S02 36C25522R0022 Addendum 1 Drawings.pdf

PDF 8 MB Posted

Attached to
Z2DA--589A7-21-700 EHRM Infrastructure Upgrades Federal contract opportunity
Solicitation number
36C25522R0022
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This addendum provides revisions to construction drawings for Electronic Health Records Management Infrastructure Upgrades project 589A7-21-700 at the Veterans Affairs Medical Center in Wichita, Kansas. The revisions include changes to site plans, communications diagrams, and architectural drawings for multiple buildings. On the site plans, revisions specify that conduit and manholes for new AT&T fiber and telephone cables will be contractor-provided and installed. Interior changes shown on architectural drawings modify existing walls to become smoke-rated and relocate electrical panels and equipment for new telecommunications rooms. The addendum provides updated drawings to reflect revisions to the construction project for infrastructure upgrades at the VA medical center.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--589A7-21-700 EHRM Infrastructure Upgrades, newest first.
File Type Posted
S02 589A7-21-700 EHRM Wichita-Pre Bid Presentation.pdf PDF
S02 Bldg 34 Hazardous Materials.pdf PDF
S02 Bldg 4 Hazardous Materials.pdf PDF
S02 Bldg 12 Hazardous Materials.pdf PDF
S02 Bldg 26 Hazardous Materials.pdf PDF
S02 Bldg 61 Hazardous Materials.pdf PDF
S02 Bldg 60 Hazardous Materials.pdf PDF
S02 Infection Control Risk Assessment for Hospital Construction and Renovation.pdf PDF
S02 Bldg 20 Hazardous Materials.pdf PDF
S02 Bldg 16 Hazardous Materials.pdf PDF
S02 Bldg 3 Hazardous Materials.pdf PDF
S02 Bldg 11 Hazardous Materials.pdf PDF
S02 Bldg 6 Hazardous Materials.pdf PDF
S02 Bldg 10 Hazardous Materials.pdf PDF
PreProposal Conference Site Visit Agenda - EHRM.doc DOC document
S02 589A7-21-700 EHRM Pre-Bid Sign In Sheet.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.docx DOCX document
S02 Past Performance Questionnaire 36C25522R0002 Project 589A7-21-700.pdf PDF
36C25522R0022.pdf PDF
589A7-21-700.IFC_R3.SITE.20210630.pdf PDF
589A7-21-700.IFC_R3.B62.20210630.pdf PDF
589A7-21-700.IFC_R3.B60.20210630.pdf PDF
589A7-21-700.IFC_R3.B34.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B21.Gen-Elec.20210630.pdf PDF
2of2_589A7-21-700.IFC_R3.B21.Telecom.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B16.Gen-Elec.20210630.pdf PDF
2of2_589A7-21-700.IFC_R3.B16.Telecom.20210630.pdf PDF
589A7-21-700.IFC_R3.B13.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B07.Gen-Elec.20210630.pdf PDF
2of2_589A7-21-700.IFC_R3.B07.Telecom.20210630.pdf PDF
589A7-21-700.IFC_R3.B06.20210630.pdf PDF
2of2_589A7-21-700.IFC_R3.B01.Telecom.20210630.pdf PDF
589A7-21-700.IFC_R3.B61.Gen-Elec.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B59.Gen-Elec.20210630.pdf PDF
589A7-21-700.IFC_R3.B20.20210630.pdf PDF
589A7-21-700.IFC_R3.B05.20210630.pdf PDF
589A7-21-700.IFC_R3.B02.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B01.Gen-Elec.20210630.pdf PDF
S02 01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
S02 Specifications 051200 thru 096900.pdf PDF
589A7-21-700.IFC_R3.B61.Telecom.20210630.pdf PDF
2of2_589A7-21-700.IFC_R3.B59.Telecom.20210630.pdf PDF
589A7-21-700.IFC_R3.B29.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B26.Gen-Elec.20210630.pdf PDF
2of2_589A7-21-700.IFC_R3.B26.Telecom.20210630.pdf PDF
589A7-21-700.IFC_R3.B19.20210630.pdf PDF
589A7-21-700.IFC_R3.B12.20210630.pdf PDF
589A7-21-700.IFC_R3.B11.20210630.pdf PDF
589A7-21-700.IFC_R3.B04.20210630.pdf PDF
589A7-21-700.IFC_R3.B03.20210630.pdf PDF
Show all 50

Z2DA--589A7-21-700 EHRM Infrastructure Upgrades has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CVE Verified Service-Disabled Veteran-Owned Small Business

TRIPLE C – THE A&E GROUP

OUR REASONABLE SERVICE - TO PROVIDE YOU WITH EXEMPLARY SERVICE

410 Grand Avenue, Suite 201C � Laramie, Wyoming 82070 � Telephone: (307) 460-2054 � Fax: (307) 460-2053

Addendum

Project: 589A7-21-700/EHRM INFRASTRUCTURE

UPGRADES, Wichita VAMC

Subject: Addendum No. 1

Date: 01/20/2022

Revisions:

1. Site

a. Site conduit and handholes for new AT&T WAN fiber and telephone copper cable shall be contractor provided/contractor installed (CPCI). AT&T will pull new fiber and copper cable after conduit and manholes are commissioned, inspected and accepted by the VA.

Fiber will be tested, terminated and placed into use by AT&T.

b. Contractor shall provide new conduit/cable tray for all ISP (Inside Plant) fiber.

2. Building 01

a. Sheet A-402: Added Key Notes 7, 8 and 9 to clarify existing conditions and demolition scope on Level 4. Identified existing ductwork, electrical disconnect and lightning protection to be relocated.

3. Building 03

a. Sheet A-401: Added Key Notes 8, 9 and 10 to clarify existing conditions and demolition scope on Level 0. Identified existing slabs, electrical panels and utilities above.

b. Sheet A-402: Added Key Note 10 to clarify existing conditions and identify existing slope/ramp on Level 1. Contractor shall coordinate with new construction.

4. Building 19

a. Sheet A-403: Added Key Note 7 to clarify existing conditions and identify existing slope/ramp on Level 2. Contractor shall coordinate with new construction.

Meeting Agenda

BLDG/Sheet Number Revision Description of / Reason for Change

SITE/AS100 ADD 01 Revised AT&T fiber/copper conduit and manholes to be CPCI.

SITE/AS100 ADD 01 All ISP fiber routes shall be new conduit/cable tray, CPCI.

SITE/T-602 ADD 01 Revised AT&T fiber/copper conduit and manholes to be CPCI.

SITE/T-602 ADD 01 All ISP fiber routes shall be new conduit/cable tray, CPCI.

B01/A-402 ADD 01 Added KN 7, 8 and 9 to clarify demolition scope.

B03/A-401 ADD 01 Added KN 8, 9 and 10 to clarify demolition scope.

B03/A-402 ADD 01 Added KN 10 to identify existing slope/ramp.

B19/A-403 ADD 01 Added KN 7 to identify existing slope/ramp.

End of Addenda

Attachments: SITE.AS100.ADD01.20220120.pdf

SITE.T-602.ADD01.20220120.pdf

B01.A-402.ADD01.20220120.pdf

B03.A-401.ADD01.20220120.pdf

B03.A-402.ADD01.20220120.pdf

B19.A-403.ADD01.20220120.pdf

F A

C P

NEW PULL BOX.

STAIR 1

ELEV. 1

ELEV.

EQUIP.

HALL

BOILER

ROOM

EXISTING CONDUIT

EXISTING ROUTE WITHIN

BUILDING

EXISTING BUILDING

NEW FIBER IN EXISTING CONDUIT -

MAIN ROUTE

EXISTING ROUTE WITHIN BUILDING -

NEEDS VERIFICATION

NEW FIBER IN NEW CONDUIT / TRAY -

MAIN ROUTE

EXISTING ELECTRICAL

CONDUIT

SERVICE PROVIDER A -

AT&T

SERVICE PROVIDER B -

COX COMM.

OMAR B

RADLEY D

RIVE

KELLOGG DRIVE

E D

G E

M O

O R

S T

R E

E T

B L E

C K

L E

Y D

R

IV

E

WATERMAN STREET

B5

B5B

B7

B6

B21

B16

B12B13B20

B10 B11

B60

B4 B1B3

B29

B62

B26

B61

B19 B2

B1C

B1B

B34

B59

B1A

COMM MANHOLE - 5

COMM MANHOLE - 3

COMM MANHOLE - 4

COMM MANHOLE - 2

COMM MANHOLE - 6

COMM MANHOLE - 9

COMM MANHOLE - 10

SOUTH END STEAM

TUNNEL / B13

COMM MANHOLE - 11

COMM

HANDHOLE - H1

B58

COMM MANHOLE - 1

COMM

MANHOLE - 7

COMM MANHOLE - 12

COMM MANHOLE - 13

COMM

MANHOLE - 8

T-604

C1

T-603

F5

T-603

C5

T-603

C1

T-606

C1

T-606

F1

T-604

F1

T-605

C1

T-605

C5

T-604

F5

(N) COMM

HANDHOLE - T2

(N) COMM HANDHOLE -

AT&T 1

(N) COMM HANDHOLE -

AT&T 2

T-605

F1

T-604

C5

T-603

F1

T-605

F5

(N) COMM

HANDHOLE -

T1

FUTURE CHILLER

LOCATION

ELEC MANHOLE

(N) COMM HANDHOLE -

AT&T 3

EXISTING PERIMETER

FENCE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A

-2

-7

E H

R M

I n fr a s tr u c tu re U p g ra d e s

W ic h it a /5

A

-2

-7

E H

R M

W ic h it a

S it e

A

R C

H .r v t

/1

/2

:2

:5

P

M

AS100

SITE PLAN - NEW COMMUNICATIONS BASE BID 589A7-21-700

SITE

06/30/21 M. Perkins K. Struble

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

5500 E. KELLOGG, WICHITA, KANSAS 67218-1607

0 30'-0" 60'-0" 120'-0"

1 EXISTING FIBER FEED TO REMAIN

2 INSTALL NEW FIBER - FEED THROUGH EXISTING CONDUIT

3 INSTALL NEW FIBER AND NEW CONDUIT OR CABLE TRAY

4 DRILL EXISTING MANHOLE CONNECT 4" PVC CONDUIT

5 CONSTRUCT TWO (2) 4" PVC CONDUIT - TRENCH AND REPLACE EXISTING

LANDSCAPE - MATCH EXISTING, SEE DETAIL B4, SHEET AS501.

DIRECTIONAL BORE AT SIDEWALK, CURB AND ASPHALT. PROVIDE FIBER

OPTIC CABLE PER SHEET T-602

6 CONSTRUCT 24"X36"X36" COMM PULLBOX, OLDCASTLE MODEL

DURALITE 2436 (TRAFFIC RATED - TIER 22) OR APPROVED EQUAL - SEE

DETAILS E1, B7 AND D7, SHEET AS501

7 PROVIDE 30"X60"X36" COMM PULLBOX, OLDCASTLE MODEL FRP 306.

AT&T WILL PULL NEW FIBER AND COPPER CABLES AFTER CONTRACTOR

PROVIDES INFRASTRUCTURE.

8 PROVIDE 48"X96"X48" COMM PULLBOX, OLDCASTLE MODEL FRP 4896.

AT&T WILL PULL NEW FIBER AND COPPER CABLES AFTER CONTRACTOR

PROVIDES INFRASTRUCTURE.

9 SEE BUILDING 34 SHEET T-101 FOR CONTINUATION

10 EXISTING TREE TO REMAIN - PROTECT IN PLACE

11 CONSTRUCT GROUND ROD SYSTEM AND BOND BAR - SEE DETAIL F7,

SHEET AS501

12 PROVIDE TWO (2) 4" PVC CONDUIT. AT&T WILL PULL NEW FIBER AND

COPPER CABLES AFTER CONTRACTOR PROVIDES INFRASTRUCTURE.

13 CONSTRUCT TWO (2) 5" PVC CONDUIT - TRENCH AND REPLACE EXISTING

LANDSCAPE - MATCH EXISTING, SEE DETAIL B4, SHEET AS501.

DIRECTIONAL BORE AT SIDEWALK, CURB AND ASPHALT. PROVIDE FIBER

OPTIC CABLE PER SHEET T-602, SEE BUILDING PLANS 5, 5B SHEET T-101

FOR ADDITIONAL INFORMATION

14 CONSTRUCT HANDHOLE AND CHASE PER B34 PLANS, SHEET A-404

LINETYPE

1" = 60'-0" F1

SITE PLAN - NEW COMMUNICATIONS BASE BID

NOTE

BASE BID: FIBER HOME RUNS FROM EACH BUILDING BACK TO B34.

PROVIDE 100' EXTRA SLACK EACH FIBER OPTIC CABLE FOR FUTURE

EXTENSION TO NEW SERVER ROOM. EXTEND FIBER FROM B34 TO B19

FOR TERMINATION AT EXISTING SERVER ROOM. FUTURE SCOPE WILL

REMOVE THIS B34 TO B19 EXTENSION. SEE SITE PLANS FOR

ADDITIONAL INFORMATION.

NOTE

AT&T/CHC contact information:

Janice Bowers CHC Consulting

(785) 806-2828 jbowers@chcconsulting.com

Jason Edwards Mgr. Osp Plng & Engrg Design Wichita, KS 316-268-2008 je1682@att.com

COX Communications contact information:

Bilal H. Batroukh, PMP Project Manager, Development T-Mobile Direct 425.436.4199 | Mobile 708.253.2018| bilal.batroukh1@t-mobile.com

Revisions: Date:

Addendum 1 01/20/2022

BLDG 1

BLDG 1A

BLDG 3

BLDG 2

BLDG 26

BLDG 61

BLDG 29

BLDG 62

BLDG 19

BLDG 34

BLDG 4

BLDG 59

BLDG 60

BLDG 20 BLDG 13 BLDG 12

BLDG 16BLDG 11S

T

E A

M T

U N

N E

L

BLDG 21

BLDG 6

BLDG 5

BLDG 5B

BLDG 7

MH

MH

MH

MH

MH

MH

MH

MH

MH

MH

MH

MH

MH

HALLWAY

3X12F

OS2-10GB

1X24F

OS2-10GB

7X24F

OS2-10GB

HH

T2

3X12F

OS2-10GB

HH

T1

MH

AT&T 1

HH

AT&T 3

MH

AT&T 2

HH

H1

SERVICE

PROVIDER B

COX COMM.

SERVICE

PROVIDER B

COX COMM.

SERVICE

PROVIDER B

COX COMM.

SERVICE

PROVIDER A

AT&T

SERVICE

PROVIDER A

AT&T

1X12F

OM4-10GB

4X12F

OM4-10GB

2X24F

OM4-10GB

6X24F

OM4-10GB

4X12F

OM4-10GB

6X24F

OM4-10GB

2X24F

OM4-10GB

3X24F

OS2-10GB

1X12F OS2-10GB

1X12F OS2-10GB

3X12F OS2-10GB

1X12F OS2-10GB

2X12F OS2-10GB

5X12F OS2-10GB

1X12F

OM4-10GB

5X12F OS2-10GB

1X12F OM4-10GB

1X12F

OM4-10GB

5X24F

OM4-10GB

7X24F

OM4-10GB

1X12F OS2-10GB

1X12F

OS2-10GB

1X12F

OS2-10GB

1X24F

OS2-10GB

1X12F

OS2-10GB

8X24F

OS2-10GB

4X12F

OS2-10GB

8X24F

OS2-10GB

4X12F

OS2-10GB

8X24F

OS2-10GB

1X24F

OM4-10GB

4X12F

OS2-10GB

8X24F

OS2-10GB

5X12F OM4-GB

14X24F OM4-10GB

4X12F OS2-10GB

8X24F OS2-10GB

BASE BID: FIBER HOME RUNS FROM EACH BUILDING BACK THROUGH B34 AND

TERMINATING IN B19. PROVIDE 100' EXTRA SLACK EACH FIBER OPTIC CABLE

FOR FUTURE EXTENSION TO NEW SERVER ROOM. EXTEND FIBER FROM SLACK

LOOPS IN B34 TO B19 FOR TERMINATION AT EXISTING SERVER ROOM. FUTURE

SCOPE WILL REMOVE THIS B34 TO B19 EXTENSION. SEE B34 TECHNOLOGY

PLANS AND SITE PLANS FOR ADDITIONAL INFORMATION.

DEDUCT ALTERNATE: FIBER HOMERUNS FROM EACH BUILDING BACK TO B19

SERVER ROOMS (001). SEE SITE PLANS FOR ADDITIONAL INFORMATION.

CONTRACTOR

PROVIDED/CONTRACTOR

INSTALLED MANHOLES AND

CONDUIT (2X 4" PVC) AND

CABLE TRAY.

AT&T WILL PULL NEW FIBER

AND COPPER CABLE. AT&T

FIBER WILL BE TESTED,

TERMINATED AND PLACED

INTO USE BY AT&T.

CONTRACTOR

PROVIDED/CONTRACTOR

CONDUIT AND CABLE TRAY

COX WILL PULL NEW FIBER

AND COPPER CABLE. COX

FIBER WILL BE TESTED

TERMINATED, AND PLACED

INTO USE BY COX.

EXISTING ROUTE WITHIN

BUILDING

EXISTING BUILDING

NEW FIBER IN EXISTING CONDUIT -

MAIN ROUTE

NEW FIBER IN NEW CONDUIT / TRAY -

MAIN ROUTE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A

-2

-7

E H

R M

I n fr a s tr u c tu re U p g ra d e s

W ic h it a /5

A

-2

-7

E H

R M

W ic h it a

S it e

A

R C

H .r v t

/1

/2

:2

:2

P

M

T-602

SITE PLAN - COMMUNICATIONS ONE-LINE

DIAGRAM - NEW BASE BID

589A7-21-700

SITE

06/30/21 M. PERKINS K. STRUBLE

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

5500 E. KELLOGG, WICHITA, KANSAS 67218-1607

1/2" = 1'-0" F1

COMMUNICATIONS ONE-LINE DIAGRAM NEW

NOT USED

Revisions: Date:

Addendum 1 01/20/2022

UP

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL

PROJECT REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW IT CLOSETS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

ACOUSTICAL OR RATED

FLEXIBLE SEALANT

FLOOR LINE

ADD ONE LAYER OF 5/8" GWB,

ONE-SIDE WITH APPROVED UL

SETTING COMPOUND BETWEEN

LAYERS AND FASTENED TO

WALL AS REQUIRED, AT

EXISTING GWB WALL

ASSEMBLIES

STRUCTURAL DECK

EXISTING METAL STUDS AND

BATT INSULATION TO REMAIN

A/C GRADE, 3/4" FIRE-TREATED

PLYWOOD TO 8'-0" ABOVE FINISHED

FLOOR, ADHERED TO CONCRETE AT

EXISTING CONCRETE WALL

ASSEMBLIES

BOTTOM OF PLYWOOD

TO BE AT 12" AFF

UL DESIGN V497

1-HOUR PARTITION RATED FROM BOTH SIDES

EXISTING GWB OR

CONCRETE WALL

ASSEMBLY, WHERE OCCURS

SIDE OF

EXISTING

ROOM OR

CORRIDOR TO

REMAIN

A-512

E4

A-512

B4

ACOUSTICAL OR RATED

SEALANT BOTH SIDES

FLOOR LINE

5/8" GWB BOTH SIDES

SOUND ATTENUATION

BATTS (SAB) PER

SCHEDULE.

CEILING LINE

STRUCTURAL DECK

METAL STUDS, SIZE

PER SCHEDULE

A-512

E4

A/C GRADE, 3/4" FIRE-

TREATED PLYWOOD TO 8'-0"

ABOVE FINISHED FLOOR

A-512

B4

AT FIRE RATED

PARTITIONS

AT SMOKE RATED

PARTITIONS

BOTTOM OF PLYWOOD TO

BE AT 12" AFF

TELECOM

ROOM

440A

119 SF

'-0

10'-0"

440A

D3

A-402

B

B

A-401

D1

S L O

P E

SLOPE

S L O

P E

SLOPE

TELECOM

ROOM

440A

119 SF

D3

A-402

/2

D3

A-402

FOURTH LEVEL

48' - 0"

1/2" / 1'-0"

'-0

TELECOM

ROOM

440A

119 SF

TIE IN NEW WALL MEMBRANE

INTO NEW ROOFING MEMBRANE

NEW EXTERIOR WALL:

FIBER-CEMENT PANELS (PRE-FINISHED, WHITE, TEXTURED,

HARDIEBOARD BASIS OF DESIGN)

2" RIGID INSULATION

MOISTURE BARRIER

EXTERIOR SHEATHING

6" METAL STUDS

5/8" GYPSUM WALL-BOARD

NEW ROOF:

EPDM ROOFING

2" RIGID INSULATION

MOISTURE BARRIER

EXTERIOR SHEATHING

6" METAL STUDS

5/8" GYPSUM WALL-BOARD

PROVIDE SLEEPERS AND NEW SUBFLOOR AS REQUIRED

FOR A LEVEL FLOOR THAT IS AT THE SAME ELEVATION

AS THE FOURTH FLOOR

SECURE BOTTOM TRACK TO ROOF STRUCTURAL DECK

TELECOM

ROOM

440A

119 SF

A-402

B7

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

KEY PLAN

B1

AREA A

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

/30 /20

B

IM

/5

A

-2

-7

E H

R M

I n fr a s tr u c tu re U p g ra d e s

W ic h it a /5

A

-2

-7

E

H R

M

W ic h it a

B

A R

C H

.r v t

/1

/2

:0

:3

P

M

A-402

ARCHITECTURAL ENLARGED PLANS - FOURTH

LEVEL

589A7-21-700

B1, 1A, 1B, 1C

06/30/21 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

5500 E. KELLOGG, WICHITA, KANSAS 67218-1607

DOOR AND FRAME SCHEDULE

IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL

FIRE RATING

HARDWARE

NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL

FIRST LEVEL 150 TELECOM ROOM 150 3' - 0" 7' - 0" 1 3/4" EXT'G WD WD NONE 3/8" EXT'G HM PTD 45 MIN SEE SPEC SEE ELEC 1,2,3

FOURTH LEVEL 440A TELECOM ROOM 440A 3' - 0" 7' - 0" 1 3/4" F HM PTD NONE 3/8" 1 HM PTD 45 MIN SEE SPEC SEE ELEC 1,2,3

NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL

U465

(TYPE A) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

A4 4" 5 1/4" 35

NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL

V438, UL U411

(TYPE B) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

B 2 1/2" 3/4" 45

1 REMOVE / RELOCATE ROOF UTILITIES / FIXTURES FOR NEW TELECOM

ROOM.

2 NEW DOOR AND FRAME IN EXISTING WALL, VERIFY DEPTH. MODIFY

EXISTING FRAMING AS REQUIRED FOR INSTALLATION. PATCH /

REPAIR ADJACENT FINISHES AS REQUIRED FOR CONTINUOUS FINISH.

3 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

4 REMOVE AND RELOCATE ROOF DRAIN. MODIFY PIPING IN CEILING

SPACE BELOW AS REQUIRED FOR RELOCATION. COORDINATE

ACCESS WITH COR.

5 REMOVE PORTION OF GUTTER TO DRAIN ONTO NEW ROOF.

6 PROVIDE NEW SLOPED INSULATION AND ROOFING MEMBRANE TO

RE-SLOPE ROOF TO DRAIN TOWARDS RELOCATED ROOF DRAIN. SEE

DETAIL F3/A-501

7 REMOVE EXISTING DUCT AND CAP BELOW ROOF DECK. REPAIR

EXISTING ROOF.

8 RELOCATE EXISTING ELECTRICAL DISCONNECT. REPULL

CONDUCTORS AND INSTALL ON NEW PARTITION

9 RECLOCATE EXISTING LIGHTNING PROTECTION SYSTEM TO

COORDINATE WITH NEW TR.

1/4" = 1'-0" B7

ARCHITECTURE FLOOR PLAN - 4TH LEVEL

1/4" = 1'-0" D7

ARCHITECTURE DEMO PLAN - 4TH LEVEL

1/4" = 1'-0" B5

ARCHITECTURE RCP - 4TH LEVEL

1/4" = 1'-0" D5

ARCHITECTURE ROOF PLAN - 4TH LEVEL

DOOR SCHEDULE NOTES:

1. DOOR PANEL AND FRAME TO BE SMOKE-RATED FOR TRANSITION, INCLUDING CLOSER, SEALS, THRESHOLD, AND SWEEP.

2. PAINT DOOR TRIM TO MATCH EXISTING TRIM PAINT IN SPACE.

3. COORDINATE DOOR PANEL, FRAME, AND HARDWARE WITH ELECTRICAL HARDWARE (ACCESS CONTROL, ELECTRICAL STRIKE, DOOR-CONTACT SWITCH, ETC.) SEE ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.

1/4" = 1'-0" D3

NEW TELECOM ROOM SECTION

NOT TO SCALE

B3

FOURTH LEVEL NEW TELECOM ROOM LOCATION

1/32" = 1'-0" F3

FOURTH FLOOR PLAN REFERENCE

RELOCATE ROOF DRAIN

REMOVE PORTION OF GUTTER TO DRAIN ONTO NEW ROOF.

Revisions: Date:

Addendum 1 01/20/2022

1/2" 1/2"

VARIES

SEE PLAN

NEW PARTITION

WALL, BEYOND -

SEE PLAN FOR

TYPE

NEW THRESHOLD,

SET IN FULL BED OF

SEALANT - EA. SIDE

& ALL AROUND, TYP.

NEW HOLLOW METAL

FRAME

NEW SWEEP

U N

D E

R C

U T

V E

R

IF

Y

1/2" 1/2"

VARIES

SEE PLAN

WALL - SEE PLAN

FOR TYPE

SEALANT - EA. SIDE

& ALL AROUND,

TYP.

HOLLOW METAL

FRAME

/2

V

A R

IE

S

S E

E P

L A

N

/2

4" 2"

ADJACENT WALL

WHERE OCCURS

SEALANT - EA SIDE &

ALL AROUND, TYP.

HOLLOW METAL

FRAME

WALL - SEE PLAN

FOR TYPE

D1

TYPICAL FRAME

H E

IG

H

T

2" WIDTH 2"

E1

FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS

F

FLUSH

F1

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL

PROJECT REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW IT CLOSETS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

BUILDING 1A

BREAK

ROOM

366 SF

E L

E C

T R

IC

A

L

A

S

F

TELECOM

ROOM

002A

100 SF

CORRIDOR

0CORRA

62 SF

SERVER

ROOM

355 SF

MECHANICAL

ROOM

650 SF

BUILDING 3

8'-2 1/4"

'-2

/8

A

A4

A

B

B

BUILDING 1A

BREAK

ROOM

366 SF

E L

E C

T R

IC

A

L

A

S

F

CORRIDOR

0CORRA

62 SF

SERVER

ROOM

355 SF

MECHANICAL

ROOM

002002

BUILDING 3

742 SF

TELECOM

ROOM

002A002A

CORRIDOR

0CORRA0CORRA

MECHANICAL

ROOM

002002

SERVER

ROOM

001001

BREAK

ROOM

006006

ELECTRICAL

006A006A

BUILDING 1ABUILDING 3

CORRIDOR

0CORRA0CORRA

MECHANICAL

ROOM

002002

SERVER

ROOM

001001

BREAK

ROOM

006006

ELECTRICAL

006A006A

BUILDING 1ABUILDING 3

TELECOM

ROOM

002A002A

A-402

C7

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

KEY PLAN

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

BUILDING

/30

/20

B

IM

/5

A

-2

-7

E H

R M

I n fr a s tr u c tu re U p g ra d e s

W ic h it a /5

A

-2

-7

E

H R

M

W ic h it a

B

A R

C H

.r v t

/1

/2

:4

:0

P

M

A-401

ARCHITECTURAL ENLARGED PLANS - GROUND

LEVEL

589A7-21-700

B3

06/30/21 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

5500 E KELLOGG, WICHITA, KANSAS 67218-1607

3" = 1'-0" F1

HOLLOW METAL THRESHOLD DETAIL

3" = 1'-0" D1

HOLLOW METAL HEAD DETAIL

3" = 1'-0" E1

HOLLOW METAL JAMB DETAIL

1/4" = 1'-0" C1

WRAPPED FRAME TYPES ELEVATIONS

1 TELECOM ROOM CEILING TO BE OPEN TO DECK ABOVE.

2 ALIGN NEW WALL WITH FACE OF EXISTING FOR CONTINUOUS

FINISH.

3 REMOVE DUMB-WAITER EQUIPMENT AND CHASE-WALLS IN IT'S

ENTIRERTY.

4 REMOVE FLOORING FOR NEW TELECOM ROOM. PREP SUBFLOOR

FOR NEW FINISH.

5 TRIANGLE HATCH INDICATES AREA KNOWN TO CONTAIN ASBESTOS

CONTAINING MATERIAL, MASTIC UNDER FLOORING. CONTRACTOR

TO VERIFY EXTENT AND FULLY REMOVE, FOLLOWING THE

REQUIREMENTS OF SPECIFICATION SECTION 02 82 11 OR 02 82 13.

6 WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL PENETRATIONS

AS NECESSARY.

7 DOOR TO BE SMOKE-RATED. SEE DOOR SCHEDULE AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE

DOOR WITH NEW ACCESS CONTROL HARDWARE.

8 REMOVE PORTION OF EXISTING SLAB TO PREPARE FOR NEW TR.

9 EXISTING UTILITIES ABOVE TO REMAIN. COORDINATE WITH NEW

PARITIONS AND PROVIDE RATED PENETRATIONS.

10 EXISTING ELECTRICAL PANELS TO BE RELOCATED AND

REINSTALLED WITH NEW TR.

1/4" = 1'-0" C7

ARCH ENLARGED FLOOR PLAN - GROUND LEVEL

1/4" = 1'-0" F7

ARCH ENLARGED DEMO FLOOR PLAN - GROUND LEVEL

1/4" = 1'-0" C5

ARCH ENLARGED RCP - GROUND LEVEL

1/4" = 1'-0" F5

ARCH ENLARGED DEMO RCP - GROUND LEVEL

DOOR AND FRAME SCHEDULE

IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL

FIRE

RATING

STC

Rating

HARDWARE

NOTESLEVEL ROOM NO. ROOM NAME DOOR NO.

WIDTH

H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICALW1

FIRST LEVEL 162 OFFICE 162 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD

FIRST LEVEL 162A TELECOM ROOM 162A 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD

GROUND LEVEL 002A TELECOM ROOM 002A 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD

SECOND FLOOR 210 TELECOM ROOM 210 3' - 6" 7' - 0" 1 3/4" EXT'G EXT'G --- --- 3/8" EXT'G EXT'G --- SEE SPEC SEE ELEC

DOOR SCHEDULE NOTES:

1. DOOR PANEL AND FRAME TO BE SMOKE-RATED FOR TRANSITION, INCLUDING CLOSER, SEALS, THRESHOLD, AND SWEEP.

2. PAINT DOOR TRIM TO MATCH EXISTING TRIM PAINT IN SPACE.

3. COORDINATE DOOR PANEL FRAME, AND HARDWARE WITH ELECTRICAL HARDWARE (ACCESS CONTROL, ELECTRICAL STRIKE, DOOR CONTACT SWITCH, ETC.) SEE ELECTRICAL PLANS FOR ADDITIONAL INFORMATION.

4. NEW DOOR PANEL AND FRAME - RE-USE EXISTING OFFICE DOOR HARDWARE.

SEE SPEC SEE ELEC

SEE SPEC SEE ELEC

1,3

1,2,3

1,2,3

2,4

F1

F1

F1

E1

E1

E1

E1

D1

D1

D1

D1

1" = 20'-0" F2

GROUND FLOOR REFERENCEPLAN

Revisions: Date:

Addendum 1 01/20/2022

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL

PROJECT REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW IT CLOSETS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

OFFICE

127 SF

POLICE /

SECURITY

SERVICE

123 SF

STORAGE

162A

42 SF

DUMB

WAITER

OFFICE

145 SF

OFFICE

167 SF

BUILDING 1ABUILDING 3

OFFICE

127 SF

POLICE /

SECURITY

SERVICE

123 SF

CORRIDOR

1CORR

322 SF

OFFICE

145 SF

CORRIDOR

1-CORR

367 SF

OFFICE

139 SF

TELECOM

ROOM

162A

148 SF

BUILDING 1ABUILDING 3

(EXT'G, VIF)

12'-1 1/4"

(E X

T 'G

, V

IF

'-2

/8

A

B

B

B

B

OFFICE

162162OFFICE

108108

CORRIDOR

1CORR1CORR

CORRIDOR

1-CORR1-CORR

POLICE /

SECURITY

SERVICE

107107

OFFICE

164164

STORAGE

162A

BUILDING 1ABUILDING 3

OFFICE

162162

OFFICE

164164

CORRIDOR

1CORR1CORR

CORRIDOR

1-CORR1-CORR

POLICE /

SECURITY

SERVICE

107107

OFFICE

108108

TELECOM

ROOM

162A162A

BUILDING 1ABUILDING 3

TELECOM

ROOM

162A162A A-402

C7

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

KEY PLAN

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

BUILDING

/30

/20

B

IM

/5

A

-2

-7

E H

R M

I n fr a s tr u c tu re U p g ra d e s

W ic h it a /5

A

-2

-7

E

H R

M

W ic h it a

B

A R

C H

.r v t

/1

/2

:4

:3

P

M

A-402

ARCHITECTURAL ENLARGED PLANS - FIRST

LEVEL

589A7-21-700

B3

06/30/21 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

5500 E KELLOGG, WICHITA, KANSAS 67218-1607

1 NEW IT CLOSET TO HAVE OPEN CEILING TO DECK

2 INFILL WINDOW OPENING TO MATCH ADJACENT FINISHES

3 TRIANGLE HATCH INDICATES AREA KNOWN TO CONTAIN ASBESTOS

CONTAINING MATERIAL, MASTIC AND FLOORING. CONTRACTOR TO

VERIFY EXTENT AND FULLY REMOVE, FOLLOWING THE

REQUIREMENTS OF SPECIFICATION SECTION 02 82 11 OR 02 82 13.

4 EXISTING WINDOW TO REMAIN, PROVIDE FURRING TO INFILL

OPENING ON INSIDE OF WALL FOR CONTINUOUS FINISH.

5 REMOVE CEILING TILE IN ROOM. ASBESTOS CONTAINING MASTIC IS

PRESENT AT BOTTOM OF THE HARD-LID CEILING STRUCTURE

ABOVE. CONTRACTOR TO VERIFY EXTENT AND QUANITIY OF

ASBESTOS CONTAINING MATERIAL AND DISPOSE OF PROPERLY AS

REQUIRED IN PROJECT SPECIFICATIONS.

6 INFILL WALL OPENING TO MATCH ADJACENT CONSTRUCTION FOR

CONTINUOUS FINISH.

7 EXISTING WALLS TO BECOME SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

8 DOOR TO BE SMOKE-RATED. SEE DOOR SCHEDULE AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE

DOOR WITH NEW ACCESS CONTROL HARDWARE.

9 REMOVE FLOORING AND WALL BASE. REFER TO INTERIOR PLANS

FOR ADDITIONAL INFORMATION.

10 EXISTING RAMP. COORDINATE NEW CONSTRUCTION WITH

EXISTING SLOPE.

1/4" = 1'-0" F7

ARCH DEMO FLOOR PLAN - FIRST LEVEL

1/4" = 1'-0" C7

ARCH FLOOR PLAN - FIRST LEVEL

1/4" = 1'-0" F5

ARCH RCP DEMO PLAN - FIRST LEVEL

1/4" = 1'-0" C5

ARCH REFLECTED CEILING PLAN - FIRST LEVEL

NOT TO SCALE

F1

FIRST LEVEL NEW TELECOM ROOM LOCATION

1/16" = 1'-0" B1

FIRST FLOOR REFERENCE PLAN

Revisions: Date:

Addendum 1 01/20/2022

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

1. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL

PROJECT REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

2. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

3. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

4. NEW IT CLOSETS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

5. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

6. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

7. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

OXYGEN

34 SF

CARDIOLOGY

TEAM

ADMIN

197 SF

HAC

34 SF

TLT

44 SF

CORRIDOR

2-CORR

331 SF

STORAGE

238 SF

OXYGEN

34 SF

CARDIOLOGY

TEAM

ADMIN

197 SF

HAC

34 SF

TLT

44 SF

CORRIDOR

2-CORR

331 SF

STORAGE

238 SF

STORAGE

106 SF

OXYGEN

34 SF

CARDIOLOGY

TEAM

ADMIN

197 SF

HAC

34 SF

TLT

44 SF

CORRIDOR

2-CORR

331 SF

TELECOM

ROOM

200A

117 SF

8'-7 7/8"

'-1

1/

2"

B

B

B

B

B

A4

A

A

STORAGE

106 SF

OXYGEN

34 SF

CARDIOLOGY

TEAM

ADMIN

197 SF

HAC

34 SF

TLT

44 SF

CORRIDOR

2-CORR

331 SF

TELECOM

ROOM

200A

117 SF

TELECOM

ROOM

200A

117 SF

A-403

B7

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

KEY PLAN

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

BUILDING

B

IM

/5

A

-2

-7

E H

R M

I n fr a s tr u c tu re U p g ra d e s

W ic h it a /5

A

-2

-7

E

H R

M

W ic h it a

B

A R

C H

.r v t

/1

/2

:5

:4

P

M

A-403

ARCHITECTURAL ENLARGED PLANS - SECOND

LEVEL

589A7-21-700

B19

06/30/21 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

5500 E. KELLOGG, WICHITA, KANSAS 67218-1607

1/4" = 1'-0" E7

ARCHITECTURAL SECOND LEVEL - DEMOLITION PLAN

1/4" = 1'-0" E4

ARCHITECTURAL SECOND LEVEL - REFLECTED CEILING DEMOLITION PLAN

1/4" = 1'-0" B7

ARCHITECTURAL SECOND LEVEL - PROPOSED PLAN

1/4" = 1'-0" B4

ARCHITECTURAL SECOND LEVEL - REFLECTED CEILING PLAN

1 MODIFY WALL FRAMING AS REQUIRED FOR NEW DOOR AND FRAME.

2 NEW DOOR AND FRAME. MODIFY WALL FRAMING AS REQUIRED.

3 EXISTING DOOR TO BECOME SMOKE RATED. SEE DOOR SCHEDULE

AND SPECIFICATION FOR ADDITIONAL INFORMATION. MODIFY DOOR

AS REQUIRED FOR NEW ACCESS CONTROL HARDWARE.

4 EXISTING WALLS TO BECOME SMOKE-RATED. MODIFY AS

REQUIRED TO EXTEND TO DECK ABOVE.

5 REMOVE SUSPENDED CEILING TILES AND GRID IN IT'S ENTIRETY.

6 TELECOM ROOM TO BE OPEN UP TO DECK ABOVE.

7 EXISTING RAMP WITH APPROX. 5" ELEVATION CHANGE.

COORDINATE WITH NEW CONSTRUCTION.

NOT TO SCALE

E2

SECOND LEVEL NEW TELECOM ROOM LOCATION

1" = 10'-0"

E1

SECOND FLOOR PLAN REFERENCE

Revisions: Date:

Addendum 1 01/20/2022

589A7-21-700_EHRM Infrastructure Upgrades_Addendum_1.20220120
SITE.AS100.ADD1.20220120
Sheets
AS100 - SITE PLAN - NEW COMMUNICATIONS BASE BID
SITE.T-602.ADD1.20220120
Sheets
T-602 - SITE PLAN - COMMUNICATIONS ONE-LINE DIAGRAM - NEW BASE BID
B01.A-402.ADD1.20220120
Sheets
A-402 - ARCHITECTURAL ENLARGED PLANS - FOURTH LEVEL
B03.A-401.ADD1.20220120
Sheets
A-401 - ARCHITECTURAL ENLARGED PLANS - GROUND LEVEL
B03.A-402.ADD1.20220120
Sheets
A-402 - ARCHITECTURAL ENLARGED PLANS - FIRST LEVEL
B19.A-403.ADD1.20220120
Sheets
A-403 - ARCHITECTURAL ENLARGED PLANS - SECOND LEVEL

File details come from the government source that posted it. Updated .