610A4-22-203 - BID Drawings.pdf

PDF 22 MB Posted

Attached to
Z1DA--Remodel Fort Wayne Chapel 610A4-22-203
Solicitation number
36C25025B0010
Issued by

About this file

This file contains the bid drawings for a chapel remodeling project at the Fort Wayne VA Medical Center (File #610A4-22-203). Based on the associated contract opportunity, these drawings detail the demolition and construction requirements for remodeling the chapel located at 2121 Lake Ave., Fort Wayne, IN 46805. The project requires adherence to infection control requirements and accounts for potential hazardous materials including asbestos and lead-based paint that may be encountered during demolition. While specific drawing details are not provided in this excerpt, they would show the technical specifications and architectural plans that contractors must follow to complete the 183-day renovation project for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.

View the file

Other files

File Type Posted
OF1419 Bid Abstract.xlsx XLSX spreadsheet
Amendment 6 - Conference Call Info.pdf PDF
36C25025B0010 A0005.pdf PDF
D1 - evo6-open.pdf PDF
000110 TABLE OF CONTENTS - Add1 2025-0228.pdf PDF
Ft Wayne VA Chapel - Lead Paint Report.pdf PDF
024120 SELECTIVE DEMOLITION - Add1 2025-0228.pdf PDF
A1 EM - Cove_LED_SPEC.pdf PDF
D1 EM - evo6-open.pdf PDF
RFIs and Responses for Remodel Fort Wayne Chapel.docx DOCX document
Ft Wayne VA Chapel - Asbestos Report.pdf PDF
Ft Wayne VA Chapel - ICRA PCRA.pdf PDF
A1 - Cove_LED_SPEC.pdf PDF
36C25025B0010 Amendment A0004.pdf PDF
D2 - KUZ1862833_specsheet.pdf PDF
A2 - upld.pdf PDF
A3 - Acolyte 1.0 Static White Micro RibbonLyte.pdf PDF
2025-0228 FWVA Chapel DRAWINGS Add1.pdf PDF
013526 SAFETY REQUIREMENTS - Add1 2025-0228.pdf PDF
087100 DOOR HARDWARE - Add1 2025-0228.pdf PDF
X1 - edg-edgr.pdf PDF
Amendment 3 - Bid Due Date Extension.pdf PDF
610A4-22-203 Remodel Fort Wayne Chapel Sign in sheet.pdf PDF
Environmental Requirements.docx DOCX document
Amendment 36C25025B0010 A0002.docx DOCX document
36C25025B0010 A00001.pdf PDF
610A4-22-203 - BID specs.pdf PDF
36C25025B0010 Solicitation.pdf PDF
Wage Determination.txt TXT text file
Contractor Certification Regarding Safety and Environmental.docx DOCX document
610A4-22-203 Basis of design cutsheets.pdf PDF
VHA Directive 1192 01.pdf PDF
RFI Form.doc DOC document
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA NORTHERN INDIANA HEALTH CARE SYSTEM

#610A4-22-203

DEPARTMENT OF VETERANS AFFAIRS

2121 LAKE AVENUE FORT WAYNE, IN 46805

REMODEL FORT WAYNE CHAPEL

G E N E R A L N O T E S

A. THE CONTRACT DRAWINGS AND SPECIFICATIONS (INDICATED BY THE SAME PROJECT NUMBER) ARE COMPLIMENTARY. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (C.O.R.) OF ANY DISCREPANCIES FOUND DURING

BIDDING AND THROUGH CONSTRUCTION.

B. DO NOT SCALE DRAWINGS; DIMENSIONS SHALL GOVERN.

C. THE GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND FIELD CONDITIONS PRIOR TO DEMOLITION AND CONSTRUCTION. IF PROVIDED, THE GENERAL CONTRACTOR SHALL EXAMINE EXISTING BUILDING DOCUMENTS. THE CONTRACTOR SHALL BRING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE CONTRACTING OFFICER

REPRESENTATIVE.

D. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF EXISTING ITEMS TO REMAIN DURING DEMOLITION AND

CONSTRUCTION.

E. IF CONSTRUCTION NOISE IS ANTICIPATED, SUBMIT A WRITTEN REQUEST TO THE C.O.R. FOR THE SCHEDULED TIME OF CONSTRUCTION ACTIVITIES. THE CONTRACTING OFFICER REPRESENTATIVE RESERVES THE RIGHT TO DISCONTINUE NOISY CONSTRUCTION AT ANY TIME. NO RADIOS SHALL BE PERMITTED AT ANY TIME IN WORK AREAS ADJACENT TO OCCUPIED SPACES.

F. ALL WORK SHALL BE DONE IN ACCORDANCE WITH APPLICABLE CODES AND FEDERAL AUTHORITIES, RULES AND REGULATIONS.

G. THESE DOCUMENTS SHOW DESIGN INTENT WITH MINIMUM CONSTRUCTION REQUIREMENTS AND MINIMUM QUALITY OF WORK EXPECTED. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS, METHODS AND TECHNIQUES FOR CONSTRUCTION

AND EXPECTED QUALITY.

H. ALL MATERIALS UTILIZED ON THIS PROJECT SHALL BE NEW UNLESS OTHERWISE NOTED TO BE SALVAGED AND REFURBISHED.

MATERIAL QUALITY SHALL MEET OR EXCEED APPLICABLE INDUSTRY STANDARDS.

I. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL EQUIPMENT INSTALLATION AND VARYING ALL REQUIRED ROUGH OPENINGS AND ROUGH-IN DIMENSIONS WITH THE EQUIPMENT MANUFACTURER AND C.O.R. PRIOR TO CONSTRUCTION.

J. FIELD VERIFY SIZES AND DIMENSIONS OF ALL EXISTING UTILITIES APPARATUSES IMPACTING NEW CONSTRUCTION. DETERMINE EXACT SIZE AND LOCATION OF PENETRATION WITHIN NEW CONSTRUCTION, TIGHTLY SEAL AND CAULK.

K. GENERAL CONTRACTOR SHALL HOST ONLINE CONSTRUCTION MANAGEMENT SOFTWARE FOR THE DURATION OF THE PROJECT.

CAMPUS LOCATION

Gravel Lot

LOT B

LOT A

LOT C LOT E

LOT F

LO

T

G

LOT H

R an da lia

D r

Lake Ave

CONTRACTOR

LAYDOWN AREA

PROJECT LOCATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EXP: 12/31/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:5

:4

P

M

GI001

COVER SHEET

20230901 PQ TD

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTS

VA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

GENERAL

GI001 COVER SHEET

GI002 ABBREVIATIONS AND SYMBOLS

GI003 OVERALL CODE AND LIFE SAFETY PLAN

ARCHITECTURE

AD101 DEMOLITION FLOOR PLAN AND REFLECTED CEILING PLAN

AD401 DEMOLITION ELEVATIONS

AE101 FLOOR PLAN AND REFLECTED CEILING PLAN

AE401 ELEVATIONS, SECTIONS, AND DETAILS

AE601 DOOR SCHEDULE AND CASEWORK DETAILS

AI101 FINISH PLAN AND SCHEDULE

ELECTRICAL

E001 LEGEND

EL101 ELECTRICAL DEMO AND NEW WORK PLAN

D R A W I N G I N D E X

N

NTS

VACINITY MAP

N

NTS

CAMPUS MAP

NOTE: RENDERINGS ARE FOR GENERAL UNDERSTANDING OF PROJECT SCOPE. THIS IS NOT INTENDED TO BE USED FOR CONSTRUCTION.

No. Revisions: Date:

BID DOCUMENTS 09/01/2023

A B B R E V I A T I O N S

A.B. ANCHOR BOLT

A.C.M. ASBESTOS CONTAINING MATERIALS

A.C.P. ASPHALT CONCRETE PAVING

A/C AIR CONDITIONING

ACOUS. ACOUSTIC

A.C.T. ACOUSTICAL CEILING TILE

A.D. AREA DRAIN

ADJ. ADJUSTABLE

AFF ABOVE FINISH FLOOR

AGG. AGGREGATE

AL. ALUMINUM

ALT. ALTERNATE

APPROX. APPROXIMATE

ARCH. ARCHITECT

ASPH. ASPHALT

BD. BOARD

BITUM. BITUMINOUS

BLDG. BUILDING

BLK. BLOCK

BLKG. BLOCKING

BM. BENCH MARK OR BEAM

BOT. BOTTOM

BRG. BEARING

BRK. BRICK

BRZ. BRONZE

BTWN. BETWEEN

B.U.R BUILT-UP ROOFING

CAB. CABINET

CARP. CARPET

C.B. CATCH BASIN

C.B.B. CEMENTITIOUS BACKER BOARD

CEM. CEMENT

CER. CERAMIC

CER.T. CERAMIC TILE

C.F.C.I. CONTRACTOR FURNISH/CONTRACTOR INSTALL

C.F.O.I. CONTRACTOR FURNISH/OWNER INSTALL

C.HK. COAT HOOK

C.I. CAST IRON

CIR. CIRCLE

C.J. CONSTRUCTION JOINT

CLG. CEILING

CLG.J. CEILING JOINT

CLKG. CAULKING

CLO. CLOSET

CLR. CLEAR

CLS. CLOSURE

CMU CONCRETE MASONRY UNIT

CNTR. COUNTER

C.O. CLEAN OUT

COL. COLUMN

COMB. COMBINATION

COMP. COMPOSITION

CONC. CONCRETE

CONN. CONNECTION

CONST. CONSTRUCTION

CONT. CONTINUOUS

CONV.O. CONVECTION OVEN

C.O.R. CONTRACTING OFFICER'S REPRESENTATIVE

CTR. CENTER

C.W. COLD WATER

CW. CURTAINWALL

DET. DETAIL

DF. DOUGLAS FIR

D.F. DRINKING FOUNTAIN

DIA. DIAMETER

DIAG. DIAGONAL

DIM. DIMENSION

DISP. DISPOSAL

DIV. DIVISION

DN. DOWN

D.O. DOOR OPENING

DR. DOOR

D.S. DOWN SPOUT

D.T. DRAIN TILE

D.W. DISHWASHER

DWG(S). DRAWING(S)

DWR. DRAWER

(E) EXISTING

EA. EACH

E.C. ELECTRICAL CONTRACTOR

E.E. EACH END

E.F. EXHAUST FAN

E.J. EXPANSION JOINT

ELEC. ELECTRICAL

ELEV. ELEVATION

E.N. EDGE NAIL

ENCL. ENCLOSURE

EQUIV. EQUIVALENT

E.S. EACH SIDE

E.W. EACH WAY

E.W.C. ELECTRICAL WATER CLOSET

EXP. EXPANSION

EXP.B. EXPANSION BOLT

EXPO. EXPOSURE

EXT. EXTERIOR

F. FACE

F.A. FIRE ALARM

F.B. FACE BRICK

F.BD. FIRE BOARD

F.BELL FIRE BELL

F.B.O. FURNISHED BY OTHERS

F.D. FLOOR DRAIN

FDN. FOUNDATION

F.E. FIRE EXTINGUISHER

F.E.C. FIRE EXTINGUISHER CABINET

F.F. FINISH FLOOR

F.G. FINISH GRADE

FGL. FIBERGLASS

F.H. FIRE HYDRANT

FH.M.S. FLAT HEAD MACHINE SCREW

FIN. FINISH

FIXT. FIXTURE

F.J. FLOOR JOIST

F.L. FLOOR LINE

FLASH FLASHING

FLOUR FLUORESCENT

FLR. FLOOR

F.N. FACE NAIL

F.O.B. FACE OF BUILDING

F.O.C. FACE OF CONCRETE

F.O.F. FACE OF FINISH

F.O.M. FACE OF MASONRY

F.O.S. FACE OF STUD

F.R.T.W. FIRE RETARDANT TREATED WOOD

F.S.C. FIRE SUPPRESSION CONTRACTOR

F.S.E.C. FOOD SERVICE EQUIPMENT CONTRACTOR

FTG. FOOTING

FUT. FUTURE

F.V.C. FIRE VAULT CABINET

GA. GAUGE

GALV. GALVANIZED

G.C. GENERAL CONTRACTOR

G.B. GRAB BAR

G.D. GARBAGE DISPOSAL

G.E. GRATE ELEVATION

G.I. GALVANIZED IRON

GL. GLASS

GLB. GLUE LAMINATED BEAM

GND. GROUND

GR. GRADE

G.S.M. GALVANIZED SHEET METAL

GYP.BD. GYPSUM BOARD

H.B. HOSE BIB

HC. HANDICAPPED

HDR. HEADER

HDWD. HARDWOOD

HDWE. HARDWARE

HGT. HEIGHT

H.M. HOLLOW METAL

HORIZ. HORIZONTAL

H.P. HIGH POINT

HR. HOUR

H.S.S. HOLLOW STRUCTURAL STEEL

HTG. HEATING

H.V.A.C. HEATING, VENTILATION & AIR CONDITIONING

H.W. HOT WATER

I.D. INSIDE DIAMETER

INSUL. INSULATION

INT. INTERIOR

INV. INVERT

JAN. JANITOR

J.H. JOIST HANGER

JST. JOIST HANGER

JT. JOINT

KIT. KINTCHEN

LAB LABORATORY

LAM. LAMINATE

LAV. LAVATORY

L.B. LAG BOLT

L.H. LEFT HAND

L.L. LIVE LOAD

L.P. LOW POINT

LT. LIGHT

MAT. MATERIAL

MAX. MAXIMUM

M.B. MACHINE BOLT

M.C. MEDICINE CABINET

MECH. MECHANICAL

MED. MEDIUM

MEMB. MEMBRANE

M.E.P. MECHANICAL, ELECTRICAL, PLUMBING

MFG. MANUFACTURER

MH. MANHOLE

MIN. MINIMUM

MIR. MIRROR

MISC. MISCELLANEOUS

M.O. MASONRY OPENING

MOD. MODULAR

MP.H. MOP HOLDER

MR. FRAMED MIRROR

M.R. MOISTURE RESISTANT

M.T. METAL THRESHOLD

MTD. MOUNTED

MTL. METAL

(N) NEW

N. NORTH

NAT. NATURAL

N.I.C. NOT IN CONTRACT

(NOT PART OF OSA APPROVAL)

NO. NUMBER

NOM. NOMINAL

NON/COM NON-COMBUSTIBLE

N.T.S. NOT TO SCALE

O/ OVER

O.A. OVERALL

OBS. OBSCURE

O.C. ON CENTER

O.D. OUTSIDE DIAMETER

O.F. OVERFLOW

OFF. OFFICE

O.F.S. OUTSIDE FACE OF STUD

O.H.W.S. OVAL HEAD WOOD SCREW

OPP. OPPOSITE

P. PAINT

P.C. PLUMBING CONTRACTOR

P.C.F. POUNDS PER CUBIC FOOT

P.E.N. PANEL EDGE NAILING

PERF. PERFORATED

PL. PLATE

P.LAM PLASTIC LAMINATE

PLAS. PLASTER

P.L.F. POUNDS PER LINEAR FOOT

PLYWD. PLYWOOD

P.M.F. PRESSED METAL FRAME

PR. PAIR

PROP. PROPERTY

P.S.F. POUNDS PER SQUARE FOOT

P.S.I. POUNDS PER SQUARE INCH

P.STA. PULL STATION

PTD. PAINTED

P.T.D. PAPER TOWEL DISPENSER

PT. POINT

P.T.D.F. PRESSURE TREATED DOUGLAS

FIR

PTN. PARTITION

P.T.R. PAPER TOWEL RECEPTACLE

P.V.C. POLYVINYL-CHLORIDE

Q.T. QUARRY TILE

RAD. RADIUS

R.B. RUBBER BASE

R.C.P. REFLECTED CEILING PLAN

R.D. ROOF DRAIN

RDWD. REDWOOD

REF. REFERENCE

REFR. REFRIGERATOR

REINF. REINFORCING

REQD. REQUIRED

RESIL. RESILIENT

R.H. ROOF HATCH

R.HK. ROBE HOOK

R.H.M.S. ROUND HEAD METAL SCREW

R.H.W.S. ROUND HEAD WOOD SCREW

RM. ROOM

R.O. ROUGH OPENING

R.W.L. RAIN WATER LEADER

S. SOUTH

S.A.B. SOUND ATTENUATION BATT

S.A.D. SEE ARCHITECTURAL DRAWINGS

S.A.F.F. SELF ADHERED FLEXIBLE FLASHING

S.A.S.M. SELF ADHERED FLEXIBLE MEMBRANE

S.BLKG. SOLID BLOCKING

SCWD. SOLID CORE WOOD DOOR

S.C.D. SEE CIVIL DRAWINGS

S.D. STORM DRAIN

S.DISP. SOAP DISPENSER

SEAL. SEALANT

SECT. SECTION

S.E.D. SEE ELECTRICAL DRAWINGS

SHR. SHOWER

SHT. SHEET

SHTG. SHEATHING

SIM. SIMILAR

SL. SLIDING

S.L.D. SEE LANDSCAPE DRAWINGS

S.M.D. SEE MECHANICAL DRAWINGS

S.N.D. SANITARY NAPKIN DISPOSAL

S.N.V. SANITARY NAPKIN DISPENSER

S.P. SOUNDPROOF

SPEC. SPECIFICATION

SQ. SQUARE

SQ.FT. SQUARE FOOT (FEET)

S.S. SANITARY SEWER

S.S.D. SEE STRUCTURAL DRAWINGS

STA. STATION

STD. STANDARD

STL. STEEL

S.STL. STAINLESS STEEL

STO. STORAGE

STRUC. STRUCTRUAL

SUSP. SUSPENDED

T.B. TACKBOARD

T&B. TOP AND BOTTOM

TEL. TELEPHONE

TEMP. TEMPERED

TER. TERRAZZO

T&G. TOUNGE AND GROOVE

THK. THICK

T.J. TOOL JOINT

T.N. TOE NAIL

T.O.C. TOP OF CURB

T.O.P TOP OF PAVEMENT

T.O.PL. TOP OF PLATE

T.O.S. TOP OF SEAT

T.O.W. TOP OF WALL

T.P.D. TOILET PAPER DISPENSER

T.S. TUBE STEEL

T.V. TELEVISION

TYP. TYPICAL

UNF. UNFINISHED

U.N.O. UNLESS NOTED OTHERWISE

UR. URINAL

U/S. UNDERSIDE

V.C.T. VINYL COMPOSITION TILE

VERT. VERTICAL

VEST. VESTIBULE

V.G. VERTICAL GRAIN

V.I.F. VERIFY IN FIELD

V.T. VINYL TILE

V.T.R. VENT TO ROOF

V.W.C. VINYL WALL COVERING

(VC) V.A. FURNISHED / CONTRACTOR INSTALLED

(VV) V.A. FURNISHED AND INSTALLED

W. WEST

W/ WITH

W/IN WITHIN

W.C. WATER CLOSET

WD. WOOD

WDW. WINDOW

W.F. WATER COOLER

W.H. WATER HEATER

W/O WITHOUT

W.P. WATER PROOF

W.R. WATER RESISTANT

WT. WEIGHT

W.W.F. WELDED WIRE FABRIC

YD. YARD

P1

A101

SIM

A101

SIM

A101

SIM

A101

SIM

LEVEL NAME W/ ELEVATION

NEW GRID HEAD

CALL OUT HEAD W/ SHEET NUMBER

ROOM NAME W/ ROOM NUMBER, AREA

& OCCUPANCY

BUILDING SECTION NUMBER W/ SHEET

NUMBER

WALL SECTION NUMBER W/

SHEET NUMBER

DOOR NUMBER

WALL TAG

KEYNOTE

REVISION TAG

FINISH TAG

DETAIL SECTION NUMBER W/

SHEET NUMBER

NORTH ARROW

LEVEL

ELEVATION

150 SF

S Y M B O L S

N

WINDOW TAGA

0 EXISTING GRID HEAD

10'-0" CEILING HEIGHT TAG

ROOM NAME

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EXP: 12/31/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:5

:4

P

M

GI002

ABBREVIATIONS AND SYMBOLS

20230901 Checker Author

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTSVA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

DN

GF

D D

D D

D

60" MH

MULTIPURPOSE

1-C-115

STAFF

LOUNGE

1-C-116

TOILET

1-C-146

TOILET

1-C-147

TEAM ROOM

(FUTURE

ELEV.)

1-C-EL3

CLEAN

UTILITY

1-C-145

CONSULT 26

1-C-144

EXAM 25

1-C-143

EXAM 24

1-C-142

OIT

1-C-139

MED ROOM 2

1-C-141

ELECTRICAL

1-C-140

HYBRID 23

1-C-138

EXAM 22

1-C-137

EXAM 21

1-C-136

HYBRID 20

1-C-135

TEAM ROOM

(FUTURE

ELEV.)

1-C-EL1-2

TOILET

1-C-132

CONSULT

1-C-129

EXAM 12

1-C-128

HYBRID 13

1-C-127

EXAM 14

1-C-126

EXAM 15

1-C-125

MED ROOM 1

1-C-124

CONSULT 16

1-C-122

CONSULT 19

1-C-119

CONSULT 18

1-C-120

CONSULT 17

1-C-121

EXAM 10

1-C-114

EXAM 9

1-C-113

EXAM 8

1-C-112

HYBRID 7

1-C-111P. TOILET

1-C-110

EXAM 6

1-C-109

EXAM 5

1-C-108

EXAM 4

1-C-107

EXAM 3

1-C-106

EXAM 2

1-C-105

NEG.

PRESSURE

HYBRID

1-C-104

STAIR 9

FUTURE

1-C-ST2

OPEN

OFFICE

1-C-148

CORRIDOR

1E-4

PATIENT

CORR.

1-C-C2

INTAKE #2

1-C-130

CORRIDOR

1-C-C3

OPEN

OFFICE

1-C-117

DW

1-C-123

DW

1-C-133

STORAGE

1-C-134

EQUIPMENT

STORAGE

1-C-118

PATIENT

CORR.

1-C-C1

INTAKE #1

1-C-103

STAIR 10

1-C-ST1

VESTIBULE

1-C-100

CONCIERGE

1-C-101A

RECEPTION

1-C-102

COFFEE

1-C-101D

KIOSKS

1-C-101C

CORRIDOR

1-C-C5

WAITING

1-C-101

WAITING

EGRESS

CORRIDOR

1-C-C4

NURSE

MANAGER

FUTURE HAC

148A

TOILET

MECHANICAL

PATIENT

EDUCATION

TOILET

STAIR 3

SOILED

UTILITY

OFFICE

RECEP

EXAM 5-2

154A

OFFICE

RECEP

CHECK-IN

EXAM 4-2

EXAM 4-1

158A

OFFICE

RN-3

EXAM 3-1

EXAM 3-2

162A

OFFICE

STAIR 4

OFFICE

CLEAN

UTILITY 2

OFFICE

PROCEDURE

PR. TOILET

167A

RN-2

EXAM 2-1

169A

OFFICE

RN-1

EXAM 1-2

172EXAM 1-1

175A

CORRIDOR

1E-3

DATA

TOILET

SMALL

CONFERENCE

STAFF

LOUNGE

MEANS

TESTING

138BELIGIBILITY

138A

PATIENT

REGISTRATION

MULTIPURPOSE

100A

STORAGE

OFFICE

LOCKERS

A169

SECURITY

MENS

TOILET

WOMENS

TOILET

DATA

176A

CONSULT

121G

OFFICE

121F

EXAM

121E

CORRIDOR

EXAM

121B

EXAM

120A

EXAM

LAB

OFFICE

TOILET

PHARMACY

ENGINEERING

109D

OFFICE

109C

MECH

A109B

STORAGE

A109A OFFICE

EXAM

EXAM

107A

EXAM

OFFICE

EXAM

EXAM

123A

EXAM

123B

EXAM

123C

WAITING

RECEP

EXAM

TOILET

OFFICE

EXAM

132BREAK

EXAM

EXAM

OFFICE

OFFICE

OFFICE

CORRIDOR

128A

OFFICE

A138

TRIAGE

A136

OFFICE

A135

EXAM

A133

EXAM

A131

EXAM

A115

EXAM

A114

EXAM

A112

EXAM

A110

EXAM

A108

OFFICE

A106

CLINIC

A102

ROOM

A102A

WAITING

A116

TOILET

A113

STORAGE

A130

H.A.C.

A129

EXAM

A111

EXAM

A128

EXAM

A109

EXAM

A126

CLEAN

UTILITY

A124

SOILED

UTILITY

A107

SOILED

UTILITY

A132 CLEAN

UTILITY

A134

ROOM

A127

OBSERVATION

A127A

BATH

A127B

MED

A137

NURSE

STATION

A145

TOILET

A146

OFFICE

A144

TOILET

A125

TOILET

A123

EMERGENCY

A139

NURSE

STATION

A122

EXAM

A105

MED

A120

EXAM

A103

EXAM

A118

OFFICE

A121

EXAM

A119

EXAM

A117

RECEPTION

A140

EXAM

A143

EXAM

A152

EXAM

A142

EXAM

A150

EXAM

A141

A170

MECH

A155

A154

OFFICE

A156

OFFICE

A156A

OFFICE

A156B

ROOM

A156C

OFFICE

A156D

EXAM

A153

STORAGE

A151

A149

OFFICE

A156F

ROOM

A156E

A157

CASHIER

A158

A159

OFFICE

STAIR 1

OFFICE

CLOSET

180A

H.A.C.

OFFICE

CHAPEL

STORAGE

192C

KITCHEN

192B

STORAGE

192A

AUDITORIUM

STORAGE

BELOW

STAIRS

OFFICE

OFFICE

CLOSET

184A

TOILET

A165

TOILET

A166

ON CALL

169E

VENDING

SPECIALTY

1-C-154

HYBRID 5-1

GARAGE

EXAM

VESTIBULE

OFFICE

OFFICE

STORAGE

WELCOME

LOUNGE

A167

STAIR 2

REGISTRATION

A164

WELCOME

DESK

A104

ONCOLOGY

WAITING

A101

REGISTER

MED

STORAGE

135A

STORAGE

134A

MED

133A

TOILET

126A

FIRE

PROTECTION

123D

SOILED

UTILITY

H.A.C.

124LACTATION

121D

EXAM

121A

MECH

EXAM

121H

110B

WAITING

BATH

VESTIBULE

EXAM

A148

MECH

A156G

VESTIBULE

STAIR 5

P A

T H

O F

T R

A V

E L

0'

PATH OF TRAVEL 230' < 250'

PROJECT AREA

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR SMOKE BARRIER

NON RATED SMOKE BARRIER

HE

EX EXIT

EP EXIT PASSAGEWAY

SUITE DESIGNATIONS

AREA OPEN TO CORRIDOR -

WITH SMOKE DETECTION

AREA OPEN TO

CORRIDOR - NO SMOKE

DETECTION REQUIRED

3 HOUR FIRE BARRIER

HAZARDOUS ROOM

UNDER RENOVATION

EXIT STAIR OR

PASSAGEWAY

EXIT SIGN

FIRE EXTINGUISHER

1 HOUR SMOKE BARRIER

HORIZONTAL EXIT PASSAGEWAY

HEALTHCARE OCCUPANCY CORRIDOR

SPRINKLER AND FIRE ALARM ZONE BOUNDARY

L E G E N D

C O D E N O T E S

2021 NFPA 101 LIFE SAFETY CODE REVIEW

BUILDING 1, 1ST FLOOR

AREA OF WORK = 1,350 GSF

CHAPTER 6 - CLASSIFICATION OF OCCUPANCY AND HAZARD OF CONTENT

6.1.2 EXISTING ASSEMBLY OCCUPANCY (CHAPTER 13) - NO CHANGE

6.2.2 HAZARD CLASSIFICATION: ORDINARY - NO CHANGE

CHAPTER 7- MEANS OF EGRESS: NO CHANGE

T7.3.1.2 OCCUPANT LOAD OF SPACE: 100 - NO CHANGE

CHAPTER 8 - FEATURES OF FIRE PROTECTION: FULLY SPRINKLERED - NO CHANGE

CHAPTER 9 - BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT: NO CHANGE

CHAPTER 10 - INTERIOR FINISH, CONTENTS, AND FURNISHES

10.2.3.1

INTERIOR WALL AND CEILING FINISH MATERIALS TESTED IN ACCORDANCE

WITH NFPA 286.

10.2.3.1.1

INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE CLASSIFIED IN

ACCORDANCE WITH NFPA 286 AND COMPLY WITH 10.2.3.2.

10.2.3.1.2

MATERIALS TESTED IN ACCORDANCE WITH 10.2.3.1.1 AND COMPLYING

WITH 10.2.3.2 SHALL BE CONSIDERED ALSO TO COMPLY WITH THE

REQUIREMENTS OF CLASS A, CLASS B, OR CLASS C IN ACCORDANCE WITH 10.2.3.3

10.2.3.2.

(1) DURING THE 40 KW EXPOSURE, FLAMES SHALL NOT SPREAD TO THE CEILING.

(2) THE FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITY OF THE SAMPLE

ON ANY WALL OR CEILING.

(3) FLASHOVER, AS DESCRIBED IN NFPA 286, SHALL NOT OCCUR.

(4) THE PEAK HEAT RELEASE RATE THROUGHOUT THE TEST SHALL NOT EXCEED

800 KW.

(5) FOR NEW INSTALLATIONS, THE TOTAL SMOKE RELEASED THROUGH-OUT THE

TEST SHALL NOT EXCEED 1000 M2.

10.2.3.3

WALL AND CEILING- CLASSIFICATIONS CHARACTERISTICS.

(1) CLASS A: FLAME SPREAD: 0-25; SMOKE DEV. : 0-450.

(2) CLASS B: FLAME SPREAD: 26-75; SMOKE DEV. : 0-450

(3) CLASS C: FLAME SPREAD: 76-200; SMOKE DEV. : 0-450

10.2.7.2

INTERIOR FLOOR- CLASSIFICATIONS CHARACTERISTICS:

(1) CLASS I: RAD FLUX: FIN .45 W/CM2

(2) CLASS II: RAD FLUX: FIN .22 W/CM2, AND MAX. .45 W/CM2

10.2.7.3

INTERIOR FLOOR FINISH- SHALL BE CLASSIFIED BASED ON NFPA 253 OR

ASTM E 648.

10.2.8.1

WALL AND CEILING FINISHES, WHERE APPROVED SPRINKLER SYSTEM INSTALLED:

CLASS C PERMITTED IN ANY LOCATION WHERE CLASS B IS REQ’D.

CLASS B PERMITTED IN ANY LOCATION WHERE CLASS A IS REQ’D.

10.2.8.2

FLOOR FINISHES, WHERE APPROVED SPRINKLER SYSTEM INSTALLED:

CLASS II PERMITTED IN ANY LOCATION WHERE CLASS I IS REQ’D.

NO CRITICAL RAD. FLUX PERMITTED IN ANY LOCATION WHERE CLASS II IS

REQ’D

20.3.5.3

AND NFPA 10 SECTION 9.9 FIRE EXTINGUISHERS ARE REQUIRED WITHIN

75’ OF ANY POINT IN THE SPACE.

- MAINTAIN ACCESSIBILITY TO EXISTING FIRE EXTINGUISHERS DURING CONSTRUCTION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EXP: 12/31/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:5

:4

P

M

GI003

OVERALL CODE AND LIFE SAFETY

PLAN

20230901 Checker Author

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTS

VA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

D

D D

AD401

AD401

AD401

AD401

AD401

STRIP WOODEN DISPLAY

FOR REFINISHING

VA TO REMOVE

ALTAR PRIOR TO

CONSTRUCTION

REMOVE SEATING

VA TO REMOVE PIANO

PRIOR TO CONSTRUCTION

REMOVE CARPET

REMOVE CARPET

REMOVE CARPET

REMOVE CARPET

REMOVE DOOR

AND FRAME

REMOVE DOOR AND FRAME

VA TO REMOVE PULPIT

PRIOR TO CONSTRUCTION

REMOVE PLANTS

REMOVE WALL BASE

THROUGHOUT ROOM

REMOVE WALL BASE

THROUGHOUT ROOM

REMOVE STAINED

GLASS - TYP.

REMOVE PEW

SEATING

REMOVE BUILT-IN WOOD SPEAKERS

REMOVE VCT -

SEE SPECS FOR

REMOVAL OF

ASBESTOS

REMOVE BUILT-IN

REMOVE BUILT-IN

STRIP WOODEN STAIRS

FOR REFINISHING

REMOVE MINI FRIDGE

SINKS TO REMAIN - SINK

BELOW MINI FRIDGE NOT

SHOWN FOR CLARITY

REMOVE WALL BASE

NO WORK IN

THIS AREAREMOVE CONFESSIONAL

OPENING

REMOVE CURTAIN

REMOVE CABINETS

AD401

TEMPORARY CONSTRUCTION BARRIER AND ZIPPER

DOOR - OPAQUE 10 MIL FIRE RETARDANT POLYETHYLENE

SHEET PLASTIC PER SPECIFICATION 01 35 26.

AD401

AD401

AD401

AD401

AD401

REMOVE 14' PENDANT LIGHT

REMOVE 14' PENDANT LIGHT

REMOVE 14' PENDANT LIGHT

REMOVE 14' PENDANT LIGHT

REMOVE 14' PENDANT LIGHT

REMOVE

DOWNLIGHT

REMOVE WIRELESS

ACCESS POINT

REMOVE WIRELESS

ACCESS POINT

REMOVE CAN LIGHTS

REMOVE WALL SCONCE

REMOVE WALL SCONCE

REMOVE CAN LIGHTS

REMOVE WALL SCONCE

REMOVE WALL SCONCE

REMOVE EXIT SIGN

REMOVE EXIT SIGN

REMOVE STAINED GLASS - TYP.

REMOVE 1' X 4'

DOWNLIGHTS

REMOVE BUILT-IN WOOD SPEAKERS

AD401

REMOVE BUILT-INS

REMOVE BUILT-INS

A. FOR ALL REMOVALS, THE GENERAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES

B. ALL ITEMS INDICATED AS DASHED SHALL BE REMOVED. THIS INCLUDES ALL FINISHES, MATERIALS, AND ASSOCIATED FIXTURES NOT SPECIFICALLY CALLED OUT. CONTRACTOR SHALL COORDINATE ALL ASSOCIATED WORK BETWEEN ALL

TRADES.

C. HALF-TONED ITEMS INDICATE EXISTING CONSTRUCTION SHALL BE PROTECTED & REMAIN.

D. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT DEMOLISHED OR REMOVED AS REQUIRED UNTIL

PERMANENT SUPPORT IS PROVIDED IN THE FINAL CONSTRUCTION.

E. UTILITIES THAT REMAIN, WITHIN WALLS BEING DEMOLISHED, SHALL BE REROUTED AS REQUIRED TO FACILITATE THE NEW

PLAN CONFIGURATION.

F. AT PENETRATIONS, ALL UTILITY SYSTEM & OTHER COMPONENTS THAT ARE SCHEDULED FOR DISCONNECTION SHALL BE REMOVED IN THEIR ENTIRETY. CONTRACTOR SHALL NOT CAP AND ABANDON IN PLACE UNLESS SPECIFICALLY NOTED OTHERWISE. ANY FIRE RESISTIVE MEMBER OR THROUGH PENETRATIONS RESULTING FROM SUCH DEMOLITION WORK SHALL BE FIRESTOPPED OR SEALED IN ACCORDANCE WITH NFPA FOR THE NECESSARY RATING PROTECTIONS.

G. SEE ELECTRICAL DRAWINGS FOR REPLACEMENT OF ALL RECEPTACLE COVERPLATES.

H. ALL PAINT IS PRESUMED TO BE LEAD-BASED PAINT UNLESS NOTED OTHERWISE. ALL CEILING, GYPSUM BOARD WALLS, AND HOLLOW METAL DOOR FRAMES ARE PAINTED. SEE SPECIFICATIONS FOR HANDLING AND DISPOSAL REQUIREMENTS.

I. PROJECT REQUIRES ICRA CLASS IV REQUIREMENTS. SEE SPECIFICATION SECTION 01 35 26 SAFETY REQUIREMENTS FOR

MORE INFORMATION.

G E N E R A L D E M O L I T I O N N O T E S

K E Y P L A N

L E G E N D

2 HOUR FIRE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EXP: 12/31/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:5

:4

P

M

AD101

DEMOLITION FLOOR PLAN AND

REFLECTED CEILING PLAN

20230901 PQ TD

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTS

VA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

N

1/4" = 1'-0"

DEMOLITION FLOOR PLAN

N

1/4" = 1'-0"

DEMOLITION REFLECTED CEILING PLAN

AD401

AD401

REMOVE WOOD DOOR AND FRAME

SANCTUARY LAMP TO REMAIN

REMOVE ROOM SIGN

REMOVE LIGHT SWITCHES

REMOVE DUPLEX OUTLETS

REMOVE DOWNLIGHTS

REMOVE 14' PENDANT LIGHT - TYP.

REMOVE WOOD DOOR

AND HM FRAME

REMOVE EXIT SIGNS

REMOVE WALL SCONCE

REMOVE DIFFUSER

REMOVE AND RELOCATE

HAND SANITIZER

REMOVE PUSH TO OPEN

REMOVE WALL BASE

REMOVE WALL BASE

REMOVE SWITCHES

PHONE TO REMAIN

REMOVE DIFFUSER

REMOVE DIFFUSER

REMOVE WALL SCONCE

REMOVE WOOD DOOR

AND HM FRAME

REMOVE WALL BASE

REMOVE EXISTING PLATFORM

STRIP WOODEN DISPLAY

FOR REFINISHING

REMOVE PLYWOOD AND TRIM

AD401

REMOVE SPEAKER

REMOVE LINEAR DIFFUSER

REMOVE SPEAKER

REMOVE LINEAR DIFFUSER

REMOVE STAINED GLASS

REMOVE LIGHT SWITCH

REMOVE DUPLEX OUTLET

REMOVE WALL BASE

REMOVE 14'-0" PENDENT LIGHT

REMOVE 2' X 2' DOWN LIGHT

VA TO REMOVE SANCTUARY LAMP

REMOVE WALL BASE

REMOVE DUPLEX OUTLET

REMOVE WOOD DOOR AND HM FRAME

AD401

STRIP WOODEN DISPLAY

FOR REFINISHING

REMOVE CARPET AT STAIRS

NOTE: ALTAR, PULPIT, AND PIANO NOT

SHOWN IN ELEVATIONS FOR CLARITY

REMOVE EXISTING PLATFORM

VA TO REMOVE TABERNACLE

REMOVE PLYWOOD AND TRIM

AD401

REMOVE STAINED GLASS

REMOVE WALL BASE

REMOVE 14' PENDANT LIGHT

REMOVE PORTION

OF WALL

REMOVE ALL WALL

MOUNTED ITEMS

TURN OVER TO THE VA

REMOVE DIFFUSER

AD401

AD401

AD401

REMOVE WOOD DOOR AND FRAME

REMOVE ROOM SIGN

REMOVE COVERPLATES

REMOVE DOWNLIGHTS

REMOVE 14' PENDANT LIGHT - TYP.

REMOVE WALL BASE

REMOVE WALL BASE

REMOVE STAINED GLASS

WINDOW - TYP.

REMOVE WALL SCONCE - TYP.

REMOVE LINEAR DIFFUSER - TYP.

REMOVE RECESSED WOODEN

DISPLAY AND ASSOCIATED TRIM

REMOVE THERMOSTAT

AND WIRING BACK TO UNIT

REMOVE EXISTING PLATFORM

REMOVE DIFFUSER

A. FOR ALL REMOVALS, THE GENERAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES

B. ALL ITEMS INDICATED AS DASHED SHALL BE REMOVED. THIS INCLUDES ALL FINISHES, MATERIALS, AND ASSOCIATED FIXTURES NOT SPECIFICALLY CALLED OUT. CONTRACTOR SHALL COORDINATE ALL ASSOCIATED WORK BETWEEN ALL

TRADES.

C. HALF-TONED ITEMS INDICATE EXISTING CONSTRUCTION SHALL BE PROTECTED & REMAIN.

D. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT DEMOLISHED OR REMOVED AS REQUIRED UNTIL

PERMANENT SUPPORT IS PROVIDED IN THE FINAL CONSTRUCTION.

E. UTILITIES THAT REMAIN, WITHIN WALLS BEING DEMOLISHED, SHALL BE REROUTED AS REQUIRED TO FACILITATE THE NEW

PLAN CONFIGURATION.

F. AT PENETRATIONS, ALL UTILITY SYSTEM & OTHER COMPONENTS THAT ARE SCHEDULED FOR DISCONNECTION SHALL BE REMOVED IN THEIR ENTIRETY. CONTRACTOR SHALL NOT CAP AND ABANDON IN PLACE UNLESS SPECIFICALLY NOTED OTHERWISE. ANY FIRE RESISTIVE MEMBER OR THROUGH PENETRATIONS RESULTING FROM SUCH DEMOLITION WORK SHALL BE FIRESTOPPED OR SEALED IN ACCORDANCE WITH NFPA FOR THE NECESSARY RATING PROTECTIONS.

G. SEE ELECTRICAL DRAWINGS FOR REPLACEMENT OF ALL RECEPTACLE COVERPLATES.

H. ALL PAINT IS PRESUMED TO BE LEAD-BASED PAINT UNLESS NOTED OTHERWISE. ALL CEILING, GYPSUM BOARD WALLS, AND HOLLOW METAL DOOR FRAMES ARE PAINTED. SEE SPECIFICATIONS FOR HANDLING AND DISPOSAL REQUIREMENTS.

I. PROJECT REQUIRES ICRA CLASS IV REQUIREMENTS. SEE SPECIFICATION SECTION 01 35 26 SAFETY REQUIREMENTS FOR

MORE INFORMATION.

G E N E R A L D E M O L I T I O N N O T E S

K E Y P L A N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EXP: 12/31/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:5

:4

P

M

AD401

DEMOLITION ELEVATIONS

20230901 PQ TD

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTS

VA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

1/4" = 1'-0"

EAST - DEMOLITION SECTION / ELEVATION

1/4" = 1'-0"

NORTH - DEMOLITION SECTION / ELEVATION

1/4" = 1'-0"

SOUTH - DEMOLITION SECTION / ELEVATION

1/4" = 1'-0"

WEST - DEMOLITION SECTION / ELEVATION

60" MH

AE401

AE401

AE401

AE401

REFINISH WOOD STAIRS -

STAIN: ST-1

LVT1

RESIN PATTERNED WINDOW WITH

HINGES/MAGNETIC LATCH AND

BACKLIT WITH LED STRIPS

SEE ELEVATIONS ON SHEET AE401

6" - DECORATIVE FAUX WOOD

PROFILE BASE THROUGHOUT ROOM

FURR-OUT WALL - 5"

DECORATIVE PANELING/WAINSCOTING

REFINISH WOODEN DISPLAY -

STAIN: ST-1

FAUX WOOD RAILING

/A

E

4/AE601

801 SF

CHAPEL

252 SF

CHANCEL

194A

54 SF

MECHANICAL

194B

102 SF

CHAPLAIN

194A

194B

AE601

RESHAPE ALTAR PLATFORM TO

MATCH SHAPE OF CEILING ABOVE

PUSH TO OPEN OPERATOR

PLASTIC LAMINATE CASEWORK

15' - 4"

ROOM SIGN

ROOM SIGN

AE601

AE401

TEMPORARY CONSTRUCTION BARRIER

AND ZIPPER DOOR - OPAQUE 10 MIL

FIRE RETARDANT POLYETHYLENE

SHEET PLASTIC PER SPECIFICATION 01

35 26.

1'

VA TO PROVIDE

NEW ALTAR

AE401

ALTERNATE #1: PROVIDE DECORATIVE

PANEL/WAINSCOTING SYSTEM TO MATCH

ADJACENT WALL IN LIEU OF CASEWORK

NEW CASEWORK - SEE

ELEVATIONS

NEW CASEWORK - SEE

ELEVATIONS

INFILL WALL - SEE DETAIL 10/AE401

INFILL WALL - SEE DETAIL 10/AE401

AE401

AE101

VA TO PROVIDE NEW PULPIT

VA TO PROVIDE NEW PIANO

AE401

AE401

AE401

AE401

LED COVE LIGHTING

HALO LED

PENDENT LIGHT

LED COVE LIGHTING

LED COVE LIGHTING

LED COVE LIGHTING

LED COVE LIGHTING

LED STRIP LIGHTING

LED CAN LIGHT

LED CAN LIGHT

LED CAN LIGHT

LED CAN LIGHT

REPAIR SCALLOPED GYPSUM CEILING

FROM EXISTING LIGHT FIXTURE

REPAIR SCALLOPED GYPSUM CEILING

FROM EXISTING LIGHT FIXTURE

REPAIR SCALLOPED GYPSUM CEILING

FROM EXISTING LIGHT FIXTURE

REPAIR SCALLOPED GYPSUM CEILING

FROM EXISTING LIGHT FIXTURE

REPAIR SCALLOPED GYPSUM CEILING

FROM EXISTING LIGHT FIXTURE

EXIT SIGN

EXIT SIGN

REPAIR GYPSUM CEILING FROM

EXISTING LIGHT FIXTURE

LED CAN

LIGHT

WIRELESS

ACCESS POINT

WIRELESS ACCESS POINT

AE401

GYPSUM SOFFIT

AE601

LED CAN LIGHT

LED CAN

LIGHT

LED CAN LIGHT

CROWN MOLDING

TYP.

CROWN MOLDING

TYP.

AE601

801 SF

CHAPEL

10' - 0"

252 SF

CHANCEL

194A

10' - 0"

9' - 6"

54 SF

MECHANICAL

194B

102 SF

CHAPLAIN

9' - 0" 10' - 0"

EXISTING BULKHEAD

AT 8'-10" AFF

A. PARTITIONS/FURRING SHALL BE 3 5/8" COLD FORMED STEEL FRAMING AND 5/8" GYPSUM BOARD, UNLESS OTHERWISE NOTED.

B. REFER TO DEMOLITION DRAWINGS FOR WORK REQUIRED IN ADVANCE OF CONSTRUCTION AND COORDINATE ACCORDINGLY.

C. ALL WALL HUNG CASEWORK AND EQUIPMENT ATTACHED TO WALLS SHALL BE ANCHORED TO FIRE RETARDANT TREATED WOOD BLOCKING ANCHORED BETWEEN STUDS UNLESS OTHERWISE NOTED. BLOCKING SHALL BE CONTINUOUS AND

LOCATED AT BOTTOM AND TOP OF EQUIPMENT.

D. SOUND ATTENUATION BATTS (SAB) ARE TO BE PLACED IN ALL PARTITIONS WHICH ENCLOSE A ROOM UNLESS NOTED

OTHERWISE.

E. PROJECT REQUIRES ICRA CLASS IV REQUIREMENTS. SEE SPECIFICATION SECTION 01 35 26 SAFETY REQUIREMENTS FOR

MORE INFORMATION.

G E N E R A L N O T E S

A. ALL VERTICAL FACES OF SOFFITS OR BULKHEADS SHALL BE FINISHED TO MATCH ADJACENT SURFACES.

B. ALL GYPSUM BOARD CEILINGS SHALL BE PAINTED P-1, UNLESS OTHERWISE NOTED.

G E N E R A L C E I L I N G N O T E S

K E Y P L A N

L E G E N D

2 HOUR FIRE BARRIER

1/4" PLYWOOD WITH WOOD

SCREWS AT 16" O.C.

FRT 2x4 WOOD SLEEPER AT 16" O.C.

LVT-1 - SEE FINISH LEGEND

CPT-2 - SEE FINISH LEGEND

V

IF4

EXISTING STRUCTURE BELOW

ALUMINUM STUD CLIP

1/2" FRT PLYWOOD WITH

WOOD SCREWS AT 16" O.C.

1/8" SMOOTH FRP PANEL - ADHERE

AND SCREW TO PLYWOOD

EDGING PROFILE FOR RESILIENT

FLOOR COVERING

BOD: SCHLUTER-VINPRO-STEP-R

AE101

FRT 2x4 WOOD STUDS AT 16" O.C.

LVT-1 - SEE FINISH LEGEND

9' - 9"

FRT BLOCKING AS REQUIRED

FOR RADIUS, TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EXP: 12/31/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:2

:5

P

M

AE101

FLOOR PLAN AND REFLECTED

CEILING PLAN

20230901 PQ TD

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTS

VA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

N

1/4" = 1'-0"

FLOOR PLAN

N

1/4" = 1'-0"

REFLECTED CEILING PLAN

1 1/2" = 1'-0"

ALTAR PLATFORM SECTION

1/2" = 1'-0"

ALTAR PLATFORM FRAMING PLAN

AE401

AE401

LED COVE LIGHTING - TYP.

HALO LED PENDENT LIGHT

STRIP LED LIGHTING

DOOR AND FRAME

OUTLET AND COVERPLATE

DECORATIVE LINEAR DIFFUSER

EXIT SIGN - CENTERED

ABOVE DOOR

SWITCHES AND COVER PLATE

6" - DECORATIVE FAUX

WOOD PROFILE BASE

DECORATIVE LINEAR

DIFFUSER

EXIT SIGN - CENTERED

ABOVE DOOR

DECORATIVE

PANELING/WAINSCOTING

RESIN PATTERNED WINDOW WITH

HINGES/MAGNETIC LATCH AND

BACKLIT WITH LED STRIPS

PUSH TO OPEN

SWITCHES AND COVERPLATE

HR-1 FAUX WOOD AND

STAINLESS STEEL RAILING -

SEE FINISH LEGEND

9' - 2" 8" 3' - 8" 8" 3' - 0" 8" 3' - 8" 8" 8' - 10"

5'

ROOM SIGN

SOFFIT

WP-1 WP-1 WP-1

WP-3 WP-3 WP-3

WP-3 WP-3 WP-3

WP-4

WP-3

P-2 P-2

WP-2 WP-2WP-2

P-2

P-2

WP-4

WP-4

AE401

WP-4

REFINISH WOODEN

DISPLAY - STAIN: ST-1

194194A193

AE101

4NEW ALTAR PLATFORM

CM-1CM-1CM-1 CM-1

2" C

LR

AE401

AE401

AE401

DECORATIVE LINEAR DIFFUSER DECORATIVE LINEAR DIFFUSER

INFILL WALL - SEE DETAIL 10/AE401INFILL WALL - SEE DETAIL 10/AE401

LIGHT SWITCH AND COVERPLATE

DUPLEX OUTLET AND

COVERPLATE

DUPLEX OUTLET AND COVERPLATE

REFINISH WOODEN DISPLAY - STAIN: ST-1

LED COVE LIGHTING

HALO LED PENDENT LIGHT

2' - 4"

FAUX WOOD AND STAINLESS

STEEL RAILING

FURR-OUT WALL - 5"

DECORATIVE

PANELING/WAINSCOTING

RESIN PATTERNED WINDOW

WITH HINGES/MAGNETIC LATCH

AND BACKLIT WITH LED STRIPS

EXIT SIGN CENTERED

ABOVE DOOR

AE401

1'

P-2 P-2

WP-4 WP-4

LVT-1 AT RISERS

FAUX WOOD RAILING

WP-4 WP-4

WP-3

WP-1

WP-2

P-2 P-2

WP-3 WP-3

WP-3

WP-3

WP-1

WP-2

WP-3

CROWN MOLDING

CROWN MOLDING

PLASTIC LAMINATE CASEWORK

AE401

NOTE: ALTAR, PULPIT, AND PIANO NOT

SHOWN IN ELEVATIONS FOR CLARITY

NEW ALTAR PLATFORM - SEE DETAIL 3/AE101

CM-1 CM-1

VA TO REINSTALL SANCTUARY LAMP

VA TO REINSTALL TABERNACLE

NEW CURTAIN HOOKS ON

BOTH SIDES OF DISPLAY

AE401

AE401

AE401

VERIFY CEILING HEIGHT

DECORATIVE LINEAR DIFFUSER

FURR-OUT WALL - 5"

DECORATIVE

PANELING/WAINSCOTING

RESIN PATTERNED WINDOW

WITH HINGES/MAGNETIC LATCH

AND BACKLIT WITH LED STRIPS

PATCH WALL DAMAGE FROM WALL MOUNTED OBJECTS

FURR-OUT WALL - 5"

DECORATIVE

PANELING/WAINSCOTING

RESIN PATTERNED WINDOW

WITH HINGES/MAGNETIC LATCH

AND BACKLIT WITH LED STRIPS

14' - 0"

6' - 4" 8" 6' - 8" 6' - 8" 8" 6' - 4"

WP-1

WP-3

WP-3

WP-3

P-2

WP-2

WP-4

CM-1

WP-1

WP-3

WP-3

P-2

WP-2

WP-4

CM-1

P-2

CM-1

PLASTIC LAMINATE CASEWORK

5'

SS-1

ALTERNATE #1: PROVIDE DECORATIVE

PANEL/WAINSCOTING SYSTEM TO MATCH

ADJACENT WALL IN LIEU OF CASEWORK

RELOCATED HAND SANITIZER

WP-3

AE401

AE401

LED COVE LIGHTING - TYP.

HALO LED PENDENT LIGHT

STRIP LED LIGHTING

INFILL WALL - SEE DETAIL 10/AE401

DOOR AND FRAME

DUPLEX OUTLET AND

COVERPLATE

6" - DECORATIVE FAUX

WOOD PROFILE BASE

RESIN PATTERNED WINDOW

WITH HINGES/MAGNETIC LATCH

AND BACKLIT WITH LED STRIPS

DECORATIVE LINEAR DIFFUSER

DECORATIVE

PANELING/WAINSCOTING

FAUX WOOD RAILING

AE401

TYP.

AE401

9 3/8" 8" 3' - 8" 8" 3' - 0" 8" 3' - 8" 8" 3' - 0" 8" 3' - 8" 8" 3' - 0" 8" 3' - 8" 8" 1' - 2"

ROOM SIGN

SOFFIT

WP-1WP-1WP-1

WP-3

WP-3WP-3WP-3

WP-4

WP-3

P-2P-2

WP-2WP-2 WP-2

P-2

WP-4

WP-3 WP-3

WP-3 WP-3

WP-1WP-1

WP-2 WP-2

WP-1WP-1

WP-2WP-2

CM-1

P-2

CM-1CM-1

WP-4 WP-4

WP-4

REFINISH WOODEN

DISPLAY - STAIN: ST-1

AE401

AE401

194B

NEW ALTAR PLATFORM -

SEE DETAIL 4/AE101

CM-1

2" C

LR

TAPE BOTTOM WITH MESH

TAPE AND PLASTER WELD

INDIRECT COVE LIGHT LEDGE.

GYPSUM BOARD - ALIGN COVE

LIGHT LEDGE WITH CEILING

ANGLED LED STRIP LIGHT -

SEE ELECTRICAL DRAWINGS

CUT OFF SCREWS TO NOT

INTERFERE WITH LIGHTS

ATTACH LIGHT LEDGE TO EXISTING

FRAMING. REMOVE EXISTING

GYPSUM AS NECESSARY

5 5/16"

1/

2"

EXISTING SCALLOPED CEILING

CONTRACTOR TO VERIFY EXISTING

FRAMING AND STRUCTURE.

LED STRIP LIGHTING AND DIFFUSER

3 5/8" COLD FORMED METAL FRAMING

RESIN PATTERNED WINDOW AND FRAME

HINGE AND MAGNETIC LATCH

EXISTING GYPSUM WALL

WP-3 TRIM - SEE

FINISH LEGEND

5/8" GYPSUM BOARD

6" COLD FORMED

METAL FRAMING

7 3/16"

WP-3 - TRIM TO FIT

WP-3 - TRIM TO FIT

6" COLD FORMED METAL FRAMING

WP-2 - SEE FINISH LEGEND

EXISTING GYPSUM WALL

WP-3 TRIM - SEE

FINISH LEGEND

5/8" GYPSUM BOARD

3 5/8" COLD FORMED

METAL FRAMING

WP-3 - TRIM TO FIT

4'

0"

5'

AE401

6" 8"

4" 4"

8" 2'

P-2

CM-1

WP-3

WP-2

WP-1

WP-2

WP-3

WP-4

4'

6"

EXISTING GYPSUM

BOARD SURFACE

WP-3 - TRIM

TO FIT

AE401

WP-4

WP-2 TRIM

WP-2 TRIM

WP-1 PANEL

DIFFUSER ATTACHED

TO EXISTING DUCTS

DIFFUSER ATTACHED

TO EXISTING DUCTS

LED STRIP LIGHTING

AND DIFFUSER

HINGE AND MAGNETIC LATCH

EXISTING GYPSUM

BOARD SURFACE

RESIN PATTERNED WINDOW

6"

8"

4"

6"

WP-4 WP-3 WP-2 CM-1

13/16"

13/16"

13/16"

5 1/2"

P R O F I L E L E G E N D

E Q

E Q

1' - 6"

SHELF

SHELF

SS-1

WP-3 - TRIM

TO FIT

CM-1

WP-4

WP-3

1'

4'

(2) LAYERS

3/4" PLYWOOD

WP-2

WP-1

WP-2

*ALL CASEWORK IS LOCKABLE.

NOTES:

A. PARTITIONS/FURRING SHALL BE 3 5/8" COLD FORMED STEEL FRAMING AND 5/8" GYPSUM BOARD, UNLESS OTHERWISE NOTED.

B. REFER TO DEMOLITION DRAWINGS FOR WORK REQUIRED IN ADVANCE OF CONSTRUCTION AND COORDINATE ACCORDINGLY.

C. ALL WALL HUNG CASEWORK AND EQUIPMENT ATTACHED TO WALLS SHALL BE ANCHORED TO FIRE RETARDANT TREATED WOOD BLOCKING ANCHORED BETWEEN STUDS UNLESS OTHERWISE NOTED. BLOCKING SHALL BE CONTINUOUS AND

LOCATED AT BOTTOM AND TOP OF EQUIPMENT.

D. SOUND ATTENUATION BATTS (SAB) ARE TO BE PLACED IN ALL PARTITIONS WHICH ENCLOSE A ROOM UNLESS NOTED

OTHERWISE.

E. PROJECT REQUIRES ICRA CLASS IV REQUIREMENTS. SEE SPECIFICATION SECTION 01 35 26 SAFETY REQUIREMENTS FOR

MORE INFORMATION.

G E N E R A L N O T E S

A. ALL VERTICAL FACES OF SOFFITS OR BULKHEADS SHALL BE FINISHED TO MATCH ADJACENT SURFACES.

B. ALL GYPSUM BOARD CEILINGS SHALL BE PAINTED P-1, UNLESS OTHERWISE NOTED.

G E N E R A L C E I L I N G N O T E S

K E Y P L A N

8"

4 7/8"

EXISTING STRUCTURE ABOVE

EXISTING GYPSUM BOARD

5/8" GYPSUM BOARD

3 5/8" 20 GA. CFS FRAMING

EXISTING FRAMING

EXISTING GYPSUM BOARD

5/8" TYPE X GYPSUM BOARD

2 1/2" 20 GA. COLD FORMED

METAL FRAMING

ALIGN FACE WITH EXISTING

E Q

E Q

*ALL CASEWORK IS LOCKABLE.

NOTES:

1' - 6" V.I.F.

MAGNETIC LATCH

BLOCKING AS REQUIRED -

SEE PHOTOS BELOW FOR

EXISTING BLOCKING

ADJUSTABLE SHELVING

EXISTING CLAY

MASONRY UNIT WALL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EXP: 12/31/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:5

:5

P

M

AE401

ELEVATIONS, SECTIONS, AND

DETAILS

20230901 PQ TD

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTS

VA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

1/4" = 1'-0"

EAST - SECTION / ELEVATION

1/4" = 1'-0"

NORTH - SECTION / ELEVATION

1/4" = 1'-0"

SOUTH - SECTION / ELEVATION

1/4" = 1'-0"

WEST - SECTION / ELEVATION

3" = 1'-0"

COVE LIGHTING DETAIL - TYPICAL

1 1/2" = 1'-0"

VERTICAL MOLDING - UPPER SECTION

1 1/2" = 1'-0"

VERTICAL MOLDING - LOWER SECTION

1" = 1'-0"

WAINSCOTING SECTION DETAIL

1" = 1'-0"

WAINSCOTING SECTION DETAIL

1/2" = 1'-0"

BACK CASEWORK SECTION

3" = 1'-0"

SOFFIT DETAIL

1" = 1'-0"

WALL INFILL - TYPICAL

1/2" = 1'-0"

CASEWORK SECTION

EXISTING WOOD FRAMING / BLOCKING

TRIM TO BE REMOVED AND REPLACED

REFINISH WOODEN DISPLAY

SLIDING DOORS TO BE

REMOVED, REFINISHED, AND

REINSTALLED

CURTAIN HOOKS TO BE

REMOVED AND REPLACED

EXISTING BLOCKING

TRIM TO BE REMOVED

AND REPLACED

EXISTING WOOD

FRAMING / BLOCKING

3' - 8"

4'

0"

PATTERNED RESIN

BACK FRONT

4'

4" 4"

4" 3' - 0" 4"

TYPE 1

SEE SCHEDULE

S E

E S

C H

E D

U L E

2" 2"

TYPE 2

SEE SCHEDULE

S E

E S

C H

E D

U L E

2" 2"

1 15/16" VARIES VARIES

REFER TO WALL

TYPE

DOUBLE STUDS

BACK TO BACK

CONTINUOUS

SEALANT BOTH

SIDES HOLLOW METAL FRAME

JAMB ANCHORS

/4

WP-3

WP-1

F S

S E

E S

C H

E D

U L E

SEE SCHEDULE

S E

E S

C H

E D

U L E

SEE SCHEDULE

4" 22"

PATTERNED

RESIN

FLUSH STAINED GLASS

4' - 0"2' - 0"

1'

1'

1'

2'

SHELVING

MINI

REFRIGERATOR

SHELVING

SHELVING

2'

8" FILLER PANEL

TALL CLOSET TALL CLOSET

FILLER PANEL

AE601

4' - 0"4' - 0"

AE601

AE601

9'

TALL CLOSET

WALL CABINETS

P-2

4" UNDERCOUNTER

DRAWERS

REFINISH WOOD STAIRS - STAIN ST-1

*ALL CASEWORK IS LOCKABLE.

ALL CASEWORK FACES SHALL BE PL-1

NOTES:

2'

0"

AE601

1-1/4" DIA.

CLOSET ROD

SHELVING

FILLER PANEL

SHELVING

TALL CLOSET

6"

8'

0"

8" 8"

8" 6'

9'

1' - 2"

5'

3/

4"

1/ 2"

3'

0"

8"

9'

4'

2'

/4

4"

UNDERCOUNTER

DRAWER

2' - 0"

WALL

CABINET

2'

0"

FILLER

PANEL

TALL CLOSET

BEYOND

LED LIGHT

E Q

E Q

E Q

A B C

D E F

NOTE: CEILING AND SOFFIT NOT SHOWN IN

RENDERING FOR CLARITY. ALL CASEWORK WITHIN

THIS ROOM IS FULL HEIGHT TO EXISTING SOFFIT.

SHELVING

FILLER PANEL

SHELVING

SHELVING

SHELVING

(3) ADJUSTABLE SHELVES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EXP: 12/31/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:5

:5

P

M

AE601

DOOR SCHEDULE AND

CASEWORK DETAILS

20230901 PQ TD

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTS

VA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

DOOR SCHEDULE

DOOR #

PANEL FRAME DETAILS

FIRE

RATING HW#

NO. OF

LEAF

DOOR

TYPE MATERIAL

DIMENSION

TYPE MATERIAL HEAD JAMBW H T

193 1 F SCWD 2' - 8" 6' - 8" 1 3/4" 1 HM - - - 1

194 2 S SCWD 5' - 0" 7' - 0" 1 3/4" 2 HM - - - 2

194A 2 S SCWD 5' - 0" 7' - 0" 1 3/4" 2 HM - - - 2.1

194B 1 F SCWD 2' - 8" 6' - 8" 1 3/4" 1 HM - - - 1

1" = 1'-0"

TYPICAL WINDOW ELEVATON

D O O R S C H E D U L E N O T E S

1. SEE HARDWARE SPECIFICATION 08 71 00 FOR HARDWARE SETS.

2. ALL DOOR FRAMES SHALL RECEIVE PAINT TYPE P-3. SEE FINISH LEGEND.

3. ALL DOORS TO BE WD-1. SEE FINISH LEGEND.

4. ALL CYLINDERS WILL BE KEYED INTO EXISTING BEST GREAT GRAND MASTER KEY SYSTEM BY THE VA. PROVIDE REMOVABLE CORE CYLINDER HOUSING.

CYLINDERS SHALL BE 7 PIN TYPE.

3" = 1'-0"

DOOR HEAD AND JAMB DETAIL

1/2" = 1'-0"

CASEWORK CLOSET

1/2" = 1'-0"

CASEWORK DESK AND CLOSET

1/2" = 1'-0"

CASEWORK SECTION DETAIL

1/2" = 1'-0"

CASEWORK SECTION DETAIL

1/2" = 1'-0"

PATTERNED RESIN OPTIONS

NTS

CHAPLAIN CASEWORK 3D

1/2" = 1'-0"

CASEWORK SECTION DETAIL

BASIS OF DESIGN: 3FORM KODA XT - SUBMIT MANUFACTURER'S PRODUCT LITERATURE,

INSTALLATION INSTRUCTIONS, AND DETAILS FOR SHOP DRAWING REVIEW

60" MH

AE401

AE401

AE401

AE401

/A

E

4/AE601

CHAPEL

CPT-1 P-1

P-2PB-1

CHANCEL

194A

CPT-2 P-1

P-2PB-1

CHAPLAIN

LVT-1 P-1

P-2RB-1

MECHANICAL

194B

AE601

AE601

LVT-1 AT RISERS

LVT-1 AT RISER

F I N I S H L E G E N D

MARK DESCRIPTION BASIS OF DESIGN STYLE/ COLOR COMMENTS

LVT-1 LUXURY VINYL TILE SHAW COMMERCIAL

BRANCHING OUT 4256V

56730 RAVINE OAK

6" X 48" - PLATFORM AND OFFICE

P-2 PAINT - TYPE 2 SHERWIN WILLIAMS ALABASTER SW7008

WP-1 WALL PANELING ACROVYN WOODGRAINS 1352-FOSSIL TEAK WALL PANELS

P-1 PAINT - TYPE 1 SHERWIN WILLIAMS WHITE GENERAL CEILING PAINT - LATEX EGGSHELL

WALL PAINT - LATEX EGGSHELL

P-3 PAINT - TYPE 3 SHERWIN WILLIAMS WORLDLY GRAY SW7043 DOOR FRAMES

PL-1 PLASTIC LAMINATE MATCH ACROVYN WP-1 MATCH 1352-FOSSIL TEAK CHANCEL CASEWORK

CPT-1 CARPET TILE PATCRAFT Z6474-INSTINSIC - 00522-MOOD DU JOUR ASHLAR - 24" X 24" RUNNING N/S - CHAPEL

HR-1 HANDRAIL CONTRACTOR TO DETERMINE MATCH WOODGRAINS 1351-SMOKEY ELM

FLOOR MOUNTED FAUX WOOD AND

STAINLESS STEEL RAIL

WP-2 WALL PANELING ACROVYN WOODGRAINS 1351-SMOKEY ELM WALL PANEL TRIM AND FRAME

CPT-2 CARPET TILE PATCRAFT Z6474-INSTINSIC - 00522-MOOD DU JOUR ASHLAR - 24" X 24" RUNNING E/W - CHANCEL

RB-1 RUBBER BASE JOHNSONITE A530 - 66 EITHER OR USED WITH LVT-1

CM-1 CROWN MOLDING ACROVYN

EDWARDS SMOOTH

WOODGRAINS 1352-FOSSIL TEAK

ALL WALLS IN THE CHAPEL WITH

WAINSCOTING

WP-3 WALL PANELING ACROVYN WOODGRAINS 1352-FOSSIL TEAK HORIZONTAL AND VERTICAL BOARDS

SS-1 SOLID SURFACE CORIAN CLAM SHELL BACK COUNTERTOP

WP-4 FAUX WOOD PROFILE BASE WOODGRAINS 1352-FOSSIL TEAK 6" PROFILE BASE - SEE DETAIL ACROVYN

ST-1 WOOD STAIN CONTRACTOR TO DETERMINE MATCH WOODGRAINS 1352-FOSSIL TEAK ALL REFINISHED WOOD SURFACES

WD-1 SOLID WOOD DOOR ACROVYN WOODGRAINS 1352-FOSSIL TEAK ALL WOOD DOORS

FLOOR FINISH

WALL BASE

F I N I S H T A G L E G E N D

ROOM NAME

WALL FINISH

CEILING FINISH

WP-4 WP-3 WP-2 CM-1

13/16"

13/16"

13/16"

5 1/2"

P R O F I L E L E G E N D

/A

E

4/AE601

5' - 0"

2' - 0"

3' - 5" 3' - 5"

A. FURNITURE PROVIDED BY VA.

B. CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR CASEWORK AND WAINSCOTING.

G E N E R A L N O T E S

K E Y P L A N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

EXP: 12/31/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:2

:0

P

M

AI101

FINISH PLAN AND SCHEDULE

20230901 PQ TD

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTS

VA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

N

1/4" = 1'-0"

FINISH FLOOR PLAN

F I N I S H S C H E D U L E

ROOM NAME

ROOM

NUMBER FLOOR CEILING WALL FINISH WALL BASE

WALL FINISH CEILING

HEIGHTN E S W

DATA 176A

CHAPLAIN 193 LVT-1 P-1 P-2 RB-1 P-2 P-2 P-2 P-2 9' - 6"

CHAPEL 194 CPT-1 P-1 P-2 PB-1 P-2 / WP-1 / WP-2 / WP-3 P-2 / WP-1 / WP-2 / WP-3 P-2 / WP-1 / WP-2 / WP-3 P-2 / WP-1 / WP-2 / WP-3 10' - 0"

CHANCEL 194A CPT-2 P-1 P-2 PB-1 P-2 P-2 P-2 P-2 10' - 0"

MECHANICAL 194B ETR ETR ETR ETR ETR ETR ETR ETR

N

1/4" = 1'-0"

FURNITURE PLAN

C

C

E

FLEXIBLE CONDUIT CONNECTION

SUBSCRIPT: WP - WEATHERPROOF, GF - GROUND FAULT CIRCUIT

INTERRUPTER

FLUSH FLOOR MOUNTED NEMA 5-20 DUPLEX RECEPTACLE

UNLESS NOTED OTHERWISE

NEMA 5-20 DUPLEX RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE

JUNCTION BOX

NON-FUSED DISCONNECT SWITCH. SIZE AS SHOWN

FUSED DISCONNECT SWITCH. SIZE FUSES FOR EQUIPMENT

BASED ON MANUFACTURERS RECOMMENDATIONS

SURFACE MOUNTED PANELBOARD OR AUTOMATIC TRANSFER

SWITCH AS INDICATED.

MOTOR

J

WP/GF

POWER

CONCEALED OR OPEN

UNDERGROUND

WIRINGLIGHTING

EXTERIOR SITE

FLUSH FLOOR MOUNTED NEMA 5-20 QUAD RECEPTACLE

UNLESS NOTED OTHERWISE

RECESSED MOUNTED PANELBOARD

RECEPTACLE, (NEMA CONFIGURATION AS NOTED)

GROUNDING

ABBREVIATIONS

NEW PAD MOUNTED TRANSFORMER

EXISTING COMMUNICATIONS MANHOLE

NEW COMMUNICATIONS MANHOLE

EXISTING POLE MOUNTED LIGHTING FIXTURE

NEW POLE MOUNTED LIGHTING FIXTURE

EXISTING UNDERGROUND ELECTRICAL LINE.

EXISTING OVERHEAD ELECTRICAL LINE.

EXISTING UNDERGROUND COMMUNICATION LINE

EXISTING OVERHEAD COMMUNICATION LINE

NEW ELECTRICAL HANDHOLE

NEW BOLLARD LIGHT FIXTURE.

EUP

EP

EUC

EC

GRID COUNTERPOISE CONDUCTOR

LIGHTNING PROTECTION ROOF CONDUCTOR

CONNECTION TO GROUND

LIGHTNING PROTECTION DOWN CONDUCTOR

RC

DC

G

AIR TERMINAL

GROUNDING ROD

STATIC GROUNDING RECEPTACLE

UP

US

UC

NEW UNDERGROUND PRIMARY

NEW UNDERGROUND SECONDARY

NEW UNDERGROUND COMMUNICATIONS

EXISTING SECTIONALIZER CABINETS

T

H

M

M

FIRE ALARM

DATA/TELEPHONE

DATA/TELEPHONE OUTLET. PROVIDE (2) CAT 6a CABLES WITHIN

CONDUIT OR OTHER APPROVED RACEWAY FROM OUTLET TO

NEAREST IT CLOSET OR CABLE TRAY. SUBSCRIPT INDICATES # OF

DATA CABLES.

NURSE CALL - A/V

PA SPEAKER, CEILING MOUNTED

NURSE CALL STATION

PS = PATIENT STATION

TS = TOILET STATION WITH PULL STRING

SW = SHOWER STATION

DS = DUTY STATION

MS = MASTER STATION

SS = STAFF STATION

NURSE CALL STATION

ZL = ZONE INDICATING DOME LIGHT FOR CORRIDOR

NURSE CALL SIGNAL

CARD READER

PANIC BUTTON

HANDICAP DOOR MOTOR

HANDICAP DOOR OPERATOR

ELECTRIC LATCH

SECURITY CAMERA CCTV - DOME

DURESS/PANIC ALARM

SECURITY / ACCESS CONTROL

TV BEDSIDE TELEVISION

PILOT LIGHT / CHIME

PUSHBUTTON

SMOKE DETECTOR

F FIRE ALARM SPEAKER/STROBE

FIRE ALARM STROBE

F FIRE ALARM SENDING STATION

S R

FIRE ALARM CONTROL RELAY. C- CONTROL I-INPUT.

DUCT DETECTOR. "R" INDICATES RETURN DUCT. "S"

INDICATES SUPPLY DUCT.

AM

C a

OS

1' x 4' FIXTURE. UPPERCASE INDICATES TYPE PER THE FIXTURE SCHEDULE.

LOWER CASE LETTER "a" INDICATES SWITCH ZONE.

OS

LC#

2' x 4' FIXTURE.

WALL MOUNTED FIXTURE.

INDUSTRIAL FIXTURE.

WALL MOUNTED FIXTURE.

EXIT SIGN WITH DIRECTIONAL ARROWS AS INDICATED

RECESSED FIXTURE, DOWNLIGHT

3-WAY, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 42" AFF.

4-WAY, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 42" AFF.

WALL MOUNTED OCCUPANCY SENSOR WITH OVERRIDE SWITCH

CEILING MOUNTED OCCUPANCY SENSOR

20 AMP, 125 VOLT SINGLE-POLE TOGGLE SWITCH MOUNTED 42" AFF.

a - CONTROLS LIGHTS WITH "a" DESIGNATION

LIGHTING CONTROLLER

D

20A, 125V DIMMER SWITCH MOUNTED 42" AFF

2' x 2' FIXTURE.

A1 a

EMERGENCY LIGHT

2' x 4' FIXTURE. SOLID FILL INDICATES FIXTURE ON LIFE SAFETY OR

EMERGENCY CIRCUIT.

(WHERE GENERATOR POWER IS NOT AVAILABLE PROVIDE A UNIT

BATTERY AT 1400 LM)

2' x 4' FIXTURE. DIAGONAL FILL INDICATES FIXTURE ON CRITICAL

CIRCUIT.

MD MOTION DETECTOR

CC

CR

EL

AP

X

PB

K

HD

HA

PP

WIRELESS ACCESS POINT

KEY PAD

COMBINATION STARTER

NEMA 5-20 DUPLEX RECEPTACLE MOUNTED 44" AFF

UNLESS NOTED OTHERWISE

NEMA 5-20 DOUBLE DUPLEX RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE

POWER CONNECTION

N

PS

N

KC KEY PAD / CARD READER

6-30R

NEMA 5-20 DUPLEX RECEPTACLE WITH USB CHARGER MOUNTED 18" AFF

UNLESS NOTED OTHERWISE

NEMA 5-20 DUPLEX SPLIT RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE

NEMA 5-20 SIMPLEX RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE

S

FACP

FIRE ALARM CONTROL PANEL

FAA

FIRE ALARM ANNUNCIATOR PANEL

F FIRE ALARM CHIME/STROBE

FIRE ALARM SPEAKER/STROBE CEILDING MOUNTEDS

F COMBINATION HORN/STROBE WITH SENDING STATIONF

HEAT DETECTOR

R DUCT REMOTE TEST STATION

K KNOX BOX

D DOOR HOLDER

DS CEILING MOUNTED DAYLIGHT SENSOR

PC PHOTOCELL

S

H

A AMPERE

AC ABOVE COUNTER, 42"AFF UNLESS OTHERWISE INDICATED

ADA MERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR - TO BOTTOM

AL ALUMINUM

1/C ONE CONDUCTOR

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CU COPPER

(E) EXISTING

EF EXHAUST FAN

(EM) EMERGENCY LIGHTING

EMT ELECTRICAL METALLIC TUBING

EWC ELECTRIC WATER COOLER

FACP FIRE ALARM CONTROL PANEL

FM FREQUENCY MODULATION

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

HACR HEATING AIR CONDITIONING REFRIGERATION

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HT HEIGHT

HZ HERTZ

IDS INTRUSION DETECTION SYSTEM

J JUNCTION BOX

KWH KILOWATT HOUR

LED LIGHT EMITTING DIODE

MCB MAIN CIRCUIT BREAKER

MH MOUNTING HEIGHT - TO CENTER

MLO MAIN LUGS ONLY

MTD MOUNTED

NEC NATIONAL ELECTRICAL CODE

NF NON FUSED

NO. NUMBER

OS OCCUPANCY SENSOR

PH PHASE

PIR PASSIVE INFRARED

RGS RIGID GALVANIZED STEEL

SM SINGLE MODE

SPD SURGE PROTECTIVE DEVICE

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

UNO UNLESS NOTED OTHERWISE

V VOLT

VA VOLTAMPERE

VVD VARIABLE VOLUME DAMPER

W WATTS

WP WEATHERPROOF

XFMR TRANSFORMER

CEILING MOUNT

D2 FIXTURE

AIRCRAFT CABLE

AIRCRAFT CABLE

D2 FIXTURE

CEILING MOUNT

CEILING

MIN: 11"

MAX: 13''

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

09/01/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:5

:5

P

M

E001

LEGEND

20230901 JB IA

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTS

VA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

LIGHTING FIXTURE SCHEDULE

IMAGE TYPE DESCRIPTION FFE_Voltage LOAD (VA) LAMP(S)

LUMINOUS

FLUX

COLOR

TEMPERATURE

MOUNTING

S-SURFACE

R-RECESSED

CH-CHAIN HUNG

P-PENDANT

A1 LED COVE LIGHT, 0-10V DIMMING 120 V 54 LED 2400 lm 4000 K COVE

A1 (EM) LED COVE LIGHT, 0-10V DIMMING 120 V 54 LED 2400 lm 4000 K COVE

A2 LED TASK LIGHTING 18 LED SURFACE

A3 LED STRIP LIGHT, 0-10V DIMMING, COLOR CHANGING 120 V 6 LED 5700 lm 4000 K PENDANT

D1 6" LED DOWNLIGHT, CLEAR REFLECTOR, SEMI-SPECULAR, 0-10V DIMMING, MEDIUM DISTRIBUTION. 0-10V

DIMMING

18 1250 lm 4230 K RECESSED

D1 (EM) 6" LED DOWNLIGHT, CLEAR REFLECTOR, SEMI-SPECULAR, 0-10V DIMMING, MEDIUM DISTRIBUTION. 0-10V

DIMMING

18 LED 1250 lm 4230 K RECESSED

D2 FRAME ACCORD OVAL LED PENDANT, MATTE BLACK. 0-10V DIMMING LED PENDANT

D3 LED STRIP LIGHTING. 0-10V DIMMING LED SURFACE

X1 SINGLE FACE EXIT SIGN WITH STENCIL RED LETTERS, WHITE BODY 4 RED LED 0 lm 0 K SURFACE

NTS

Chandelier Detail

120/277 V

120/277 V

2987 lm

2987 lm

3500 K

120/277 V

120/277 V

120/277 V

120/277 V

LED

2605 lm 4000 K

D/3

GF

D/3

D/3

D/3

D/3

D/3

D/3

D/3

D

36" MH

D

60" MH

D D

D D

A1

A1 (EM)

A1

A1

A1

A1

A1

A1

A1

X1

X1

A1

A3

A3

A3

A3

A3

A3

TYP

TYP

TYP

HA

HD

HA

AE401

D1D1

D1 D1

D1

D1 (EM)

D1

D1 (EM)

D1

D1 (EM)

D1

D1 (EM)

D1 D1 D2

D1

D1

D1

D3

A2

TALL CABINET

b a a a ab c c c c c c c c a c c c c d d d d d d

11 11

11 11 a b c d b c a d

TYP

TYP

TYP

CHAPEL

AP

AP

27 27

TELEPHONE

REMOVE 14' PENDANT LIGHT

REMOVE 14' PENDANT LIGHT

REMOVE 14' PENDANT LIGHT

REMOVE 14' PENDANT LIGHT

REMOVE 14' PENDANT LIGHT

REMOVE 2' X 2'

LIGHT

REMOVE 1' X 4'

LIGHT

REMOVE WIRELESS

ACCESS POINT

REMOVE WIRELESS

ACCESS POINT

REMOVE CAN LIGHTS

REMOVE WALL

SCONCE

REMOVE WALL

SCONCE

REMOVE CAN LIGHTS

REMOVE WALL

SCONCE

REMOVE WALL

SCONCE

REMOVE EXIT

SIGN

REMOVE 1' X 4'

LIGHT

REMOVE SPEAKERS

REMOVE 1' X 4'

LIGHT

REMOVE

LIGHT SWITCH

HA

HD

HA 4

REMOVE

LIGHT SWITCH

TYP

TYP

CHAPEL

EM

AP

AP

DATA

176A

CHAPEL

DATA DROP

DATA CLOSET

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

09/01/2023

A u to d e s k D o c s /F t W a y n e V

A

R e m o d e l C h a p e l/ F

F E

F t W a y n e

R e m o d e l C h a p e l_

B rv t

/3

/2

:5

:5

P

M

EL101

ELECTRICAL DEMO AND NEW

WORK PLAN

20230901 BS IA

REMODEL FORT WAYNE CHAPEL 610A4-22-203

FORT WAYNE, IN

BID DOCUMENTS

VA NORTHERN

INDIANA

HEALTHCARE

SYSTEM

Approved: Veteran's Affairs Medical Center

N

1/4" = 1'-0"

ELECTRICAL FLOOR PLAN

D R A W I N G N O T E S :

1 TYPE A3 LED COLOR CHANGING LIGHTS MOUNTED BEHIND STAINED GLASS WINDOW. (4) 3' LIGHTS IN EACH WINDOW, TOP

BOTTOM AND BOTH SIDES. CONNECT WITH MAINTAINED CIRCUIT IN DEMO PHASE.

2 LED LIGHT FIXTURE MOUNTED IN COVE. ANGLED UPWARD. SEE ARCHITECTURAL DRAWINGS FOR MOUNTING LOCATION

AND DETAILS. CONNECT WITH MAINTAINED CIRCUIT IN DEMO PHASE.

3 REMOVE WALL SCONCE AND SURFACE WIREMOLD RACEWAY AND WIRING TO NEXT DEVICE. PROTECT AND MAINTAIN EMERGENCY CIRCUIT TO BE USED IN THE INSTALLATION OF NEW EMERGENCY FIXTURES IN NEW WORK PHASE.

4 REMOVE ADA ACTUATOR BUTTON.

5 REMOVE ADA DOOR OPENING MOTOR LOCATED ABOVE DOOR. PRESERVE CIRCUIT FOR USE IN NEW WORK.

6 INSTALL ADA ACTUATOR BUTTON AND CONNECT TO NEW ADA DOOR OPENING MOTOR ABOVE DOOR.

7 INSTALL ADA DOOR OPENING MOTOR ABOVE DOOR TO OPERATE BOTH DOORS IN DOORWAY AND ACTIVATED BY ADA

DOOR ACTUATOR. USE MAINTAINED EXISTING CIRCUIT FROM DEMO PHASE.

8 INSTALL LED STRIP LIGHT UNDER CABINET. MOUNT DRIVER INSIDE TALL CABINET AT OR NEAR THE TOP. ROUTE WIRING HIDDEN IN CABINET FROM DRIVER TO LED STRIP. CONNECT TO D1 LIGHT FIXTURE CIRCUIT IN ROOM.

9 TYPE D2 LED LED CHANDELIER MOUNTED WITH AIRCRAFT CABLE. SEE SHEET AE401 FOR HANGING HEIGHT. SEE SHEET

E001 FOR D2 FIXTURE DETAIL. CONNECT USING PRESERVED EXISTING CIRCUIT.

10 TYPE D3 LED LIGHTS MOUNTED AROUND SOFFIT IN CEILING.

This is the start of the file's text. The full file is on GovTribe.