Door Controller DC1000 Data Sheet.pdf
PDF 261 KB Posted
- Solicitation number
- 36C25722B0027
About this file
This document contains a data sheet for the DC1000 Door Controller and information on a federal contract opportunity to replace elevators at a Department of Veterans Affairs facility.
The data sheet provides specifications for the DC1000 Door Controller, which allows for robust and sophisticated monitoring and locking of egress points. It supports up to four indoor and one outdoor keypads, monitors its own status, and reports errors. The controller integrates with the Arial system to centrally manage users and send and receive events, alarms, and commands. It has built-in relays for door locking and alarms, as well as inputs and outputs. The opportunity notice is to replace four elevators at a Veterans Affairs medical center for project number 671-20-128. The solicitation was issued by VA Veterans Health Administration VISN 17. No further details are provided on pricing, response dates, or award information.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25722B0027 0011.docx | DOCX document | |
| 36C25722B0027 0010.docx | DOCX document | |
| 36C25722B0027 0009.docx | DOCX document | |
| Supplemental Information.pdf | ||
| 36C25722B0027 0008.docx | DOCX document | |
| 36C25722B0027 0007.docx | DOCX document | |
| IMG_0415.pdf | ||
| 36C25722B0027 0006.docx | DOCX document | |
| 36C25722B0027 0005.docx | DOCX document | |
| IMG_0416.jpg | JPG image | |
| 36C25722B0027 0004.docx | DOCX document | |
| Sign-in-Sheet Pre-Bid Site Visit.pdf | ||
| 36C25722B0027 0003.docx | DOCX document | |
| 36C25722B0027 0002.docx | DOCX document | |
| VAAR 852.236-92.pdf | ||
| Dwg 6 Cfig 6 Selective Elevator Monitor Inside of Elev Rev3.pdf | ||
| Pre Bid - Sign In Sheet.pdf | ||
| 36C25722B0027 0001.docx | DOCX document | |
| 36C25722B0027_2.docx | DOCX document | |
| VA AM Elevator Replacement 100 CD Specifications.pdf | ||
| VA AM Elevator Replacement 100 CD Drawings 04192022 SM.pdf |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATA SHEET
DC1000 Door Controller Provides robust and sophisticated egress point monitoring and locking at the door with optional central management. Supports indoor and outdoor keypads.
Description The DC1000 Door Controller is based on the EX5700 Door Controller and provides protection at a door. It is typically used for doors that are always locked, such as the side doors to a building. It can be used as a standalone product at the Door and can also be integrated with Arial.
Key Features Keypads Up to four Indoor Keypads and one Outdoor Keypad may be connected to the Controller.
The Controller enables the use of alarm reset and PIN codes/Badge Reader swipe to lock/unlock the door accordingly. The Keypads are powered by the Controller.
Error Reporting The Controller monitors its own status 24/7 using an internal mechanism. If there is a technical problem with the Controller, it provides a visual indication via its LED and sends the error information to the Indoor Keypad. Errors are reported to Arial as well.
LED Indications The Controller LED displays indications of its status: Day Mode, Night Mode, Alarm, Override and Error.
Integration with Arial The Controller sends mode change indications, alarms, events, status and errors to Arial. The communication can be via an embedded Inovonics transmitter or through the network. When connected to the Network, users (staff and visitors) can be centrally managed from Arial.
Controller Relays The Controller is equipped with two relays.
Relay 1 is dedicated to the door maglock control. Relay 2 is activated when there is an alarm condition and is usually connected to an annunciator.
Inputs and Outputs The Controller has four inputs and four outputs that can be used for various use cases. In addition to door input that reports door status, there are alarm, override and Request for Exit inputs. Two of the outputs can be configured to be activated based on event/status change.
Product Highlights
• Supports Multiple Keypads – Four Indoor Keypads and one Outdoor Keypad can be connected.
• Flexible Installation – Includes various mounting options.
• Easy Configuration – Controller settings configured using a mobile application.
Users configuration using Arial.
• Staff and Visitor Access – Controls access of staff and visitors by verifying pin codes and/or badges.
• Built-in Relays – Built-in relays provieded to lock the door and annunciate alarms.
• Users – Supports up to 1,000 users (staff and visitors).
• Badge Support – Supports the Wiegand 26 card format.
• Arial Integration – Sends events to Arial via inovonics or the network. When using the network, the communication between the DC1000 and Arial can be bi-directional. Start/Stop Night and Override Modes and Alarm Reset commands can be sent from Arial to the Controller. As well, staff and visitor records in the Controller can be centrally managed in Arial.
• Easy Firmware Upgrade – Controller upgrade using the mobile app or centrally from the Arial system. Keypads are simultaneously upgraded.
Data Sheet: DC1000 Door Controller
© 2020 STANLEY Healthcare. All rights reserved. 0971-453-000 Rev A. December 2020. KB Article: 12268
75 Portsmouth Blvd., Suite 220, Portsmouth, NH 03801 1-888-622-6992 stanleyhealthcare.com stanleyhealthcare@sbdinc.com
About STANLEY Healthcare Over 15,000 hospitals and senior living communities rely on STANLEY Healthcare solutions to empower caregivers to deliver better care. STANLEY Healthcare is a part of Stanley Black & Decker and a proud supporter of the Alzheimer’s Association®. Learn more at www.stanley.healthcare.com.
Product Specifications
Part Number SKU: DC-1000-NA, DC-1000-E
Dimensions 245 mm x 200 mm x 60 mm (9.6 in. x 7.9 in. x 2.4 in.)
Weight 780 g (27.5 oz.)
Housing Polycarbonate and ABS
Power Input voltage 24-48 VDC Maximum power consumption: 24 W.
Maximum current consumption: with 24 V – 1 A; with 48 V – 0.5 A
Network Interface Ethernet (RJ-45)
Environmental Operating temperature: 0 to 50°C (32°F to 122°F) Humidity: 0 to 95%, non-condensing
Certification Radio:
FCC Part 15, sub-part C class B, EN 300-330, EN 300 220, EN 300 328
RSS-247 (Canada)
EMC:
FCC Part 15 sub-part B
EN 301 489, IEC 60601,
ICES-003
Safety EN 60950, UL/CSA 60950, IEC 60950, IEC 60601
Relays (Dry Contacts) Two: 15 VDC, 2 A, 30 W; 24 VDC, 1.25 A, 30 W; 30 VDC, 1 A, 30 W;
NO (Normally Open) or NC (Normally Closed) Class 2
Outputs Four: Secure Door Lock, TIF (not used), programmable, programmable.
Open drain outputs, up to 100 mA @ 12V
Note: The open drain outputs switch power provided from an external source.
Inputs Four: Alarm, Override, Door Status, REX. To activate the input, it must be shorted to GND. Max. cable resistance – 5 Ohm
Up to 10 m cable (at least 26 AWG)
RS485A, RS485B Indoor Keypad interface, up to 10 m cable (at least 26 AWG)
D0, D1 Wiegand Keypad interface, up to 10 m cable (at least 26 AWG)