This document provides notification of an upcoming solicitation for construction services. The Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 22 will issue an Invitation for Bid on or about April 12, 2021 via beta.SAM.gov to perform construction work for Project 600-20-120, Electronic Health Record Modernization Infrastructure Upgrades at the VA Long Beach Healthcare System located at 5901 E. 7th Street, Long Beach, CA 90822. The work includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures. The project is set aside 100% for Service-Disabled Veteran-Owned Small Businesses listed in the Vendor Information Pages database. The North American Industry Classification Code is 236220 for commercial and institutional building construction with a size standard of $39.5 million. The magnitude of the construction project is estimated between $10,000,000 to $20,000,000. A site visit will be scheduled for prospective bidders.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2"C
4"C
4"C
2"C
TELECOM
ROOM W428
126.T-408
TELECOMMUNICATIONS
ENLARGED PLAN TR ROOM W428
SCALE: 1/4" = 1' - 0" NORTH
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH
VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.
EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO
REMAIN.
EXISTING 12”W LADDER RACK MOUNTED AT 84" AFF AND FIXED
TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).
KEY NOTES FOR DETAIL 1
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONESCALE: NONE
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i l e
P a t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
PROPOSED SEQUENCE OF WORK (T&E) FOR A
TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)
STEP 1 REMOVE CEILING AND GRID AND
TEMPORARILY SUPPORT THE EXISTING
LIGHT FIXTURE, HVAC DIFFUSER AND
SMOKE DETECTOR.
STEP 2 INSTALL LIGHT FIXTURE AND QUAD
RECEPTACLE (WHERE APPLICABLE).
REATTACH SMOKE DETECTOR.
STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL
CABLE ENTRY FROM EUD.
STEP 4 INSTALL SLOPED LADDER RACK
FROM EZ PATH ENTRY POINT TO EXISTING
CABLE LADDER RACK.
STEP 5 POPULATE AVAILABLE SPACE IN EXISTING
RACK WITH NEW 48 PORT PATCH PANEL
CAT 6A COMPLIANT.
STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG
CORRIDOR ALONG MAIN CABLE ROUTE.
STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE
PATH FROM CORRIDOR TO EACH ROOM.
STEP 8 INSTALL EUD CABLES FROM TR TO THE
CORRIDORS ALONG MAIN CABLE ROUTE.
COIL UP CABLES AT EACH TAKE OFF POINT
TO INDIVIDUAL ROOMS AND LEAVE IT
ABOVE CEILING.
STEP 9 SCHEDULE A GROUP OF ROOMS FOR
INSTALLATION OF NEW FACEPLATE WITH
THREE RJ45 JACKS.
STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE
AND LET IT HANGING OUT TEMPORARILY.
STEP 11 TEST AND CERTIFY THE CABLE BY A
GROUP OF ROOMS TBD AND SCHEDULED.
STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT
TR ROOM AND AT EUD FACEPLATE.
STEP 13 VALB OIT TO CROSS CONNECT NEW 48
PORT PATCH PANEL TO CISCO SWITCH
AND ACTIVATE THE NEW EUD FACEPLATE.
STEP 14 VALB OIT TO SWITCH THE EUD DEVICE
FROM OLD FACE PLATE TO NEW
FACEPLATE.
STEP 15 EUD DEVICE ARE NOW CONNECTED TO
NEW CABLING.
STEP 16 PULLOUT AND REMOVE EXISTING DATA
CABLE FORM THE EUD TO TR ROOM
EXISTING PATCH PANEL.
STEP 17 REMOVE ASSOCIATED EXISTING PATCH
PANEL FORM THE DATA RACK.
STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE
ROOMS HAVE BEEN COMPLETED.
STEP 19 CLEAN UP AND PAINT TR ROOM.
STEP 20 INSTALL TEMPERATURE AND HUMIDITY
SENSOR.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
8.
9.
126.T-408A
TELECOMMUNICATIONS RACK
ELEVATIONS
TELECOMMUNICATIONS RACK
ELEVATIONS
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NONE
10 8
10 8
10 8
10 8
10 8
10 8
10 8
KEY NOTES
EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED
AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH
ITEMS) UN HATCH ITEMS TO REMAIN.
QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE
OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.
TO BE REPLACED.
NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400
SERIES DRAWING.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
8.
9.
ELEVATION 1 AND 2
ELEVATION 1 AND 2
O S
T
P
O S
T
1"C EMPTY
2"C EMPTY
2"C
1"C
2"C
1"C
2"C
1"C
4" SLEEVE
QS SERVER
ROOM W416
126.T-409
SCALE: 1/4" = 1' - 0" NORTH
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH
VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.
EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO
REMAIN.
EXISTING 12”W CABLE RACK MOUNTED AT 84" AFF AND FIXED
TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).
KEY NOTES FOR DETAIL 1
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONESCALE: NONE
SCALE: NONE SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
PROPOSED SEQUENCE OF WORK (T&E) FOR A
TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)
STEP 1 REMOVE CEILING AND GRID AND
TEMPORARILY SUPPORT THE EXISTING
LIGHT FIXTURE, HVAC DIFFUSER AND
SMOKE DETECTOR.
STEP 2 INSTALL LIGHT FIXTURE AND QUAD
RECEPTACLE (WHERE APPLICABLE).
REATTACH SMOKE DETECTOR.
STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL
CABLE ENTRY FROM EUD.
STEP 4 INSTALL SLOPED LADDER RACK
FROM EZ PATH ENTRY POINT TO EXISTING
CABLE LADDER RACK.
STEP 5 POPULATE AVAILABLE SPACE IN EXISTING
RACK WITH NEW 48 PORT PATCH PANEL
CAT 6A COMPLIANT.
STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG
CORRIDOR ALONG MAIN CABLE ROUTE.
STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE
PATH FROM CORRIDOR TO EACH ROOM.
STEP 8 INSTALL EUD CABLES FROM TR TO THE
CORRIDORS ALONG MAIN CABLE ROUTE.
COIL UP CABLES AT EACH TAKE OFF POINT
TO INDIVIDUAL ROOMS AND LEAVE IT
ABOVE CEILING.
STEP 9 SCHEDULE A GROUP OF ROOMS FOR
INSTALLATION OF NEW FACEPLATE WITH
THREE RJ45 JACKS.
STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE
AND LET IT HANGING OUT TEMPORARILY.
STEP 11 TEST AND CERTIFY THE CABLE BY A
GROUP OF ROOMS TBD AND SCHEDULED.
STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT
TR ROOM AND AT EUD FACEPLATE.
STEP 13 VALB OIT TO CROSS CONNECT NEW 48
PORT PATCH PANEL TO CISCO SWITCH
AND ACTIVATE THE NEW EUD FACEPLATE.
STEP 14 VALB OIT TO SWITCH THE EUD DEVICE
FROM OLD FACE PLATE TO NEW
FACEPLATE.
STEP 15 EUD DEVICE ARE NOW CONNECTED TO
NEW CABLING.
STEP 16 PULLOUT AND REMOVE EXISTING DATA
CABLE FORM THE EUD TO TR ROOM
EXISTING PATCH PANEL.
STEP 17 REMOVE ASSOCIATED EXISTING PATCH
PANEL FORM THE DATA RACK.
STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE
ROOMS HAVE BEEN COMPLETED.
STEP 19 CLEAN UP AND PAINT TR ROOM.
STEP 20 INSTALL TEMPERATURE AND HUMIDITY
SENSOR.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
126.T-409A
TELECOMMUNICATIONS RACK
ELEVATIONS
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NONE
13 NEW 2U 48 PORT PATCH
PANEL (CAT 6A) FROM
SERVER CABINET.
KEY NOTES
EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED
AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH
ITEMS) UN HATCH ITEMS TO REMAIN.
QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE
OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.
TO BE REPLACED.
NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400
SERIES DRAWING.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
8.
9.
ELEVATION 1 AND 2 ELEVATION 1 AND 2
ROOM W521A
126.T-410
SCALE: 1/4" = 1' - 0" NORTH
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH
VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.
EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO
REMAIN.
EXISTING 12”W CABLE RACK MOUNTED AT 84" AFF AND FIXED
TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).
KEY NOTES FOR DETAIL 1
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE
SCALE: NONESCALE: NONE
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
PROPOSED SEQUENCE OF WORK (T&E) FOR A
TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)
STEP 1 REMOVE CEILING AND GRID AND
TEMPORARILY SUPPORT THE EXISTING
LIGHT FIXTURE, HVAC DIFFUSER AND
SMOKE DETECTOR.
STEP 2 INSTALL LIGHT FIXTURE AND QUAD
RECEPTACLE (WHERE APPLICABLE).
REATTACH SMOKE DETECTOR.
STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL
CABLE ENTRY FROM EUD.
STEP 4 INSTALL SLOPED LADDER RACK
FROM EZ PATH ENTRY POINT TO EXISTING
CABLE LADDER RACK.
STEP 5 POPULATE AVAILABLE SPACE IN EXISTING
RACK WITH NEW 48 PORT PATCH PANEL
CAT 6A COMPLIANT.
STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG
CORRIDOR ALONG MAIN CABLE ROUTE.
STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE
PATH FROM CORRIDOR TO EACH ROOM.
STEP 8 INSTALL EUD CABLES FROM TR TO THE
CORRIDORS ALONG MAIN CABLE ROUTE.
COIL UP CABLES AT EACH TAKE OFF POINT
TO INDIVIDUAL ROOMS AND LEAVE IT
ABOVE CEILING.
STEP 9 SCHEDULE A GROUP OF ROOMS FOR
INSTALLATION OF NEW FACEPLATE WITH
THREE RJ45 JACKS.
STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE
AND LET IT HANGING OUT TEMPORARILY.
STEP 11 TEST AND CERTIFY THE CABLE BY A
GROUP OF ROOMS TBD AND SCHEDULED.
STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT
TR ROOM AND AT EUD FACEPLATE.
STEP 13 VALB OIT TO CROSS CONNECT NEW 48
PORT PATCH PANEL TO CISCO SWITCH
AND ACTIVATE THE NEW EUD FACEPLATE.
STEP 14 VALB OIT TO SWITCH THE EUD DEVICE
FROM OLD FACE PLATE TO NEW
FACEPLATE.
STEP 15 EUD DEVICE ARE NOW CONNECTED TO
NEW CABLING.
STEP 16 PULLOUT AND REMOVE EXISTING DATA
CABLE FORM THE EUD TO TR ROOM
EXISTING PATCH PANEL.
STEP 17 REMOVE ASSOCIATED EXISTING PATCH
PANEL FORM THE DATA RACK.
STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE
ROOMS HAVE BEEN COMPLETED.
STEP 19 CLEAN UP AND PAINT TR ROOM.
STEP 20 INSTALL TEMPERATURE AND HUMIDITY
SENSOR.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
126.T-410A
TELECOMMUNICATIONS RACK
ELEVATIONS
TELECOMMUNICATIONS RACK
ELEVATIONS
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NONE
8 NEW 2U 48 PORT PATCH
PANEL (CAT 6A) FROM
BLDG 126 5TH FLOOR.
KEY NOTES
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
8.
9.
EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED
AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH
ITEMS) UN HATCH ITEMS TO REMAIN.
QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE
OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.
TO BE REPLACED.
NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400
SERIES DRAWING.
2"C EMPTY
1"C 2"C
1 1/4" EMPTY
1" EMPTY
1 1/4" EMPTY
2"C
4"C
TEL CLOSET
W520B
126.T-411
SCALE: 1/4" = 1' - 0" NORTH
1 EXISTING WALL MOUNTED EQUIPMENT DATA RACKS WITH
VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.
EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO
REMAIN.
KEY NOTES FOR DETAIL 1
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE
SCALE: NONESCALE: NONE
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
PROPOSED SEQUENCE OF WORK (T&E) FOR A
TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)
STEP 1 REMOVE CEILING AND GRID AND
TEMPORARILY SUPPORT THE EXISTING
LIGHT FIXTURE, HVAC DIFFUSER AND
SMOKE DETECTOR.
STEP 2 INSTALL LIGHT FIXTURE AND QUAD
RECEPTACLE (WHERE APPLICABLE).
REATTACH SMOKE DETECTOR.
STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL
CABLE ENTRY FROM EUD.
STEP 4 INSTALL SLOPED LADDER RACK
FROM EZ PATH ENTRY POINT TO EXISTING
CABLE LADDER RACK.
STEP 5 POPULATE AVAILABLE SPACE IN EXISTING
RACK WITH NEW 48 PORT PATCH PANEL
CAT 6A COMPLIANT.
STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG
CORRIDOR ALONG MAIN CABLE ROUTE.
STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE
PATH FROM CORRIDOR TO EACH ROOM.
STEP 8 INSTALL EUD CABLES FROM TR TO THE
CORRIDORS ALONG MAIN CABLE ROUTE.
COIL UP CABLES AT EACH TAKE OFF POINT
TO INDIVIDUAL ROOMS AND LEAVE IT
ABOVE CEILING.
STEP 9 SCHEDULE A GROUP OF ROOMS FOR
INSTALLATION OF NEW FACEPLATE WITH
THREE RJ45 JACKS.
STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE
AND LET IT HANGING OUT TEMPORARILY.
STEP 11 TEST AND CERTIFY THE CABLE BY A
GROUP OF ROOMS TBD AND SCHEDULED.
STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT
TR ROOM AND AT EUD FACEPLATE.
STEP 13 VALB OIT TO CROSS CONNECT NEW 48
PORT PATCH PANEL TO CISCO SWITCH
AND ACTIVATE THE NEW EUD FACEPLATE.
STEP 14 VALB OIT TO SWITCH THE EUD DEVICE
FROM OLD FACE PLATE TO NEW
FACEPLATE.
STEP 15 EUD DEVICE ARE NOW CONNECTED TO
NEW CABLING.
STEP 16 PULLOUT AND REMOVE EXISTING DATA
CABLE FORM THE EUD TO TR ROOM
EXISTING PATCH PANEL.
STEP 17 REMOVE ASSOCIATED EXISTING PATCH
PANEL FORM THE DATA RACK.
STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE
ROOMS HAVE BEEN COMPLETED.
STEP 19 CLEAN UP AND PAINT TR ROOM.
STEP 20 INSTALL TEMPERATURE AND HUMIDITY
SENSOR.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
126.T-411A
TELECOMMUNICATIONS RACK
ELEVATIONS
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NONE
KEY NOTES
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
8.
9.
EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED
AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH
ITEMS) UN HATCH ITEMS TO REMAIN.
QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE
OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.
TO BE REPLACED.
NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400
SERIES DRAWING.
4"C
4"C
2"C
2"C
4"C
126.T-412
TELECOMMUNICATIONS
ENLARGED PLAN TR ROOM 627
ROOM W627
TELECOM
SCALE: 1/4" = 1' - 0" NORTH
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH
VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.
EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO
REMAIN.
EXISTING 12”W LADDER RACK MOUNTED AT 84" AFF AND FIXED
TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).
KEY NOTES FOR DETAIL 1
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE
SCALE: NONESCALE: NONE
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
PROPOSED SEQUENCE OF WORK (T&E) FOR A
TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)
STEP 1 REMOVE CEILING AND GRID AND
TEMPORARILY SUPPORT THE EXISTING
LIGHT FIXTURE, HVAC DIFFUSER AND
SMOKE DETECTOR.
STEP 2 INSTALL LIGHT FIXTURE AND QUAD
RECEPTACLE (WHERE APPLICABLE).
REATTACH SMOKE DETECTOR.
STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL
CABLE ENTRY FROM EUD.
STEP 4 INSTALL SLOPED LADDER RACK
FROM EZ PATH ENTRY POINT TO EXISTING
CABLE LADDER RACK.
STEP 5 POPULATE AVAILABLE SPACE IN EXISTING
RACK WITH NEW 48 PORT PATCH PANEL
CAT 6A COMPLIANT.
STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG
CORRIDOR ALONG MAIN CABLE ROUTE.
STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE
PATH FROM CORRIDOR TO EACH ROOM.
STEP 8 INSTALL EUD CABLES FROM TR TO THE
CORRIDORS ALONG MAIN CABLE ROUTE.
COIL UP CABLES AT EACH TAKE OFF POINT
TO INDIVIDUAL ROOMS AND LEAVE IT
ABOVE CEILING.
STEP 9 SCHEDULE A GROUP OF ROOMS FOR
INSTALLATION OF NEW FACEPLATE WITH
THREE RJ45 JACKS.
STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE
AND LET IT HANGING OUT TEMPORARILY.
STEP 11 TEST AND CERTIFY THE CABLE BY A
GROUP OF ROOMS TBD AND SCHEDULED.
STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT
TR ROOM AND AT EUD FACEPLATE.
STEP 13 VALB OIT TO CROSS CONNECT NEW 48
PORT PATCH PANEL TO CISCO SWITCH
AND ACTIVATE THE NEW EUD FACEPLATE.
STEP 14 VALB OIT TO SWITCH THE EUD DEVICE
FROM OLD FACE PLATE TO NEW
FACEPLATE.
STEP 15 EUD DEVICE ARE NOW CONNECTED TO
NEW CABLING.
STEP 16 PULLOUT AND REMOVE EXISTING DATA
CABLE FORM THE EUD TO TR ROOM
EXISTING PATCH PANEL.
STEP 17 REMOVE ASSOCIATED EXISTING PATCH
PANEL FORM THE DATA RACK.
STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE
ROOMS HAVE BEEN COMPLETED.
STEP 19 CLEAN UP AND PAINT TR ROOM.
STEP 20 INSTALL TEMPERATURE AND HUMIDITY
SENSOR.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
126.T-412A
TELECOMMUNICATIONS RACK
ELEVATIONS
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NONE
9 NEW 2U 48 PORT PATCH
PANEL (CAT 6A) FROM
SERVER CABINET.
KEY NOTES
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
8.
9.
EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED
AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH
ITEMS) UN HATCH ITEMS TO REMAIN.
QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE
OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.
TO BE REPLACED.
NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400
SERIES DRAWING.
ELEVATION 1 AND 2
4"C
2"C
4"C
2"C
126.T-413
ROOM 727
TELECOM
SCALE: 1/4" = 1' - 0" NORTH
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH
VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.
EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO
REMAIN.
EXISTING 12”W LADDER RACK MOUNTED AT 84" AFF AND FIXED
TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).
KEY NOTES FOR DETAIL 1
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONESCALE: NONE
SCALE: NONE SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
PROPOSED SEQUENCE OF WORK (T&E) FOR A
TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)
STEP 1 REMOVE CEILING AND GRID AND
TEMPORARILY SUPPORT THE EXISTING
LIGHT FIXTURE, HVAC DIFFUSER AND
SMOKE DETECTOR.
STEP 2 INSTALL LIGHT FIXTURE AND QUAD
RECEPTACLE (WHERE APPLICABLE).
REATTACH SMOKE DETECTOR.
STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL
CABLE ENTRY FROM EUD.
STEP 4 INSTALL SLOPED LADDER RACK
FROM EZ PATH ENTRY POINT TO EXISTING
CABLE LADDER RACK.
STEP 5 POPULATE AVAILABLE SPACE IN EXISTING
RACK WITH NEW 48 PORT PATCH PANEL
CAT 6A COMPLIANT.
STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG
CORRIDOR ALONG MAIN CABLE ROUTE.
STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE
PATH FROM CORRIDOR TO EACH ROOM.
STEP 8 INSTALL EUD CABLES FROM TR TO THE
CORRIDORS ALONG MAIN CABLE ROUTE.
COIL UP CABLES AT EACH TAKE OFF POINT
TO INDIVIDUAL ROOMS AND LEAVE IT
ABOVE CEILING.
STEP 9 SCHEDULE A GROUP OF ROOMS FOR
INSTALLATION OF NEW FACEPLATE WITH
THREE RJ45 JACKS.
STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE
AND LET IT HANGING OUT TEMPORARILY.
STEP 11 TEST AND CERTIFY THE CABLE BY A
GROUP OF ROOMS TBD AND SCHEDULED.
STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT
TR ROOM AND AT EUD FACEPLATE.
STEP 13 VALB OIT TO CROSS CONNECT NEW 48
PORT PATCH PANEL TO CISCO SWITCH
AND ACTIVATE THE NEW EUD FACEPLATE.
STEP 14 VALB OIT TO SWITCH THE EUD DEVICE
FROM OLD FACE PLATE TO NEW
FACEPLATE.
STEP 15 EUD DEVICE ARE NOW CONNECTED TO
NEW CABLING.
STEP 16 PULLOUT AND REMOVE EXISTING DATA
CABLE FORM THE EUD TO TR ROOM
EXISTING PATCH PANEL.
STEP 17 REMOVE ASSOCIATED EXISTING PATCH
PANEL FORM THE DATA RACK.
STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE
ROOMS HAVE BEEN COMPLETED.
STEP 19 CLEAN UP AND PAINT TR ROOM.
STEP 20 INSTALL TEMPERATURE AND HUMIDITY
SENSOR.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
126.T-413A
TELECOMMUNICATIONS RACK
ELEVATIONS
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NONE
8 NEW 2U 48 PORT PATCH
PANEL (CAT 6A) FROM
SERVER CABINET.
KEY NOTES
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
8.
9.
EXISTING PATCH PANEL AND 2U MANAGER TO BE REMOVED
AFTER NEW 48 PORT PATCH PANEL IS IN PLACE (HATCH
ITEMS) UN HATCH ITEMS TO REMAIN.
QUANTITY OF 48 PORT PATCH PANEL SHOWN IS INCLUSIVE
OF 15% ADDITIONAL PATCH PANEL FOR FUTURE USE.
TO BE REPLACED.
NEW BY ELECTRICAL CONTRACTOR. SEE ELECTRICAL 400
SERIES DRAWING.
4"C
4"C 2"C
4"C
2"C
4"C
ROOM 827
TELECOM
126.T-414
TELECOMMUNICATIONS
ENLARGED PLAN TR ROOM 827
SCALE: 1/4" = 1' - 0" NORTH
1 EXISTING 19" X 84" HIGH EQUIPMENT DATA RACKS WITH
VERTICAL AND HORIZONTAL CABLE MANAGEMENT TO REMAIN.
EXISTING TELECOMMUNICATIONS GROUND BUS BAR (TGB) TO
REMAIN.
EXISTING 12”W CABLE RACK MOUNTED AT 84" AFF AND FIXED
TO TOP OF EQUIPMENT RACKS TO REMAIN (TYPICAL).
KEY NOTES FOR DETAIL 1
SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONE SCALE: NONE SCALE: NONE
SCALE: NONESCALE: NONE
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
PROPOSED SEQUENCE OF WORK (T&E) FOR A
TYPICAL TR ROOM (EXCEPT TR313 BUILDING 1)
STEP 1 REMOVE CEILING AND GRID AND
TEMPORARILY SUPPORT THE EXISTING
LIGHT FIXTURE, HVAC DIFFUSER AND
SMOKE DETECTOR.
STEP 2 INSTALL LIGHT FIXTURE AND QUAD
RECEPTACLE (WHERE APPLICABLE).
REATTACH SMOKE DETECTOR.
STEP 3 INSTALL EZ PATH FOR NEW HORIZONTAL
CABLE ENTRY FROM EUD.
STEP 4 INSTALL SLOPED LADDER RACK
FROM EZ PATH ENTRY POINT TO EXISTING
CABLE LADDER RACK.
STEP 5 POPULATE AVAILABLE SPACE IN EXISTING
RACK WITH NEW 48 PORT PATCH PANEL
CAT 6A COMPLIANT.
STEP 6 INSTALL WALL MOUNTED J-HOOKS ALONG
CORRIDOR ALONG MAIN CABLE ROUTE.
STEP 7 INSTALL PENDANT J-HOOKS ALONG CABLE
PATH FROM CORRIDOR TO EACH ROOM.
STEP 8 INSTALL EUD CABLES FROM TR TO THE
CORRIDORS ALONG MAIN CABLE ROUTE.
COIL UP CABLES AT EACH TAKE OFF POINT
TO INDIVIDUAL ROOMS AND LEAVE IT
ABOVE CEILING.
STEP 9 SCHEDULE A GROUP OF ROOMS FOR
INSTALLATION OF NEW FACEPLATE WITH
THREE RJ45 JACKS.
STEP 10 PULL OUT THE EXISTING RJ45 FACEPLATE
AND LET IT HANGING OUT TEMPORARILY.
STEP 11 TEST AND CERTIFY THE CABLE BY A
GROUP OF ROOMS TBD AND SCHEDULED.
STEP 12 TERMINATE AND INSTALL RJ45 JACKS AT
TR ROOM AND AT EUD FACEPLATE.
STEP 13 VALB OIT TO CROSS CONNECT NEW 48
PORT PATCH PANEL TO CISCO SWITCH
AND ACTIVATE THE NEW EUD FACEPLATE.
STEP 14 VALB OIT TO SWITCH THE EUD DEVICE
FROM OLD FACE PLATE TO NEW
FACEPLATE.
STEP 15 EUD DEVICE ARE NOW CONNECTED TO
NEW CABLING.
STEP 16 PULLOUT AND REMOVE EXISTING DATA
CABLE FORM THE EUD TO TR ROOM
EXISTING PATCH PANEL.
STEP 17 REMOVE ASSOCIATED EXISTING PATCH
PANEL FORM THE DATA RACK.
STEP 18 REPEAT STEP 9 TO STEP 17 UNTIL ALL THE
ROOMS HAVE BEEN COMPLETED.
STEP 19 CLEAN UP AND PAINT TR ROOM.
STEP 20 INSTALL TEMPERATURE AND HUMIDITY
SENSOR.
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK WITH
NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE
THESE NEW PATCH PANELS ARE POPULATED REMOVE
EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A
COMPLIANT 48 PORT PATCH PANEL. BEFORE
DISCONNECTING AND REMOVINF EXISTING PATCH PANEL,
RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING
IN THOSE PATCH PANELS TO EUD HAVE BEEN
SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND
CAT6A COMPLIANT PATCH PANEL.
FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE
GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.
1.
2.
3.
4.
5.
6.
7.
126.T-414A
TELECOMMUNICATIONS RACK
ELEVATIONS
SCALE: NONE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NONE
9 NEW 2U 48 PORT PATCH
PANEL (CAT 6A) FROM
SERVER CABINET.
KEY NOTES
ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR
ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)
CAT6A (WHITE, GRAY AND BLUE) IN NEW CAT6A COMPATIBLE
JACKS ON NEW FACEPLATE AT EACH EUD OUTLET AND
LABEL IT AS SHOWN. TERMINATE ON TR END IN A CAT6A
COMPATIBLE RJ45 JACKS AND NEW CAT6A COMPLIANT 48
PORT PATCH PANEL. EACH CABLE TO EUD OUTLETS SHALL
BE TESTED AND CERTIFIED BY CABLE MANUFACTURER’S
CERTIFIED INSTALLER.
SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE
DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE
COORDINATION WITH OIT.
INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCHPANEL IN
EXISTING RACKS IN TR ROOM.
RING AND STRING METHOD WILL BE USED TO INSTALL NEW
CAT6A CABLES.
OLD FACE PLATE WILL BE PULLED OUT AND LEFT HANGING
AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE
NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A
COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE
THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD
WILL BE DISCONNECTED FROM OLD FACEPLATE AND
CONNECTED TO NEW FACE PLATE BY OIT.
LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL
EQUIPMENTS AND RACKS FROM DUST & DAMAGE.
POPULATE AVAILABLE SPACES IN THE EXISTING RACK…