This is a product specification document for the EVO6 6-inch General Illumination Round Downlight manufactured by Gotham Architectural Downlighting. The document details a recessed LED downlight fixture featuring Bounding Ray optical design with 45° cutoff, unitized optics that mechanically attach the light engine to the lower reflector, and multiple distribution options ranging from very narrow to wide beam spreads.
The fixture offers lumen outputs from 250 to 17,500 lumens with efficacies up to 110 lumens per watt, color temperatures from 2700K to 5000K, and CRI options of 80 or 90+. Key features include 70% lumen maintenance at 60,000 hours, wet location rating for covered ceilings, dimming capabilities down to 1% or dark, Energy Star certification, and multiple control options including nLight wired and wireless systems. The document includes detailed photometric data, dimensional drawings, mounting specifications, and wiring diagrams for various control configurations. Multiple trim styles and finishes are available, including flangeless installation options using a micro-thin polymer mud ring system.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EVO6-OPEN
GOTHAM ARCHITECTURAL DOWNLIGHTING | 1400 Lester Road Conyers, GA 30012 | P 800-705-SERV (7378) | gothamlighting.com © 2014-2022 Acuity Brands Lighting Inc. All Rights Reserved. Rev. 11/09/22 Specifications subject to change without notice.
Luminaire Type:
Catalog Number:
Multiple Layers of Light
General Illumination Round Downlight 6"
OVERVIEW
COM
PLIM
EN
TARY PRODU
CTS
• Bounding Ray™ optical design
• Unitized optics mechanically attach the light engine to the lower reflector for complete optical alignment.
• 45° cutoff to source and source image
• Fully serviceable and upgradeable lensed LED light engine
• 70% lumen maintenance at 60,000 hours
• 2.5 MacAdam Ellipse; 85 CRI typical, 90+ CRI optional
• Fixtures are wet location, covered ceiling
• Available with 10% dimming, 1% dimming, or dim to dark
• Batwing distribution with feathered edges provides even illumination on horizontal and vertical surfaces
• ENERGY STAR® certified product
• UGR of zero for fixtures aimed at nadir with a cut-off equal to or less than 60deg per CIE 117-1995 Discomfort Glare in Interior Lighting. UGR FAQ
Feature Set
Distribution
Superior Performance
Very Narrow (VND)
0.5 S:MH
Narrow (ND)
0.7 S:MH
Wide (WD)
1.2 S:MH
Medium (MD)
0.8 S:MH
Medium Wide (MWD)
1.0 S:MH
Nominal Lumens 250 500 750 1000 1500 2000 2500 3000 3500 4000 4500 5000 6000 8000 10,000 12,000 15,000 17,500
Delivered Lumens 297 519 776 994 1471 2006 2537 3077 3542 4027 4533 5256 6371 8247 10637 12332 15776 17801
Wattage 3.4 6.2 8.2 9.6 14.7 19.7 24.7 29.5 33.8 39.0 47.3 48.7 57.6 74.9 97.1 115.0 150.9 175.3
Lumens per Watt 87.4 83.7 94.6 103.5 100.1 101.8 102.7 104.3 104.8 103.3 95.8 107.9 110.6 110.1 109.5 107.2 104.5 101.5
250 - 8,000 lumens
10,000 - 17,500 lumens
Coordinated Apertures | Multiple Layers of Light
EVO + Incito — Multiple Layers of LightGeneral Illumination Layer | EVO High Center Beam Layer | Incito
Downlight Adjustable Open Wallwash
Lensed Wallwash
Cylinder Pinhole Bevel Hyperbolic
MRI Surgical Suite
Patient Room
Dynamic Food Service Vandal/Tamper Clean Room Shower Steam Room
Core
Healthcare
Special Applications
*Based on 3500K AR LSS MWD 80CRI https://gothamlighting.acuitybrands.com https://www.acuitybrands.com/-/media/abl/acuitybrands/files/resources/customer-tools/lighting-design-resources/ab-ugr-faq.pdf?forceBehavior=open) https://www.acuitybrands.com/-/media/abl/acuitybrands/files/resources/customer-tools/lighting-design-resources/ab-ugr-faq.pdf?forceBehavior=open https://www.acuitybrands.com/resources/buy-american
GOTHAM ARCHITECTURAL DOWNLIGHTING | 1400 Lester Road Conyers, GA 30012 | P 800-705-SERV (7378) | gothamlighting.com © 2014-2022 Acuity Brands Lighting Inc. All Rights Reserved. Rev. 11/09/22 Specifications subject to change without notice.
General Illumination Round Downlight6"
A+ Capable options indicated by this color background.
Luminaire Type:
Catalog Number:
ORDERING NOTES
1. Not available with finishes.
2. Replace with applicable RAL number and finish when ready to order. See RAL BRO-
CHURE for available color options. Not available with emergency battery pack options.
3. Not available with emergency battery pack options.
4. Supplied with factory installed step down transformer.
5. Refer to TECH-240 for compatible dimmers.
6. Not available with nLight®.
7. Specify voltage.
8. For use with different reflector finish only (i.e. AR, PR, WTR, GR options). Not applicable with WR (white reflector) or FL (flangeless) option.
9. For use with different reflector finish only (i.e. AR, PR, WTR, GR options). Not applicable with BR (black reflector) or FL (flangeless) option.
10. ER for use with generator supply power. Will require an emergency hot feed and normal hot feed.
11. Fixture begins at 80% light level. Must be specified with NLT or NLTER. Only available with EZ10 and EZ1 drivers.
12. 12,000LM max with EL or nLight® options. 5,000LM max with Lutron drivers combined with EL. Not available with ELR, HAO, or EXAB, or any nLight® AIR dimming options.
13. Only available 5000LM - 15,000LM with eldoLED drivers.
14. Not available DALI or DMX drivers. Not available with CP or N80 options. Not recommended for metal ceiling installations.
15. When combined with the EZ1, EZ10, or EZB option, normal luminaires (non-emergency) can be used as a normal power sensing device for nearby nLight AIR devices and luminaires with EM emergency options.
ACCESSORIES – order as separate catalog numbers (shipped separately)
SCA6 Sloped ceiling adapter. Degree of slope must be specified (5D, 10D, 15D, 20D, 25D, 30D). Ex: SCA6 10D. Refer to TECH-190.
CTA EVO6 6" Aperture ceiling thickness adapter, for up to 8,000LM (extends mounting frame to accommodate ceiling thickness up to 5").
CTA4-8 YK 4"-8" Aperture ceiling thickness adapter for use with EDXB or CP up to 8,000LM, or nTune options (extends mounting frame to accommodate ceiling thickness up to 5").
CTA4-8 YKHL 6" Aperture ceiling thickness adapter, for 10,000LM and up (extends mounting frame to accommodate ceiling thickness up to 5"). For use with CWW/DWW trims, EDXB, CP or nTune options.
ISD BC 0-10V wallbox dimmer. Refer to ISD-BC.
ORDERIN
G IN
FORM
ATION
EXAMPLE: EVO6 35/150 AR MWD LSS MVOLT EZ1
Series Color Temperature Nominal Lumen Values Reflector & Flange Color Trim Style Finish
EVO6 27/ 2700 K
30/ 3000 K 35/ 3500 K 40/ 4000 K 50/ 5000 K
02 250 lumens 05 500 lumens 07 750 lumens 10 1000 lumens 15 1500 lumens 20 2000 lumens 25 2500 lumens 30 3000 lumens 35 3500 lumens
40 4000 lumens 45 4500 lumens 50 5000 lumens 60 6000 lumens 80 8000 lumens 100 10000 lumens 120 12000 lumens 150 15000 lumens 175 17500 lumens
AR Clear PR Pewter WTR Wheat GR Gold WR1 White BR1 Black WRAMF1 White Anti-microbial TRALTBD1,2 RAL paint for pricing only TCPC1 Custom paint color
(blank) Self-flanged FL Flangeless
LSS Semi-specular LD Matte-diffuse LS Specular
Distribution Voltage Driver4
VND Very Narrow (0.5 s/mh) ND Narrow (0.7 s/mh) MD Medium (0.9 s/mh) MWD Medium Wide (1.0 s/
mh) WD Wide (1.2 s/mh)
MVOLT
3472,3
GZ10 0-10V driver dims to 10% GZ1 0-10V driver dims to 1% EZ1 eldoLED 0-10V ECOdrive. Linear dimming to 1% min.
EZB eldoLED 0-10V SOLOdrive. Logarithmic dimming to <1%.
EDAB5 eldoLED SOLOdrive DALI. Logarithmic dimming to <1%.
EDXB5 eldoLED POWERdrive DMX with RDM (remote device management).
Square Law dimming to <1%. Includes termination resistor. Refer to DMXR Manual. Minimum 1000 lumens/Maximum 15000 lumens.
ECOD5 Lutron Ecosystem digital Hi-Lume 1% soft-on, fade to black. Max: 4000LM.
Control Interface Emergency Options Options
NLT6 nLight® dimming pack controls
NLTER2,6,9 nLight® dimming pack controls emergency circuit
NLTAIR213,14 nLight® AIR enabled
NLTAIRER22,9,13 nLight® AIR enabled emergency
NLTAIREM22,13 nLight® AIR Dimming Pack Wireless Controls. Controls fixtures on emergency circuit with battery pack options.
EL9 Emergency battery pack, 10W, with integral test switch
ELR9 Emergency battery pack, 10W, with remote test switch
ELSD9 Emergency battery pack, 10W, with self-diagnostics, integral test switch
ELRSD9 Emergency battery pack, 10W, with self-diagnostics, remote test switch
E10WCP9 Emergency battery pack, 10W Constant Power, CA Title 20 compliant with integral test switch
E10WCPR9 Emergency battery pack, 10W Constant Power, CA Title 20 compliant with remote test switch
BGTD Bodine generator transfer device.
Specify 120V or 277V.
SF Single fuse. Specify 120V or 277V.
TRW7 White painted flange TRBL8 Black painted flange FRALTBD2 Flange ring only RAL color for pricing only FCPC Flange custom paint color N8010 nLight® Lumen Compensation GTD generator transfer device. Specify 120V or 277V 90CRI High CRI (90+) CP11 Chicago Plenum. Specify 120V or 277V for 5000lm and above.
HAO12 HAO High Ambient Option (40°C) RRL_ RELOC®-ready luminaire connectors enable a simple and consistent factory installed option across all ABL luminaire brands. Available only with RRLA, RRLB, RRLAE, and RRLC12S. Refer to RRL spec sheet on www.acuitybrands.
com for RELOC® product specifications. Above ceiling access required.
https://gothamlighting.acuitybrands.com https://www.acuitybrands.com/-/media/abl/acuitybrands/files/resources/customer-tools/paint-colors/architectural-ral-color-brochure.pdf https://www.acuitybrands.com/-/media/abl/acuitybrands/files/resources/customer-tools/paint-colors/architectural-ral-color-brochure.pdf https://gothamlighting.acuitybrands.com/-/media/abl/gothamlighting/files/resources/technical-bulletins/tech-240.pdf http://www.acuitybrandslighting.com/library/GAL/documents/OtherDocuments/tech-190.pdf http://www.acuitybrandslighting.com/library/SYN/documents/SpecSheets/ISD_BC.pdf https://img.acuitybrands.com/public-assets/catalog/248102/rrl.pdf issac Rectangle issac Rectangle issac Rectangle issac Rectangle issac Rectangle issac Rectangle issac Rectangle issac Rectangle
GOTHAM ARCHITECTURAL DOWNLIGHTING | 1400 Lester Road Conyers, GA 30012 | P 800-705-SERV (7378) | gothamlighting.com © 2014-2022 Acuity Brands Lighting Inc. All Rights Reserved. Rev. 11/09/22 Specifications subject to change without notice.
General Illumination Round Downlight6"
Optical Assembly Optical design is a Bounding Ray™ design with 45° cutoff to source and source image. Top-down flash characteristic for superior glare control.
Unitized optics shall have mechanical attachment of the light engine to the lower reflector for complete optical alignment.
Electrical The luminaire shall operate from a 50 or 60 Hz ±3 Hz AC line over a voltage ranging from 120 VAC to 277 VAC. The fluctuations of line voltage shall have no visible effect on the luminous output.
The luminaire shall have a power factor of 90% or greater at all standard operating voltages and full luminaire output.
Sound Rated A+. Driver shall be >80% efficient at full load across all input voltages.
Input wires shall be 18AWG, 300V minimum, solid copper.
Controls Luminaire shall be equipped with interface for nLight wired or wireless network with integral power supply as per specification.
Dimming The luminaire shall be capable of continuous dimming without perceivable stroboscopic flicker as measured by flicker index (ANSI/IES RP-16-10) over a range of 100 – 10%, 100 – 1.0% or 100 – 0.1% of rated lumen output with a smooth shut off function to step to 0%.
eldoLED LED drivers shall conform to IEEE P1789 standards. Alternatively, manufacturers must demonstrate conformance with product literature and testing which demonstrates this performance. Systems that do not meet IEEE P1789 will not be considered.
Driver is inaudible in 24dB environment, and stable when input voltage conditions fluctuate over what is typically experienced in a commercial environment.
Construction Fully serviceable and upgradeable lensed LED light engine, both the driver and light engine are suitable for field maintenance and are serviceable from above or below the ceiling.
Luminaire housing shall be constructed of 16-gauge galvanized steel and have preinstalled telescopic mounting bars with maximum 32" and minimum 15" extension and 4" vertical adjustment.
Luminaires shall be suitable for installation in ceilings up to 1½" thick. (specify ceiling thickness adapter to extend frame to accommodate ceiling thickness up to 5").
Tool-less adjustments shall be possible after installation.
The assembly and manufacturing process for the luminaire shall be designed to assure all internal components are adequately supported to withstand mechan-ical shock and vibration.
25°C ambient temperature standard (1/2" clearance on all sides from non-combustible materials in non-IC applications, unless marked spacing noted oth-erwise). For use in insulated ceilings, a 3" clearance on all sides from insulation is required (unless marked spacing noted otherwise). 40°C high ambient optional.
Listings Fixtures are CSA certified to meet US and Canadian Standards: All fixtures manufactured in strict accordance with the appropriate and current requirements of the “Standards for Safety” to UL, wet location covered ceiling. Luminaire configurations are Energy Star certified through testing in EPA–recognized laborato-ries, with the results reviewed by an independent, accredited certification organization. Visit www.energystar.gov for specific configurations listed.
BUY AMERICAN ACT
This product is assembled in the USA and meets the Buy America(n) government procurement requirements under FAR, DFARS and DOT regulations. Please refer to www.acuitybrands.com/buy-american for additional information.
Photometrics LEDs tested to LM-80 standards. Measured by IESNA Standard LM-79-08 in an accredited lab. Lumen output shall not decrease by more than 30% over the minimum operational life of 60,000 hours.
Color appearance from luminaire to luminaire of the same type and in all configurations, shall be consistent both initially and at 60,000 hours and operate within a tolerance of <2.5 MacAdam ellipse as defined by a point at the intersection of the CCT line and the black body locus line in CIE chromaticity space.
Warranty 5-year limited warranty. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/warranty/terms-and-conditions
Note:
Actual performance may differ as a result of end user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
SPECIFICATION
S
Capable Luminaire This item is an A+ capable luminaire, which has been designed and tested to provide consistent color appearance and out-of-the-box control compatibility with simple commissioning.
• All configurations of this luminaire meet the Acuity Brands’ specification for chromatic consistency
• This luminaire is part of an A+ Certified solution for nLight® control networks when ordered with drivers marked by a shaded background*
• This luminaire is part of an A+ Certified solution for nLight® control networks, providing advanced control functionality at the luminaire level, when selection includes driver and control options marked by a shaded background* To learn more about A+, visit www.acuitybrands.com/aplus.
*See ordering tree for details https://gothamlighting.acuitybrands.com http://www.energystar.gov https://www.acuitybrands.com/resources/buy-american http://www.acuitybrands.com/support/warranty/terms-and-conditions http://www.acuitybrands.com/aplus
GOTHAM ARCHITECTURAL DOWNLIGHTING | 1400 Lester Road Conyers, GA 30012 | P 800-705-SERV (7378) | gothamlighting.com © 2014-2022 Acuity Brands Lighting Inc. All Rights Reserved. Rev. 11/09/22 Specifications subject to change without notice.
General Illumination Round Downlight6"
Flangeless
Flangeless Installation Gotham’s flangeless option utilizes a micro-thin polymer mud ring that mini-mizes the amount of drywall compound required to finish the ceiling. The end result is a virtually undetectable flangeless downlight installation.
The polymer mud ring is installed independent of the of the recessed frame, therefore floating with the ceiling. This innovation minimizes any surface cracks during reflector installation, ceiling movement and any future service to the recessed frame, wiring, electronics, etc.
Partially finished mud ring, showing cross-section detail.
An EVO downlight requires only approximately 3" of plaster to finish.
EVO with flangeless trim https://gothamlighting.acuitybrands.com
GOTHAM ARCHITECTURAL DOWNLIGHTING | 1400 Lester Road Conyers, GA 30012 | P 800-705-SERV (7378) | gothamlighting.com © 2014-2022 Acuity Brands Lighting Inc. All Rights Reserved. Rev. 11/09/22 Specifications subject to change without notice.
General Illumination Round Downlight6"
Tables of Use
Delivered Lumens = 1.25 x P x LPW
P = Output power of emergency driver. P = 10W for PS1055CP
LPW = Lumen per watt rating of the luminaire. This information is available on the ABL luminaire spec sheet.
How to Estimate Delivered Lumens in Emergency Mode
Marked Spacing in Inches 40°C Ambient
Lumen Package
Fixed Center to Center MIN
Fixture Center to Building Member MIN
Space Above Fixture
24 12 5
48 24 910000
12000
15000 72 36 9
Marked Spacing Chicago Plenum Enclosure in Inches 25°C Ambient
Lumen Package
Fixed Center to Center MIN
Fixture Center to Building Member MIN
Space Above Fixture
250-6000 None None None
8000 36 18 6
10000 48 24 3
12000
Marked Spacing Chicago Plenum Open Frame in Inches 25°C Ambient
Lumen Package
Fixed Center to Center MIN
Fixture Center to Building Member MIN
Space Above Fixture
250-5000 None None None
6000 24 12 5
36 18
10000
12000
15000
17500 72 36
Marked Spacing in Inches 25°C Ambient
Lumen Package
Fixed Center to Center MIN
Fixture Center to Building Member MIN
Space Above Fixture
500-5000 None None None
6000 24 12 5
36 18
10000
12000
15000
17500 72 36
Driver Control Provided
(note: 347V/UVOLT versions provided with 347 option selected)
Nomenclature Description NLT NLTER NLTAIR2 NLTAIRER2
GZ10 0-10V driver dims to 10% nPP16 D EFP nPP16 D ER EFP RPP20 D 24V G2 RPP20 D 24V ER G2
GZ1 0-10V driver dims to 1% nPP16 D EFP nPP16 D ER EFP RPP20 D 24V G2 RPP20 D 24V ER G2
EZ10 eldoLED 0-10V ECOdrive nPS 80 EZ nPS 80 EZ ER RPP20 D 24V G2 RPP20 D 24V ER G2
EZ1 eldoLED 0-10V ECOdrive nPS 80 EZ nPS 80 EZ ER RPP20 D 24V G2 RPP20 D 24V ER G2
EZB eldoLED 0-10V SOLOdrive nPS 80 EZ nPS 80 EZ ER RPP20 D 24V G2 RPP20 D 24V ER G2
EVO - eldoLED Driver Default Dimming Curve
Nomenclature Min Dimming Driver Dim Curve Control Dim Curve
EZ10 10% Linear Linear/Logarithmic
EZ1 1% Linear Linear/Logarithmic
EXA1 1% Linear Linear/Logarithmic
EZB <1% Logarithmic Linear
EDAB <1% Logarithmic Linear
EXAB <1% Logarithmic Linear
EDXB <1% Square Linear
GOTHAM ARCHITECTURAL DOWNLIGHTING | 1400 Lester Road Conyers, GA 30012 | P 800-705-SERV (7378) | gothamlighting.com © 2014-2022 Acuity Brands Lighting Inc. All Rights Reserved. Rev. 11/09/22 Specifications subject to change without notice.
General Illumination Round Downlight6"
DIM
EN
SION
AL DATA
250LM-5000LM Standard
6000LM-8000LM Standard
10,000LM-17,500LM Standard
6000LM-8000LM Battery Pack
10,000LM-17,500LM Battery Pack
250LM-5000LM Battery Pack
*Dimensions in inches [centimeters] Aperture: 6 1/4" [15.9)] Ceiling Opening: 7 1/8" [18.1] self-flanged
Overlap Trim: 7 1/2" [19.1] 7 1/4" [18.4] flangeless
9.94
22.50
19.10
15.64
19.10 7.49
15.64
15.91 7.49
16.86
15.91 9.94
9.94
22.50
19.10
15.64
19.10 7.49
15.64
15.91 7.49
16.86
15.91 9.94
9.94
22.50
19.10
15.64
19.10 7.49
15.64
15.91 7.49
16.86
15.91 9.94
9.94
22.50
19.10
15.64
19.10 7.49
15.64
15.91 7.49
16.86
15.91 9.94
Aperture: Ø 6-1/4" [15.9]
Ceiling Cutout: Ø 7-1/8" [18.1] Self-flanged
Overlap Trim: Ø 7-1/2" [19.1]
Ceiling Cutout: Ø 7-1/4" [18.4] Flangeless
1000LM-5000LM Standard
7 1/2" 19.010 15/16" 27.7
11 3/4" 29.9
Aperture: Ø 6-1/4" [15.9]
Ceiling Cutout: Ø 7-1/8" [18.1] Self-flanged
Overlap Trim: Ø 7-1/2" [19.1]
Ceiling Cutout: Ø 7-1/4" [18.4] Flangeless
1000LM-5000LM Battery Pack
7 1/2" 19.0 19" 48.3
19" 48.3
GOTHAM ARCHITECTURAL DOWNLIGHTING | 1400 Lester Road Conyers, GA 30012 | P 800-705-SERV (7378) | gothamlighting.com © 2014-2022 Acuity Brands Lighting Inc. All Rights Reserved. Rev. 11/09/22 Specifications subject to change without notice.
General Illumination Round Downlight6"
DIM
EN
SION
AL DATA
5000LM (Lutron & POWER Drive Only), 6000LM & 8000LM Open Frame CP
250LM - 6000LM CP Enclosed with Battery Pack and/or nLight™ Only
10000LM - 17,500LM Lumen Open Frame CP
*Dimensions in inches [centimeters]
7.55
17.72
15.91
9.79
18.59
15.91
9.45
16.70
21.66
8,000LM CP Enclosed with Battery Pack and/or nLight™ Only
10,000LM-12,000LM CP Enclosed with Battery Pack and/or nLight™ Only
12.5916.70
21.66
15.59 16.70
21.66
5000LM ECO/SOLO Drive Open Frame CP
7.55
18.39
15.91
250LM-4500LM CP
18-3/8
15-7/8 7-5/8
GOTHAM ARCHITECTURAL DOWNLIGHTING | 1400 Lester Road Conyers, GA 30012 | P 800-705-SERV (7378) | gothamlighting.com © 2014-2022 Acuity Brands Lighting Inc. All Rights Reserved. Rev. 11/09/22 Specifications subject to change without notice.
General Illumination Round Downlight6"
Photom etry
EVO6 35/15 AR MWD LS INPUT WATTS: 14.7, DELIVERED LUMENS: 1471LM, LPW= 100, 1.03 S/MH, TEST NO. LTL27783P1505
EVO6 35/45 AR MWD LS INPUT WATTS: 47.3, DELIVERED LUMENS: 4532.7LM, LPW= 95.8, 1.03 S/MH, TEST NO. LTL27783P1649
EVO6 35/175 AR MWD LS INPUT WATTS: 175.3, DELIVERED LUMENS: 17801LM, LPW=101.5, 1.06 S/MH, TEST NO. ISF 34035P268
PRINT DATE: TEST NO:
MANUFACTURER:
LUMINAIRE CATALOG NO.:
LUMINAIRE DESCRIPTION:
LUMENS PER LAMP:
[_LAMPTYPE]
[_FAMILY]
[_PRODUCTID]
[_APERTURE]
[_MOUNTING]
[_TOTALLUMINAIRELUMENS]
[_INPUTWATTAGE]
[_PHYSICALDIMENSIONS]
August 21, 2019 LTL27783P1505
Gotham Architectural Lighting
EVO6 35/15 6AR MWD LS
EVO 6IN ROUND, 80 CRI, 3500K, 1500LM, MED WIDE DIST, CLEAR, SPECULAR
1470.902
LED
EVO6 Downlight
63386fee-968b-4ef0-8e23-2c8cb7eecbb2
Recessed
1470.9
14.7
-0.52, -0.52, 0
0° 20°
40°
60°
80°
Ave Lumens
Zone Lumens % Lamp
0° - 30°
0° - 40°
0° - 60°
0° - 90°
90° - 180°
0° - 180°
1061.4
1393.5
1469.5
1470.9
0.0
1470.9
72.2
94.7
99.9
100.0
0.0
*100.0
*Efficiency
Coefficients of Utilization pf 20% pc 80% 70% 50% pw 50% 30% 10% 50% 30% 10% 50% 30% 10%
R C
R
50% beam -
54.4°
10% beam -
77.9°
Mounting
Height
Inital FC
Center
Beam Diameter FC Diameter FC
8.0
10.0
12.0
14.0
16.0
47.3
25.4
15.9
10.8
7.9
5.7
7.7
9.8
11.8
13.9
23.7
12.7
7.9
5.4
3.9
8.9
12.1
15.3
18.6
21.8
4.7
2.5
1.6
1.1
0.8
Spacing to Mounting Height:1.0
PRINT DATE: TEST NO:
MANUFACTURER:
LUMINAIRE CATALOG NO.:
LUMINAIRE DESCRIPTION:
LUMENS PER LAMP:
[_LAMPTYPE]
[_FAMILY]
[_PRODUCTID]
[_APERTURE]
[_MOUNTING]
[_TOTALLUMINAIRELUMENS]
[_INPUTWATTAGE]
[_PHYSICALDIMENSIONS]
August 21, 2019 LTL27783P1649
Gotham Architectural Lighting
EVO6 35/45 6AR MWD LS
EVO 6IN ROUND, 80 CRI, 3500K, 4500LM, MED WIDE DIST, CLEAR, SPECULAR
4532.66
LED
EVO6 Downlight ed1ca051-14fb-4c48-a55a-ae02682856fe
Recessed
4532.7
47.3
-0.52, -0.52, 0
0° 20°
40°
60°
80°
Ave Lumens
Zone Lumens % Lamp
0° - 30°
0° - 40°
0° - 60°
0° - 90°
90° - 180°
0° - 180°
3270.7
4294.2
4528.3
4532.7
0.0
4532.7
72.2
94.7
99.9
100.0
0.0
*100.0
*Efficiency
Coefficients of Utilization pf 20% pc 80% 70% 50% pw 50% 30% 10% 50% 30% 10% 50% 30% 10%
R C
R
50% beam -
54.4°
10% beam -
77.9°
Mounting
Height
Inital FC
Center
Beam Diameter FC Diameter FC
8.0
10.0
12.0
14.0
16.0
145.8
78.4
48.9
33.4
24.2
5.7
7.7
9.8
11.8
13.9
72.9
39.2
24.4
16.7
12.1
8.9
12.1
15.3
18.6
21.8
14.6
7.8
4.9
3.3
2.4
Spacing to Mounting Height:1.0
PRINT DATE: TEST NO:
MANUFACTURER:
LUMINAIRE CATALOG NO.:
LUMINAIRE DESCRIPTION:
OTHER:
LUMENS PER LAMP:
[_FAMILY]
[_PRODUCTID]
[_MOUNTING]
[_TOTALLUMINAIRELUMENS]
[_INPUTWATTAGE]
[_PHYSICALDIMENSIONS]
[_ATHD]
[_CURRENT]
[_LUMENS]
[_OFFSETS]
[_POWERFACTOR]
[_VOLTAGE]
August 21, 2019 ISF 34035P268
Gotham Architectural Lighting
EVO6 35/175 AR MWD LS
6IN DOWNLIGHT, 3500K, 17500LM, MEDIUM WIDE DIST, SPECULAR FINISH
LUMINIT 60 degree
17801.03
EVO 6 Downlight b20eba01-6b09-4542-8943-4be01ba06969
RECESSED DOWNLIGHT
17801.1
175.3
0.5, 0.5, 0
0.16%
0.82
9,923.30
X:65.00 Y:0.00
0.9911
119.73
0° 20°
40°
60°
80°
12800
Ave Lumens
16146
15998
16006
13362
Zone Lumens % Lamp
0° - 30°
0° - 40°
0° - 60°
0° - 90°
90° - 120°
90° - 130°
90° - 150°
90° - 180°
0° - 180°
12002.3
16291.0
17746.3
17801.0
0.0
0.0
0.0
0.0
17801.0
67.4
91.5
99.7
100.0
0.0
0.0
0.0
0.0
*100.0
*Efficiency
Coefficients of Utilization pf 20% pc 80% 70% 50% pw 50% 30% 10% 50% 30% 10% 50% 30% 10%
R C
R
50% beam -
55.7°
10% beam -
79.8°
Mounting
Height
Inital FC
Center
Beam Diameter FC Diameter FC
8.0
10.0
12.0
14.0
16.0
533.7
287.0
178.9
122.1
88.6
5.8
7.9
10.0
12.1
14.3
266.9
143.5
89.4
61.0
44.3
9.2
12.5
15.9
19.2
22.6
53.4
28.7
17.9
12.2
8.9
Spacing to Mounting Height:1.1
Lumen Output Multiplier
CRI CCT Multplier
2700K 0.96
300K 1.00
3500K 1.00
4000K 1.01
5000K 1.07
2700K 0.80
300K 0.83
3500K 0.85
4000K 0.87
5000K 0.91
Distributions
Nomenclature Beam Angle Field Angle
VND 30 64
ND 44 69
MD 54 82
MWD 67 89
WD 71 92
Reflector Finish Multiplier
Reflector Finish Multiplier
LS - Specular 1
LSS - Semi Specular 0.956
WR - White 0.87
LD - Matte Diffuse 0.85
BR - Black 0.73
GOTHAM ARCHITECTURAL DOWNLIGHTING | 1400 Lester Road Conyers, GA 30012 | P 800-705-SERV (7378) | gothamlighting.com © 2014-2022 Acuity Brands Lighting Inc. All Rights Reserved. Rev. 11/09/22 Specifications subject to change without notice.
General Illumination Round Downlight6"
A B
A
N
LIGH
T AIR
N
LIGH
T nLight® Wired Control Accessories Order as separate catalog number. Visit nLight.
Wall Switches
On/Off single pole
On/Off two pole
On/Off & raise/lower single pole
On/Off & raise/lower two pole
Graphic touchscreen
Photocell Controls
Dimming
Model Number nPODM (color) nPODM 2P (color) nPOD DX (color) nPODM 2P DX (color) nPOD GFX (color) nCM ADCX nLight® Wired Control Accessories (cont.)
Occupancy Sensors (PIR/dual tech)
Small motion 360o , ceiling
Large motion 360o , ceiling
Wide View
Wall switch with raise/lower
Cat-5 Cables (plenum rated)
10’, CAT5
15’, CAT5
Model Number nCM 9 / nCM PDT 9 nCM 10 / nCM PDT 10 nWV 16 / nWV PDT 16 nWSX LV DX / nWSX PDT LV DX
CAT5 10FT J1
CAT5 15FT J1
nLight® AIR is the ideal solution for retrofit or new construction spaces where adding communication wiring is cost prohibitive. The integrated nLight AIR rPP20 Power Pack is part of each EVO Luminaire ordered with the NLTAIR option.
These individually addressable controls offer the ultimate in flexibility during initial setup and for space repurposing.
nLight® The nLight® solution is a digital networked lighting control system that provides both energy savings and increased user configurability by cost effectively integrating time-based, daylight-based, sensor-based and manual lighting control schemes.
nLight® AIR Control Accessories Order as separate catalog number. Visit nLight AIR.
Wall Switches
On/Off single pole
On/Off two pole
On/Off & raise/lower single pole
On/Off & raise/lower two pole
Model Number rPODB (color) G2 rPODB 2P (color) G2 rPODB DX (color) G2 rPODB 2P DX (color) G2 nLight® AIR Control Accessories (cont.)
Occupancy Sensors (PIR/dual tech)
Small motion 360o , ceiling
Large motion 360o , ceiling
Model Number rCMS 9 / rCMS PDT 9 rCMS 10 / rCMS PDT 10
UL924 Sequence of Operation
The below information applies to all nLight AIR devices with an EM option.
• EM devices will remain at their high-end trim and ignore wireless lighting control commands, unless a normal-power-sensed (NPS) broadcast is received at least every 8 seconds.
• Using the CLAIRITY+ mobile app, EM devices must be associated with a group that includes a normal power sensing device to receive NPS broadcasts.
• Only non-emergency rPP20, rLSXR, rSBOR, rSDGR, and nLight AIR luminaires with version 3.4 or later firmware can provide normal power sensing for EM devices. See specification sheets for control devices and luminaires for more information on options that support normal power sensing.
CAT-5e Cable Line Power Low Voltage
Dimming Wires
Wiring Key nCM
Fixtures ordered without the NLT option nPODMA DX
Fixtures ordered with the NLT option nCM nPODMA DX nPS 80 EZ or nPP16 D rPP20 rPODBA DX RCMSB
Fixtures ordered without the NLTAIR option
CLAIRITYTM +
Mobile App rPODBA DX
CLAIRITYTM +
Mobile App
Fixtures ordered with the NLTAIR option
Line Power Low Voltage
Dimming Wires
Wiring Key
Possibilites for nLight® wired
Possibilites for nLight® AIR https://gothamlighting.acuitybrands.com https://www.acuitybrands.com/brands/lighting-controls/nlight https://www.acuitybrands.com/brands/lighting-controls/nlight
| Text Field 2: D1 (EM) |
| Text Field 3: |
| Text Field 4: |
| Text Field 5: |
| Text Field 6: |
| Text Field 7: |
| Text Field 8: |
| Text Field 9: |
| Text Field 10: |
| Text Field 11: |
| Text Field 12: |
| Text Field 13: |
| Text Field 14: |
| Text Field 15: |
| Text Field 17: |
| Text Field 16: |
File details come from the government source that posted it. Updated .