2of2_589A7-21-700.IFC_R3.B07.Telecom.20210630.pdf

PDF 5 MB Posted

Attached to
Z2DA--589A7-21-700 EHRM Infrastructure Upgrades Federal contract opportunity
Solicitation number
36C25522R0022
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This solicitation is for a construction project to upgrade electronic health records management infrastructure at the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15. Required work includes infrastructure upgrades, telecommunications installations and renovations, and low voltage cabling at 5500 E. Kellogg in Wichita, Kansas. The solicitation number is 36C25522R0022. Plans and specifications are provided to guide work on fire protection, mechanical, electrical and telecommunications systems. Responses are due by June 30, 2021, with award anticipated in July 2021.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--589A7-21-700 EHRM Infrastructure Upgrades, newest first.
File Type Posted
36C25522R0022 0002.pdf PDF
S02 Bldg 1 Hazardous Materials.pdf PDF
S02 Bldg 2 Hazardous Materials.pdf PDF
S02 01 00 00 Appendix A - Bid Form Template.Revision1.20220124.xlsx XLSX spreadsheet
S02 Bldg 19 Hazardous Materials.pdf PDF
S02 Bldg 13 Hazardous Materials.pdf PDF
S02 Bldg 7 Hazardous Materials.pdf PDF
S02 Bldg 26 Hazardous Materials.pdf PDF
S02 Bldg 61 Hazardous Materials.pdf PDF
S02 Bldg 60 Hazardous Materials.pdf PDF
S02 Infection Control Risk Assessment for Hospital Construction and Renovation.pdf PDF
S02 Bldg 20 Hazardous Materials.pdf PDF
S02 Bldg 16 Hazardous Materials.pdf PDF
S02 Bldg 3 Hazardous Materials.pdf PDF
S02 Bldg 11 Hazardous Materials.pdf PDF
S02 Bldg 6 Hazardous Materials.pdf PDF
S02 Bldg 10 Hazardous Materials.pdf PDF
S02 589A7-21-700 EHRM Wichita-Pre Bid Presentation.pdf PDF
S02 Bldg 34 Hazardous Materials.pdf PDF
S02 Bldg 4 Hazardous Materials.pdf PDF
S02 Bldg 12 Hazardous Materials.pdf PDF
36C25522R0022 0001.pdf PDF
S02 36C25522R0022 Addendum 1 Drawings.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19 Updated 12-14-2021.docx DOCX document
PreProposal Conference Site Visit Agenda - EHRM.doc DOC document
S02 589A7-21-700 EHRM Pre-Bid Sign In Sheet.pdf PDF
S02 Past Performance Questionnaire 36C25522R0002 Project 589A7-21-700.pdf PDF
36C25522R0022.pdf PDF
S02 Specifications 260511 thru 330800.pdf PDF
S02 Specifications 000100 thru 047200.pdf PDF
589A7-21-700.IFC_R3.B61.Gen-Elec.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B59.Gen-Elec.20210630.pdf PDF
589A7-21-700.IFC_R3.B20.20210630.pdf PDF
589A7-21-700.IFC_R3.B05.20210630.pdf PDF
589A7-21-700.IFC_R3.B02.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B01.Gen-Elec.20210630.pdf PDF
589A7-21-700.IFC_R3.SITE.20210630.pdf PDF
589A7-21-700.IFC_R3.B62.20210630.pdf PDF
589A7-21-700.IFC_R3.B60.20210630.pdf PDF
589A7-21-700.IFC_R3.B34.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B21.Gen-Elec.20210630.pdf PDF
2of2_589A7-21-700.IFC_R3.B21.Telecom.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B16.Gen-Elec.20210630.pdf PDF
2of2_589A7-21-700.IFC_R3.B16.Telecom.20210630.pdf PDF
589A7-21-700.IFC_R3.B13.20210630.pdf PDF
1of2_589A7-21-700.IFC_R3.B07.Gen-Elec.20210630.pdf PDF
589A7-21-700.IFC_R3.B06.20210630.pdf PDF
2of2_589A7-21-700.IFC_R3.B01.Telecom.20210630.pdf PDF
S02 01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
S02 Specifications 051200 thru 096900.pdf PDF
Show all 50

Z2DA--589A7-21-700 EHRM Infrastructure Upgrades has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTE: NOT ALL ABBREVIATIONS AND

SYMBOLS APPLY TO THIS PROJECT.

ELECTRICAL ABBREVIATIONS

CR

MD

MD

DC

ES

RX

SECURITY DOOR CONTACT. PROVIDE AND INSTALL 4S BACK BOX ABOVE DOOR WITH A 1" EMT

CONDUIT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE. PROVIDE ALL CONDUIT,

CONDUIT SUPPORT, CONNECTORS, COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET

BOX AND MUD RING.

WALL MOUNTED SINGLE SENSOR CAMERA. PROVIDE AND INSTALL 4S BACK BOX W/ A 1" EMT

CONDUIT STUBBED INTO NEAREST ACCESSIBLE CEILING SPACE (U.O.N). PROVIDE ALL CONDUIT, CONDUIT SUPPORT, CONNECTORS, COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET BOX

AND MUD RING. EACH CAMERA TO HAVE ONE(1) CATEGORY 6A CABLE PROVIDED BY SECURITY

CONTRACTOR. PROVIDE WITH MANUFACTURER'S WALL MOUNTING ACCESSORIES.

CARD READER OUTLET. PROVIDE AND INSTALL 4S BACK BOX AT SWITCH HEIGHT WITH A 1" EMT

CONDUIT CONNECTED TO THE DOOR CONTACT OUTLET BOX. PROVIDE ALL CONDUIT, CONDUIT

SUPPORT, CONNECTORS, COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET BOX AND MUD

RING.

VOICE / DATA OUTLET - FLOORBOX. PROVIDE AND INSTALL (4) CAT 6A CMP CABLES/JACKS

TERMINATED IN FLOOR BOX. PROVIDE AND INSTALL (2) 1-1/4" CONDUIT STUBBED TO NEAREST FURRED WALL , ROUTE CONDUIT TO ACCESSIBLE LOCATION ABOVE FINISHED CEILING. PROVIDE BUSHINGS AND PULLSTRING, U.O.N. USE EXISTING CONDUIT RISERS IN-WALL AND EXTEND ALL

CABLES TO NEW CABLE TRAY AND ROUTE TO TR INDICATED. SEE T-700 SERIES SHEETS FOR

NUMBER OF CABLES REQUIRED AT EACH WAO.

VOICE / DATA OUTLET - WALL MOUNTED. PROVIDE AND INSTALL (4) CAT 6A CMP CABLES / JACKS TERMINATED IN 6-PORT FACEPLATE AT 18" AFF. PROVIDE AND INSTALL 5S JBOX WITH SINGLE GANG MUDRING AND 1-1/4" CONDUIT STUBBED TO ACCESSIBLE CEILING LOCATION. PROVIDE BUSHINGS AND PULLSTRING, U.O.N. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER). USE EXISTING

CONDUIT RISERS IN-WALL AND EXTEND ALL CABLES TO NEW CABLE TRAY AND ROUTE TO TR

INDICATED. SEE T-700 SERIES SHEETS FOR NUMBER OF CABLES REQUIRED AT EACH WAO.

VOICE / DATA OUTLET - CEILING MOUNTED. PROVIDE AND INSTALL (2) CAT 6A CMP CABLES / JACKS

TERMINATED IN A 2-PORT FACEPLATE AT FINISHED CEILING. (NOTE: AT HARDLID CEILING

LOCATIONS PROVIDE AND INSTALL 5SJBOX WITH 1-1/4" CONDUIT STUBBED TO ACCESSIBLE CEILING LOCATION. PROVIDE BUSHINGS AND PULLSTRING, U.O.N.) SURFACE TYPE ("F" DENOTES FLUSH TYPE) USE EXISTING CONDUIT RISERS IN-WALL AND EXTEND ALL CABLES TO NEW CABLE TRAY AND ROUTE TO TR INDICATED. SEE T-700 SERIES SHEETS FOR NUMBER OF CABLES REQUIRED AT EACH

WAO.

REQUEST-TO-EXIT. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL 1" EMT CONDUIT

CONNECTED TO THE DOOR POSITION SWITCH BOX. PROVIDE

ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUIT, CONDUIT SUPPORT, CONNECTORS,

COUPLINGS, PLASTIC BUSHINGS, PULL STRINGS, OUTLET BOX AND MUD RING.

ELECTRIFIED DOOR HARDWARE. PROVIDE AND INSTALL 1" EMT CONDUIT CONNECTED TO THE

DOOR CONTACT OUTLET BOX.

CEILING MOUNTED SECURITY MOTION SENSOR. PROVIDE AND INSTALL 1-GANG BACK BOX AND (1) 1" CONDUIT STUBBED UP TO ACCESSIBLE CEILING SPACE. PROVIDE BUSHINGS AND PULLSTRING, U.O.N.

WALL MOUNTED SECURITY MOTION SENSOR. PROVIDE AND INSTALL 1-GANG BACK BOX AND (1) 1" CONDUIT STUBBED UP TO ACCESSIBLE CEILING SPACE. PROVIDE BUSHINGS AND PULLSTRING, U.O.N.

TELECOMMUNICATIONS DATA OUTLET ABOVE CEILING

A INTERCOMMUNICATION SYSTEM ( AI PHONE)

D D FURNITURE/EQUIPMENT FEED DEDICATED JUNCTION BOX. PROVIDE AND INSTALL RACO 260 5S JUNCTION BOX WITH (1) 1-1/4" CONDUIT TO ACCESSIBLE CEILING. EXTEND TO CABLE TRAY.

MOUNTING HEIGHT NOTES:

1. ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.

2. REFER TO EQUIPMENT ELEVATION DRAWINGS FOR COORDINATION WITH

CASEWORK.

3. MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.

4. REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL ELECTRICAL DEVICE

MOUNTING HEIGHTS AND DEVICE ALIGNMENT RULES.

WALL SWITCHES

RECEPTACLES

TELECOMMUNICATIONS OUTLETS

TELECOMMUNICATIONS OUTLETS - WALL PHONE

CLOCK OUTLETS

TV OUTLETS

PUSHBUTTONS

VOLUME CONTROLS

NURSE CALL STATIONS

NURSE CALL DOME LIGHTS

DIMMERS

ACCESS CONTROL DEVICES

VANITY LIGHT IN TOILET

INTERCOM

FIREMAN'S PHONE

FIRE ALARM - PULL STATIONS

FIRE ALARM DEVICES HORN/SPEAKERS/STROBES

(MOUNTING HEIGHT AT THE TOP OF THE FIRE ALARM DEVICE OR

6" BELOW CEILING WHICH IS LOWER)

4'-0" AFF

1'-6" AFF

1'-6" AFF

4'-0" AFF

7'-0" AFF

1'-6" AFF

4'-0" AFF

4'-0" AFF

4'-0" AFF

7'-6" AFF

4'-0" AFF

4'-0" AFF

6" ABOVE THE MIRROR, UON

4'-0" AFF

4'-0" AFF

4'-0" AFF

7'-2" AFF TO TOP

SECURITY SYSTEM SYMBOLS

TELECOMMUNICATION SYMBOLS

MOUNTING HEIGHTS

REFERENCE SYMBOLS

SECTION NUMBER

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING NUMBER WHERE DRAWN

E1-1.0

KEY NOTE

E1-1.0

DISCONNECT SWITCHES

MOTOR STARTERS

PANELBOARDS & CABINETS

INDIVIDUAL CIRCUIT BREAKERS

5'-6" AFF

5'-6" AFF

6'-0" AFF TO TOP

5'-6" AFF

WAP

WIRELESS ACCESS POINT OUTLET - CEILING MOUNTED. PROVIDE AND INSTALL (1) CAT 6A CMP CABLES / JACKS TERMINATED IN A SURFACE MOUNT BOX ABOVE FINISHED CEILING. (NOTE: AT HARDLID CEILING LOCATIONS, PROVIDE AND INSTALL 5S JBOX WITH 1-1/4" CONDUIT STUBBED TO ACCESSIBLE CEILING LOCATION. PROVIDE BUSHINGS AND PULLSTRING, U.O.N. TERMINATE CABLES ON JACKS IN 2-PORT FACE PLATE. PROVIDE 25FT. SLACK ON EVERY CABLE IF THE DISTANCE

ALLOWS. PROVIDE (1) CAT6A CMP GREEN TO VA-IDF.

SPST

SWBD

SYM

STD

SW

SPEC(S)

SPDT

SPKR

SF

SEC

SINGLE POLE SINGLE THROW

SINGLE POLE DOUBLE THROW

SYMMETRICAL

SWITCHBOARD

STANDARD

SWITCH

SECONDARY

SQUARE FOOT

SPECIFICATION(S)

SPEAKER

PRI

RCLP

RM

SCH, SCHED

RP

REF

REC/RCPT

RSC

RLA

RF

R, RE

QTY

PWR

PT

PVC

PA

PH, ∅

PF

PNL

PE

PB

P

OPP

OHE/T

OH

OFOI

OFCI

NO., NUM, #

OC

NTS

AMERICAN WIRE GAUGE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTOMATIC TRANSFER SWITCH

AMPERE INTERRUPTING CAPACITY

ALTERNATING CURRENT

ABOVE FINISHED COUNTER

AWG

BDF

B/BUR

BUILDING DISTRIBUTION FRAME

BURIED

AUTO

AUX

ARCH

AT

ATS

ALT

AFG

AIC

AFC

AFF

AC

AF

AUXILIARY

ALTERNATE

ARCHITECT

AUTOMATIC

AMPERES TRIP

AMPERE FRAME (BREAKER RATING)

MTG

NC

NEMA

NO

NIC

NEC

N

MV

MH

MOCP

MTD

MLO

MIN

MISC

MECH

MCC

MFR

MCA

MCB

RIGID STEEL CONDUIT

RATED (RUNNING) LOAD AMPS

RECEPTACLE PANELBOARD

ROOM

SCHEDULE

RADIO FREQUENCY

RECEPTACLE

REFRIGERATOR

RELOCATE AS SHOWN

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

REMOTE CONTROL LIGHTING PANEL

QUANTITY

POWER

PUBLIC ADDRESS

PANEL

PRIMARY

PULL BOX

POWER FACTOR

PHOTO ELECTRIC

PHASE

POLE

OPPOSITE

OWNER FURNISHED, CONTRACTOR INSTALLED

OWNER FURNISHED, OWNER INSTALLED

OVERHEAD ELECTRIC/TELEPHONE

OVERHEAD

ON CENTER

NOT TO SCALE

NUMBER

MOUNTING

NATIONAL ELECTRICAL CODE

MEDIUM VOLTAGE (OVER 600V LESS THAN

35KV)

NORMALLY CLOSED

NORMALLY OPEN

NOT IN CONTRACT

NEUTRAL

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAXIMUM OVERCURRENT PROTECTION

MOUNTED

MISCELLANEOUS

MAIN LUGS ONLY

MINIMUM

MANHOLE

MANUFACTURER

MECHANICAL

SWGR SWITCHGEAR

AIR HANDLING UNITAHU

MTS MANUAL TRANSFER SWITCH

PDP POWER DISTRIBUTION PANEL

AMPERESA OR AMP

OCPD OVERCURRENT PROTECTION DEVICE

A

M

B

N

O

P

Q

R

S

T

SPD SURGE PROTECTIVE DEVICE

OD OUTLET DESIGNATOR

LOW VOLTAGE (BELOW 50 VOLTS)

L-L

L-N

LTG

LV

LIGHTING

LINE TO LINE

LINE TO NEUTRAL

1000 CIRCULAR mils

KILOVOLTS (THOUSAND VOLTS)

KILOWATTS (THOUSAND WATTS)

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)

ISOLATED GROUND

KWH

LAN

LA

KW

KVA

Kcmil

KV

KILOWATT-HOURS

IR

KEY INTERLOCK

JUNCTION BOX

INCH/INCHES (")

INFRARED

GROUND FAULT INTERRUPTER

HAND-OFF-AUTOMATIC

HIGH PRESSURE SODIUM

HEATING VENTILATION AND AIR CONDITIONING

HERTZ

HVAC

HZ

HTR

HR

HT

HPS

HOA

HP

HEATER

HEIGHT

HORSEPOWER

HOUR

GFI

G, GND, GRD

GEN

FLUOR

FL, FLR

GROUND

GENERATOR

FOOT/FEET (')

FLUORESCENT

FLOOR

CMP

FIRE ALARM ANNUNCIATOR PANEL

EQUIPMENT GROUND

FAAP

FLA

FDR

FA

FULL LOAD AMPS

FEEDER

FIRE ALARM

FUSE

EG

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

DBB

dB

DAS

DISPLAY BACKBOX

DISTRIBUTED ANTENNA SYSTEM

DECIBEL

CPT

CU

CT

COM, COMM

CKT

CLG

COPPER

COMMUNICATIONS

CIRCUIT

CEILING

COMMUNICATIONS PLENUM (CABLE JACKET

RATING)

CB CONDUIT BANK

COMMUNICATIONS RISER (CABLE JACKET RATING)

FIRE ALARM CONTROL PANELFACP

FIRE ALARM EXTENDER PANELFAEP

CCTV CLOSED CIRCUIT TELEVISION

CP CONSOLIDATION POINT

FLEX FLEXIBLE

HAND HOLEHH

LIGHTING CONTROL PANELLC, LCP

LIGHTING PANEL

L-G LINE TO GROUND

CMR

F

FT

IN

IG

JB, JBOX

K

LP

FOOT CANDLEFC

DMARC POINT OF DEMARCATION BETWEEN UTILITIES OR

BETWEEN UTILITIES AND OWNER PREMISE

EQUIPMENT

C

D

E

F

G

H

I

J

K

L

HORIZONTAL MOUNTINGH

COR CONTRACTING OFFICER'S REPRESENTATIVE

X

XFMR

WP

WHM

W/

W/O

W

VFD

VA

V

UPS

UL

UON

UG

UGS

UGT

UGP

TYP

TV

TP

TEL,TELE

TELECOM

TC

TRANSFORMER

REMOVE DEVICE

WATT HOUR METER

WEATHERPROOF

VOLTS

VARIABLE FREQUENCY DRIVE/

VARIABLE FREQUENCY MOTOR

CONTROLLER

WITHOUT

WITH

WATTS

VETERANS ADMINISTRATION

UNDERGROUND PRIMARY

UNDERGROUND SECONDARY

UNDERGROUND TELEPHONE

UNDERWRITER'S LABORATORY

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

UNDERGROUND

TELECOMMUNICATIONS

TYPICAL

TELEVISION

TAMPERPROOF

TIME CLOCK

TELEPHONE

TB TERMINAL BLOCK

TBB TELEPHONE BACKBOARD

U

V

W

X

Z

TPST TRIPLE POLE SINGLE THROW

FDS FORWARD DEPLOYED SERVICES

JOINT SECURITY ARCHITECTUREJSA

PIV PERSONAL IDENTITY VERIFICATION

GENERAL NOTES

1. ALL TELECOMMUNICATIONS WORK SHALL COMPLY WITH THE LATEST EDITION OF VA STANDARDS TELECOMMUNICATIONS INFRASTRUCTURE STANDARDS AND CURRENT MANUFACTURER AND BICSI INSTALLATION PRACTICES. THESE STANDARDS HAVE BEEN ESTABLISHED TO EXCEED ALL CURRENT CODE AND BICSI INSTALLATION PRACTICE. ANY ITEMS THAT RAISE QUESTION SHALL BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION MANAGER AND REPRESENTATIVE IN WRITING. IT IS ALWAYS A BEST PRACTICE TO PROVIDE THE AHJ WITH DETAIL ON ANY AND ALL CONSTRUCTION ITEMS THAT COULD BE QUESTIONED BY THE AHJ. THE PROJECT DOCUMENTATION PACKAGE STANDARDS ARE NOT TO BE INTERPRETED NOR CONSIDERED AS AUTHORIZATION TO DEVIATE FROM ANY CODE OR REGULATION. IT IS THE CONTRACTOR’S RESPONSIBILITY TO VALIDATE THAT THESE REQUIREMENTS WILL MEET THE EQUIPMENT MANUFACTURER’S REQUIREMENT TO

PROVIDE A MINIMUM 25-YEAR SCS FOR ALL LABOR AND MATERIALS WARRANTIES.

2. IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN ITEMS INDICATED ON THE PLANS AND/OR SPECIFICATIONS OR WITH THE AHJ REQUIREMENTS, THE DOCUMENT WHICH PRESCRIBES AND ESTABLISHES THE COMPLETE JOB AS PER MANUFACTURER OR THE HIGHER STANDARD SHALL PREVAIL. ALL DISCREPANCIES ARE TO BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION

MANAGER AND THE VA REPRESENTATIVE IN WRITING IMMEDIATELY UPON DISCOVERY.

3. OMISSIONS FROM THE DRAWINGS OR FROM THE SPECIFICATIONS OR THE MISDESCRIPTION OF DETAILS OF WORK WHICH ARE CLEAR AND NECESSARY TO CARRY OUT THE INTENT FOR THE DRAWINGS AND SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR MISDESCRIBED DETAILS OF THE WORK.

THE CONTRACTOR SHALL NOTIFY THE CONSTRUCTION MANAGER AND VA REPRESENTATIVE UPON IDENTIFICATION OF SUCH OMISSIONS, MISDESCRIPTION, AND UNCLEAR DIRECTIONS IMMEDIATELY.

THE CONTRACTOR SHALL PERFORM ALL PROJECT TASKS AND ASSEMBLY BUILDS AS PER BICSI STANDARDS AND MANUFACTURER’S REQUIREMENTS ALONG WITH COORDINATING AND WORKING

WITH THE VA TO CORRECT SUCH DOCUMENTATION ERRORS.

4. THE CONTRACTOR SHALL CHECK ALL DRAWINGS FURNISHED IMMEDIATELY UPON THEIR RECEIPT AND PROMPTLY NOTIFY THE VA OF ANY DISCREPANCIES. THIS INCLUDES BUT NOT LIMITED TO, DISCREPANCIES BETWEEN DRAWINGS AND SPECIFICATIONS, OR DRAWINGS AND MANUFACTURER INSTALLATION INSTRUCTIONS, OR DRAWINGS AND GOVERNING CODES AND BEST PRACTICES. THE CONTRACTOR SHALL BRING TO THE ATTENTION OF THE CONSTRUCTION MANAGER AND VA COR ANY DISCREPANCIES BETWEEN DRAWINGS AND HOW THE CONTRACTOR NORMALLY DELIVERS THE

SERVICES DESCRIBED IN THE DRAWINGS OR SPECIFICATIONS.

5. ALL MATERIALS AND EQUIPMENT FURNISHED AND INSTALLED SHALL BE NEW AND FREE FROM ANY KNOWN DEFECT. ALL EQUIPMENT SHALL BEAR THE UNDERWRITERS LABORATORIES LABEL (UL™) LISTING, CLASSIFIED, AND/OR PERFORMANCE VERIFIED MARK OR FROM A VA APPROVED ALTERNATIVE TESTING ORGANIZATION. ALL MATERIALS SHALL BE INSTALLED AND USED IN THE MANNER FOR WHICH THE MANUFACTURER INTEND THEM FOR. THIS APPLIES FOR BOTH PIECE PARTS AND COMPLETE FUNCTIONING ASSEMBLIES.

6. CONTRACTOR IS REQUIRED TO RECEIVE WRITTEN APPROVAL FOR ALL RECOMMENDED AND REQUIRED WORK DEVIATIONS AND CLARIFICATIONS TO THE PLANS AND SPECIFICATIONS OF THIS

PROJECT BY THE VA AND ITS REPRESENTATIVES PRIOR TO ANY FIELD ACTIVITY.

7. ALL WORK MUST BE COMPLETED IN AS PER MANUFACTURER INSTALLATION REQUIREMENTS AND BICSI INSTALLATION PRACTICES. THE VA DEMANDS THE UTMOST PROFESSIONALISM WHEN WORK IS BEING PERFORMED ON CAMPUS AND HOLDS ALL CONTRACTORS TO THAT LEVEL OF PROFESSIONALISM. THE WORK SITE SHALL BE KEPT CLEAN AND FREE FROM DEBRIS. IT IS EVERY CONTRACTOR AND ALL THEIR REPRESENTATIVE’S RESPONSIBILITY TO GUARD AGAINST ANY DAMAGE TO VA PROPERTY AND THE IMMEDIATE REPAIR IF ANY DAMAGE IS CAUSED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONDUCTING A FINAL CLEANUP OF THE WORK SITE PRIOR TO FINAL SYSTEM ACCEPTANCE AS PART OF THE PUNCH-LIST PROCESS.

8. THE CONTRACTOR SHALL NOT BORE, NOTCH, OR IN ANY WAY CUT INTO ANY STRUCTURAL MEMBER WITHOUT WRITTEN APPROVAL FROM THE VA, ARCHITECT, AND STRUCTURAL ENGINEER. WITH PERMISSION FROM THE ABOVE AND PRIOR TO ALL CUTTING, DRILLING, NOTCHING, CORING, ETC. OF CONCRETE STRUCTURE AND FAÇADE THESE SURFACES SHALL BE X-RAYED OR GROUND PENETRATING RADAR USED TO ACCURATELY LOCATE REBAR, POST-TENSION CABLES & RODS, CONDUITS, AND ANY OTHER EMBEDDED POTENTIAL OBSTRUCTIONS TO

ENSURE THAT NO DAMAGE IS CAUSED TO ANY STRUCTURAL REINFORCEMENTS.

9. FOR THE PURPOSE OF CLEARNESS AND LEGIBILITY THE TELECOM DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC. THE SIZE AND LOCATION OF EQUIPMENT IS SHOWN TO SCALE WHEREVER POSSIBLE. THE CONTRACTOR SHALL VERIFY ALL FIELD CONDITIONS WITH INFORMATION INDICATED ON THE DRAWINGS AND DESCRIBED IN THE SPECIFICATION SECTIONS WHERE TELECOM WORK

INTERFACES WITH OTHER TRADES.

10. THE CONTRACTOR SHALL TAKE SPECIAL PRECAUTIONS WHEN WORKING IN AREAS WITH EXISTING CEILINGS AND SHALL BE RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILING TILES WITHOUT DAMAGING OR SOILING THE CEILING TILES. CHIPPED, DAMAGED, CRACKED, OR BROKEN TILES ARE THE CONTRACTOR’S RESPONSIBILITY TO REPLACE WITH LIKE TILES.

11. ALL FOOTAGES IDENTIFIED ON DRAWINGS OR SCALED OFF OF DRAWINGS ARE TO BE CONSIDERED ESTIMATES AND ARE RECOMMENDED TO BE FIELD VERIFIED BY CONTRACTOR PRIOR TO

ORDERING OF MATERIAL

12. ALL CABLE TRAYS, LADDER (TYPE) RACKING, CONDUIT, EQUIPMENT RACKS, PROTECTION PANELS, AND CABLE SHEATHS SHALL BE BONDED TO AN APPROVED TELECOMMUNICATIONS BONDING

ASSEMBLY.

13. ACCORDING TO TIA STANDARDS AND BICSI METHODOLOGIES PULL-BOXES LOCATED WITHIN A STRUCTURE ARE TO BE PLACED AT 100’ INCREMENTS AND PROPERLY SPACED WITHIN RUNS OF MORE THAN 150’. PULL-BOXES ARE TO BE PLACED IN CONDUIT RUNS THAT EXCEED A MAXIMUM OF 180-DEGREES IN CHANGES OF DIRECTION. TELECOMMUNICATIONS PULL-BOXES ARE TO BE SIZED AT A MINIMUM OF TWELVE (12) TIMES THE DIAMETER OF THE LARGEST CONDUIT. PULL-BOXES SHOULD NOT BE USED FOR CHANGES OF DIRECTION. THESE STANDARDS ARE TO BE ADHERED TO WHERE EVER PRACTICAL AND ANY DEVIATION TO THESE STANDARDS REQUIRES A SHOP-DRAWING, IF DISCOVERED DURING THE SUBMITTAL PHASE, TO REMEDIATE THE ISSUE OR BY AN RFI DURING THE CONSTRUCTION INSTALLATION PHASE. THE VA MAY ELECT TO INCREASE THE CONDUIT SIZE OR QUANTITY OF CONDUITS TO MITIGATE THE ISSUE FOR THE EXCESS LENGTH, ADDITIONAL QUANTITY OF CHANGES OF DIRECTION, AND/OR THE REDUCED SIZE OF PULL-BOXES WITHIN THE GIVEN PATHWAY. THE CONTRACTOR IS REQUIRED TO HAVE APPROVAL IN WRITING PRIOR TO ANY ROUGH-IN

WORK OR MATERIAL PROCUREMENT.

14. AS A STANDARD, ALL INTER-BUILDING PATHWAYS SHALL HAVE A MINIMUM OF 20% AVAILABLE CAPACITY AT THE SCHEDULED END OF THE PROJECT. SHOULD THIS PERCENTAGE NOT BE ACHIEVABLE, THIS ISSUE MUST BE BROUGHT TO THE ATTENTION OF THE CONSTRUCTION MANAGER AND THE VA REPRESENTATIVE.

15. WHERE PATHWAY CONSISTS OF MULTIPLE CONDUITS OR SLEEVES, A PATHWAY MUST BE FILLED TO CURRENT TIA AND BICSI INSTALLATION RECOGNIZED MAXIMUM FILL BEFORE UTILIZING THE NEXT

VACANT OR PARTIALLY FILLED PATHWAY.

16. OVERHEAD AND WALL MOUNTED LADDER (TYPE) RACKING INSTALLATION SHALL MATCH THE DRAWINGS AS CLOSELY AS POSSIBLE AND REQUIRES A SHOP DRAWING FOR EACH ROOM LOCATION.

THE PACKAGE IS TO INCLUDE A BILL OF MATERIALS WITH PART NUMBERS FROM RACKING MANUFACTURER FOR MOUNTING AND CONNECTION PIECE PARTS. PRIOR TO ANY ROUGH-IN WORK BEING

PERFORMED THESE SUBMITTALS MUST BE APPROVED BY THE VA REPRESENTATIVE.

17. ALL CABLING AND THEIR PATHWAYS PASSING THROUGH A RATED FIRE OR SMOKE BARRIER MUST BE PROPERLY SLEEVED AND FIRE STOPPED USING APPROVED (UL CLASSIFIED) FIRE STOP ASSEMBLIES. FIRESTOP ASSEMBLIES ARE TO BE INSTALLED PER THE MANUFACTURER’S INSTRUCTIONS FOR THE TYPE OF BARRIER, PATHWAY SIZE, AND QUANTITY OF CABLES THE FIRESTOP ASSEMBLY IS BEING INSTALLED FOR. CONTRACTOR IS REQUIRED TO MAINTAIN TRAINING RECORDS FOR ALL STAFF PERFORMING FIRESTOP ASSEMBLY INSTALLATION WORK.

18. CABLE PULLING – LINE/ROPE/TAPE SHALL BE PLACED IN ALL NEW CONDUITS. ALL CONDUITS SHALL ALSO BE CAPPED AND/OR PROPERLY FIRE STOPPED IN A MANNER APPROVED BY THE VA AND THE

AHJ.

19. EACH OSP CABLE SHALL BE EQUIPPED WITH A PERMANENT LABEL INDICATING CABLE TYPE, PAIR OR OPTICAL STRAND COUNTS, DISTANT END COMMONLY USED BUILDING NAME/NUMBER AND CABLE LENGTH. BOTH ENDS OF EACH CABLE SHALL BE LABELED CLEARLY SO THAT THEY CAN BE EASILY MATCHED TO EACH OTHER.

20. ALL CABLE SPLICES SHALL BE CONTAINED WITHIN AN APPROVED SPLICE CASE DESIGNED FOR THE LOCATION AND PURPOSE. THE SUBMITTAL FOR THE ENCLOSURE SHALL IDENTIFY WEATHER THE ENCLOSURE IS RE-ENTERABLE. AS PART OF THE SUBMITTAL A LISTING OF ANY AND ALL ADDITIONAL PARTS ARE REQUIRED TO RESTORE THE INTEGRITY OF THE ENCLOSURE SHOULD THE SPLICE

CASE BE REQUIRED TO BE ENTERED OPERATIONALLY.

21. OPTICAL FIBER CABLE SHALL BE PLACED WITH A MINIMUM OF THREE (3) METER MAINTENANCE LOOP AT EACH END OF THE RUN, AT EACH SIDE OF A SEISMIC JOINT, IN EACH MAINTENANCE HOLE (MH), VAULT, ETC. THE MAINTENANCE LOOP SHALL BE SECURED IN SUCH A MANNER TO PROVIDE MECHANICAL PROTECTION OF THE CABLE. AS PART OF THE SUBMITTAL PHASE THE CONTRACTOR IS TO PROVIDE SINGLE-LINE SHOP DRAWINGS OF THE LOCATIONS OF ALL MAINTENANCE LOOPS AND TO INCLUDE ANY RECOMMENDED LOOPS TO BE ADDED IN PULL-BOXES FOR EACH INDIVIDUAL

PATHWAY RUNS.

22. ALL OPTICAL FIBER CABLE SHALL BE TESTED USING ANSI/TIA STANDARDS AND BICSI INSTALLATION APPROVED TESTING PLATFORM. THIS TEST MUST BE PERFORMED BI-DIRECTIONALLY ON ALL STRANDS AND ALL RECORDS ARE TO BE OPENED AND VIEWED IN A STANDARD PLATFORM THAT DOES NOT CAUSE THE VA TO PURCHASE OR LICENSE FOR SUCH VIEWING. THE VA AT ITS DESECRATION MAY REQUIRE TO SEE THE TESTER’S CALIBRATION RECORD AND WILL NOTIFY THE CONTRACTOR OF THIS REQUEST PRIOR TO OR POST TESTING OPERATION. ALL BI- DIRECTIONAL

TESTING SHALL PERFORM TO THE FOLLOWING STANDARDS:

A. ANSI/TIA - 568.3-D

B. ANSI/TIA - 526.7

C. ANSI/TIA - 455

23. OPTICAL FIBER CABLE SPLICING SHALL UTILIZE FUSION SPLICING TECHNIQUES AND REQUIRE A SHOP DRAWING DURING THE SUBMITTAL PHASE OF THE PROJECT PRIOR TO ANY ROUGH-IN. ANY AND ALL CABLE SPICING REQUIRES A WRITTEN APPROVAL BY THE VA BEFORE ANY MATERIAL PURCHASING OR ROUGH-IN.

24. CONTRACTOR TO COORDINATE WAO AND SUPPORTING CONDUIT AND CABLE TRAY WITH THE ELECTRICAL CONTRACTOR WHERE THE ELECTRICAL CONTRACTOR IS A DIFFERENT ORGANIZATION

THAN LOW-VOLTAGE CABLING/CONDUIT CONTRACTOR FOR PROPER PLACEMENT.

25. ALL STATION CABLES SHALL BE NEATLY DRESSED AND SECURED EVERY FIVE FEET AT A MINIMUM.

26. ALL VA-IT STATION CABLES SHALL BE TERMINATED ON THE SAME FLOOR AS THE FLOOR SERVING BDF/IDF UNLESS OTHERWISE NOTED IN THESE DRAWINGS.

27. ALL STATION CABLING IS TO BE MECHANICALLY PROTECTED IN PLACE UNLESS OTHERWISE IDENTIFIED IN THESE DRAWINGS, BY A CONTRACT CHANGE RECORD, OR BY A RFI RESPONSE FROM THE

VA REPRESENTATIVE IN WRITING DIRECTING SURFACE-MOUNT EXPOSED AS THE CABLE INSTALLATION MEANS.

28. ALL NEW STATION CABLES SHALL BE TESTED AND DOCUMENTED USING RECOGNIZED MANUFACTURER INSTALLATION REQUIREMENTS AND BICSI INSTALLATION PRACTICES. UTP (CATEGORY) CABLE

TESTING RESULTS SHALL BE ONE TEST RECORD FOR EACH CABLE AND THE RECORD MUST INCLUDE THE VA APPROVED CABLE IDENTIFICATION STANDARD NAMING/NUMBERING SCHEME. OPTICAL FIBER TESTING SHALL FOLLOW ALL VA AND MANUFACTURER INSTALLATION PRACTICES. COAX TESTING SHALL FOLLOW BOTH VA AND SCTE CABLE TESTING PRACTICES.

29. THE VA REQUIRES A ONE (1) METER SLACK LOOP FOR ALL WAO SUPPORTED BY OPEN CEILING CABLE DISTRIBUTION. THE SLACK LOOP MUST BE SUPPORTED ABOVE THE WAO IN NEAT AND REPEATABLE FASHION THAT MEETS BOTH BICSI INSTALLATION AND MANUFACTURER PRACTICES.

30. ALL STATION OUTLETS, WAO, AND TERMINATION POINTS INCLUDING EXISTING WAO UTILIZED UNDER THIS PROJECT SCOPE SHALL BE PROPERLY LABELED AND IDENTIFIED USING THE STANDARD VA INTERNAL DISTRIBUTION NAMING/NUMBERING SCHEME. ALL LABELS ARE TO BE MACHINE GENERATED AND AN EXCEL TYPE MATRIX CREATED DEFINING LOCATION OF BOTH ENDS OF EACH LABELED CABLE. AS-BUILT CLOSEOUT PACKAGE MUST INCLUDE THESE STATION AND TERMINATION POINTS IDENTIFIED ON FLOOR PLANS FOR EACH LEVEL/FLOOR IN ADDITION TO THE STATION CABLING MATRIX. THE SAME CABLE IDENTIFICATION IS ALSO REQUIRED TO BE INCLUDED ON EACH CABLE TESTED RECORD BOTH HARD AND SOFT-COPY RECORD.

31. STANDARD WORKSTATION OUTLET (AKA WORK AREA OUTLETS OR WAO) SHALL CONSIST OF A 5S X 2-7/8” DEEP METAL BOX, FED WITH A MINIMUM 1-1/4” CONDUIT. BACK BOX TO BE FITTED WITH

SINGLE-GANG FINISH RING FOR 6-PORT FACEPLATE.

32. STANDARD WAO FACEPLATE SHALL CONSIST OF A SINGLE-GANG PLATE, 6-POSTION, WHITE IN COLOR, AND UNIVERSAL MULTI-PURPOSE PORTS TO SUPPORT THE FOLLOWING TERMINATIONS; UTP, SCTP, COAX, OPTICAL FIBER, USB, VARIOUS A/V CONNECTORS, ETC. ALL UNUSED PORTS SHALL BE FITTED WITH BLANK INSERTS.

33. STANDARD WORKSTATION CONSISTS OF A MINIMUM OF FOUR (4) CATEGORY 6A, CMP, GRAY, BLUE, AND WHITE CABLES.

34. INCLUDED AS PART OF THE CABLING AS-BUILT DOCUMENTATION PACKAGE, IT IS THE CONTRACTOR’S RESPONSIBILITY TO PROVIDE TO THE VA THE STRUCTURED CABLING SOLUTION

MANUFACTURER’S 25-YEAR WARRANTY CERTIFICATE FOR THE PROJECT.

35. THE WAO UTP 8-CONDUCTOR JACKS ARE DESCRIBED WITHIN THIS DOCUMENT SET AS RJ-45 JACKS/INSERTS. THE DESIGNERS ARE AWARE THAT ABBREVIATION RJ-45 IS A FCC –REGISTERED JACK

WITH 8-CONDUCTORS AND DESCRIPTION IN THIS DOCUMENT SET IS FOR A UTP CATEGORY CABLE RATED JACK/INSERT AND NOT FOR FCC INTERFACE JACKS.

36. ALL NEW CABLING SHALL CONFORM TO THE SCS INCLUDING BEING INSTALLED BY A CERTIFIED INSTALLER AND SIGNED OFF BY A MANUFACTURER REPRESENTATIVE.

37. NOT ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET ARE USED IN THE DRAWING SET CURRENTLY, BUT ARE THERE, SHOULD THE SCOPE GROW TO INCLUDE SUCH WORK.

38. THE CONTRACTOR SHALL PROVIDE WIRE GUARDS FOR ALL EXPOSED AUDIO, VISUAL, AND NETWORK DEVICES LOCATED IN AREAS THAT CAN BE SUBJECT TO VANDALISM SUCH AS WAITING ROOMS, RESTROOMS, LOCKER AND SHOWER ROOMS, MULTI-PURPOSE/DINING, CHECK-IN AREAS/LABS, & ASSEMBLY ROOMS. AND ALL HALLWAYS AND CORRIDORS ASSOCIATED WITH THESE SPACES

39. ALL CONDUITS CROSSING BUILDING SEISMIC SEPARATIONS OR EXPANSION JOINTS SHALL BE PROVIDED WITH APPROVED CONNECTORS. REFER TO ARCHITECTURAL PLANS FOR ALL EXPANSION

JOINT LOCATIONS.

40. COORDINATE INSTALLATION OF LIGHTING FIXTURES WITH CABLE TRAY AND EQUIPMENT IN BDF, IDF, AND ALL A/V ROOMS/SPACES TO MAINTAIN REQUIRED LIGHTING LEVELS WITH ALL EQUIPMENT IN

PLACE.

41. FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS OR SHOP DRAWINGS ON THE APPROVED DRAWINGS, THE INSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE ELECTRICAL

ENGINEER AND THE FIELD REPRESENTATIVE FOR THE VA.

42. VA, MANUFACTURER, BICSI INSTALLATION PRACTICES FOR PROJECT SUBMITTALS AND SHOP DRAWINGS ARE IDENTIFIED IN SPECIFICATIONS SECTIONS LISTED IN DIVISION 26, 27, AND 28, OF THE

PROJECT CONTRACT DOCUMENTATION SET.

43. J-HOOK ROUTING IS AN "IN-THE-FIELD" INSTALLATION CHOICE AND SHALL BE REQUIRED TO BE DOCUMENTED ON ALL AS-BUILT PACKAGES. SLEEVES REQUIRED TO COMPLETE THESE J- HOOK

ROUTINGS SHALL BE CONSIDERED AND INCLUDED IN THE J-HOOK ROUTE EQUIPMENT PACKAGE FROM THE CONTRACTOR AS CPCI PATHWAY EQUIPMENT. J-HOOK SLEEVES THROUGH RATED AND NON-RATED ASSEMBLIES SHALL NOT BE A REQUIREMENT OF THIS DRAWING PACKAGE AS THEY ARE FIELD DEFINED LOCATIONS AND QUANTITIES.

44. CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS SHOWING ALL PROPOSED CABLE ROUTING, CABLE TRAY LOCATIONS AND SIZING, J-HOOK LOCATIONS, PENETRATIONS, DEVICE LOCATIONS, EQUIPMENT LOCATIONS, WAO LOCATIONS, ETC. PRIOR TO BEGINNING WORK. THESE DRAWINGS SHALL BE COORDINATED WITH NEW AND EXISTING SYSTEMS TO MAINTAIN ALL REQUIRED CLEARANCES AND ACCESS FOR NEW AND EXISTING EQUIPMENT. COORDINATION DRAWINGS MUST BE REVIEWED AND APPROVED BY VA/AE PRIOR TO BEGINNING INSTALLATION WORK.

45. CONTRACTOR SHALL SUBMIT PROPOSED NEW RACK ELEVATIONS FOR EACH TELECOMMUNICATIONS ROOM/ RACK PRIOR TO BEGINNING WORK. TERMINATION LOCATIONS AND RACK

CONFIGURATIONS SHALL BE APPROVED PRIOR TO BEGINNING WORK.

46. CONTRACTOR SHALL SUBMIT WEEKLY CABLE TESTING/ TERMINATION REPORTS FOR VA/AE REVIEW AS AREAS ARE COMPLETED TO ENSURE CABLE PERFORMANCE MEETS BICSI AND CONTRACT

REQUIREMENTS.

47. INFECTION CONTROL PROTOCOL SHALL BE MAINTAINED AT ALL TIMES, INCLUDING NEGATIVE AIR HEPA FILTERED CONTAINMENTS. MOBILE HEPA CARTS SHALL BE USED FOR CABLE PULLING ACTIVITIES AS REQUIRED BY THE SPECIFICATIONS. COORDINATE ALL ACTIVITY WITH THE VA. SEE SPECIFICATION SECTION 01 35 26 SAFETY REQUIREMENTS FOR ADDITIONAL INFORMATION.

STANDARD OUTLET INFORMATION

X ROOM NUMBER - OUTLET DESIGNATOR

W WALL PHONE JACK @ +42" AFF (ADA)

H WALL PHONE JACK @ +84" AFF (ADA)

WP WEATHERPROOF

AV AUDIO VIDEO CABLES (SPECIFIC USE,

INSTALLED POINT TO POINT)

# NUMBER (IDENTIFICATION) OR COUNT

(#) NUMBER IS QUANTITY

A/E ARCHITECT/ENGINEER

AH AMPERE HOUR

AUTHORITY HAVING JURISDICTIONAHJ

ASSISTIVE LISTENING SYSTEMALS

ACCESS POINTAP

ALUMINUM, STEEL, POLYETHYLENEASP

AMERICAN SOCIETY FOR TESTING AND MATERIALSASTM

AUDIOVISUAL CONTRACTORAVC

BMS

BLDG

BUILDING

BUILDING

BS-IDF

BRKR, BKR

BUILDING SERVICES INTERMEDIATE DISTRIBUTION

FRAME

BREAKER

BTU BRITISH THERMAL UNIT

CATV COMMUNITY ANTENNA TELEVISION (CABLE

TELEVISION)

C CONDUIT

CONDUIT ONLY - WITH PULL WIREC.O.

CONSOLIDATION POINTCP

CAPTURED SCREW CONNECTORCSC

DISTRIBUTION PANEL

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROWDPDT

DWG

DPST

DIST

DISC

DC

DP

DN

DRAWING

DISTRIBUTION

DIRECT CURRENT

DISCONNECT

DOWN

DIV DIVISION

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

ELECTRIC, ELECTRICAL

ELECTRIC METALLIC CONDUIT

ELECTRICAL CONTRACTOR

EWC

EWH

ELEC

EQ, EQUIP

EM, EMERG

EMT

ELEV

ENCL

E.C.

EQUIPMENT

ELEVATOR

EMERGENCY

ENCLOSURE

EXISTINGE, EX, EXIST

X EMPTY (OUTLET WITH NO CABLE,

FUTURE USE).

F FURNITURE SYSTEM JACK

C COAXIAL CABLE RG-11

M WALL MOUNTED MONITOR

T VOIP - TELEPHONE

TV TELEVISION OUTLET

WAP WIRELESS ACCESS POINT

NOTES

1. WORK AREA OUTLET CONDUIT HAS BEEN DESIGNED FOR CATEGORY 6A CMP CABLE DISTRIBUTION WITH 5S BACK-BOX AND

1-1/4" IN CONDUIT.

2. FILL FACTOR IS CALCULATED USING 0.265 IN O.D. FOR SUPERIOR ESSEX CAT6A CMP 77-246-YB AT A WEIGHT OF 23 LBS/KFT.

EACHEA

ENTRANCE FACILITYEF

EMI ELECTROMAGNETIC INTERFERENCE

EMS EMERGENCY MANAGEMENT SYSTEM

ENT ELECTRICAL NONMETALLIC TUBING

FLOOR BOXFB

FDC OPTICAL - FIBER DISTRIBUTION CENTER

FEXT FAR END CROSSTALK

FIN FINISH

FIXT FIXTURE

FOC FIBER OPTIC CABLE

FPS FRAMES PER SECOND

GA GAUGE

GC GENERAL CONTRACTOR

GALVANIZD RIGID CONDUITGRC

INTERCOM

IDF

INSIDE DIAMETER OR INSIDE DIMENSION

INTERMEDIATE DISTRIBUTION FRAME

ID

IC

ISP INTERNET SERVICE PROVIDER

M METER

MAC MEDIA ACCESS CONTROL

MDF MAIN DISTRIBUTION FRAME

MM MULTI-MODE

MOB MEDICAL OFFICE BUILDING

MTU MULTI TENNET UNIT

WS WORK STATION

WiFi

WIRELESS FIDELITY (LOCALIZED WIRELESS USER

ACCESS INTERNET/NETWORK)

WAO WORK AREA OUTLET / WORK STATION OUTLET

WBS WORK BREAKDOWN STRUCTURE

V-A VOLTS-AMPERES

ND NETWORK DEVICE

NE NETWORK ENCLOSURE

NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NEXT NEAR END CROSSTALK

OF OPTICAL FIBER

OSP OUTSIDE PLANT

OTDR OPTICAL TIME DOMAIN REFLECTOMETER

POE POWER OVER ETHERNET

PPF PIXELS PER FOOT

PR PAIR

PSU POWER SUPPLY UNIT

PTP POINT-TO-POINT

REQ'D REQUIRED

RM ROOM

RMC RIGID METAL CONDUIT

RMS RACK MOUNTED SPACE

RNC RIGID NONMETALLIC CONDUIT

RU RACK UNIT

SAC SECURITY AND ACCESS CONTROL

SCS STUCTURED CABLING SOLUTION

ScTP SCREENED TWISTED PAIR

SM SINGLE-MODE

SNR SIGNAL TO NOISE RATIO

SQ SQUARE

STP SHIELDED TWISTED PAIR

SYS SYSTEM

TCP/IP TRANSMISSION CONTROL PROTOCOL/

INTERNET PROTOCOL

TE TELECOMMUNICATION ENCLOSURE

TGB TELECOMMUNICATIONS GROUNDING BUSBAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TR TELECOMMUNICATIONS ROOM OR SPACE

UD UNDERGROUND DUCT

UTP UNSHIELDED TWISTED PAIR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/5

A

-2

-7

E H

R M

I n fr a s tr u c tu re U p g ra d e s

W ic h it a

/5

A -2

-7

.E

R H

M .W ic h it a .B

.M E

P .r v t

/1

/2

:4

:4

A

M

T-001

TELECOMMUNICATION ABBREVIATIONS AND

SYMBOLS

589A7-21-700

B7

06/30/2021 M. Perkins G. Weaver

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

5500 E. KELLOGG, WICHITA, KANSAS 67218-1607

Revisions: Date:

/3

0/

/3

0/

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

MECH

STAIR

MECH.

MECH.

TECH SUPPORT

UTILITY

IT CLOSET

SUPERVISOR

STAIR

MECH.

CUBICLES

STORAGE

STORAGE

HSKP

HALL

ELEV

STORAGE

007A

HALL

HALL

007-A

006-A

006-B

003-A

003-AP-A

003-C

003-B

001-A 001-B 001-C

001-AP-A

001-D001-E

006-AP-A

TYP.

TYP.

TYP.

ELEV.

OFFICE

OFFICE

STORAGE

HALL

CONSULT #1

HALL

OFFICE

PSA

NURSE OFFICE

WOMENS R.R.

MENS R.R.

REAR ENTRY

HALL

OFFICE

OFFICE

REAR ENTRY

HALL

STAIR

STAIR

HALL

CUBICLES

LOBBY

HALL

WAITING

HALL

123-A

124-A

121-AP-A

121-B

121-A

115-A

115-AP-A

114-A

111-B

111-AP-A

111-A

112-A

106-AP-A106-B

102-A

101-A

TYP.

TYP.

TELECOM ROOM

103A

T-101

F5

TYP.

ELEVATOR

CUBICLES

OFFICE

UNI-SEX TOILET

OFFICE

CLOSET

OFFICE

OFFICE

OFFICE

HALL

STAIR 1

STAIR

HALL

LOBBY

HALL

213-A

213-AP-A

212-A

209A-A

211-A

208-A

203-F

203-G

207-A

203-E

203-D

203-C

203-B 203-A

201A-A

201-A

TYP.

TYP.

TELECOM ROOM

201A

T-101

F7

208-AP-A

203-AP-A

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/5

A

-2

-7

E H

R M

I n fr a s tr u c tu re U p g ra d e s

W ic h it a

/5

A -2

-7

.E

R H

M .W ic h it a .B

.M E

P .r v t

/1 /2

:0

:4

A

M

T-100

TELECOMMUNICATION PLANS - GROUND, FIRST,

AND SECOND LEVEL

589A7-21-700

B7

06/30/2021 M. Perkins G. Weaver

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

5500 E. KELLOGG, WICHITA, KANSAS 67218-1607

SCALE: 1/4" = 1'-0"

F2

TELECOMMUNICATION PLAN -

GROUND LEVEL

SCALE: 1/4" = 1'-0"

F4

TELECOMMUNICATION PLAN - FIRST

LEVEL

SCALE: 1/4" = 1'-0"

F7

TELECOMMUNICATION PLAN -

SECOND LEVEL

NOTE: NOT ALL KEYNOTES ARE USED ON EACH SHEET

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTEED SOLUTION FOR THE CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL

THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE

NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR

TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE

TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF

EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE

TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL

PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE

EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE

REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH

EXISTING CONDUIT CAPACITY.

H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO

PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE

OR JUNCTION BOX.

I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.

J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW

EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE

TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.

K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING

BACK TO THE RACK.

L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL

STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL

INFORMATION

M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL

TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE

DOCUMENTS. HANG ON THE WALL WITHIN THE IT CLOSET.

N. REFER TO T-600 SERIES SHEET FOR PHOTO DOCUMENTATION OF EXISTING

CONDITIONS.

1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS

ON SHEET T-501 FOR ADDITIONAL INFORMATION.

2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE

NEW CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON

SHEET T-501 FOR ADDITIONAL INFORMATION

3. EXISTING 4-POST RACK AND WIRE MANAGEMENT COMPONENTS TO REMAIN,

PROTECT IN PLACE.

4. PROVIDE NEW RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS

AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE

SPECIFICATIONS. PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION

AND TRANSFER DATA CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK.

PROVIDE TEMPORARY EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES

AND OTHER DEVICES TO ENSURE UNINTERRUPTED SERVICE. ONCE ALL

EXISTING DATA CIRCUITS ARE RELOCATED TO NEW PATCH PANELS ON THE

NEW RACK AND ALL EXISTING DEVICES TO REMAIN ARE TRANSFERRED TO THE

NEW RACK, REMOVE THE EXISTING RACK AND INSTALL THE NEW RACKS IN THE

FINAL PERMANENT POSITION.

5. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS

FOR ADDITIONAL INFORMATION.

6. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE

CAREFULLY PROTECTED IN PLACE UNTIL THE NEW RACK IS INSTALLED. ALL

EXISTING DEVICES ON THE EXISTING RACK SHALL BE TRANSFERRED TO THE

NEW LOCATION ON THE NEW RACK. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS SHOWING THE PROPOSED NEW RACK ELEVATION AND PROVIDE A

PHASING PLAN FOR TRANSFERRING ALL EXISTING DEVICES TO REMAIN TO THE

NEW RACKS.

7. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY

SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT

COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK.

COORDINATE FIXTURES WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

8. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION

SENSOR, AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN

WISENET XNP-6320. MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET.

INTEGRATE CAMERA INTO EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH

EXISTING IT NETWORK.

9. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.

10. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR

HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH

ENDS TO PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.

11. EXISTING 4" CONDUIT THROUGH WALL WITH ONE (1) 12F MULTI-MODE OPTICAL

CABLE TO BE PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND

FIBER IS INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT

SLEEVE AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A

PHASING PLAN FOR TRANSFERRING FIBER.

12. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.

13. PROVIDE (4) 4" CONDUIT RISER AND FIRE RATED PENENTRATION TO THE TR

ABOVE.

14. PROVIDE (4) " CONDUIT RISER AND FIRE RATED PENENTRATION TO THE FLOOR

BELOW.

15. PROVIDE NEW iSTAR EDGE (ESTAR002) ACCESS CONTROL SYSTEM. INSTALL

PER MANUFACTURERS RECOMMENDATIONS.

DEDUCT ALTERNATE #1:

REMOVE ALL SCOPE OF WORK ASSOCIATED WITH

TELECOM ROOMS 103A AND 201A. PROVIDE FIRE,

MECHANICAL, ELECTRICAL, AND TELECOMMUNICATIONS

SCOPE OF WORK FROM TELECOM ROOM 001 IN EXISTING

GROUND FLOOR TELECOM ROOM 009.

DEDUCT ALTERNATE #1:

REMOVE ALL SCOPE OF WORK ASSOCIATED WITH

TELECOM ROOMS 103A AND 201A. PROVIDE FIRE,

MECHANICAL, ELECTRICAL, AND TELECOMMUNICATIONS

SCOPE OF WORK FROM TELECOM ROOM 001 IN EXISTING

GROUND FLOOR TELECOM ROOM 009.

DEDUCT ALTERNATE #1:

REMOVE ALL SCOPE OF WORK ASSOCIATED WITH

TELECOM ROOMS 103A AND 201A. PROVIDE FIRE,

MECHANICAL, ELECTRICAL, AND TELECOMMUNICATIONS

SCOPE OF WORK FROM TELECOM ROOM 001 IN EXISTING

GROUND FLOOR TELECOM ROOM 009.

Revisions: Date:

OR ADDI

4-POST

TELECOM ROOM

103A

103A-A

A

-B

103A-C

TYP.

13103A-CAM-01

14 15

TELECOM ROOM

201A

201A-A

A

-B

201A-C

TYP.

WALL SYMBOL LEGEND

EXISTING CONSTRUCTION TO REMAIN

SMOKE AND 1-HR RATED FIRE

BARRIER AND OPENINGS

SMOKE AND 2-HR RATED FIRE BARRIER

AND OPENINGS

SMOKE BARRIER AND OPENINGS

1 HR RATED FIRE BARRIER AND

OPENINGS

2 HR RATED FIRE BARRIER AND OPENINGS

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

KEY PLAN

KEYNOTES

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/5

A

-2

-7

E H

R M

I n fr a s tr u c tu re U p g ra d e s

W ic h it a

/5

A -2

-7

.E

R H

M .W ic h it a .B

.M E

P .r v t

/1 /2

:0

:4

A

M

T-101

TELECOMMUNICATION ENLARGED PLANS 589A7-21-700

B7

06/30/2021 M. Perkins G. Weaver

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

5500 E. KELLOGG, WICHITA, KANSAS 67218-1607

SCALE: 1/2" = 1'-0"

F5

TELECOMMUNICATION ENLARGED

PLAN - FIRST LEVEL - ROOM 103A -

NEW

SCALE: 1/2" = 1'-0"

F7

TELECOMMUNICATION ENLARGED

PLAN - SECOND LEVEL - ROOM 201A -

NEW

A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,

FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.

B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL

OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW.

C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END

WARRANTEED SOLUTION FOR THE CABLING.

D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.

E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR

EXCEED CATEGORY 6A STANDARDS.

F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.

G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL

THINWALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE

NOTED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR

PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A

MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR

TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE

TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF

EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE

TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL

PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE

EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE

REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH

EXISTING CONDUIT CAPACITY.

H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO

PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE

OR JUNCTION BOX.

I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.

J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW

EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE

TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.

K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING

BACK TO THE RACK.

L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL

STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL

INFORMATION

M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL

TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE

DOCUMENTS. HANG ON THE WALL WITHIN THE IT CLOSET.

N. REFER TO T-600 SERIES SHEET FOR PHOTO DOCUMENTATION OF EXISTING

CONDITIONS.

1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH

EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS

ON SHEET T-501 FOR ADDITIONAL INFORMATION.

2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE

NEW CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON

SHEET T-501 FOR ADDITIONAL INFORMATION

3. EXISTING 4-POST RACK AND WIRE MANAGEMENT COMPONENTS TO REMAIN,

PROTECT IN PLACE.

4. PROVIDE NEW RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS

AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE

SPECIFICATIONS. PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION

AND TRANSFER DATA CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK.

PROVIDE TEMPORARY EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES

AND OTHER DEVICES TO ENSURE UNINTERRUPTED SERVICE. ONCE ALL

EXISTING DATA CIRCUITS ARE RELOCATED TO NEW PATCH PANELS ON THE

NEW RACK AND ALL EXISTING DEVICES TO REMAIN ARE TRANSFERRED TO THE

NEW RACK, REMOVE THE EXISTING RACK AND INSTALL THE NEW RACKS IN THE

FINAL PERMANENT POSITION.

5. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS

FOR ADDITIONAL INFORMATION.

6. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE

CAREFULLY PROTECTED IN PLACE UNTIL THE NEW RACK IS INSTALLED. ALL

EXISTING DEVICES ON THE EXISTING RACK SHALL BE TRANSFERRED TO THE

NEW LOCATION ON THE NEW RACK. CONTRACTOR SHALL PROVIDE SHOP

DRAWINGS SHOWING THE PROPOSED NEW RACK ELEVATION AND PROVIDE A

PHASING PLAN FOR TRANSFERRING ALL EXISTING DEVICES TO REMAIN TO THE

NEW RACKS.

7. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY

SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT

COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK.

COORDINATE FIXTURES WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

8. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION

SENSOR, AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN

WISENET XNP-6320. MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET.

INTEGRATE CAMERA INTO EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH

EXISTING IT NETWORK.

9. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.

10. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR

HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH

ENDS TO PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.

11. EXISTING 4" CONDUIT THROUGH WALL WITH ONE (1) 12F MULTI-MODE OPTICAL

CABLE TO BE PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND

FIBER IS INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT

SLEEVE AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A

PHASING PLAN FOR TRANSFERRING FIBER.

12. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.

13. PROVIDE (4) 4" CONDUIT RISER AND FIRE RATED PENENTRATION TO THE TR

ABOVE.

14. PROVIDE (4) " CONDUIT RISER AND FIRE RATED PENENTRATION TO THE FLOOR

BELOW.

15. PROVIDE NEW iSTAR EDGE (ESTAR002) ACCESS CONTROL SYSTEM. INSTALL

PER MANUFACTURERS RECOMMENDATIONS.

NOTE: NOT ALL KEYNOTES ARE USED ON EACH SHEET

DEDUCT ALTERNATE #1:

REMOVE ALL SCOPE OF WORK ASSOCIATED WITH TELECOM ROOMS 001,

103A, AND 201A. PROVIDE FIRE, MECHANICAL, ELECTRICAL, AND

TELECOMMUNICATIONS SCOPE OF WORK FROM TELECOM ROOM 001 IN

EXISTING GROUND FLOOR TELECOM ROOM 009.

Revisions: Date:

T B

B T

B B

TBBTBB

T B

B T

B B

T B

C T

B C

TBC TBC

T B

C T

B C

TBBTBB

T B

B T

B B

B B

C B

B C

B B

C B

B C

BBCBBC

TBBTBB

T B

B T

B B

SLACK LOOP

COMMUNICATION

CABLING

WALL

CONDUIT THROUGH

WALL TO OUTLET

4-11/16" SQUARE,

2-1/8" DEEP JUNCTION

BOX WITH 1-DEVICE

RAISED MUD RING

COVER PLATE

AT FIRE RATED WALLS

PROVIDE FIRE RATED

PATHWAY ("EZ PATH"

OR EQUIVALENT) PER

SPECIFICATIONS

AT FIRE RATED WALLS

PROVIDE FIRE RATED

PENETRATION PER

SPECIFICATIONS.

BASIS OF DESIGN: HILTI

SPEED SLEEVE.

FOR CABLE TRAY ONLY PENETRATIONS FOR CONDUIT PENETRATIONS

STRUCTURE

THREADED ROD

UNISTRUT

SUPPORTS

CABLE TRAY - VOICE DATA

CABLING ONLY

J-HOOKS FOR VOICE /

DATA CABLING

MOUNTED TO

THREADED ROD.

J-HOOKS SHALL NOT

EXCEED 4' ON CENTER

SPACING

TELECOM ROOM #

EQPT. RACK ID #

TR1-A

PATCH PANEL #A

WIRE MANAGEMENT

PATCH PANEL #B

WIRE MANAGEMENT

PATCH PANEL #C

WIRE MANAGEMENT

PATCH PANEL #

OUTLET ROOM #

OUTLET DESIGNATION

221-A

1 2 3 4 5 6

221-B

PANEL

221-C

7 8 9 10

221-D 222-A 222-B 222-C 222-D

223-A 223-B 223-C 223-D 224-A 224-B 224-C 224-D

11 12 13 14 15 16 17 18 19 20 21 22 23 24

43 44 45 46 47 4837 38 39 40 41 4231 32 33 34 35 3625 26 27 28 29 30

4-PAIR PLENUM CATEGORY 6A UTP TO

WORKSTATION OUTLETS

-TYPICAL

UTILIZE CABLE RADIUS OR STRINGER

DROP TO SUPPORT CABLE WEIGHT

AND MAINTAIN BEND RADIUS IN

TRANSITION FROM LADDER RACK TO

VERTICAL WIRE MANAGEMENT. USE AT

EACH LOCATION CABLES DESCEND

FROM LADDER RACK.

-TYPICAL

CONTRACTOR SHALL ROUTE

CABLES FROM ONE SIDE ONLY

WHERE A SINGLE VERTICAL WIRE

MANAGEMENT PANEL AT RACK.

CONTRACTOR TO SPLIT FEED OF HORIZ. DATA CABLES

ACROSS AND ABOVE/BELOW INDIVIDUAL PATCH PANELS.

AS DEPICTED. WHEN WIRING TO RACK(S).

-TYPICAL

CONTRACTOR SHALL BUNDLE ALL CABLES

WITHIN TELECOM CLOSETS AND ROOMS

USING HOOK-AND-LOOP ("VELCRO") TYPE

CABLE TIES ONLY. USE OF NYLON TIES

WITHIN TELECOM SPACES SHALL NOT BE

PERMITTED.

CONTRACTOR IS TO RUN CABLES INWARD FROM

REAR SIDE OF HORIZONTAL WIRE MANAGEMENT

TO PATCH PANEL 110 IDC'S. MAINTAIN CABLE

JACKET TIGHT TO CENTER OF INDIVIDUAL IDC.

CONTRACTOR IS NOT TO PLACE CABLES

IN "SIDEWAYS" ACROSS PATCH PANEL,

WITH CABLE BUNDLE BETWEEN 110 IDC'S.

DETAIL NOTE:

A CONTRACTOR REQUEST TO VARY FROM METHODOLOGIES ILLUSTRATED ABOVE MUST BE

SUBMITTED IN WRITING FOR TELECOMMUNICATIONS ENGINEER'S APPROVAL.

REQUEST MUST BE ACCOMPANIED BY LEGIBLE, DETAILED ILLUSTRATION AND PHOTO(S) OF PAST

PROJECTS DEPICTING METHODOLOGY REQUESTED. NO DEVIATIONS ACCEPTED WITHOUT

ENGINEER'S WRITTEN APPROVAL.

J-BOX #7 TEL CONDUIT #1 TR1-ER

TEL CONDUIT #2 TR1-ER

TEL CONDUIT #3 TR1-TR2

TEL CONDUIT #1 TR1-ER

TEL CONDUIT #2 TR1-ER

TEL CONDUIT #3 TR1-TR2

U-089-1-202A

CABLE #

ORIGIN (TR NAME)

DESTINATION (OUTLET NAME)

CABLE TYPE:

C = COPPER

F = FIBER

CX = COAX CABLE

U = UTP

LABEL WITHIN 6"

OF CABLE BREAKOUT

LABEL CABLE EVERY 4' MINIMUM

CABLE TRAY

CABLE RUNWAY

RADIUS DROP

BASIS OF DESIGN:

EATON B-LINE SERIES

VENTILATED TROUGH

1-1/4" CONDUIT & CONNECTOR.

4-11/16" SQUARE, 2-1/8" DEEP OR

5" SQUARE, 2-1/8" DEEP

JUNCTION BOX WITH KNOCKOUTS.

4-11/16" SQUARE

1-DEVICE RAISED

MUD RING.

CABLE LENGTH 12"

COIL IN BACK BOX

MODULAR JACK OR

BLANK AS NEEDED

FACEPLATE

CATEGORY 6A CABLES

(QTY AS INDICATED

ON PLANS)

1-1/4" KNOCKOUT

8-PIN MODULAR

CAT 6A

221-TR1

113-B

1.3.B.28

1.3.B.29

TELECOM ROOM #

TELECOM ROOM ID#

SERVICING CLOSET

PORT LABEL

OUTLET ID

OUTLET ID

OUTLET ROOM #

PATCH PANEL PORT

PATCH PANEL #

EQPT. RACK ID

TELECOM ROOM ID#

EXISTING CEILING MOUNTED WIRLESS

ACCESS POINT TO REMAIN, NOT SHOWN

FOR CLARITY

EXISTING OUTLET

BOX TO REMAIN

8-PIN MODULAR

CAT6A DATA/VOICE

BLANK

(FUTURE 8-PIN MODULAR

CAT6A DATA/VOICE)

8-PIN MODULAR

CAT6A DATA/VOICE

BLANK

(FUTURE 8-PIN MODULAR

CAT6A DATA/VOICE)

8-PIN MODULAR

CAT6A DATA/VOICE

8-PIN MODULAR

CAT6A DATA/VOICE

221-TR1

201-A

1.1.B.36 1.1.B.37

BLANK

PATCH PANEL PORT

PATCH PANEL #

EQPT. RACK ID

TELECOM ROOM ID#

TELECOM ROOM #

TELECOM ROOM ID#

SERVICING CLOSET

PORT LABEL

OUTLET ID

OUTLET ID

OUTLET ROOM #

BLANK

1.1.B.36 1.1.B.37

2700V INSULATORS

STAND-OFFS

COPPER BUS BAR.

BOLT CONNECTION WITH

COMPRESSION SPADE LUG

FITTING (TYPICAL)PROVIDE BONDING TO

CONNECTIONS TO

CABLE TRAY SYSTEMS

AND EQUIPMENT RACKS

(TYPICAL)

# 4/0 BARE COPPER - 1" PVC

CONDUIT TO MAIN TMGB

FIRST FLOOR

G

T-501 A7

RACK 1

12 2

RACK 2

1. NEW EQUIPMENT RACK, FREESTANDING, STEEL,

PROTECT IN PLACE. TELECOMUNICATIONS CHANEL

RACK, 19" RAILS, #12-24 TAPED EIA HOLE PATERN, 30"

DEP CHANEL MINIMUM, 7' HIGH, 45RU, WHITE.

2. NEW 6" VERTICAL WIRE MANAGEMENT SYSTEM,

PROTECT IN PLACE.

3. NEW 12" LADDER STYLE HORIZONTAL CABLE TRAY

MOUNTED ABOVE RACKS, PROTECT IN PLACE.

4. NEW 19" WIDE GROUND BUS BAR MOUNTED TO RACK.

5. NEW 20" X 4" TELECOMMUNICATIONS GROUNDING

BUSBAR. SEE SHEET T-501 FOR FURTHER INFORMATION.

6. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE

POWER SUPPLY (UPS) WITH NEMA 20A L21-20P INPUT

AND L21-20R OUTPUT. SEE T-502 FOR MORE DETAILS.

7. NEW "ZONEIT" 30A 3-PHASE PDU BASE UNIT, REQUIRES

(2) 30A 3-PHASE WYE CIRCIRCUITS WITH L21-30R

RECEPTACLES. SEE T-502 FOR MORE DETAILS.

Wichita

Wichita

PRIMARY BONDING

BUSBAR (PBB)

TYPICAL THIRD

LEVEL CLOSET

TYPICAL

MID- LEVEL CLOSET

LOWEST LEVEL

CLOSET

CABLE TRAY

TYPICAL

EQUIPMENT

RACK

TYPICAL

UP TO NEXT

CLOSET TYP)

STEEL

COLUMN

TYPICAL

SECONDARY BONDING

BUSBAR (SBB)

TYPICAL

RACK BONDING

BUSBAR (RBB)

TYPICAL

BONDING BUSBAR IN THE SERVICE

ENTRANCE ROOM OR GROUND

BUSBAR IN THE SERVICE ENTRANCE

SECTION (SES).

NOTES:

A. PROVIDE BONDING TERMINATIONS PER BICSI 607

REQUIREMENTS.

B. THE 'TBB' CONDUCTOR SHALL BE CONTINUOUS

BETWEEN THE FIRST AND LAST BONDING

BUSBARS IN STRING, DO NOT DAISY CHAIN THE

CONDUCTOR BETWEEN MULTIPLE BONDING

BUSBARS. REFER TO 'TBB' CONDUCTOR SIZING

CHART THIS SHEET FOR SIZE INFORMATION. THE

LENGTH OF CONDUCTOR IS FROM THE LOWEST

BONDING BAR TO THE HIGHEST FLOOR BONDING

BAR IN SINGLE STRING.

C. PROVIDE A 'BBC' CONDUCTOR AT THE TOP FLOOR

AND ON EVERY THIRD FLOOR IN A BUILDING WITH

MORE THAN THREE FLOORS. THE 'BBC' SHALL BE

SIZED AND ROUTED PER THE 'TBB'

REQUIREMENTS.

D. ALL CONDUCTORS ARE #6 AWG, UNLESS NOTED

OTHERWISE.

E. BOND ALL EXPOSED PIPE IN THE ROOM.

#6 AWG BONDING JUMPER FROM

TELECOM CABLE TRAY

TELECOMMUNICATIONS ROOM

GROUNDING BUS BAR.

#6 AWG BONDING JUMPER

FROM EACH TELECOM EQUIPMENT

RACK TO TELECOMMUNICATIONS

ROOM GROUNDING BUS BAR.

4 POST

V E

R T

IC

A

L W

IR

E

M A

N A

G E

M E

N T

LADDER STYLE CABLE TRAY

PROVIDE A #6 AWG BONDING JUMPER

TO THE GROUND BAR OF EACH

PANELBOARD LOCATED IN SAME ROOM.

PROVIDE A #6 AWG BONDING

JUMPER TO BUILDING STEEL

STRUCTURE

NTS

D7

TELECOMMUNICATIONS

OUTLET CONDUIT ROUTING

NTS

C4

CABLE TRAY / FIRE STOPPING

NTS

C3

CABLE TRAY DETAIL

NTS

C7

TELECOMMUNICATIONS EQUIPMENT

RACK IDENTIFICATION SCHEME

NTS

D3

(TYPICAL) PATCH PANEL LABELING - (3) CABLE OUTLET PATCH PANEL CONFIGURATION

NTS

D8

TYPICAL TELECOMMUNICATION RACK

WIRING METHODOLOGY REAR ELEV.

NTS

A8

TELECOMMUNICATIONS CONDUIT

IDENTIFICATION SCHEME

NTS

D1

TYPICAL CABLE IDENTIFICATION SCHEME

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/5

A

-2

-7

E H

R M

I n fr a s…