MH111.pdf
PDF 487 KB Posted
- Solicitation number
- 36C25020B0059
About this file
This document contains a federal contract opportunity notice and related mechanical plans for interior deficiencies corrections at a Veterans Affairs medical center. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 will issue a solicitation on or around August 10, 2020 for project number 539-20-211 to correct deficiencies at its Cincinnati VAMC. The project magnitude is between $500,000 and $1,000,000, with a NAICS code of 238220 and business size standard of $16.5 million. This is a 100% set-aside for small businesses with a preference for service-disabled veteran-owned small businesses. Offerors must be registered and verified in VIP and SAM databases. The mechanical plans specify repairs and upgrades to ventilation, cooling equipment, and walk-in coolers/freezers in various rooms. The contract duration shall not exceed 180 calendar days from notice to proceed. Bonds will be required.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ED000A - BASEMENT ELECTRICAL DEMO PLAN- AREA A.pdf | ||
| AE111.pdf | ||
| FX101 - FIRE PROTECTION BASEMENT PLANS.pdf | ||
| Asbestos Survey Report.pdf | ||
| 114121 Walk-In Coolers and Freezers.pdf | ||
| AD112.pdf | ||
| Site Visit Sign In Sheet.pdf | ||
| EP000A - BASEMENT ELECTRICAL NEW WORK - AREA A.pdf | ||
| 2nd Sign in Sheet.pdf | ||
| 230511 Common Work Results for HVAC.pdf | ||
| MD101.pdf | ||
| AE101.pdf | ||
| 36C25020B0059 0002.docx | DOCX document | |
| AD111.pdf | ||
| 36C25020B0059 0001.docx | DOCX document | |
| Corbin Russwin Locksets Sole Source Justification - Redacted.pdf | ||
| S02 RFI Form.docx | DOCX document | |
| S02 Contractor EMR Certification Form.docx | DOCX document | |
| 539-20-211_Specifications (Combined).pdf | ||
| 100_ CD Drawings_Combined -07202020.pdf | ||
| 36C25020B0059.docx | DOCX document | |
| Wage Determination.pdf |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PATIENT
TOILET
SHOWER
ROOM
108A
SUPPLY
106B
AAMS
106A
EF-1
210 CFM
EG-1
100 CFM
EG-1
8"ø EA
"ø
E A
6" ø
EA
L-1
PHARMACY
MENS
RESTROOM
MENS
SHOWER
156A
ELEVATOR
LOBBY
148A
6" ø
EA
8" ø
EA
100 CFM
EG-1
160 CFM
EG-1
EF-2
10"ø EA L-2 1
4 BEDROOM
4 BEDROOM
4 BEDROOM
1 9
MENS
LOCKER
025A
WOMENS
LOCKER
EF-3
CORRIDOR
C*B*3
HAC
L-3
100 CFM
EG-1
225 CFM
EG-1 225 CFM
EG-1
6"ø EA 12"ø EA
TOILET
EMPLOYEE
BREAK ROOM
MENS RR
210 CFM
7270 CFM
RG-1
(E)20"x16" (E)12"x8"RA
8 8
8" ø
8" ø
10"ø
ACCU-010A
ACCU-006
COOLER
COOLER
FREEZER
010A
COOLER
ACCU-008 ACCU-010
DIRTY
CLOTHES
CLEAN
CLOTHES
007A
DIET. STOR.
2 2 2
3 3 3
4 4H.W. TANK
007A
A. NEW WORK IS INDICATED WITH HEAVY LINE WEIGHT.
B. LOCATE VOLUME DAMPERS AS FAR AWAY FROM AIR DEVICES AND AS
CLOSE TO TAKEOFFS FROM MAINS AS POSSIBLE TO PREVENT NOISE
(MINIMUM OF FIVE FEET AWAY FROM AIR DEVICES WHEREVER POSSIBLE).
LOCATE VOLUME DAMPERS SO THEY CAN BE ACCESSED THROUGH LAY-
IN CEILING TILE OR WITH REMOTE VOLUME DAMPER ADJUSTMENT
DEVICE WITH CABLE LOCATED INSIDE THE DUCT AND ADJUSTMENT
DEVICE INSIDE AIR DEVICE COVER. FOR VOLUME DAMPERS ACCESSIBLE
FROM LAY-IN CEILINGS, PROVIDE HANDLE WITH LOCKING QUADRANT AND
INSULATION STAND-OFF DEVICE TO PREVENT HANDLE FROM
CONFLICTING WITH EXTERNAL DUCT INSULATION. SEE VOLUME DAMPER
DETAIL.
C. INSTALL ALL EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH
MANUFACTURERS’ RECOMMENDATIONS, CONTRACT DOCUMENTS,
APPLICABLE CODES, REGULATIONS, AND OWNER STANDARDS.
D. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT,
DUCT AND PIPING INSULATION IS APPLIED.
E. THE LOCATIONS OF ITEMS SHOWN ON THE DRAWINGS OR REQUIRED BY
THE SPECIFICATIONS NOT DEFINITELY FIXED BY DIMENSIONS ARE
APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE
THE BEST RESULTS MUST BE DETERMINED BY THE PROJECT SITE
CONDITIONS AND SHALL HAVE THE APPROVAL OF THE OWNER AND
ENGINEER BEFORE BEING INSTALLED.
F. DO NOT SCALE DRAWINGS.
G. INSTALL EQUIPMENT WITH MINIMUM ACCESS CLEARANCE AS
RECOMMENDED BY CODE AND MANUFACTURERS.
H. SEE PHASING NOTES ON SHEET GI001.
G E N E R A L N O T E S
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FFE INC
110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
C :\U se rs
\q ui nn \D oc um en ts
\F t T ho m as
(2
9)
_p at ric k.
qu in nF
BN
EU
.rv t 8/
/2
2:
:0
PM
MH111
ENLARGED MECHANICAL PLANS CORRECT FCA DEFICIENCIES -
FTD INTERIOR DEFICIENCIES
FT THOMAS, KY 41075
539-20-211
BUILDING 64
05/01/20 GVC CAL
1/4" = 1'-0"1 ROOM 108 & 108A NEW WORK
1/4" = 1'-0"2 ROOM 156 & 156A NEW WORK
1/4" = 1'-0"3 ROOMS 025, 025A, 026 NEW WORK
1/8" = 1'-0"4 ENLARGED BASEMENT MECHANICAL PLAN
1 PROVIDE A NEW DEDICATED EXHAUST FAN, EXHAUST GRILLES, DUCT, DUCT
ACCESSORIES, FITTINGS, AND LOUVER, AND BALANCE TO AIRFLOW SHOWN.
2 PROVIDE A NEW AIR-COOLED CONDENSING UNIT, EVAPORATOR, AND
REFRIGERANT PIPING FOR THE COOLER/FREEZER. PROVIDE A COMPLETELY
NEW WALK-IN COOLER/FREEZER ENCLOSURE SYSTEM THAT FITS EXISTING
ROOM DIMENSIONS – SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.
3 MOUNT CONDENSING UNIT TO WALL 18" AFG WITH BRACKET MOUNT.
4 CONTRACTOR SHALL COORDINATE INSTALLATION OF COOLERS AND
FREEZER WITH C.O.R. FOR DOMESTIC WATER WORK TO BE COMPLETED
UNDER SEPARATE CONTRACT (BY VA).
5 ROUTE OF REFRIGERANT PIPING WAS BASED ON THE ASHRAE STANDARDS 15
& 34. REROUTING OF PIPING SHALL BE APPROVED BY MECHANICAL ENGINEER
OF RECORD.
6 REBALANCE EXISTING RETURN AIR DEVICES SO ROOM 025A MENS LOCKER
HAS 210 CFM RETURN AIRFLOW.
7 PROVIDE NEW RETURN AIR DEVICE RG-1 AND BALANCE TO AIRFLOW SHOWN.
8 BALANCE SUPPLY IN ROOM 025A TO 310 CFM; SUPPLY IN ROOM 025 TO 470
CFM; SUPPLY IN ROOM 026 TO 320 CFM AND RETURN IN ROOM 026 TO 120
CFM.
9 CONTRACTOR SHALL COORDINATE WITH VA COR ABOUT EXACT CONTROL
TIE-IN LOCATIONS WITHIN CONTROL CLOSETS LISTED IN NOTE B ON MH501.
D R A W I N G N O T E S
Revisions: Date:
100% Construction/BID Documents 05/01/2020 Addendum #2 09/02/2020
| Sheets |
| MH111 - ENLARGED MECHANICAL PLANS |