
(TYP.)
WIRE
MANAGER
(TYP.)
4" CONDUIT
(TYP.)
WALL
WALL
SCALE: NONE
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
SEE
FOR CONTINUATION
SEE
500.T-1B2
FOR CONTINUATION
SEE
500-T.1B1
FOR CONTINUATION
4''
1''
FIBER FOR
ATT & T & VERIZON
200 PAIR ON
EXISTING CABLE TRAY
4 - 4"C (EX)
2 ACTIVE COPPER
2 INACTIVE COPPER
(TO BE PULLED OUT)
2 - NEW 4"C
500.T-401
TELECOMMUNICATIONS
ENLARGED PLAN - MPOE
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
EXISTING DATA RACK WITH FIBER PATCH PANEL
& CISCO SWITCH.
NEW 4X4 POST DATA RACK FOR AT &T &
VERIZON & T-MOBILE.
EXISTING 110 BLOCK TERMINATION RACK.
EXISTING LADDER RACK 12''W.
EXISTING ELECTRICAL PANEL T500.
18''W LADDER RACK (EX).
EXISTING TELEPHONE BACKBOARD.
NEW 2''C WITH 200 PAIR PAIR CAT3 CABLE TO
NEW NEW MCR.
TERMINATE 200 PAIR ON 110 BLOCK.
COORDINATE EXACT LOCATION WITH VA O IT.
EXIST DATA RACK WITH FIBER PATCH PANEL
CISCO SWITCH.
T-MOBILE RACK.
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
SCALE: 1/4" = 1' - 0"
NORTH
500.T-401A
TELECOMMUNICATIONS RACK
ELEVATION - MPOE
SCALE: NONE
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
AFF
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
3 1U 24 PORT PATCH PANEL
4 2U 48 PORT PATCH PANEL
CABLE INFORMATION
1 CAT6E
RACK 1 RACK 2 RACK 3 RACK 4
5 3U 48 PORT PATCH PANEL DIGITAL
6 2U FIBER PATCH PANEL
7 1U SWITCH
8 110 BLOCK
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
9 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
10 PDU. SEE KEY NOTE 18 ON E-001
RACK EQUIPMENT CABLE INFORMATION
1 ALL CAT5E
WALL
1 PLYWOOD BACKBOARD (EX)
2 WALL MOUNTED 110 BLOCK
WALL
MM
SS
500.T-402
TELECOMMUNICATIONS
ENLARGED PLAN - ROOM 10SJ
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
SCALE: 1/4" = 1' - 0"
NORTH
TELECOMMUNICATIONS
ENLARGED PLAN - ROOM 10SJ (NEW)
TR ROOM
10 SJ
1 INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT PAINT.
NEW 12'' X 1 1/ 2'' LADDER RACK (BLACK)
CHATSWORTH OR EQUAL.
NEW 4-POST DATA RACK.
NEW TGB GROUND BUS. SEE RISER ON E-705.
TDU (TUBE DISTRIBUTION UNIT).
NEW 50 PAIR (CAT 2) ON 110 BLOCK. 50 PAIR CAT
3 TO EXISTING 10SJ ON INTERSTITIAL LEVEL.
500.T-402A
TELECOMMUNICATIONS RACK
ELEVATION TR 10SJ
SCALE: NONE
AFF
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1 RACK 2 RACK 3
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
MM
SS
500.T-403
TELECOMMUNICATIONS
ENLARGED PLAN - ROOM 10SO
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
SCALE: 1/4" = 1' - 0"
NORTH
TELECOMMUNICATIONS
ENLARGED PLAN - ROOM 10SO (NEW)
TR ROOM
10 SO
1 INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT PAINT.
12'' X 1 1/ 2'' LADDER RACK (BLACK) CHATSWORTH
OR EQUAL.
4-POST DATA RACK.
NEW TGB GROUND BUS. SEE RISER ON E-705.
TDU (TUBE DISTRIBUTION UNIT).
NEW 50 PAIR (CAT 2) ON 110 BLOCK. 50 PAIR CAT 3
TO EXISTING 10SO ON INTERSTITIAL LEVEL.
NEW 50 PAIR (CAT 2) ON 110 BLOCK. 50 PAIR CAT 3
TO EXISTING 10SN ON INTERSTITIAL LEVEL.
500.T-403A
TELECOMMUNICATIONS RACK
ELEVATION TR 10SO
SCALE: NONE
AFF
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
20-SCE-07
KEY NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
ROOM & RACK EQUIPMENT
1 1U WIRE MANAGER
2 2U WIRE MANAGER
CABLE INFORMATION
1 CAT6A
3 3U 48 PORT PATCH PANEL DIGITAL
4 2U FIBER PATCH
5 1U SWITCH CISCO
6 110 BLOCK
2 CAT3
RACK (TYP.)
LADDER RACK (TYP.)
WIRE MANAGER (TYP.)
RACK 1 RACK 2 RACK 3
7 4U 3000VA UPS. SEE KEY NOTE 18
ON E-001
8 PDU. SEE KEY NOTE 18 ON E-001
2 4
MM SS
5 5
500.T-404
TELECOMMUNICATIONS
ENLARGED PLAN - ROOM 10SA
0' 2' 4' 12'
SCALE: 1/4" = 1'-0"
A
Fi le
P at h
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
PM EW/JB
A
GENERAL NOTES
C
D
1. PROVIDE UL LISTED FIRESTOPPING AT ALL
PENETRATIONS OF FIRE RATED WALLS.
2. USE EZ PATH OR SIMILAR TO ALLOW CABLES TO
PENETRATE WALLS, W/O LIMITING ABILITY TO
ADD/REMOVE CABLES AT A LATER TIME W/O
RESEALING.
3. COORDINATE RELOCATION OF EXISTING EQUIPMENT
AND FURNITURE WITH THE VA AS INDICATED ON
PROJECT NOTE 5 ON GI001.
20-SCE-07
KEY NOTES
GENERAL NOTE
FIRE PROTECTION
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMPCONSULTANT
32 4 5 6 7 8 9 10
Project Director
Revisions: Date:
ARCHITECT/ENGINEER OF RECORD
17075 Via Del Campo, San Diego, CA 92127 Phone: 858.946.0333
20801.12
691-20-200
June 15, 2021
FULLY SPRINKLERED
11301 WILSHIRE BOULEVARD
WEST LOS ANGELES, CA 90073
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades, WLA
FINAL CONSTRUCTION
DOCUMENTS
ALL EXISTING CAT 5E AND BELOW (INCLUDING UNUSED CAT
3 CABLES) SHALL BE REMOVED FROM TR ROOM PATCH
PANELS TO EACH EXISTING EUD OUTLETS. THESE EXISTING
CABLES ARE TO BE REMOVED AFTER NEW CAT6A CABLES
HAVE BEEN INSTALLED AND TERMINATED AT BOTH ENDS IN
CAT6A COMPARABLE RJ45 JACKS.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A
COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD
OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN
A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH
EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE
MANUFACTURER’S CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVING EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
X-RAY SCAN THE FLOOR TO IDENTIFY LOCATION OF
EXISTING REBAR AND DRILL HOLES TO MISS THE REBARS.
HOLE SIZE SHALL NOR EXCEED 5” TO ALLOW EZ-PATH 33
SERIES TO GO THROUGH. SEE DETAIL 4 ON T-501.
1.
2.
3.
4.
5.
6.
7.
8.
9.
SCALE: 1/4" = 1' - 0"
NORTH
TELECOMMUNICATIONS
ENLARGED PLAN - ROOM 10SA (NEW)
TR ROOM
10 SA
1 INSTALL NEW FIRE RATED TELEPHONE
BACKBOARD ON WALLS 8'-0'' HIGH DO NOT PAINT.
12'' X 1 1/ 2'' LADDER RACK (BLACK)
CHATSWORTH OR EQUAL.
4-POST DATA RACK
NEW TGB GROUND BUS. SEE RISER ON E-705.
TDU (TUBE DISTRIBUTION UNIT)
PROVIDE 1-CAT6A CABLE TO EACH 3 POE CCTV
CAMERA LOCATIONS FROM CCTV SWITCH IN TR.
ASSUME UP TO 15O FEET CABLE LENGTH PER
CAMERA LOCATION. TERMINATE IN PATCH PANEL
IN TR ROOM ON ONE END AND CCTV CAMERA AT
THE OTHER END. COORDINATE WITH VA AND
DOCUMENT ON SHOP DRAWING. SEE DETAIL 3
ON T-505.
NEW 50 PAIR (CAT…