This document provides notification of an upcoming solicitation for construction services. The Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 22 will issue an Invitation for Bid on or about April 12, 2021 via beta.SAM.gov to perform construction work for Project 600-20-120, Electronic Health Record Modernization Infrastructure Upgrades at the VA Long Beach Healthcare System located at 5901 E. 7th Street, Long Beach, CA 90822. The work includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures. The project is set aside 100% for Service-Disabled Veteran-Owned Small Businesses listed in the Vendor Information Pages database. The North American Industry Classification Code is 236220 for commercial and institutional building construction with a size standard of $39.5 million. The magnitude of the construction project is estimated between $10,000,000 to $20,000,000. A site visit will be scheduled for prospective bidders.

View the file

Other files for this federal contract opportunity

Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2"C

4"C

4"C

2"C

TELECOM

ROOM W428

126.T-408

TELECOMMUNICATIONS

ENLARGED PLAN TR ROOM W428

SCALE: 1/4" = 1' - 0" NORTH

1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH

VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.

EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO

REMAIN.

EXISTING 12”W LADDER RACK MOUNTED AT 84" AFF AND FIXED

TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).

KEY NOTES FOR DETAIL 1

SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONESCALE: NONE

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i l e

P a t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

PROPOSED SEQUENCE OF WORK (T&E) FOR A

TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)

STEP 1 REMOVE CEILING AND GRID AND

TEMPORARILY SUPPORT THE EXISTING

LIGHT FIXTURE, HVAC DIFFUSER AND

SMOKE DETECTOR.

STEP 2 INSTALL LIGHT FIXTURE AND QUAD

RECEPTACLE (WHERE APPLICABLE).

REATTACH SMOKE DETECTOR.

STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL

CABLE ENTRY FROM EUD.

STEP 4 INSTALL SLOPED LADDER RACK

FROM EZ PATH ENTRY POINT TO EXISTING

CABLE LADDER RACK.

STEP 5 POPULATE AVAILABLE SPACE IN EXISTING

RACK WITH NEW 48 PORT PATCH PANEL

CAT 6A COMPLIANT.

STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG

CORRIDOR ALONG MAIN CABLE ROUTE.

STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE

PATH FROM CORRIDOR TO EACH ROOM.

STEP 8 INSTALL EUD CABLES FROM TR TO THE

CORRIDORS ALONG MAIN CABLE ROUTE.

COIL UP CABLES AT EACH TAKE OFF POINT

TO INDIVIDUAL ROOMS AND LEAVE IT

ABOVE CEILING.

STEP 9 SCHEDULE A GROUP OF ROOMS FOR

INSTALLATION OF NEW FACEPLATE WITH

THREE RJ45 JACKS.

STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE

AND LET IT HANGING OUT TEMPORARILY.

STEP 11 TEST AND CERTIFY THE CABLE BY A

GROUP OF ROOMS TBD AND SCHEDULED.

STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT

TR ROOM AND AT EUD FACEPLATE.

STEP 13 VALB OIT TO CROSS CONNECT NEW 48

PORT PATCH PANEL TO CISCO SWITCH

AND ACTIVATE THE NEW EUD FACEPLATE.

STEP 14 VALB OIT TO SWITCH THE EUD DEVICE

FROM OLD FACE PLATE TO NEW

FACEPLATE.

STEP 15 EUD DEVICE ARE NOW CONNECTED TO

NEW CABLING.

STEP 16 PULLOUT AND REMOVE EXISTING DATA

CABLE FORM THE EUD TO TR ROOM

EXISTING PATCH PANEL.

STEP 17 REMOVE ASSOCIATED EXISTING PATCH

PANEL FORM THE DATA RACK.

STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE

ROOMS HAVE BEEN COMPLETED.

STEP 19 CLEAN UP AND PAINT TR ROOM.

STEP 20 INSTALL TEMPERATURE AND HUMIDITY

SENSOR.

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

8.

9.

126.T-408A

TELECOMMUNICATIONS RACK

ELEVATIONS

TELECOMMUNICATIONS RACK

ELEVATIONS

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

SCALE: NONE

10 8

10 8

10 8

10 8

10 8

10 8

10 8

KEY NOTES

EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED

AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH

ITEMS) UN HATCH ITEMS TO REMAIN.

QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE

OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.

TO BE REPLACED.

NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400

SERIES DRAWING.

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

8.

9.

ELEVATION 1 AND 2

ELEVATION 1 AND 2

O S

T

P

O S

T

1"C EMPTY

2"C EMPTY

2"C

1"C

2"C

1"C

2"C

1"C

4" SLEEVE

QS SERVER

ROOM W416

126.T-409

SCALE: 1/4" = 1' - 0" NORTH

1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH

VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.

EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO

REMAIN.

EXISTING 12”W CABLE RACK MOUNTED AT 84" AFF AND FIXED

TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).

KEY NOTES FOR DETAIL 1

SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONESCALE: NONE

SCALE: NONE SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

PROPOSED SEQUENCE OF WORK (T&E) FOR A

TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)

STEP 1 REMOVE CEILING AND GRID AND

TEMPORARILY SUPPORT THE EXISTING

LIGHT FIXTURE, HVAC DIFFUSER AND

SMOKE DETECTOR.

STEP 2 INSTALL LIGHT FIXTURE AND QUAD

RECEPTACLE (WHERE APPLICABLE).

REATTACH SMOKE DETECTOR.

STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL

CABLE ENTRY FROM EUD.

STEP 4 INSTALL SLOPED LADDER RACK

FROM EZ PATH ENTRY POINT TO EXISTING

CABLE LADDER RACK.

STEP 5 POPULATE AVAILABLE SPACE IN EXISTING

RACK WITH NEW 48 PORT PATCH PANEL

CAT 6A COMPLIANT.

STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG

CORRIDOR ALONG MAIN CABLE ROUTE.

STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE

PATH FROM CORRIDOR TO EACH ROOM.

STEP 8 INSTALL EUD CABLES FROM TR TO THE

CORRIDORS ALONG MAIN CABLE ROUTE.

COIL UP CABLES AT EACH TAKE OFF POINT

TO INDIVIDUAL ROOMS AND LEAVE IT

ABOVE CEILING.

STEP 9 SCHEDULE A GROUP OF ROOMS FOR

INSTALLATION OF NEW FACEPLATE WITH

THREE RJ45 JACKS.

STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE

AND LET IT HANGING OUT TEMPORARILY.

STEP 11 TEST AND CERTIFY THE CABLE BY A

GROUP OF ROOMS TBD AND SCHEDULED.

STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT

TR ROOM AND AT EUD FACEPLATE.

STEP 13 VALB OIT TO CROSS CONNECT NEW 48

PORT PATCH PANEL TO CISCO SWITCH

AND ACTIVATE THE NEW EUD FACEPLATE.

STEP 14 VALB OIT TO SWITCH THE EUD DEVICE

FROM OLD FACE PLATE TO NEW

FACEPLATE.

STEP 15 EUD DEVICE ARE NOW CONNECTED TO

NEW CABLING.

STEP 16 PULLOUT AND REMOVE EXISTING DATA

CABLE FORM THE EUD TO TR ROOM

EXISTING PATCH PANEL.

STEP 17 REMOVE ASSOCIATED EXISTING PATCH

PANEL FORM THE DATA RACK.

STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE

ROOMS HAVE BEEN COMPLETED.

STEP 19 CLEAN UP AND PAINT TR ROOM.

STEP 20 INSTALL TEMPERATURE AND HUMIDITY

SENSOR.

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

126.T-409A

TELECOMMUNICATIONS RACK

ELEVATIONS

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

SCALE: NONE

13 NEW 2U 48 PORT PATCH

PANEL (CAT 6A) FROM

SERVER CABINET.

KEY NOTES

EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED

AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH

ITEMS) UN HATCH ITEMS TO REMAIN.

QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE

OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.

TO BE REPLACED.

NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400

SERIES DRAWING.

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

8.

9.

ELEVATION 1 AND 2 ELEVATION 1 AND 2

ROOM W521A

126.T-410

SCALE: 1/4" = 1' - 0" NORTH

1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH

VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.

EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO

REMAIN.

EXISTING 12”W CABLE RACK MOUNTED AT 84" AFF AND FIXED

TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).

KEY NOTES FOR DETAIL 1

SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONE

SCALE: NONESCALE: NONE

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

PROPOSED SEQUENCE OF WORK (T&E) FOR A

TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)

STEP 1 REMOVE CEILING AND GRID AND

TEMPORARILY SUPPORT THE EXISTING

LIGHT FIXTURE, HVAC DIFFUSER AND

SMOKE DETECTOR.

STEP 2 INSTALL LIGHT FIXTURE AND QUAD

RECEPTACLE (WHERE APPLICABLE).

REATTACH SMOKE DETECTOR.

STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL

CABLE ENTRY FROM EUD.

STEP 4 INSTALL SLOPED LADDER RACK

FROM EZ PATH ENTRY POINT TO EXISTING

CABLE LADDER RACK.

STEP 5 POPULATE AVAILABLE SPACE IN EXISTING

RACK WITH NEW 48 PORT PATCH PANEL

CAT 6A COMPLIANT.

STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG

CORRIDOR ALONG MAIN CABLE ROUTE.

STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE

PATH FROM CORRIDOR TO EACH ROOM.

STEP 8 INSTALL EUD CABLES FROM TR TO THE

CORRIDORS ALONG MAIN CABLE ROUTE.

COIL UP CABLES AT EACH TAKE OFF POINT

TO INDIVIDUAL ROOMS AND LEAVE IT

ABOVE CEILING.

STEP 9 SCHEDULE A GROUP OF ROOMS FOR

INSTALLATION OF NEW FACEPLATE WITH

THREE RJ45 JACKS.

STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE

AND LET IT HANGING OUT TEMPORARILY.

STEP 11 TEST AND CERTIFY THE CABLE BY A

GROUP OF ROOMS TBD AND SCHEDULED.

STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT

TR ROOM AND AT EUD FACEPLATE.

STEP 13 VALB OIT TO CROSS CONNECT NEW 48

PORT PATCH PANEL TO CISCO SWITCH

AND ACTIVATE THE NEW EUD FACEPLATE.

STEP 14 VALB OIT TO SWITCH THE EUD DEVICE

FROM OLD FACE PLATE TO NEW

FACEPLATE.

STEP 15 EUD DEVICE ARE NOW CONNECTED TO

NEW CABLING.

STEP 16 PULLOUT AND REMOVE EXISTING DATA

CABLE FORM THE EUD TO TR ROOM

EXISTING PATCH PANEL.

STEP 17 REMOVE ASSOCIATED EXISTING PATCH

PANEL FORM THE DATA RACK.

STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE

ROOMS HAVE BEEN COMPLETED.

STEP 19 CLEAN UP AND PAINT TR ROOM.

STEP 20 INSTALL TEMPERATURE AND HUMIDITY

SENSOR.

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

126.T-410A

TELECOMMUNICATIONS RACK

ELEVATIONS

TELECOMMUNICATIONS RACK

ELEVATIONS

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

SCALE: NONE

8 NEW 2U 48 PORT PATCH

PANEL (CAT 6A) FROM

BLDG 126 5TH FLOOR.

KEY NOTES

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

8.

9.

EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED

AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH

ITEMS) UN HATCH ITEMS TO REMAIN.

QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE

OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.

TO BE REPLACED.

NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400

SERIES DRAWING.

2"C EMPTY

1"C 2"C

1 1/4" EMPTY

1" EMPTY

1 1/4" EMPTY

2"C

4"C

TEL CLOSET

W520B

126.T-411

SCALE: 1/4" = 1' - 0" NORTH

1 EXISTING WALL MOUNTED EQUIPMENT DATA RACKS WITH

VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.

EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO

REMAIN.

KEY NOTES FOR DETAIL 1

SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONE

SCALE: NONESCALE: NONE

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

PROPOSED SEQUENCE OF WORK (T&E) FOR A

TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)

STEP 1 REMOVE CEILING AND GRID AND

TEMPORARILY SUPPORT THE EXISTING

LIGHT FIXTURE, HVAC DIFFUSER AND

SMOKE DETECTOR.

STEP 2 INSTALL LIGHT FIXTURE AND QUAD

RECEPTACLE (WHERE APPLICABLE).

REATTACH SMOKE DETECTOR.

STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL

CABLE ENTRY FROM EUD.

STEP 4 INSTALL SLOPED LADDER RACK

FROM EZ PATH ENTRY POINT TO EXISTING

CABLE LADDER RACK.

STEP 5 POPULATE AVAILABLE SPACE IN EXISTING

RACK WITH NEW 48 PORT PATCH PANEL

CAT 6A COMPLIANT.

STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG

CORRIDOR ALONG MAIN CABLE ROUTE.

STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE

PATH FROM CORRIDOR TO EACH ROOM.

STEP 8 INSTALL EUD CABLES FROM TR TO THE

CORRIDORS ALONG MAIN CABLE ROUTE.

COIL UP CABLES AT EACH TAKE OFF POINT

TO INDIVIDUAL ROOMS AND LEAVE IT

ABOVE CEILING.

STEP 9 SCHEDULE A GROUP OF ROOMS FOR

INSTALLATION OF NEW FACEPLATE WITH

THREE RJ45 JACKS.

STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE

AND LET IT HANGING OUT TEMPORARILY.

STEP 11 TEST AND CERTIFY THE CABLE BY A

GROUP OF ROOMS TBD AND SCHEDULED.

STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT

TR ROOM AND AT EUD FACEPLATE.

STEP 13 VALB OIT TO CROSS CONNECT NEW 48

PORT PATCH PANEL TO CISCO SWITCH

AND ACTIVATE THE NEW EUD FACEPLATE.

STEP 14 VALB OIT TO SWITCH THE EUD DEVICE

FROM OLD FACE PLATE TO NEW

FACEPLATE.

STEP 15 EUD DEVICE ARE NOW CONNECTED TO

NEW CABLING.

STEP 16 PULLOUT AND REMOVE EXISTING DATA

CABLE FORM THE EUD TO TR ROOM

EXISTING PATCH PANEL.

STEP 17 REMOVE ASSOCIATED EXISTING PATCH

PANEL FORM THE DATA RACK.

STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE

ROOMS HAVE BEEN COMPLETED.

STEP 19 CLEAN UP AND PAINT TR ROOM.

STEP 20 INSTALL TEMPERATURE AND HUMIDITY

SENSOR.

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

126.T-411A

TELECOMMUNICATIONS RACK

ELEVATIONS

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

SCALE: NONE

KEY NOTES

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

8.

9.

EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED

AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH

ITEMS) UN HATCH ITEMS TO REMAIN.

QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE

OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.

TO BE REPLACED.

NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400

SERIES DRAWING.

4"C

4"C

2"C

2"C

4"C

126.T-412

TELECOMMUNICATIONS

ENLARGED PLAN TR ROOM 627

ROOM W627

TELECOM

SCALE: 1/4" = 1' - 0" NORTH

1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH

VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.

EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO

REMAIN.

EXISTING 12”W LADDER RACK MOUNTED AT 84" AFF AND FIXED

TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).

KEY NOTES FOR DETAIL 1

SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONE

SCALE: NONESCALE: NONE

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

PROPOSED SEQUENCE OF WORK (T&E) FOR A

TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)

STEP 1 REMOVE CEILING AND GRID AND

TEMPORARILY SUPPORT THE EXISTING

LIGHT FIXTURE, HVAC DIFFUSER AND

SMOKE DETECTOR.

STEP 2 INSTALL LIGHT FIXTURE AND QUAD

RECEPTACLE (WHERE APPLICABLE).

REATTACH SMOKE DETECTOR.

STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL

CABLE ENTRY FROM EUD.

STEP 4 INSTALL SLOPED LADDER RACK

FROM EZ PATH ENTRY POINT TO EXISTING

CABLE LADDER RACK.

STEP 5 POPULATE AVAILABLE SPACE IN EXISTING

RACK WITH NEW 48 PORT PATCH PANEL

CAT 6A COMPLIANT.

STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG

CORRIDOR ALONG MAIN CABLE ROUTE.

STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE

PATH FROM CORRIDOR TO EACH ROOM.

STEP 8 INSTALL EUD CABLES FROM TR TO THE

CORRIDORS ALONG MAIN CABLE ROUTE.

COIL UP CABLES AT EACH TAKE OFF POINT

TO INDIVIDUAL ROOMS AND LEAVE IT

ABOVE CEILING.

STEP 9 SCHEDULE A GROUP OF ROOMS FOR

INSTALLATION OF NEW FACEPLATE WITH

THREE RJ45 JACKS.

STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE

AND LET IT HANGING OUT TEMPORARILY.

STEP 11 TEST AND CERTIFY THE CABLE BY A

GROUP OF ROOMS TBD AND SCHEDULED.

STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT

TR ROOM AND AT EUD FACEPLATE.

STEP 13 VALB OIT TO CROSS CONNECT NEW 48

PORT PATCH PANEL TO CISCO SWITCH

AND ACTIVATE THE NEW EUD FACEPLATE.

STEP 14 VALB OIT TO SWITCH THE EUD DEVICE

FROM OLD FACE PLATE TO NEW

FACEPLATE.

STEP 15 EUD DEVICE ARE NOW CONNECTED TO

NEW CABLING.

STEP 16 PULLOUT AND REMOVE EXISTING DATA

CABLE FORM THE EUD TO TR ROOM

EXISTING PATCH PANEL.

STEP 17 REMOVE ASSOCIATED EXISTING PATCH

PANEL FORM THE DATA RACK.

STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE

ROOMS HAVE BEEN COMPLETED.

STEP 19 CLEAN UP AND PAINT TR ROOM.

STEP 20 INSTALL TEMPERATURE AND HUMIDITY

SENSOR.

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

126.T-412A

TELECOMMUNICATIONS RACK

ELEVATIONS

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

SCALE: NONE

9 NEW 2U 48 PORT PATCH

PANEL (CAT 6A) FROM

SERVER CABINET.

KEY NOTES

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

8.

9.

EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED

AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH

ITEMS) UN HATCH ITEMS TO REMAIN.

QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE

OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.

TO BE REPLACED.

NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400

SERIES DRAWING.

ELEVATION 1 AND 2

4"C

2"C

4"C

2"C

126.T-413

ROOM 727

TELECOM

SCALE: 1/4" = 1' - 0" NORTH

1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH

VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.

EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO

REMAIN.

EXISTING 12”W LADDER RACK MOUNTED AT 84" AFF AND FIXED

TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).

KEY NOTES FOR DETAIL 1

SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONESCALE: NONE

SCALE: NONE SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

PROPOSED SEQUENCE OF WORK (T&E) FOR A

TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)

STEP 1 REMOVE CEILING AND GRID AND

TEMPORARILY SUPPORT THE EXISTING

LIGHT FIXTURE, HVAC DIFFUSER AND

SMOKE DETECTOR.

STEP 2 INSTALL LIGHT FIXTURE AND QUAD

RECEPTACLE (WHERE APPLICABLE).

REATTACH SMOKE DETECTOR.

STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL

CABLE ENTRY FROM EUD.

STEP 4 INSTALL SLOPED LADDER RACK

FROM EZ PATH ENTRY POINT TO EXISTING

CABLE LADDER RACK.

STEP 5 POPULATE AVAILABLE SPACE IN EXISTING

RACK WITH NEW 48 PORT PATCH PANEL

CAT 6A COMPLIANT.

STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG

CORRIDOR ALONG MAIN CABLE ROUTE.

STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE

PATH FROM CORRIDOR TO EACH ROOM.

STEP 8 INSTALL EUD CABLES FROM TR TO THE

CORRIDORS ALONG MAIN CABLE ROUTE.

COIL UP CABLES AT EACH TAKE OFF POINT

TO INDIVIDUAL ROOMS AND LEAVE IT

ABOVE CEILING.

STEP 9 SCHEDULE A GROUP OF ROOMS FOR

INSTALLATION OF NEW FACEPLATE WITH

THREE RJ45 JACKS.

STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE

AND LET IT HANGING OUT TEMPORARILY.

STEP 11 TEST AND CERTIFY THE CABLE BY A

GROUP OF ROOMS TBD AND SCHEDULED.

STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT

TR ROOM AND AT EUD FACEPLATE.

STEP 13 VALB OIT TO CROSS CONNECT NEW 48

PORT PATCH PANEL TO CISCO SWITCH

AND ACTIVATE THE NEW EUD FACEPLATE.

STEP 14 VALB OIT TO SWITCH THE EUD DEVICE

FROM OLD FACE PLATE TO NEW

FACEPLATE.

STEP 15 EUD DEVICE ARE NOW CONNECTED TO

NEW CABLING.

STEP 16 PULLOUT AND REMOVE EXISTING DATA

CABLE FORM THE EUD TO TR ROOM

EXISTING PATCH PANEL.

STEP 17 REMOVE ASSOCIATED EXISTING PATCH

PANEL FORM THE DATA RACK.

STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE

ROOMS HAVE BEEN COMPLETED.

STEP 19 CLEAN UP AND PAINT TR ROOM.

STEP 20 INSTALL TEMPERATURE AND HUMIDITY

SENSOR.

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

126.T-413A

TELECOMMUNICATIONS RACK

ELEVATIONS

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

SCALE: NONE

8 NEW 2U 48 PORT PATCH

PANEL (CAT 6A) FROM

SERVER CABINET.

KEY NOTES

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

8.

9.

EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED

AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH

ITEMS) UN HATCH ITEMS TO REMAIN.

QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE

OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.

TO BE REPLACED.

NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400

SERIES DRAWING.

4"C

4"C 2"C

4"C

2"C

4"C

ROOM 827

TELECOM

126.T-414

TELECOMMUNICATIONS

ENLARGED PLAN TR ROOM 827

SCALE: 1/4" = 1' - 0" NORTH

1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH

VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.

EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO

REMAIN.

EXISTING 12”W CABLE RACK MOUNTED AT 84" AFF AND FIXED

TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).

KEY NOTES FOR DETAIL 1

SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONESCALE: NONE

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

PROPOSED SEQUENCE OF WORK (T&E) FOR A

TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)

STEP 1 REMOVE CEILING AND GRID AND

TEMPORARILY SUPPORT THE EXISTING

LIGHT FIXTURE, HVAC DIFFUSER AND

SMOKE DETECTOR.

STEP 2 INSTALL LIGHT FIXTURE AND QUAD

RECEPTACLE (WHERE APPLICABLE).

REATTACH SMOKE DETECTOR.

STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL

CABLE ENTRY FROM EUD.

STEP 4 INSTALL SLOPED LADDER RACK

FROM EZ PATH ENTRY POINT TO EXISTING

CABLE LADDER RACK.

STEP 5 POPULATE AVAILABLE SPACE IN EXISTING

RACK WITH NEW 48 PORT PATCH PANEL

CAT 6A COMPLIANT.

STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG

CORRIDOR ALONG MAIN CABLE ROUTE.

STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE

PATH FROM CORRIDOR TO EACH ROOM.

STEP 8 INSTALL EUD CABLES FROM TR TO THE

CORRIDORS ALONG MAIN CABLE ROUTE.

COIL UP CABLES AT EACH TAKE OFF POINT

TO INDIVIDUAL ROOMS AND LEAVE IT

ABOVE CEILING.

STEP 9 SCHEDULE A GROUP OF ROOMS FOR

INSTALLATION OF NEW FACEPLATE WITH

THREE RJ45 JACKS.

STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE

AND LET IT HANGING OUT TEMPORARILY.

STEP 11 TEST AND CERTIFY THE CABLE BY A

GROUP OF ROOMS TBD AND SCHEDULED.

STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT

TR ROOM AND AT EUD FACEPLATE.

STEP 13 VALB OIT TO CROSS CONNECT NEW 48

PORT PATCH PANEL TO CISCO SWITCH

AND ACTIVATE THE NEW EUD FACEPLATE.

STEP 14 VALB OIT TO SWITCH THE EUD DEVICE

FROM OLD FACE PLATE TO NEW

FACEPLATE.

STEP 15 EUD DEVICE ARE NOW CONNECTED TO

NEW CABLING.

STEP 16 PULLOUT AND REMOVE EXISTING DATA

CABLE FORM THE EUD TO TR ROOM

EXISTING PATCH PANEL.

STEP 17 REMOVE ASSOCIATED EXISTING PATCH

PANEL FORM THE DATA RACK.

STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE

ROOMS HAVE BEEN COMPLETED.

STEP 19 CLEAN UP AND PAINT TR ROOM.

STEP 20 INSTALL TEMPERATURE AND HUMIDITY

SENSOR.

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

7.

126.T-414A

TELECOMMUNICATIONS RACK

ELEVATIONS

SCALE: NONE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

SCALE: NONE

9 NEW 2U 48 PORT PATCH

PANEL (CAT 6A) FROM

SERVER CABINET.

KEY NOTES

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE

JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND

LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A

COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48

PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL

BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S

CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD WILL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACK…