This notice announces an upcoming solicitation for construction services required for the Electronic Health Record Modernization Infrastructure Upgrades project at the VA Long Beach Healthcare System in Long Beach, California. Work includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures. The project is valued between $10-20 million. The solicitation will be issued on April 12, 2021 via beta.sam.gov as an Invitation for Bid. A mandatory site visit will be scheduled. The North American Industry Classification Code is 236220 for commercial and institutional building construction. The procurement is set aside 100% for Service-Disabled Veteran-Owned Small Businesses. Responses are due by 2:00 PM Pacific Time on May 13, 2021.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EX
ZEMXA-22
NEW GROUND BUS BAR
EX GROUND ROD
EX
TDU EX
EXWALL MOUNTED
EX FC
2.E-401
ELECTRICAL ENLARGED PLAN TR
ROOM N108A
TELEPHONE
CLOSET
N108A
SCALE: 1/4" = 1' - 0" NORTH
TELEPHONE
CLOSET
N108A
SCALE: 1/4" = 1' - 0" NORTH
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 1.E-131.
BUILDING 2
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
TELEPHONE
CLOSET
N108A
SCALE: 1/4" = 1' - 0" NORTH
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
NEW SMOKE DETECTOR TO BE INSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 4 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 4 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
KEY NOTES FOR DETAILS 2 , 3 , 4
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i l e
P a t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
EXISTING WIREWAY AT RACK
TDU EX
1EX
TDU EX
EX
EX
IT/DATA
E-108
5C.E-401
ELECTRICAL ENLARGED PLAN TR
ROOM E108
5C
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
SCALE: 1/4" = 1' - 0" NORTH
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR DETECTOR TO BE
RE-INSTALLED. PROTECT AND TEMPORARILY SUPPORT
DURING CONSTRUCTION. COORDINATE WITH
ELECTRICAL SHOP TO BYPASS THE SMOKE DETECTOR
FROM FIRE ALARM SYSTEM.
KEY NOTES FOR DETAILS 2 AND 3
IT/DATA
E-108
SCALE: 1/4" = 1' - 0" NORTH
SCALE: 1/4" = 1' - 0" NORTH
BUILDING 5C
IT/DATA
E-108
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
6.E-401
ELECTRICAL ENLARGED PLAN TR
ROOM 34
SCALE: 1/4" = 1' - 0" NORTH
BUILDING 6
TELEPHONE
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 2 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE
BOTH SWITCH. SEE WIRING DIAGRAM DETAIL 2 .
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
EX
1EMXP-15
NEW GROUND BUS BAR
TDU EX
EX
TDU EX
EX
TELEPHONE
ROOM 111
8.E-401
ELECTRICAL ENLARGED PLAN TR
ROOM 111
SCALE: 1/4" = 1' - 0" NORTH
SCALE: 1/4" = 1' - 0" NORTH
TELEPHONE
ROOM 111
FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
FOR PANEL LOCATION SEE .
1.
2.
3.
BUILDING 8
TELEPHONE
ROOM 111
SCALE: 1/4" = 1' - 0" NORTH
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5.
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE WIRING DIAGRAM DETAIL 4 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
EX
EX
50.E-401
ELECTRICAL ENLARGED PLAN
TR ROOM 101B
SCALE: 1/4" = 1' - 0" NORTH
SCALE: 1/4" = 1' - 0" NORTH
COMMUNICATIONS
ROOM 101B
TELE-
COMMUNICATIONS
ROOM 101B
TELE-
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
BUILDING 50
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
NOT USED.
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 4 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
KEY NOTES FOR DETAILS 2 AND 3
SCALE: 1/4" = 1' - 0" NORTH
COMMUNICATIONS
ROOM 101B
TELE-
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
SCALE: 1/4" = NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
EX
TDU EX
1EMXF-29
1EMXF-29
EX 1EMXF
EX 1EMXE
EX
EX
TDU EX
126.E-401
SCALE: 1/4" = 1' - 0"
NORTH
TELECOMMUNICATION
EQUIP AREA
W128V
TELECOMMUNICATION
EQUIP AREA
W128V
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON WALL.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
REPLACE EXISTING DUPLEX RECEPTACLE AND COVER PLATE IN EXISTING
2-GANG BOX WITH TWO NEW (RED) DUPLEX RECEPTACLES AND NEW
COVER PLATE AT THIS LOCATION. EXISTING BRANCH CIRCUIT SHALL
REMAIN
EXISTING EMERGENCY ELECTRICAL PANEL 1EMXF 100A 208/120V.
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
KEY NOTES FOR DETAILS 2 AND 3
SCALE: 1/4" = 1' - 0"
NORTH
TELECOMMUNICATION
EQUIP AREA
W128V
SCALE: 1/4" = 1' - 0"
NORTH
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
EXEX
EX
2EMXF-24
EX
EX
EX
EX
TDU EX
126.E-402
ELECTRICAL ENLARGED PLAN
SECOND FLOOR TR ROOMS W220
AND W232
TELE AND SIG
CLOSET
W220
SCALE: 1/4" = 1' - 0" NORTHSCALE: 1/4" = 1' - 0" NORTH
S AND T
CLOSET
W232TELE AND SIG
CLOSET
W220
SCALE: 1/4" = 1' - 0" NORTH
S AND T
CLOSET
W232
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126.E-121.
SECOND FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM W220
SECOND FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM W220
SECOND FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM W232
SCALE: 1/4" = 1' - 0" NORTH
SECOND FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM W232
SURFACE MOUNT NEW FIXTURE TYPE A (LED) ON EXISTING CEILING
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5.
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE WIRING DIAGRAM DETAIL 4 .
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO REMAIN.
EXISTING HARD CEILING TO REMAIN.
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
PROVIDE NEW HOME RUN, 3/4"C.-2#12 + 1#12 EG, TO PANEL AND CIRCUIT
INDICATED. VERIFY CIRCUIT INDICATED IS A SPARE BREAKER PRIOR TO
ROUGH-IN.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5.
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE WIRING DIAGRAM DETAIL 8 .
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
TELE AND SIG
CLOSET
W220
SCALE: 1/4" = 1' - 0" NORTHSCALE: 1/4" = 1' - 0" NORTH
S AND T
CLOSET
W232
SECOND FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM W220
SECOND FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM W232
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
KEY NOTES FOR DETAILS 2 , 3 , 4 KEY NOTES FOR DETAILS 6 , 7 , 8
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
PANEL UPS NO.1
PANEL UPS NO.2
PANEL UPS NO.3
PANEL UPS NO.4
UPS NO.3-24UPS NO.3-22
EXISTING
LADDER RACK
TO REMAIN
SERVER
CABINET
(TYPICAL)
S AND T
CLOSET
W232
126.E-403
ELECTRICAL ENLARGED PLAN
SECOND FLOOR - TR ROOM
SERVER ROOM E221
SCALE: 1/4" = 1' - 0" NORTH
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126.E-121 AND THIS SHEET.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE
LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
SECOND FLOOR ELECTRICAL ENLARGED POWER PLAN - NEW -
TR ROOM SERVER ROOM E221
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
KEY NOTES
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
EX
3EMXB-36
TDU EX
EX
EX
EX
TEL
326A
TELECOM
ROOM 321
126.E-404
ELECTRICAL ENLARGED PLAN
THIRD FLOOR - TR 321 AND 326A
SCALE: 1/4" = 1' - 0" NORTH
SCALE: 1/4" = 1' - 0" NORTH
TEL
326A
TELECOM
ROOM 321
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126.E-131.
THIRD FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM 326A
SCALE: 1/4" = 1' - 0" NORTH
THIRD FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW TR ROOM 326A
THIRD FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM 321
SCALE: 1/4" = 1' - 0" NORTH
THIRD FLOOR ELECTRICAL
ENLARGED POWER PLAN - TR
NEW - ROOM 321
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
TELECOM
ROOM 321
SCALE: 1/4" = 1' - 0"
NORTH
THIRD FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM 321
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
NEW SMOKE DETECTOR TO BE INSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 8 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 8 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
EXISTING LAY-IN CEILING TO BE REMOVED.
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
EXISTING SMOKE DETECTOR RE INSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO ACTIVATE THE SMOKE
DETECTOR.
NEW 1/2'' X 2'' X 12'' TGB (GROUND BUS) CONNECT TO GROUND BUS IN
TR 321 USING #1/0 INSULATED GREEN CONDUCTOR. RUN OVERHEAD
ABOVE CEILING. SURFACE MOUNT ON WALL USING CABLE CLIP.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 4 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 4 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
TEL
326A
SCALE: 1/4" = 1' - 0" NORTH
THIRD FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM 326A
KEY NOTES FOR DETAILS 2 , 3 , 4 KEY NOTES FOR DETAILS 6 , 7 , 8
EXISTING WIREWAY AT RACK EXISTING WIREWAY AT RACK
TDU EX
EX
TDU EX
EX
4EMXA-12
TDU EX
4EMXB-22
TDU EX
EX
TDU EX
EX
EX
TDU EX
TELECOM
ROOM W428
QS SERVER
ROOM W416
126.E-405
ELECTRICAL ENLARGED PLAN
FOURTH FLOOR - TR ROOM W416
AND W428
SCALE: 1/4" = 1' - 0" NORTH
SCALE: 1/4" = 1' - 0" NORTH
TELECOM
ROOM W428
QS SERVER
ROOM W416
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126.E-141.
FOURTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM W416
SCALE: 1/4" = 1' - 0" NORTH
FOURTH FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM W416
FOURTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM W428
SCALE: 1/4" = 1' - 0" NORTH
FOURTH FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM W428
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
NEW SMOKE DETECTOR. SURFACE MOUNT ON UNDERSIDE OF SLAB
ABOVE. EXTEND CONDUIT AND WIRE TO IT. EXISTING FA SYSTEM &
CONNECT COORDINATE WITH ELECTRICAL SHOP TO ACTIVATE THE SMOKE
DETECTOR.
NEW 1/2'' X 2'' X 12'' TGB (GROUND BUS) CONNECT TO GROUND BUS IN
TR W428 USING #1/0 INSULATED GREEN CONDUCTOR. RUN OVERHEAD
ABOVE CEILING. SURFACE MOUNT ON WALL USING CABLE CLIP.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 4 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 4 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
REPLACE EXISTING 30 AMP 2-POLE SPARE BREAKER WITH ONE NEW 20
AMP 1-POLE BREAKER FOR THIS CIRCUIT. NEW BREAKER SHALL MATCH
EXISTING MANUFACTURER AND AIC RATINGS.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 8 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 8 .
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
TELECOM
ROOM W428
SCALE: 1/4" = 1' - 0" NORTH
FOURTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM W428
QS SERVER
ROOM W416
SCALE: 1/4" = 1' - 0" NORTH
FOURTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM W416
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
KEY NOTES FOR DETAILS 2 , 3 , 4
KEY NOTES FOR DETAILS 6 , 7 , 8
1 EX
EX
EX
EX
EX
EX
EX
EX
5EGZ-10
126.E-406
ELECTRICAL ENLARGED PLAN
FIFTH FLOOR - TR ROOMS W520B
AND W521A
SCALE: 1/4" = 1' - 0" NORTH
FIFTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM W520B
SCALE: 1/4" = 1' - 0" NORTH
FIFTH FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM W520B
ROOM W521A
SCALE: 1/4" = 1' - 0" NORTH
FIFTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM W521A
SURFACE MOUNT NEW FIXTURE TYPE A (LED) ON EXISTING CEILING
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW 1/2'' X 2'' X 12'' TGB (GROUND BUS) CONNECT TO GROUND BUS IN
TR 521A USING #1/0 INSULATED GREEN CONDUCTOR. RUN OVERHEAD
ABOVE CEILING. SURFACE MOUNT ON WALL USING CABLE CLIP.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 4 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 4 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR DETECTOR TO BE
RE-INSTALLED. PROTECT AND TEMPORARILY SUPPORT
DURING CONSTRUCTION. COORDINATE WITH
ELECTRICAL SHOP TO BYPASS THE SMOKE DETECTOR
FROM FIRE ALARM SYSTEM.
HARD CEILING TO REMAIN.
TEL CLOSET
W520B
SCALE: 1/4" = 1' - 0" NORTH
FIFTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM W520B
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR DETECTOR TO BE
RE-INSTALLED. PROTECT AND TEMPORARILY SUPPORT
DURING CONSTRUCTION. COORDINATE WITH
ELECTRICAL SHOP TO BYPASS THE SMOKE DETECTOR
FROM FIRE ALARM SYSTEM.
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 8 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 8 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
ROOM W521A
SCALE: 1/4" = 1' - 0" NORTH
FIFTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM W521A
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126.E-151.
ROOM W521A
SCALE: 1/4" = 1' - 0" NORTH
FIFTH FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM W521A
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
KEY NOTES FOR DETAILS 2 , 3 , 4
KEY NOTES FOR DETAILS 6 , 7 , 8
TEL CLOSET
W520B
TEL CLOSET
W520B
EX
EX
7EMXA-2
6EMXA-23
EX
EX
TDU EX EX
EX
126.E-407
ROOM W627TELECOM
ROOM 727TELECOM
SCALE: 1/4" = 1' - 0" NORTH
ROOM W627TELECOM
ROOM 727TELECOM
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126.E-161 & 126.E-171.
SEVENTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM 727
SCALE: 1/4" = 1' - 0" NORTH
SEVENTH FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM 727
SCALE: 1/4" = 1' - 0" NORTH
SIXTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM W627
SCALE: 1/4" = 1' - 0" NORTH
SIXTH FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM W627
ROOM W627TELECOM
SCALE: 1/4" = 1' - 0" NORTH
SIXTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM W627
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
PROVIDE NEW 20 AMP 1-POLE BREAKER IN EXISTING BUSSED SPACE. NEW
BREAKER SHALL MATCH EXISTING MANUFACTURER AND AIC RATINGS.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 4 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 4 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
ROOM 727TELECOM
SCALE: 1/4" = 1' - 0" NORTH
SEVENTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM 727
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 8 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 8 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
KEY NOTES FOR DETAILS 2 , 3 , 4 KEY NOTES FOR DETAILS 6 , 7 , 8
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
8EMXA-5
EX
EX
EX
EX
EX
EX
EX
ROOM 827
TELECOM
ROOM 813B
TELECOM
126.E-408
ROOM 827
TELECOM
ROOM 813B
TELECOM
SCALE: 1/4" = 1' - 0"
NORTH
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126.E-181.
EIGHT FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM 813B
ELECTRICAL ENLARGED PLAN
EIGHT FLOOR - TR ROOM 813B
AND TR ROOM 827
SCALE: 1/4" = 1' - 0"
NORTH
EIGHT FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM 813B
SCALE: 1/4" = 1' - 0"
NORTH
EIGHT FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM 827
SCALE: 1/4" = 1' - 0"
NORTH
EIGHT FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM 827
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5.
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE WIRING DIAGRAM DETAIL 4 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
SURFACE MOUNT NEW FIXTURE TYPE A (LED) ON EXISTING CEILING
CONNECT TO EXISTING LIGHTING CIRCUIT
RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
EXISTING SMOKE DETECTOR.
NEW 1/2'' X 2'' X 12'' TGB (GROUND BUS) CONNECT TO GROUND
BUS IN TR 827 USING #1/0 INSULATED GREEN CONDUCTOR.
RUN OVERHEAD ABOVE CEILING. SURFACE MOUNT ON WALL
USING CABLE CLIP.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5.
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE WIRING DIAGRAM DETAIL 8 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO REMAIN.
HARD CEILING TO REMAIN.
SCALE: 1/4" = 1' - 0"
NORTH
EIGHT FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM 813B
SCALE: 1/4" = 1' - 0"
NORTH
EIGHT FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM 827
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT
RACK
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT
RACK
KEY NOTES FOR DETAILS 2 , 3 , 4 KEY NOTES FOR DETAILS 6 , 7 , 8
ROOM 827
TELECOM
ROOM 813B
TELECOM
EXISTING WIREWAY AT
RACK
EXISTING WIREWAY AT
RACK
9EMXA
11EMXA-17
EX
EX
EX
EX
EX EX
EX
EX
TDU EX
ROOM W923C
TELECOM
126.E-409
ROOM W1121
TELECOM
ROOM W923C
TELECOM
ROOM W1121
TELECOM
SCALE: 1/4" = 1' - 0" NORTH
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126.E-191 AND 126.R-1111.
ELEVENTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM 1121
SCALE: 1/4" = 1' - 0" NORTH
ELEVENTH FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM 1121
SCALE: 1/4" = 1' - 0" NORTH
NINTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM W923C
SCALE: 1/4" = 1' - 0" NORTH
NINTH FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM W923C
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 4 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 4 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 8 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 8 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
SCALE: 1/4" = 1' - 0" NORTH
ELEVENTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM 1121
SCALE: 1/4" = 1' - 0" NORTH
NINTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM W923C
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
KEY NOTES FOR DETAILS 2 , 3 , 4 KEY NOTES FOR DETAILS 6 , 7 , 8
ROOM W923C
TELECOM
ROOM W1121
TELECOM
EX EX
10EMXA-19
EX
EX
EX
EX
CLOSET
NETWORKING
ROOM 1013B
TELECOM
W1027
126.E-410
ELECTRICAL ENLARGED PLAN
TENTH FLOOR - TR ROOM E1013B
AND 1027
SCALE: 1/4" = 1' - 0" NORTH
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126.E-1101.
TENTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM E1013B
SCALE: 1/4" = 1' - 0" NORTH
TENTH FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM E1013B
SCALE: 1/4" = 1' - 0" NORTH
TENTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM W1027
SCALE: 1/4" = 1' - 0" NORTH
TENTH FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM W1027
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 4 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 4 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
SURFACE MOUNT NEW FIXTURE TYPE A (LED) ON EXISTING CEILING
CONNECT TO EXISTING LIGHTING CIRCUIT RECONNECT TO EXISTING
CIRCUIT AND EXISTING WALL SWITCH.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
NEW 1/2'' X 2'' X 12'' TGB (GROUND BUS) CONNECT TO GROUND BUS IN
TR 1027 USING #1/0 INSULATED GREEN CONDUCTOR. RUN OVERHEAD
ABOVE CEILING. SURFACE MOUNT ON WALL USING CABLE CLIP.
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5. SEE WIRING DIAGRAM DETAIL 8 .
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE DETAIL 8 .
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO REMAIN.
EXISTING HARD CEILING TO REMAIN.
SCALE: 1/4" = 1' - 0" NORTH
TENTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM E1013B
SCALE: 1/4" = 1' - 0" NORTH
TENTH FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM W1027
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
KEY NOTES FOR DETAILS 2 , 3 , 4 KEY NOTES FOR DETAILS 6 , 7 , 8
CLOSET
NETWORKING
W1027
CLOSET
NETWORKING
W1027
ROOM 1013B
TELECOM
ROOM 1013B
TELECOM
LEBA
LE1B-9
EX
EX
EX
EX
EX
EX
EX
EX
TELE
CLOSET
OP-04
126A.E-401
126A
TEL/DAT
ROOM
1N111
TELE
CLOSET
OP-04
TEL/DAT
ROOM
1N111
SCALE: 1/4" = 1' - 0" NORTH
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126A.E-101 & 126A.E-111.
FIRST FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
NEW - TR ROOM 1N11
SCALE: 1/4" = 1' - 0" NORTH
FIRST FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM 1N11
SCALE: 1/4" = 1' - 0" NORTH
BASEMENT FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN - TR
NEW - ROOM OP-04
SCALE: 1/4" = 1' - 0" NORTH
BASEMENT FLOOR ELECTRICAL
ENLARGED POWER PLAN - NEW
- TR ROOM OP-04
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
EXISTING QUAD RECEPTACLE TO REMAIN.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE WIRING DIAGRAM DETAIL 4 .
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE WIRING DIAGRAM DETAIL 8 .
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
TELE
CLOSET
OP-04
TEL/DAT
ROOM
1N111
SCALE: 1/4" = 1' - 0" NORTH
FIRST FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM 1N11
SCALE: 1/4" = 1' - 0" NORTH
BASEMENT FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN - TR
DEMO - ROOM OP-04
0' 2' 4' 8'
SCALE: 1/4" = 1'-0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
U.S. Department of Veterans Affairs
B
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Project Director
Revisions: Date:
Key Plan
PM EW/JB
NORTH
A
GENERAL NOTES
17075 Via Del Campo, San Diego, CA 92127
Phone: 858.946.0333
ARCHITECT/ENGINEER OF RECORD
C
D
20-SCE-04
GENERAL NOTE
FIRE PROTECTION
1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO
ANY FIREPROOFED COMPONENTS.
SYMBOLS LIST
2 HOUR FIRE BARRIER
1 HOUR FIRE BARRIER
2 HOUR FIRE/SMOKE BARRIER
SMOKE BARRIER
SMOKE PARTITION
1 HOUR FIRE/SMOKE BARRIER
3 HOUR FIRE BARRIER
FULLY SPRINKLERED
Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach
5901 E. SEVENTH STREET, LONG BEACH, CA 90822
600-20-120
CONTRACT DOCUMENTS
December 16, 2020
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
EXISTING WIREWAY AT RACK
SCALE: NO SCALE
UPS
K K
EXISTING OR NEW
RECEPTACLE AT WALL
NEW RECEPTACLE AT RACK
KEY NOTES FOR DETAILS 2 , 3 , 4 KEY NOTES FOR DETAILS 6 , 7 , 8
TDU EX
EX
EX
TDU EX
LE2B-29
CU
SS
F
F
LE2B-40,42
LE2B-36,38
LE2B-27
EX
TDU EX
EX
EX
TDU EX
EX
TELECOM/
DATA ROOM
2N107
126A.E-402
126A
SCALE: 1/4" = 1' - 0" NORTH
TELECOM/
DATA ROOM
301B
TELECOM/
DATA ROOM
2N107
TELECOM/
DATA ROOM
301B
1. FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.
2. FOR PANEL SCHEDULE SEE E-700 SERIES DRAWINGS.
3. FOR PANEL LOCATION SEE 126A.E-121.
THIRD FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM 301B
SCALE: 1/4" = 1' - 0" NORTH
THIRD FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM 301B
SCALE: 1/4" = 1' - 0" NORTH
SECOND FLOOR ELECTRICAL
ENLARGED LIGHTING PLAN -
DEMO - TR ROOM 2N107
SCALE: 1/4" = 1' - 0" NORTH
SECOND FLOOR ELECTRICAL
ENLARGED POWER PLAN -
NEW - TR ROOM 2N107
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETECTOR.
CONNECT NEW DDC CONTROL PANEL TO EXISTING RECEPTACLE CIRCUIT
IN TR ROOM. COORDINATE EXACT LOCATION OF DDC CONTROL WITH
CONTROL CONTRACTOR.
KEY OPERATED SELECTOR SWITCH. ONE KEY TO OPERATE BOTH SWITCH.
SEE WIRING DIAGRAM DETAIL 4 .
NEW RACK MOUNTED UPS 2000VA/ 120V VERTIV LIEBERT
GXT5-2000 LVRT2UXL5.
EXISTING FIXTURE TO BE DISCONNECTED AND
REMOVED. CIRCUIT AND SWITCH TO BE RE-USED.
EXISTING SMOKE DETECTOR TO BE RE-INSTALLED.
PROTECT AND TEMPORARILY SUPPORT DURING
CONSTRUCTION. COORDINATE WITH ELECTRICAL SHOP
TO BYPASS THE SMOKE DETECTOR FROM FIRE ALARM
SYSTEM.
MOUNT NEW FIXTURE TYPE A (LED) ON
1 15/16'' UNISTRUT. CONNECT TO EXISTING LIGHTING CIRCUIT MOUNT
9'-0'' AFF. RECONNECT TO EXISTING CIRCUIT AND EXISTING WALL SWITCH.
MOUNT QUAD RECEPTACLE (RED) ON SIDE OF CABLE LADDER RACK.
3/4''C- 2 #12 + 1 #12 EG.
EXISTING SMOKE DETECTOR REINSTALLED. SURFACE MOUNT ON
UNDERSIDE OF SLAB ABOVE. EXTEND CONDUIT AND WIRE TO IT.
COORDINATE WITH ELECTRICAL SHOP TO RE-ACTIVATE THE SMOKE
DETEC…