OR Isolation Panels - Project 554-23-103 Replace OR Booms.pdf

PDF 6 MB Posted

Attached to
Z2DA--554-23-103 Replace OR Booms (VA-23-00012203)
Solicitation number
36C25923R0033
Issued by

About this file

This document includes photos and notes related to a project to replace operating room booms at the Robert J. Dole VA Medical Center in Aurora, Colorado. The project involves replacing booms in eight operating rooms, identified as OR1A, OR1B, OR2A, OR2B, OR3A, OR3B, OR4A, OR4B, OR5A, OR5B, OR6A, OR6B, OR7A, and OR7B. The notes specify that electrical receptacles in the operating rooms must be on dedicated isolated power system circuits, with the exception of receptacles mounted in surgical booms or service columns which may be on two per circuit. Low leakage wire is required for branch circuits to operating room receptacles.

The related federal contract opportunity is solicitation number 36C25923R0033 to replace the operating room booms under project number 554-23-103. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19.

View the file

Other files

File Type Posted
36C25923R0033 0006.docx DOCX document
attendance 1 of 2 Feb 24 2023.pdf PDF
36C25923R0033 0005.docx DOCX document
attendance 2 of 2 Feb 24 2023.pdf PDF
Site Visit 2 Meeting Doc.docx DOCX document
03 Lighting.pdf PDF
03 Power.pdf PDF
36C25923R0033 0004.docx DOCX document
03 Equip and Lighting Mounting.pdf PDF
03 Structural Steel.pdf PDF
03 Plumb Med Gas.pdf PDF
03 Equipment.pdf PDF
03 HVAC mechanical.pdf PDF
03-03 Room Elevations.pdf PDF
03 Reflected Ceiling Plans.pdf PDF
36C25923R0033 0003.docx DOCX document
36C25923R0033 0002.docx DOCX document
Site Visit Meeting Doc.docx DOCX document
attendance 1 of 2.pdf PDF
SOW r2 proj 554-23-103 Replace OR Booms.docx DOCX document
attendance 2 of 2.pdf PDF
03_DAT_Med Equip Support Steel_Unistrut_As-Builts - opt.pdf PDF
36C25923R0033 0001.docx DOCX document
Wage Determination CO20230015 1 13 2023.pdf PDF
36C25923R0033_1.docx DOCX document
SPECS proj 554-23-103 Replace OR Booms.pdf PDF
S02 Past Performance Questionnaire.docx DOCX document
Drawings proj 554-23-103.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project 554-23-103 Replace OR Booms

OR Isolation Panel Photos

RMR VAMC

1700 N. Wheeling St.

Aurora, CO 80045

NOTES:

1. For Surgical / Operating Rooms, Isolated Power System (IPS), each receptacle shall be connected to an IPS on a dedicated circuit in a dedicated homerun conduit, except for those receptacles mounted in the surgical booms or service columns, which may be wired two to a circuit. Multiwire circuits are prohibited.

2. For Surgical / Operating Rooms, Isolated Power System (IPS), use low leakage wire for the powered conductors of branch circuit wiring, for example XHHW-2, dielectric constant of less than 3.5. THHN may be used for the ground wires only.

OR1A

Upper left

OR1B

Upper right

OR2 A&B

OR2A

OR2A

OR2B

OR2B

OR3 A&B

OR3A

OR3B

OR4 A&B

OR4A

OR4A

OR4B

OR4B

OR5 A&B

OR5A

OR5A

OR5B

OR5B

OR6 A&B

OR6A

OR6A

OR6B

OR6B

OR7A

OR7B