This document provides notice of an upcoming solicitation for construction services. The Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 22 will issue an Invitation for Bid on or around April 12, 2021 via beta.SAM.gov to perform construction work for Project 600-20-120, Electronic Health Record Modernization Infrastructure Upgrades at the VA Long Beach Healthcare System located at 5901 E. 7th Street, Long Beach, CA 90822. The work includes general construction, alterations, mechanical and electrical work, utility systems, necessary demolition and removal of existing structures. The project is set aside 100% for Service-Disabled Veteran-Owned Small Businesses listed in the Vendor Information Pages database. The North American Industry Classification Code is 236220 for commercial and institutional building construction with a size standard of $39.5 million. The magnitude of the construction project is estimated between $10,000,000 to $20,000,000. A site visit will be scheduled for potential offerors.

View the file

Other files for this federal contract opportunity

Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE PENETRATIONS NOTE

- M -

MAIN CIRCUIT BREAKER

NEUTRAL

MCB

N

- N -

PHASE

POWER

PANEL

PWR

PNL

- R -

- P -

ROOM

RECEPTACLE

RM

RECEPT

- B -

AMPERE

- A -

A

- C -

CIRCUIT

CIRCUIT BREAKER

BUILDING

CONDUIT

BLDG

CKT

C

CB

- E -

EG

- G -

GROUNDG, GND

EQUIPMENT GROUND

ABBREVIATIONS

VOLT OR VOLTAGE

VOLT AMPEREVA

V

- V -

WATTW

- W -

- J -

- K -

KILOVOLT AMPERE

KILOVOLT

JUNCTION BOX

KV

KW

KVA

JB

KILOWATT

ABOVE FINISHED FLOORAFF

UON UNLESS OTHERWISE NOTED

- U -

E1.01

AC

X

MOTOR TYPE

REVISION

RISER TAGPOINT OF CONNECTION

SCHEDULE NUMBER

# LIGHT FIXTURE TYPE

INDICATES DETAIL NUMBER

SHEET NUMBER TO FIND DETAIL

SPECIFIC NOTE/

POINT OF DISCONNECTION

REFERENCE NOTE

ANNOTATIONS

EWC ELECTRIC WATER COOLER

T-001

TELECOMMUNICATIONS

GENERAL NOTES: VETERANS ADMINISTRATION HAS AWARDED CERNER A CONTRACT TO TAKE OVER THE MANAGEMENT OF VETERANS HEALTHCARE RECORDS, REPLACING THE LEGACY VISTA ELECTRONIC HEALTH RECORD (EHR) SYSTEM AND MERGING THE NEW CERNER EHR SYSTEM WITH THAT OF THE DEPARTMENT OF DEFENSE. CERNER HAS PUBLISHED A GUIDELINE “OEHRM REQUIREMENT SPECIFICATION VERSION 1.0” THAT DETAILS REQUIREMENTS FOR CABLING AND DATA TRANSMISSION FOR THE ELECTRONIC HEALTH RECORD MODERNIZATION SYSTEM. THE EXISTING IT INFRASTRUCTURE IS NOT CAPABLE OF MEETING THE REQUIREMENT.

THE MAIN OBJECTIVE OF THIS PROJECT IS TO UPGRADE THE EXISTING IT INFRASTRUCTURE TO MAKE IT COMPATIBLE WITH AND MEET REQUIREMENTS OF THE

CERNER EHRM.

THERE ARE 17 BUILDINGS AND TOTAL OF 45 TR (TELECOMMUNICATION ROOM) INVOLVED. IN ADDITION, MDF ROOM AND MAIN SERVER ROOM WILL REQUIRE SOME ADDITION OF FIBER AND CERNER EQUIPMENT. ALL TR ARE NETWORKED WITH THE MAIN SERVER ROOM AND MDF ROOM USING SINGLE MODE FIBER. TELECOM RACK WITH 48 PORT PATCH PANELS ARE ALSO INSIDE THE MDF ROOM AND SERVER ROOM. ALL CABLES ON THESE RACKS ARE TO BE REPLACED WITH CAT 6A CABLES AND CAT6A COMPLIANT RJ45 JACKS. ALL CABLES SHALL BE TESTED AND CERTIFIED BY CABLE MANUFACTURER'S CERTIFIED CABLE CONTRACTOR.

LISTED BELOW ARE THE DETAILED IT REQUIREMENT SCOPE OF THE PROJECT.

1. REPLACE EXISTING COPPER CABLES WITH CAT6A AS SHOWN.

2. INSTALL NEW TWO 24 STRAND SINGLE MODE AIR BLOWN FIBER FROM MDF TO SERVER ROOM BUILDING 126. TWO-24 STRAND SINGLE MODE FIBER SHALL BE INSTALLED IN EXISTING CELL TUBE WHICH HAS BEEN TESTED AND IS CLEAR OF ANY OBSTRUCTION. PLEASE SEE CELL TUBE RISER DIAGRAM SHOWING THE ROUTING OF THE NEW FIBER. TWO 24 STRAND SINGLE MODE FIBER TO BE AIR BLOWN AND AS MANUFACTURED BY SUMITOMO. 24 STRAND SINGLE MODE FIBER TO BE TERMINATED ON THE WEST RACK AND 24 STRAND ON THE EAST RACK OF SERVER ROOM E221. CONNECTOR TYPE TO BE LC.

3. PROVIDE 15% MORE DATA DROPS THAN WHAT IS REQUIRED PROJECT WIDE AND AS SHOWN ON PLANS. ADD NEW EUDS AT LOCATIONS DETERMINED BY CEDT DURING CONSTRUCTION ACTIVITIES AND AFTER COMPLETION OF CD (POST 100% SUBMISSION).

4. PROJECT REQUIRES 1 GbE CONNECTIVITY TO DESKTOP AND OTHER EUDS AND AT EACH NEW WALL JACKS.

5. REMOVE EXISTING LAY-IN CEILING IN ALL TR ROOMS.

6. PROVIDE FOUR NEW FOUR POST RACKS IN EXPANDED PORTION OF RM 313 BLDG 1 & ONE 4-POST RACK FOR BIOMED IN TR 189 BLDG. 164.

7. NEW PATCH PANEL TO BE CAT6A 48 PORT FLAT (NON-ANGLED) PATCH PANEL AND COMPLY WITH EIA/TIA 310-E. PATCH PANELS TO HAVE HOLES FOR RJ45 JACKS ALIGNED IN TWO HORIZONTAL ROWS PER PANEL. PROVIDE HORIZONTAL AND VERTICAL CABLE MANAGERS. HORIZONTAL TO BE PLACED BETWEEN EACH 48 PORT PATCH PANEL AND VERTICAL PLACED BETWEEN EACH FOUR POST RACKS AND ON EACH END OF FINAL ASSEMBLY.

8. ALL PATCH PANELS SHALL BE LABELED PER IT-SOP #07-013.

9. INSTALL NEW LADDER RACK IN TR313A BLDG 1 AND CONNECT TO EXISTING.

10. NON-VA EQUIPMENT IN TR (GUEST WIRELESS SWITCHES, GUEST WIRELESS PANELS, BIOMEDICAL/PATIENT MONITORING SWITCHES, BIOMEDICAL/PATIENT MONITORING PANELS, ETC) ARE NOT INCLUDED IN THIS CONTRACT.

11. REPLACE ALL BIOMEDICAL CABLING THAT DOES NOT MEET CERNER EHRM GUIDELINES SHALL BE REPLACED AS PART OF THIS CONTRACT. ALL

BIOMEDICAL CABLING WILL BE ORANGE IN COLOR AS SHOWN ON THESE DRAWINGS.

12. ALL INSTALLED FIBER CABLE SHALL BE TERMINATED. UN-TERMINATED FUTURE CAPACITY FIBER CABLE NOT PERMITTED.

13. FIBER CONTRACTOR SHALL BE CERTIFIED SUMITOMO INSTALLER.

14. GOVERNMENT TO INSTALL SFP (IN EXISTING SINGLE MODE FIBERS AS REQUIRED) TO REDUCE THE SIGNAL STRENGTH DUE TO SHORT LENGTH OF PATH FOR BOTH NEW AND EXISTING FIBERS IN THE ENTIRE CAMPUS, INCLUDING 167T ROOM E110 AND BUILDING 168T ROOM 168T-00. SFP WILL BE

GOVERNMENT FURNISHED AND GOVERNMENT INSTALLED.

15. PROVIDE MOUNTING OF FIBER TERMINATION UNITS AT THE TOP OF EAST AND WEST EQUIPMENT RACK IN SERVER ROOM. THE UNIT SHALL ACCOMMODATE AT LEAST 48 (TOTAL) STRANDS OF SINGLE MODE FIBER, LC CONNECTORS. TERMINATION UNITS TO BE HIGHEST OEM APPROVED DENSITY OF FIBER LC TERMINATORS WHILE MAINTAINING HIGH LEVEL OF MANAGEABILITY. PROVIDE PROPER LC COUPLERS FOR EACH PAIR OF FIBER OPTIC CABLE LC

CONNECTORS.

16. PROVIDE AND INSTALLLC/LC PATCH CORDS OF MATCHING TYPE FOR EACH PAIR OF FIBER OPTIC STRANDS WITH CONNECTOR TO MATCH COUPLERS.

17. WORK WITH LOCAL OIT TO DEVELOP FIBER LABELING PLAN THAT IS COMPLIANT WITH ANSI 606-B AND CONSISTENT THROUGH OUT THE FACILITY. PRESENT THIS

PLAN AS PART OF 95% DESIGN PROCESS.

18. COPPER REPLACEMENT TO INCLUDE ALL CABLING RATED CAT5 AND BELOW THROUGHOUT THE FACILITY TO INCLUDE JACK/PATCH PANELS AT BOTH ENDS.

19. CAT5E AND GREATER, INCLUDING CORRESPONDING NETWORK HARDWARE AND TERMINATION UNITS MAY REMAIN IN PLACE WITH FOLLOWING EXCEPTION:

1. ALL COPPER CABLING ON FLOORS PROVIDING PERMANENT MOBILE OR TEMPORARY IMAGING SERVICES SHALL BE CAT 6A. SEE TABLE 2 ON T-001.

20. CAT3 CABLES THAT ARE USED FOR NON-VOIP PHONES SHALL REMAIN IN PLACE. THE REMAINDER OF THE CAT3 WILL BE DEMO AND REMOVED FROM EUDs TO TR

ROOM.

21. NEW CABLE PATHWAYS TO SUPPORT REPLACEMENT OF EXISTING DEFICIENT CABLES AND NEW CABLES ARE SHOWN. ANY DEVIATION FROM IT SHALL BE

DOCUMENTED AND SUBMITTED AS SHOP DRAWING.

22. ALL NEW CAT6A CABLES TO BE PLENUM RATED.

23. PROVIDE EACH NETWORK DROP WITH THREE PLENUM RATED CAT6A CABLES COLOR CODED IN GRAY/BLUE/WHITE WITH THE CORRESPONDING COLOR-CODED

GRAY/BLUE WHITE MODULAR JACK.

24. REPLACE JACKS AT EUDs JACK TO BE CAT6A COMPLIANT U.O.N.

25. PROVIDE CAT6A MODULAR JACKS CAPABLE OF ACCEPTING AND FUNCTIONING WITH OTHER MODULAR EG RJ11.

26. PROVIDE PATCH CORDS CONFORMING TO EIA/ECA 310-3 DIMENSIONS AND SUITABLE FOR MOUNTING IN STANDARD EQUIPMENT RACKS WITH 48 RJ45 JACKS

ALIGNED IN TWO HORIZONTAL ROWS PER PATCH PANEL.

27. CABLING SHALL BE COMBED AND DRESSED NEATLY.

28. LABEL ALL FACE PLATE PER IT-SOP #07-013 CABLE INSTALLATION LABELING AND TESTING.

29. CABLING FOR WAP AND DISTRIBUTED ANTENNA SYSTEM (DAS) ARE NOT PART OF THIS PROJECT.

30. PROVIDE DETAILED MOP. REFER TO SHEET G1003 FOR MINIMUM REQUIREMENTS FOR THE SEPARATE PHASING PLAN AND MOPS.

ABBREVIATIONS VA

EHRM ELECTRONIC HEALTH RECORD MODERNIZATION

CERNER INFORMATION TECHNOLOGY COMPANY

CEDT CERNER EHRM DEPLOYMENT TEAM

EUD END USER DEVICE

CIH CERTIFIED INDUSTRIAL HYGIENIST

LBVAMC LONG BEACH VA MEDICAL CENTER

MDF MAIN DISTRIBUTION FRAME

TR TELECOMMUNICATIONS ROOM

OIT OFFICE OF INFORMATION TECHNOLOGY

3D

3D

WALL MTD DATA OUTLET

W/3 CAT 6A DROPS

FLOOR MTD DATA OUTLET

W/3 CAT 6A DROPS

SEE DRAWING T-504

ABBREVIATIONS

SM

MM

SFP

ORL

OTDR

UTP

LAN

SINGLE MODE FIBER

MULTI MODE FIBER

SMALL FORM FACTOR PLUGGABLE TRANSCEIVER

OPTICAL RETURN LOSS

OPTICAL TIME DOMAIN REFLECTOMETER

UNSHIELDED TWISTED PAIR

LOCAL AREA NETWORK

EIA

TIA

OS1, OS2

OS2

ELECTRONIC INDUSTRIES ASSOCIATION

TELECOMMUNICATION INDUSTRY ASSOCIATION

TYPE OF SINGLE MODE FIBER

AIR BLOWN SINGLE MODE FIBER

1. PROVIDE EQUIPMENT SUBMITTALS AND SHOP DRAWINGS IN ACCORDANCE WITH THE SPECIFICATIONS AND THE PROJECT SCHEDULE. NO INSTALLATION SHALL PROCEED WITHOUT APPROVAL OF THE SHOP

DRAWINGS.

2. MINIMAL STORAGE WILL BE AVAILABLE ON THE CONSTRUCTION SITE. CABLING CONTRACTOR

RESPONSIBLE FOR RECEIVING AND STORING MATERIALS AND FOR COORDINATING MATERIALS

DELIVERY TO THE JOB-SITE.

3. COMMUNICATIONS CABLES INSTALLED SHALL BE INSTALLED IN ACCORDANCE WITH THE

REQUIREMENTS DETAILED HEREIN AND SHALL BE FREE OF KINKS, TWISTS, SHARP BENDS,

UNNECESSARY LOOPS OR WORKMANSHIP DEFECT.

4. PROPERLY SEAL WALL PENETRATIONS THROUGH FIRE RATED WALL & FLOOR USING EZ PATH

DETAILED ON T-504.

5. RUN OPEN CABLE FOR EACH SYSTEM IN SLEEVES, J-HOOKS DEDICATED FOR THE SYSTEM.

6. SEPARATE AND BUNDLE CABLE BY SYSTEM.

7. MAINTAIN EIA/ TIA RECOMMENDED SEPARATIONS BETWEEN CABLING OF DIFFERENT SYSTEMS. 6''

FROM LIGHT FIXTURES. 24'' FROM 480V & 12'' FROM 208V.

8. MAINTAIN RECOMMENDED SEPARATIONS BETWEEN CABLING AND INTERFERENCE PRODUCING

ELECTRICAL DEVICES SUCH AS POWER CABLING, ELECTRICAL PANELS, FLUORESCENT LIGHTS,

BALLAST RELAYS, ELECTRIC MOTORS, MOTOR CONTROLLERS, VFD, TRANSFORMERS AND OTHER

ELECTROMAGNETIC DEVICES. SEE NOTE 7.

9. WHERE CABLE IS OPEN ON J-HOOK SYSTEM, RUN PARALLEL OR PERPENDICULAR TO WALLS AND

SUPPORT A MINIMUM OF EVERY 5 FEET USING APPROVED J-HOOKS.

10. ALL CABLE HOOKS AND OTHER CABLE SUPPORT DEVICES SHALL BE ATTACHED TO THE BUILDING

STRUCTURE IN ACCORDANCE WITH CODES AND DETAILS SHOWN ON THESE SET OF DRAWINGS.

11. NO OPEN CABLE SHALL BE DRAPED OVER OR SUPPORTED ON PLUMBING, ELECTRICAL, MEDICAL GAS, FIRE SUPPRESSION, OR OTHER PIPING OR DUCTWORK.

12. ALL CABLES TO BE PLENUM RATED.

13. THE CABLE LENGTH FROM THE TERMINATION POINT IN TR TO EUD IN THE WORK AREA SHALL NOT

EXCEED 295FEET INDEPENDENT OF MEDIA TYPE.

14. VISUALLY INSPECT CONNECTIONS ON CABLE TO ENSURE PROPER COMPLIANCE WITH EIA/TIA 568B

TERMINATION.

15. INSPECT ALL EXPOSED PORTIONS OF THE CABLE TO INSURE A MINIMUM OF 4 TIMES THE CABLE

DIAMETER BEND RADIUS AT ANY POINT.

16. ENSURE NO CABLE BUNDLES OR TIE POINTS DISPLAY KINKS, SHARP BENDS, CREASING OR

DEFORMATION OF OUTER SHEATH OR SIGNS OF EXCESSIVE PULLING FORCE.

17. IN TR CABLES SHOULD BE COMBED AND DRESSED UP BEFORE BUNDLING AND USING VELCRO STRAPS.

ZIP TIES OR TWIST TIES SHALL NOT BE USED. STRAPS SHALL BE SPACED AT APPROPRIATE DISTANCE

TO ENSURE CABLES ARE HELD TOGETHER.

18. ON THE RACK THE CABLES SHOULD BE DIVIDED IN THE MIDDLE, WHERE HALF FLOWS TO THE LEFT

AND HALF FLOWS TO THE RIGHT.

19. ALL CABLING SHALL BE INSTALLED BY CABLE MANUFACTURER'S CERTIFIED

INSTALLER.

20. BEFORE ACCEPTANCE OF ANY NEWLY INSTALLED COMMUNICATIONS WIRING, THE CABLE WILL

UNDERGO SEVERAL LEVELS OF TESTING TO ENSURE THAT ALL MATERIALS AND INSTALLATION

CONFORM TO STANDARDS INCLUDED IN THE DRAWINGS AND SPECIFICATIONS. THIS WILL INCLUDE BOTH THE UTP AND FIBER OPTICS SYSTEMS. FAILURE TO MEET THE DRAWINGS AND SPECIFICATIONS REQUIREMENTS SHALL CONSTITUTE REASON TO REJECT THE INSTALLATION UNTIL ALL PROBLEMS

ARE SOLVED.

21. ALL RECORDED TESTING RESULTS SHALL REMAIN IN THE APPROPRIATE TR. TEST BOTH CABLES AND THEIR CORRESPONDING CONNECTING SYSTEMS AS A WHOLE UNIT TO ENSURE SYSTEM INTEGRITY.

22. TEST ALL FIBER OPTICS CABLE AND COMPONENTS COMPRISING THE BACKBONE SYSTEM. TEST ALL

FIBER STRAND IN BOTH DIRECTION. USE OTDR OPERATING AT BOTH 1310 AND 1550 NM

WAVELENGTHS.

23. PHYSICAL LABELING FOR ALL CABLES AND RELATED COMPONENTS IS REQUIRED COMPONENTS WILL DEPEND HEAVILY ON ADHERING TO A LOGICAL LABELING SCHEME TO ENABLE EXPEDIENT PATCH

PANEL, DATA JACK AND SWITCH PORT IDENTIFICATION.

24. PROVIDE ALL NEW CABLING IN THE BUILDING S WITH AN AS-BUILT ELECTRONIC AND PAPER FORMATS, FOR THE CABLE PLANT. EACH TR WIRING CLOSETS CABLE PLANT AS-BUILT SHALL BE INSTALLED IN A

FOLDER ON THE BACK OF THE DOOR SECURED IN A HOLDER ATTACHED TO THE DOOR.

25. CABLING DIAGRAM: SUBMIT, FOR APPROVAL, A COMPLETE CABLING DIAGRAM. THE DIAGRAM SHALL BE BASED ON THE DRAWING INCLUDED IN THE CONSTRUCTION DOCUMENTS. IT SHALL BE UPDATED TO SHOW QUANTITIES AND PART NUMBERS FOR ALL COMPONENTS INCLUDING PATCH PANELS, CABLE, SERVER CABINETS AND EQUIPMENT RACKS AND ALL OTHER ASSOCIATED COMPONENTS. INCLUDE THE

FOLLOW:

1). DETAIL AND ELEVATION DRAWINGS: PROVIDE TR RACK ELEVATION, ENLARGED TR

ROOM LAYOUT.

2). BUILDING COMPOSITE FLOOR PLANS: PROVIDE BUILDING FLOOR PLANS SHOWING END USER DEVICE (EUD) OUTLET LOCATIONS AND CONFIGURATION, TYPES OF JACKS, DISTANCE FOR EACH

CABLE, AND CABLE ROUTING LOCATIONS.

3). FLOOR PLANS TO INCLUDE:

a. FINAL ROOM NUMBERS AND ACTUAL BACKBONE CABLING AND PATHWAY LOCATIONS

(HORIZONTAL AND VERTICAL) AND LABELING.

b. RISER FLOOR PENETRATION / DATA POLE LOCATION AFTER SCANNING THE FLOOR FOR

REBARS.

c. INPUTS AND OUTPUTS OF EQUIPMENT IDENTIFIED ACCORDING TO LABELS INSTALLED ON

CABLES AND EQUIPMENT.

d. DEVICE LOCATIONS WITH LABELS.

e. EZ PATH SLEEVES.

f. WIRING DIAGRAM.

g. LABELING AND ADMINISTRATION DOCUMENTATION.

METHOD OF PROCEDUREMOP

SPECIFIC NOTE/

REFERENCE NOTE

DESCRIPTION OF THE PROJECT

FIRE PROTECTION WALL SYMBOLS

POWER SYMBOLS

GROUND BUS BAR (TGB)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i l e

P a t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date: PM EW/JB

A

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

MOUNTEDMTD

THRU THROUGH

- T -

WAP WIRELESS ACCESS POINT

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

3D

CEILING PENDANT

MOUNTED DATA OUTLET

W/3CAT 6A DROPS

TABLES

T-002

FAILED SINGLE MODE FIBER

STRAND LIST

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date: PM EW/JB

A

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

164 166165

TELECOMMUNICATIONS SITE PLAN (REFERENCE ONLY)

SCALE: 1/128" = 1' - 0" NORTH

TS-001

TELECOMMUNICATIONS SITE PLAN

AND DRAWING LIST

TELECOMMUNICATION DRAWING LIST

T-001 TELECOMMUNICATIONS SYMBOL LIST, GENERAL NOTES ABBREVIATIONS AND FIBER

INFRASTRUCTURE RISER

T-002 FAILED SINGLE MODE FIBER STRAND LIST

TS-001 TELECOMMUNICATIONS SITE PLAN AND DRAWING LIST

1.T-101 TELECOMMUNICATIONS BASEMENT FLOOR

1.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

1.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

1.T-131 TELECOMMUNICATIONS THIRD FLOOR PLAN

1.T-141 TELECOMMUNICATIONS FOURTH FLOOR PLAN

1.T-151 TELECOMMUNICATIONS FIFTH FLOOR PLAN

2.T-101 TELECOMMUNICATIONS BASEMENT FLOOR

2.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

2.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

2.T-131 TELECOMMUNICATIONS THIRD FLOOR PLAN

5C.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

6.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

7.T-101 TELECOMMUNICATIONS BASEMENT FLOOR

7.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

7.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

7.T-131 TELECOMMUNICATIONS THIRD FLOOR PLAN

8.T-101 TELECOMMUNICATIONS BASEMENT FLOOR

8.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

8.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

8.T-131 TELECOMMUNICATIONS THIRD FLOOR PLAN

50.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

126.T-101 TELECOMMUNICATIONS BASEMENT FLOOR

126.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

126.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

126.T-131 TELECOMMUNICATIONS THIRD FLOOR PLAN

126.T-141 TELECOMMUNICATIONS FOURTH FLOOR PLAN

126.T-151 TELECOMMUNICATIONS FIFTH FLOOR PLAN

126.T-161 TELECOMMUNICATIONS SIXTH FLOOR PLAN

126.T-171 TELECOMMUNICATIONS SEVENTH FLOOR PLAN

126.T-181 TELECOMMUNICATIONS EIGHTH FLOOR PLAN

126.T-191 TELECOMMUNICATIONS NINTH FLOOR PLAN

126.T-1101 TELECOMMUNICATIONS TENTH FLOOR PLAN

126.T-1111 TELECOMMUNICATIONS ELEVENTH FLOOR PLAN

126A.T-101 TELECOMMUNICATIONS BASEMENT FLOOR

126A.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

126A.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

126A.T-131 TELECOMMUNICATIONS THIRD FLOOR PLAN

138.T-101 TELECOMMUNICATIONS BASEMENT FLOOR

138.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

138.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

149.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

149.T-112 TELECOMMUNICATIONS FIRST FLOOR PLAN

150.T-101 TELECOMMUNICATIONS BASEMENT FLOOR

150.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

150.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

160.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

161.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

164.T-111 TELECOMMUNICATIONS FIRST FLOOR

164.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

164.T-131 TELECOMMUNICATIONS THIRD FLOOR PLAN

165.T-101 TELECOMMUNICATIONS BASEMENT FLOOR

165.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

165.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

166.T-111 TELECOMMUNICATIONS FIRST FLOOR PLAN

166.T-121 TELECOMMUNICATIONS SECOND FLOOR PLAN

1.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 103

1.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

1.T-402 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 313 – DEMO WORK

1.T-402A TELECOMMUNICATIONS RACK ELEVATIONS

1.T-403 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 313 – NEW WORK

2.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM N108A

2.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

5C.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM E108

5C.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

6.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 34

6.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

8.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 111

8.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

50.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM101B

50.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-401 TELECOMMUNICATIONS ENLARGED PLAN MDF ROOM W50

126.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-402 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM W128V

126.T-402A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-403 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM W232

126.T-403A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-404 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM W220

126.T-404A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-405 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM SERVER ROOM E221

126.T-405A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-405B TELECOMMUNICATIONS RACK ELEVATIONS

126.T-406 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 321

126.T-406A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-407 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 326A

126.T-407A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-408 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM W428

126.T-408A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-409 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM W416

126.T-409A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-410 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM W521A

126.T-410A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-411 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM W520B

126.T-411A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-412 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 627

126.T-412A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-413 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 727

126.T-413A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-414 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 827

126.T-414A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-415 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 813B

126.T-415A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-416 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM W923C

126.T-416A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-417 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM W11211

126.T-417A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-418 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM W1027

126.T-418A TELECOMMUNICATIONS RACK ELEVATIONS

126.T-419 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM E1013B

126.T-419A TELECOMMUNICATIONS RACK ELEVATIONS

126A.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM OP-04

126.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

126A.T-402 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 1N111

126.T-402A TELECOMMUNICATIONS RACK ELEVATIONS

126A.T-403 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 2N107

126.T-403A TELECOMMUNICATIONS RACK ELEVATIONS

126A.T-404 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM OP-301B

126.T-404A TELECOMMUNICATIONS RACK ELEVATIONS

138.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 139A

138.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

149.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 109A

149.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

149.T-402 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM T128A

149.T-402A TELECOMMUNICATIONS RACK ELEVATIONS

150.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM R-6

150.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

150.T-402 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM T128A

150.T-402A TELECOMMUNICATIONS RACK ELEVATIONS

150.T-403 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM U120

150.T-403A TELECOMMUNICATIONS RACK ELEVATIONS

150.T-404 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM V110A

150.T-404A TELECOMMUNICATIONS RACK ELEVATIONS

160.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 126

160.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

161.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 100A

161.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

164.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 140

164.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

164.T-402 TELECOMMUNICATIONS ENLARGED PLAN ROOM 189

164.T-402A TELECOMMUNICATIONS RACK ELEVATIONS

164.T-403 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 223

164.T-403A TELECOMMUNICATIONS RACK ELEVATIONS

164.T-404 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM 323

164.T-404A TELECOMMUNICATIONS RACK ELEVATIONS

165.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM C135

165.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

165.T-402 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM C211

165.T-402A TELECOMMUNICATIONS RACK ELEVATIONS

166.T-401 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM F121

166.T-401A TELECOMMUNICATIONS RACK ELEVATIONS

166.T-402 TELECOMMUNICATIONS ENLARGED PLAN TR ROOM F208

166.T-402A TELECOMMUNICATIONS RACK ELEVATIONS

T-501 TELECOMMUNICATIONS DETAILS

T-502 TELECOMMUNICATIONS DETAILS

T-503 TELECOMMUNICATIONS DETAILS

T-504 TELECOMMUNICATIONS DETAILS

T-601 INFRASTRUCTURE FIBER RISER BLDG 8, 161 AND 126

LEGEND

BUILDING IN SCOPE

BLDG.

BLDG.

126A

MDF

W50

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date: PM EW/JB

A

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

C

D

20-SCE-04

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

0' 64' 128' 256'

SCALE: 1/128" = 1'-0"

ELEVATOR

MACHINE RM

B-031A

MECH RM

STORAGE

NOURISH

B-028

CART WASHER

AREA

CO

RR

ID

OR

CC

-B

-1

CORRIDOR

CC-B-5

CO

NN

EC

TI

ON

CO

RR

ID

OR

CC

-B -6

CO

RR

ID

OR

CC

-B

-1

ENTRANCE

MED MEDIA

ENTRANCE

MAIL RM

BOILER

CHAMBER

STORAGE

TRASH

COMPACTOR

AREA

TRASH

COMPACTOR WELL

LAB STORAGE

B-037

ELEVATOR

S-10

ELEVATOR

S-9

EMS

SUPV

OFFICE

EMS SUPV

OFFICE

B-034

PHARMACY

STORAGE

B-015

STORAGE

B-016

GENERAL

STORAGE

B-017

B-019B

CHIEFS OFFICE

B-019A

B-019

TELE CLOSET

STAIR

CORRIDOR

C-B-9

ELEVATOR

P-7

ELEVATOR

P-8

WORK SPACE

B-22B

SEC/RECEPT

B-029

PASSENGER

ELEVATOR LOBBY

PHOTO STUDIO

B-021

FINISHING

RM

B-22D

STORAGE

B-22A

COMPUTER

RM

B-22C

OFFICE

B-22E

CLASS RM

B-22F

CO

RR

ID

OR

C- B-

8 CLASS RM

B-23

CONTROL RM

B-23A

GENERAL

STORAGE

B-24

MED/GRAPHICS DESIGN

OFFICE

B-25

GRAPHIC

ARTIST

B-26

EQUIP

CHECKOUT

B-027MI

CR

OS

CO

PE

RM

B-

7BCHIEF

B-029A

HAC

STORAGE

B-031

GENERAL

STORAGE

B-013

GENERAL

STORAGE

B-012

ENV CARE

SUPV

OFFICE

B-011

RE

CO

RD

MG

MT

OF

FI

CE

B-

9C

BOILER RM

B-014

CO

RR

ID

OR

CC

-B

-1

4 SUPPLY RM

35B

35A

STORAGE

SUPPLY AND

EQUIPMENT

ISSUE

MAIL RM

HAC STORAGE

ELECTRICAL

PANEL

SVC RM ELEVATOR

LOBBY

VE

RY

D

AR

K

RM

B-

7A

B-014A

B-014B

CENTER

DATA CABLES GOING

UP TO FLOOR ABOVE

SEE 1.T-111

EXISTING

TDU-01-31A

ROOM 31A

SEE

7.T-101

FOR

CONTINUATION

NEW 2 CELL TUBE

W/ 24 STRAND SINGLE

MODE FIBER OS2 (SUMITOMO)

ABOVE CEILING

(FROM MDF W50 TO TR 100A BLDG. 101)

DATA CABLES GOING

UP TO FLOOR ABOVE

SEE 1.T-111

SCALE: 1/8" = 1' - 0" NORTH

1.T-101

TELECOMMUNICATIONS

BASEMENT FLOOR PLAN

BUILDING 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

SCALE: 1/8" = 1'-0"

0' 4' 8' 16'

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

SCALE: NONE

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A

COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD

OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN

A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH

EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE

MANUFACTURER’S CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD SHALL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE SHALL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACKS WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVING EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

RECOMMENDED ROUTING OF NEW CAT6A BUNDLED CABLE

ON PENDANT MOUNTED U-HOOKS. SEE DETAILS ON

STRUCTURAL DRAWING.

NEW PLENUM RATED 3-CAT6A (GRAY, BLUE WHITE) DROP IN

FREE AIR WITHIN WALL CAVITY. SUPPORT USING WALL

MOUNTED J-HOOKS OR SUSPENDED FROM STRUCTURE

ABOVE. SEE DETAIL ON DRAWINGS T-501, T-503 & T-504.

NEW FACEPLATE WITH GRAY, BLUE AND WHITE CAT6A

COMPLIANT RJ45.

NOT USED.

FOR FLOOR MOUNTED DATA OUTLET PROVIDE TEMPORARY

DATA CABLING. REMOVE EXISTING CABLE FROM UNDER

FLOOR FEED & INSTALL NEW RJ45 JACK.

PROVIDE MULTI RACEWAY MTD EUD AT LAB BENCHES AND

TEMPORARY CABLING. REMOVE EXISTING CABLE FROM

MULTI RACEWAY & INSTALL NEW CAT 6A CABLES &

ASSOCIATED RJ 45 JACKS.

PROVIDE NEW EUD AT EXISTING MULTIRACEWAY. PROVIDE

TEMPORARY CABLING. REMOVE EXISTING CABLE FROM

MULTIRACEWAY AND INSTALL NEW CAT6A CABLES AND

ASSOCIATED RJ45 JACKS AND FACEPLATE.

FOR PREWIRED SYSTEM FURNITURE PROVIDE TEMPORARY

CABLE TO EUD AT SYSTEMS FURNITURE. PULL OLD CABLES OUT

AND INSTALL NEW CABLES AND RJ45 JACK (CAT 6A COMPLIANT

AND ASSOCIATED NEW FACEPLATE).

BEFORE DISCONNECTING PROVIDE TEMPORARY DATA DROP FOR

NURSE STATION. REMOVE EXISTING CABLE AND INSTALL NEW IN

THE EXISTING CONDUIT ABOVE THE CEILING O FLOOR BELOW.

EXISTING FIBER BOX TDU-126-E221 WITH TUBE CELL GOING TO

MDF FROM W50. INSTALL 2-24 STRAND SINGLE MODE AIR BLOWN

FIBER FROM MDF TO THIS BOX AND EXTEND 24 STARND TO EACH

OF THE EAST AND WEST RACKS. TERMINATE IN FIBER PANEL

USING LC CONNECTOR.

(NOT ALL KEY NOTES ARE APPLICABLE TO THIS SHEET)

KEY NOTES

7.

8.

9.

STAFF

WOMEN

112A

MECH

SHAFT

DOC

CONN

CORRIDOR

MC-C6

S101A

STAIR

CORRIDOR

C-1-2

CORRIDOR

C-1-4

CORRIDOR

C-1-5

CORRIDOR

C-1-6

CORRIDOR

C-1-1

W

AI

TI

NG

A

RE

A

MEN REST

RM

N104

HAC

N103

MECH

SHAFT

CLOSET

IT

STORAGE

N166

SVC ELEVATOR

LOBBY

ELEVATOR

S-9

ELEVATOR

S-10

NURSE CASE

MGR

S116

NURSE CASE

MGR

116A

NURSE

S117

STAFF LOUNGE

GROUP RM

PSYCH

RN CARE

CO-ORDR OFFICE

118A

MEDICATION

RM

DOC OFFICE

S120

WAITING AREA

S123

NURSE

PSYCH

S122

PSYCH

OFFICE

S124

TELECOM

STAIR

CORRIDOR

C-1-3

ELEVATOR

P-8

ELEVATOR

P-7

PASSENGER

ELEVATOR

ELOBBY

RN CARE

CO-ORDR

S101L

CONFERENCE

RM

S101M

OFFICE

S101K

CASE MGR

OFFICE

S101J

EXAM/

TREATMENT RM

S102G S

PATHOLOGIST

TRAINEE

S102F

STAIR

SPEECH

PATHOLOGIST

OFFICE

S102D

WAITING

S102C

CHIEF

SPEECH

PATHOLOGY

S102B

SPEECH

PATHOLOGIST

S102A

STAFF

PSYCHIATRIST

S101H

OFFICE

S101G

OFFICE

S101F

DOCTORS OFFICE

S101E

NURSE

CASE MGR

OFFICE

S101D

WAITING

AREA

S101

DIABETIC

S101C

ADMIN

NURSE

OFFICE

S101B

HAC

SOCIAL

WORKER

COUPLES

OFFICE

S105

OF

FI

CE

S1

-1EXAM RM

S106

NURSE

PRACTITIONER

S107

STAFF

PSYCHATRIST

S108

STAFF

PSYCHIATRISTS

EXAM RM

S109

OFFICE

S110

HAC

SOCIAL

WORKER

OFFICE

S114

OFFICE

S114A

PRIMARY CARE

NURSE

PRACTITIONER

S113

STAFF

MEN

NO 3

NO 2

FE

SOUND

BOOTH

CLASS RM

FAC

PEER

SUPPORT

OFFICE

S102E

IT

STORAGE

N166B

S123A

CENTERFEC

CORRIDOR

EMS SVC

N166A

C1-3A

SOLARIUM

CORRIDOR

C-1-7

DATA CABLES UP TO

FLOOR ABOVE

SEE 1.T-121

TO BLDG 7 SEE DRAWING

7.T-111, CAT 6A CABLES FROM BLDG. 7

TO TR 103 (ABOVE CEILING).

T-501

CAT 6A CABLES FROM BLDG. 7

FROM FLOOR ABOVE. SEE

DRAWING 1.T-121.

CAT 6A CABLES FROM BLDG. 2

FROM FLOOR ABOVE. SEE

DRAWING 1.T-121

FOR CONTINUATION

DATA CABLES UP TO

FLOOR ABOVE

SEE 1.T-121

DATA CABLES

FROM FLOOR

BELOW TO

FLOOR ABOVE

SEE 1.T-101 &

1.T-121 & DETAIL

T-501

DATA CABLES FROM FLOOR

BELOW TO FLOOR ABOVE

SEE 1.T-101 & 1.T-121 & DETAIL

SCALE: 1/8" = 1' - 0" NORTH

1.T-111

TELECOMMUNICATIONS FIRST

FLOOR PLAN

SEE DETAIL 1

SHEET 1.T-401

FOR ENLARGED PLAN

BUILDING 1

TR:103

SEE SHEET 2.T-111

FOR CONTINUATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

SCALE: 1/8" = 1'-0"

0' 4' 8' 16'

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A

COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD

OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN

A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH

EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE

MANUFACTURER’S CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD SHALL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE SHALL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACKS WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVING EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

RECOMMENDED ROUTING OF NEW CAT6A BUNDLED CABLE

ON PENDANT MOUNTED U-HOOKS. SEE DETAILS ON

STRUCTURAL DRAWING.

NEW PLENUM RATED 3-CAT6A (GRAY, BLUE WHITE) DROP IN

FREE AIR WITHIN WALL CAVITY. SUPPORT USING WALL

MOUNTED J-HOOKS OR SUSPENDED FROM STRUCTURE

ABOVE. SEE DETAIL ON DRAWINGS T-501, T-503 & T-504.

NEW FACEPLATE WITH GRAY, BLUE AND WHITE CAT6A

COMPLIANT RJ45.

NOT USED.

FOR FLOOR MOUNTED DATA OUTLET PROVIDE TEMPORARY

DATA CABLING. REMOVE EXISTING CABLE FROM UNDER

FLOOR FEED & INSTALL NEW RJ45 JACK.

PROVIDE MULTI RACEWAY MTD EUD AT LAB BENCHES AND

TEMPORARY CABLING. REMOVE EXISTING CABLE FROM

MULTI RACEWAY & INSTALL NEW CAT 6A CABLES &

ASSOCIATED RJ 45 JACKS.

PROVIDE NEW EUD AT EXISTING MULTIRACEWAY. PROVIDE

TEMPORARY CABLING. REMOVE EXISTING CABLE FROM

MULTIRACEWAY AND INSTALL NEW CAT6A CABLES AND

ASSOCIATED RJ45 JACKS AND FACEPLATE.

FOR PREWIRED SYSTEM FURNITURE PROVIDE TEMPORARY

CABLE TO EUD AT SYSTEMS FURNITURE. PULL OLD CABLES OUT

AND INSTALL NEW CABLES AND RJ45 JACK (CAT 6A COMPLIANT

AND ASSOCIATED NEW FACEPLATE).

BEFORE DISCONNECTING PROVIDE TEMPORARY DATA DROP FOR

NURSE STATION. REMOVE EXISTING CABLE AND INSTALL NEW IN

THE EXISTING CONDUIT ABOVE THE CEILING O FLOOR BELOW.

EXISTING FIBER BOX TDU-126-E221 WITH TUBE CELL GOING TO

MDF FROM W50. INSTALL 2-24 STRAND SINGLE MODE AIR BLOWN

FIBER FROM MDF TO THIS BOX AND EXTEND 24 STARND TO EACH

OF THE EAST AND WEST RACKS. TERMINATE IN FIBER PANEL

USING LC CONNECTOR.

(NOT ALL KEY NOTES ARE APPLICABLE TO THIS SHEET)

KEY NOTES

7.

NOW AN OFFICE

FEC

PH

AR

MA

CY

VE

ND

OR

CLOSET

200X

EP

200J

ST

OR

AG

E

0W

0V

CORRIDOR

C2-5

CO

RR

ID

OR

C2 -4

VISUAL INFO

SPECIALIST

OFFICE

CORRIDOR

C2-3

STUDENT

CO-ORDR OFFICE

NURSE

OFFICE

INPATIENT

CLINICAL

PHARMACY

RESIDENT

218B

INPATIENT

CLINICAL SUP

RESIDENCY

PROG DIR

218A

STERILE

PROCESSING

CORRIDOR

ELEVATOR

S-10

ELEVATOR

S-9

MECH

SHAFT

CO

RR

ID

OR

STORAGE

232A

HAC

GENERAL

STORAGE

PHARMACY

AND CLINICAL

SUPPORT

SVCS

BUSINESS

MGR OFFICE

ADMIN ASST

OFFICE

PRAYER AND

MEDITATION RM

NUTRITION

OFFICE

225A

MEN TOILET

FAC

INFORMATICS

PHARMACIST

WOMEN

TIOLET

HAC

CLOSET

CORRIDOR

C2-1

PASSENGER

ELEVATOR

LOBBY

EL

EV

AT

OR

P-

EL

EV

AT

OR

P-

CORRIDOR

C2-6

CORRIDOR

C2-8

CO

RR

ID

OR

C2 -7

QA/QC COORD

OFFICE

200A

LAB / OPERATIONS

MGR OFFICE

200B

SUPPLY

TECHNICIAN

OFFICE

200C

CO

NN

EC

TI

ON

CO

RR

ID

OR

MC

-C

CO

RR

ID

OR

C2 -2

ELECTRIC

CLOSET

CL

OS

ET

2A

RED CROSS

VOLUNTEERS

BREAK RM

223A

STAIR

NO 3

PHARMACY/ CONFERENCE

BREAKROOM

PHARMACY

ADMINISTRATIVE

OFFICE

COPY

219H

CONFERENCE RM

CORRIDOR

C2-10

ACTING

CHIEF OF

PATHOLOGY

200Z

STAIR

PGM SUPPORT

OFFICE

200Y

CONFERENCE

RM

200U

CO

RR

ID

OR

C2 -1

PATHOLOGIST

OFFICE

200T

PATHOLOGIST

OFFICE

200S

NURSING OFFICER

OF THE DAY (NOD)

OFFICE

ST

OR

AG

E

3MECH

SHAFT

CHIEF OF

PATHOLOGY

OFFICE

200D

CLOSET

200G

SECY

OFFICE

200E

MULTI-HEADED

MICROSCOPE RM

200H

COPY/ BREAK RM

200F

PATHOLOGY

RESIDENTS

AREA

200K

PATHOLOGY

TRANSCRIPTION

RECORD RM

200L

MI

CR

OS

CO

PE

RM 20

0M

PATHOLOGIST

OFFICE

200N

PATHOLOGIST

OFFICE

200P

PATHOLOGIST

OFFICE

200Q

PATHOLOGIST

OFFICE

200R

STAIR

NO 2

EQ

UI

PM

EN

T

ST

OR

AG

E

ALCOVE

FAC

STORAGE

201P

202P

P

CENTER

SVC ELEVATOR LOBBY

203A

DATA CABLES FROM

FLOOR BELOW AND

THIS FLOOR UP TO

3RD FLOOR TR 313

SEE 1.T-111, 1.T-131

AND 1.T-403

CAT 6A CABLES FROM 3RD

FLOOR ABOVE. SEE 1.T-131 FOR

CONTINUATION.

CAT 6A CABLES DOWN

TO TR 103 ON 1ST

FLOOR. SEE 1.T-111

FOR CONTINUATION

T-501

SEE 2.T-121

FOR CONTINUATION

DATA CABLES FROM FLOOR

BELOW TO CEILING SPACE OF

THIS LEVEL SEE 1.T-111 AND

DETAIL

T-501

DATA CABLES FROM FLOOR BELOW & THIS FLOOR UPTO

THIRD FLOOR SEE 1.T-131 AND DETAIL

T-501

DATA CABLES FROM FLOOR

BELOW UPTO CEILING OF

THIRD FLOOR ABOVE SEE

1.T-131 AND DETAIL

T-501

DATA CABLES FROM FLOOR

BELOW TO CEILING SPACE OF

THIS FLOOR SEE 1.T-111 AND

DETAIL

T-501

DATA CABLES FROM FLOOR

BELOW TO CEILING SPACE OF

THIS FLOOR SEE 1.T-111 AND

DETAIL

T-501

SCALE: 1/8" = 1' - 0" NORTH

1.T-121

TELECOMMUNICATIONS SECOND

FLOOR PLAN

BUILDING 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

SCALE: 1/8" = 1'-0"

0' 4' 8' 16'

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A

COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD

OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN

A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH

EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE

MANUFACTURER’S CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD SHALL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE SHALL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACKS WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVING EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

RECOMMENDED ROUTING OF NEW CAT6A BUNDLED CABLE

ON PENDANT MOUNTED U-HOOKS. SEE DETAILS ON

STRUCTURAL DRAWING.

NEW PLENUM RATED 3-CAT6A (GRAY, BLUE WHITE) DROP IN

FREE AIR WITHIN WALL CAVITY. SUPPORT USING WALL

MOUNTED J-HOOKS OR SUSPENDED FROM STRUCTURE

ABOVE. SEE DETAIL ON DRAWINGS T-501, T-503 & T-504.

NEW FACEPLATE WITH GRAY, BLUE AND WHITE CAT6A

COMPLIANT RJ45.

NOT USED.

FOR FLOOR MOUNTED DATA OUTLET PROVIDE TEMPORARY

DATA CABLING. REMOVE EXISTING CABLE FROM UNDER

FLOOR FEED & INSTALL NEW RJ45 JACK.

PROVIDE MULTI RACEWAY MTD EUD AT LAB BENCHES AND

TEMPORARY CABLING. REMOVE EXISTING CABLE FROM

MULTI RACEWAY & INSTALL NEW CAT 6A CABLES &

ASSOCIATED RJ 45 JACKS.

PROVIDE NEW EUD AT EXISTING MULTIRACEWAY. PROVIDE

TEMPORARY CABLING. REMOVE EXISTING CABLE FROM

MULTIRACEWAY AND INSTALL NEW CAT6A CABLES AND

ASSOCIATED RJ45 JACKS AND FACEPLATE.

FOR PREWIRED SYSTEM FURNITURE PROVIDE TEMPORARY

CABLE TO EUD AT SYSTEMS FURNITURE. PULL OLD CABLES OUT

AND INSTALL NEW CABLES AND RJ45 JACK (CAT 6A COMPLIANT

AND ASSOCIATED NEW FACEPLATE).

BEFORE DISCONNECTING PROVIDE TEMPORARY DATA DROP FOR

NURSE STATION. REMOVE EXISTING CABLE AND INSTALL NEW IN

THE EXISTING CONDUIT ABOVE THE CEILING O FLOOR BELOW.

EXISTING FIBER BOX TDU-126-E221 WITH TUBE CELL GOING TO

MDF FROM W50. INSTALL 2-24 STRAND SINGLE MODE AIR BLOWN

FIBER FROM MDF TO THIS BOX AND EXTEND 24 STARND TO EACH

OF THE EAST AND WEST RACKS. TERMINATE IN FIBER PANEL

USING LC CONNECTOR.

(NOT ALL KEY NOTES ARE APPLICABLE TO THIS SHEET)

KEY NOTES

7.

8.

9.

SCALE: NONE

CL CL

4 x D

CORE DRILL WITH

DIAMETER D

VESTIBULE

316A

FEMALE TOILET

ELECTRICAL

CLOSET

309A

TOILET

RM

327B

TELE-COMM

CLOSET

315A

302F

DRESSING

RM

323A

LOCKER

327A

CORRIDOR

CORRIDOR

C3-2

CO

RR

ID

OR

C3 -5

CO

RR

ID

OR

C3 -5

A

CORRIDOR

C3-3

CORRIDOR

C3-4

CORRIDOR

C3-4A

STERILE SUPPLY RM

322B

CO

NN

EC

TI

NG

CO

RR

ID

OR

MC

-C

ELEVATOR LOBBY

TOILET

(LIBRARY)

BREAK RM

335C

EL

EV

AT

OR

EL

EV

AT

OR

LIBRARY

STORAGE

335B

LIBRARY

OFFICE

LIBRARY

OFFICE

335A

MALE

TOILET

PASSENGER

ELEVATOR

LOBBY

301D

ORTHO NURSES

OFFICE

301A

ORTHO

STORAGE

301B

ELECTRICAL

RM

301E

ORTHO

WAITING

AREA

301C

ORTHO

RECEPTION

AREA

ORTHO

PHYSICIAN

OFFICE

EQUIPMENT

STORAGE

ORTHO

CHIEFS

OFFICE

OR

TH

O

SE

CR

EA

TA

RY

OF

FI

CE

5 ORTHO

LIBRARY RM

STAIR

ORTHO

CONFERENCE

RM

ORTHO

EXAM RM

307A

ORTHO

EXAM RM

ORTHO

EXAM RM

308A

ORTHO

EXAM RM

ORTHO

CAST RM

ORTHO

STORAGE

310A

ORTHO

CAST RM

310B

ORTHO DR

OFFICE

311CLOSET

CASE MGR

OFFICE

CATH LAB

WAITING RM

CATH

LAB

OFFICE

314AASST CHIEF

CARDIAC CRITICAL

CARE UNIT

OFFICE

CHIEF CARDIAC

CATH LAB

319A

WORK

STATION

ASST CHIEF

CARDIAC

319B

SOILED

UTILITY

320CONTROL RM

CARDIAC

CATH LAB

EQUIP

RM

322A

STAIR

ELEVATOR

ELEVATOR

ELECTRICAL

VAULT RM

TELE RM

STAIR

BREAK RM

EQUIPMENT

STORAGE

326A

CONFERENCE RM

COPIER

RM

OFFICE

OFFICE

324A

ENTRANCE

REST

ROOM

323D

HAC

323C

CH

IE

F

CA

RD

IO

LO

GY

OF

FI

CE

3B

NO 2

NO 3

P-8

P-7

S-

S-

ALCOVE

323E

TEL

FAC

TELE-COMM

FEC

325A

CENTER

SHAFT

CO

RR

ID

OR

C3 -6

A

CORRIDOR

C3-6

SHAFT

2 2

ABOVE CEILING 3RD FLOOR

DATA CABLES FROM FLOOR

BELOW TO CEILING OF THIS

FLOOR SEE 1.T-121 AND DETAIL

T-501

CAT 6A CABLES FROM BLDG. 7

TO TR 103 (ABOVE CEILING)

TO BLDG. 7 SEE DRAWING

7.T-131

TO NEW

PATCH

PANEL

DATA CABLES FROM FOURTH

FLOOR TO CEILING OF 3RD

FLOOR SEE 1.T-141

T-501

DATA CABLES FROM FOURTH

FLOOR TO CEILING OF THIS

FLOOR SEE 1.T-141

DATA CABLES FROM FOURTH

FLOOR TO CEILING OF THIS

FLOOR SEE 1.T-121 AND DETAIL

T-501

DATA CABLES FROM

FLOOR ABOVE TO

CEILING SPACE OF THIS

FLOOR SEE 1.T-141

SCALE: 1/8" = 1' - 0" NORTH

1.T-131

TELECOMMUNICATIONS THIRD

FLOOR PLAN

SEE DETAIL 1

SHEET 1.T-403

FOR ENLARGED PLAN

BUILDING 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

SCALE: 1/8" = 1'-0"

0' 4' 8' 16'

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A

COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD

OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN

A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH

EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE

MANUFACTURER’S CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD SHALL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE SHALL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACKS WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVING EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

RECOMMENDED ROUTING OF NEW CAT6A BUNDLED CABLE

ON PENDANT MOUNTED U-HOOKS. SEE DETAILS ON

STRUCTURAL DRAWING.

NEW PLENUM RATED 3-CAT6A (GRAY, BLUE WHITE) DROP IN

FREE AIR WITHIN WALL CAVITY. SUPPORT USING WALL

MOUNTED J-HOOKS OR SUSPENDED FROM STRUCTURE

ABOVE. SEE DETAIL ON DRAWINGS T-501, T-503 & T-504.

NEW FACEPLATE WITH GRAY, BLUE AND WHITE CAT6A

COMPLIANT RJ45.

NOT USED.

FOR FLOOR MOUNTED DATA OUTLET PROVIDE TEMPORARY

DATA CABLING. REMOVE EXISTING CABLE FROM UNDER

FLOOR FEED & INSTALL NEW RJ45 JACK.

PROVIDE MULTI RACEWAY MTD EUD AT LAB BENCHES AND

TEMPORARY CABLING. REMOVE EXISTING CABLE FROM

MULTI RACEWAY & INSTALL NEW CAT 6A CABLES &

ASSOCIATED RJ 45 JACKS.

PROVIDE NEW EUD AT EXISTING MULTIRACEWAY. PROVIDE

TEMPORARY CABLING. REMOVE EXISTING CABLE FROM

MULTIRACEWAY AND INSTALL NEW CAT6A CABLES AND

ASSOCIATED RJ45 JACKS AND FACEPLATE.

FOR PREWIRED SYSTEM FURNITURE PROVIDE TEMPORARY

CABLE TO EUD AT SYSTEMS FURNITURE. PULL OLD CABLES OUT

AND INSTALL NEW CABLES AND RJ45 JACK (CAT 6A COMPLIANT

AND ASSOCIATED NEW FACEPLATE).

BEFORE DISCONNECTING PROVIDE TEMPORARY DATA DROP FOR

NURSE STATION. REMOVE EXISTING CABLE AND INSTALL NEW IN

THE EXISTING CONDUIT ABOVE THE CEILING O FLOOR BELOW.

EXISTING FIBER BOX TDU-126-E221 WITH TUBE CELL GOING TO

MDF FROM W50. INSTALL 2-24 STRAND SINGLE MODE AIR BLOWN

FIBER FROM MDF TO THIS BOX AND EXTEND 24 STARND TO EACH

OF THE EAST AND WEST RACKS. TERMINATE IN FIBER PANEL

USING LC CONNECTOR.

(NOT ALL KEY NOTES ARE APPLICABLE TO THIS SHEET)

KEY NOTES

7.

MENS

TOILET

WOMENS

TOILET

ELECTRIC

CLOSET

EEO MGR

CORRIDOR

C4-4

SMALL CONF

RM

ST

OR

AG

E

RM 42

MECH HVAC RM

CORRIDOR

C4-1

SVC ELEVATOR

LOBBY

PASSENGER

ELEVATOR

LOBBY

CORRIDOR

C4-2

ADMIN

PRIMARY CARE

OFFICE

STAIR

EL

EV

AT

OR

S-

EL

EV

AT

OR

S-

BREAK RM

403A

COMPLIANCE

OFFICE

FI

LE

S

TO

RA

GE

R M

ELEVATOR

P-7

ELEVATOR

P-8

MEDICINE

OFFICE

402 RESTROOM

EEO

RECORDS

SECY

OFFICE

OFFICE RM

423A

MECH

SHAFT

OFFICE RM

CONFERENCE

RM

419B

CHIEF OF

PATIENT

CARE SVCS

CHIEF

OF

MEDICINE

PUBLIC

RELATIONS

AD

MI

NI

ST

RA

TI

VE

OF

FI

CE

FAC

DIRECTOR OF

PUBLIC

AFFAIRS

OFFICE

REGIONAL

COUNCIL

ADMIN

OFFICER

CHIEF OF

STAFF

CONFERENCE

409A EEO

OFFICE

409B

OFFICE RM

OFFICE RM

OFFICE RM

OFFICE RM

FAC

NO-3

STAIR

NO-2

STAIR

EC

OFFICE RM

OFFICE RM

OFFICE RM

OFFICE RM

OFFICE RM

CHIEF OFFICE RM

OFFICE RM

445A

C O

P Y

M A

C H

I N

E

F I L E

C A

B I N

E T

S

OFFICE RM

OFFICE RM

OFFICE RM

OFFICE RM

OFFICE RM

OFFICE RM

OFFICE RM

BREAK RM

ST

OR

AG

E

RM 42

OFFICE RM

OFFICE RM

CORRIDOR

C4-7

CORRIDOR

C4-5

CO

RR

ID

OR

C4 -9

CORRIDOR

C4-6

432A

CENTER

COPY

CORRIDOR

DATA CABLES FROM THIS FLOOR

DOWN TO CEILING OF 3RD FLOOR

SEE 1.T-131 & DETAIL

T-501

DATA CABLES FROM THIS FLOOR

DOWN TO CEILING OF 3RD FLOOR

SEE 1.T-131 & DETAIL

T-501

DATA CABLES FROM FLOOR

ABOVE TO CEILING SPACE OF THIS FLOOR

SEE 1.T-151

DATA CABLES FROM THIS FLOOR

DOWN TO CEILING OF 3RD FLOOR

SEE 1.T-131 & DETAIL

T-501

SCALE: 1/8" = 1' - 0" NORTH

1.T-141

TELECOMMUNICATIONS FOURTH

FLOOR PLAN

BUILDING 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

PM EW/JB

NORTH

A

GENERAL NOTES

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

ARCHITECT/ENGINEER OF RECORD

SCALE: 1/8" = 1'-0"

0' 4' 8' 16'

C

D

20-SCE-04

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FULLY SPRINKLERED

Electronic Health Records Modernization (EHRM) Infrastructure Upgrades - Long Beach

5901 E. SEVENTH STREET, LONG BEACH, CA 90822

600-20-120

CONTRACT DOCUMENTS

December 16, 2020

ALL NEW CAT6A CABLES TO BE ROUTED TO RESPECTIVE TR

ROOMS AS INDICATED. TERMINATE NEW COLOR CODED (3)

CAT6A CABLES (WHITE, GRAY AND BLUE) IN NEW CAT6A

COMPATIBLE JACKS ON NEW FACEPLATE AT EACH EUD

OUTLET AND LABEL IT AS SHOWN. TERMINATE ON TR END IN

A CAT6A COMPATIBLE RJ45 JACK AND NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. EACH CABLE TO EACH

EUD OUTLET SHALL BE TESTED AND CERTIFIED BY CABLE

MANUFACTURER’S CERTIFIED INSTALLER.

SWITCHOVER FROM THE OLD CABLE SYSTEM SHALL BE

DONE ROOM BY ROOM AND FLOOR BY FLOOR IN CLOSE

COORDINATION WITH OIT.

INSTALL NEW 48 PORT CAT6A COMPATIBLE PATCH PANEL IN

EXISTING RACKS IN TR ROOM.

RING AND STRING METHOD SHALL BE USED TO INSTALL NEW

CAT6A CABLES.

OLD FACE PLATE SHALL BE PULLED OUT AND LEFT HANGING

AND REMAIN CONNECTED TO EUD TEMPORARILY WHILE THE

NEW FACEPLATE WILL BE INSTALLED WITH NEW CAT6A

COMPATIBLE DATA JACKS AND NEW CAT6A CABLE. ONCE

THE NEW CABLES ARE TESTED AND CERTIFIED THE EUD

WILL BE DISCONNECTED FROM OLD FACEPLATE AND

CONNECTED TO NEW FACE PLATE BY OIT.

LAY-IN CEILING TO BE REMOVED IN TR. PROTECT ALL

EQUIPMENTS AND RACKS FROM DUST & DAMAGE.

POPULATE AVAILABLE SPACES IN THE EXISTING RACKS WITH

NEW CAT6A COMPLIANT 48 PORT PATCH PANEL. ONCE

THESE NEW PATCH PANELS ARE POPULATED REMOVE

EXISTING PATCH PANEL TO MAKE ROOM FOR NEW CAT6A

COMPLIANT 48 PORT PATCH PANEL. BEFORE

DISCONNECTING AND REMOVING EXISTING PATCH PANEL,

RING OUT AND VERIFY THAT THE DATA CABLES ORIGINATING

IN THOSE PATCH PANELS TO EUD HAVE BEEN

SUCCESSFULLY REPLACED WITH NEW DATA CABLE AND

CAT6A COMPLIANT PATCH PANEL.

FOR CORE DRILLING SLAB REQUIREMENTS PLEASE SEE

GENERAL NOTE 7 ON STRUCTURE DRAWING S-001.

1.

2.

3.

4.

5.

6.

RECOMMENDED ROUTING OF NEW CAT6A BUNDLED CABLE

ON PENDANT MOUNTED U-HOOKS. SEE DETAILS ON

STRUCTURAL DRAWING.

NEW PLENUM RATED 3-CAT6A (GRAY, BLUE WHITE) DROP IN

FREE AIR WITHIN WALL CAVITY. SUPPORT USING WALL

MOUNTED J-HOOKS OR SUSPENDED FROM STRUCTURE

ABOVE. SEE DETAIL ON DRAWINGS T-501, T-503 & T-504.

NEW FACEPLATE WITH GRAY, BLUE AND WHITE CAT6A

COMPLIANT RJ45.

NOT USED.

FOR FLOOR MOUNTED DATA OUTLET PROVIDE TEMPORARY

DATA CABLING. REMOVE EXISTING CABLE FROM UNDER

FLOOR FEED & INSTALL NEW RJ45 JACK.

PROVIDE MULTI RACEWAY MTD EUD AT LAB BENCHES AND

TEMPORARY CABLING. REMOVE EXISTING CABLE FROM

MULTI RACEWAY & INSTALL NEW CAT 6A CABLES &

ASSOCIATED RJ 45 JACKS.

PROVIDE NEW EUD AT EXISTING MULTIRACEWAY. PROVIDE

TEMPORARY CABLING. REMOVE EXISTING CABLE FROM

MULTIRACEWAY AND INSTALL NEW CAT6A CABLES AND

ASSOCIATED RJ45 JACKS AND FACEPLATE.

FOR PREWIRED SYSTEM FURNITURE PROVIDE TEMPORARY

CABLE TO EUD AT SYSTEMS FURNITURE. PULL OLD CABLES OUT

AND INSTALL NEW CABLES AND RJ45 JACK (CAT 6A COMPLIANT

AND ASSOCIATED NEW FACEPLATE).

BEFORE DISCONNECTING PROVIDE TEMPORARY DATA DROP FOR

NURSE STATION. REMOVE EXISTING CABLE AND INSTALL NEW IN

THE EXISTING CONDUIT ABOVE THE CEILING O FLOOR BELOW.

EXISTING FIBER BOX TDU-126-E221 WITH TUBE CELL GOING TO

MDF FROM W50. INSTALL 2-24 STRAND SINGLE MODE AIR BLOWN

FIBER FROM MDF TO THIS BOX AND EXTEND 24 STARND TO EACH

OF THE EAST AND WEST RACKS. TERMINATE IN FIBER PANEL

USING LC…