Asbestos Survey Report.pdf

PDF 3 MB Posted

Attached to
Z1DA--Correct FCA Deficiencies - FTD Interior Deficiencies -539-20-211
Solicitation number
36C25020B0059
Issued by

About this file

This notice announces a forthcoming solicitation for corrective facility condition deficiencies interior work. The Veterans Affairs Cincinnati VAMC intends to release solicitation number 36C25020B0059 for project number 539-20-211 with a projected value between $500,000 and $1,000,000. The work must be completed within 180 days of the notice to proceed. The solicitation will be a 100% set-aside for small businesses with an emphasis on service-disabled veteran-owned small businesses. The NAICS code is 238220 for the business size standard of $16.5 million. Interested offerors should register on beta.sam.gov where the full solicitation will be posted on or around August 10, 2020. Successful offerors must comply with VA security requirements and be registered and verified on vip.vetbiz.gov and sam.gov. Offerors must demonstrate no more than three serious OSHA or EPA violations and an experience modification rate of 1.0 or below. Bonds will be required in the form of bid, payment, and performance bonds.

View the file

Other files

File Type Posted
MH111.pdf PDF
ED000A - BASEMENT ELECTRICAL DEMO PLAN- AREA A.pdf PDF
AE111.pdf PDF
FX101 - FIRE PROTECTION BASEMENT PLANS.pdf PDF
114121 Walk-In Coolers and Freezers.pdf PDF
AD112.pdf PDF
Site Visit Sign In Sheet.pdf PDF
EP000A - BASEMENT ELECTRICAL NEW WORK - AREA A.pdf PDF
2nd Sign in Sheet.pdf PDF
230511 Common Work Results for HVAC.pdf PDF
MD101.pdf PDF
AE101.pdf PDF
36C25020B0059 0002.docx DOCX document
AD111.pdf PDF
36C25020B0059 0001.docx DOCX document
Corbin Russwin Locksets Sole Source Justification - Redacted.pdf PDF
S02 RFI Form.docx DOCX document
S02 Contractor EMR Certification Form.docx DOCX document
539-20-211_Specifications (Combined).pdf PDF
100_ CD Drawings_Combined -07202020.pdf PDF
36C25020B0059.docx DOCX document
Wage Determination.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Asbestos Survey

VA Project: Correct FCA Deficiencies – B64

VA Project No.: 539-20-211

Fort Thomas VA Medical Center

1000 Fort Thomas Avenue

Fort Thomas, KY 41075

January 30, 2020

Terracon Project No. N1197176

Prepared for:

FFE, Inc.

Cincinnati, Ohio 45246

Prepared by:

Terracon Consultants, Inc.

Cincinnati, Ohio 45226

Terracon Consultants, Inc., 611 Lunken Park Dr ive, C incinnat i , OH 45226

P (513) 321-5816 terracon.com

FEE, Inc.

438 Springfield Pike, Suite C

Cincinnati, Ohio 45215

Attn: Mr. Clint Weekley, PE, CBCP, LEED AP President

T: 513.522.0956

E: clint.weekley@ffe-serv.com

Re: Asbestos Survey

VA Project: Correct FCA Deficiencies – B64

VA Project No.: 539-20-211

Fort Thomas VA Medical Center

1000 Fort Thomas Avenue

Fort Thomas, KY, 41075

Dear Mr. Weekley, Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report for the above-referenced renovation project to FFE, Inc. (Client). The purpose of this report is to present the results of an asbestos survey which was performed at the site on January 14, 2020, and in general accordance with our proposal number PN1197176, dated May 10, 2019. We understand that this survey was requested for the purpose of a planned renovation project which will have impacts at various locations in Building 64 (B64) at the Fort Thomas VA Medical Center (FTVAMC).

Asbestos-containing materials (ACM) were identified as a result of the survey. Please refer to the attached report for detail.

Terracon appreciates the opportunity to provide this service to FFE, Inc. If you have any questions regarding this report, please contact the undersigned at 513-321-5816.

Sincerely, Terracon Consultants, Inc.

Lem Weyer Joseph A. Tussey, CHMM

Environmental Technician Sr. Associate / Group Manager

KY Asbestos Management Planner

Correct FCA Deficiencies – B64 ■ Fort Thomas VAMC January 30, 2020 ■ Terracon Project No. N1197176

TABLE OF CONTENTS

EXECUTIVE SUMMARY .......................................................................................................................... i

1.0 INTRODUCTION

1.1 Project Objective

1.2 Reliance

2.0 PROJECT DESCRIPTION

3.0 FIELD ACTIVITIES

3.1 Visual Assessment

3.2 Physical Assessment

3.3 Sample Collection

3.4 Sample Analysis

4.0 REGULATORY OVERVIEW

5.0 FINDINGS AND RECOMMENDATIONS

6.0 LIMITATIONS/GENERAL COMMENTS

APPENDIX A IDENTIFIED ASBESTOS-CONTAINING MATERIALS BY HOMOGENEOUS AREA (HA)

APPENDIX B ASBESTOS SURVEY SAMPLE & RESULTS SUMMARY

APPENDIX C ASBESTOS ANALYTICAL LABORATORY DATA

APPENDIX D LICENSES AND CERTIFICATIONS

APPENDIX E PROJECT / SAMPLE LOCATION DRAWINGS

APPENDIX F PHOTOS

Responsive ■ Resourceful ■ Reliable i

EXECUTIVE SUMMARY

Terracon Consultants, Inc. (Terracon) conducted an asbestos survey which was specifically limited to within the boundaries and intent of the planned renovation project entitled “Correct FCA

Deficiencies – FTD Interior Deficiencies” for Building 64 (B64) at the Fort Thomas VA Medical

Center (FTVAMC). We understand that this survey was requested prior to renovation for the purpose of compliance with the EPA National Emission Standards for Hazardous Air Pollutants

(NESHAP) regulation (40 CFR Part 61, Subpart M). The survey included identifying and sampling suspect asbestos-containing materials (ACM) for laboratory analysis, and providing information regarding the identity, location, condition, and approximate quantities of ACM (if any) pertaining to specific building components which may be impacted by the planned renovation as indicated on Client-provided drawings (see Appendix E). The survey was performed on January 14, 2020 by a Commonwealth of Kentucky Department of Environmental Protection, Division of Air Quality-licensed Asbestos Management Planner. The survey was conducted in general accordance with our proposal number PN1197176, dated May 10, 2019, and the sampling protocols established in USEPA 40 Code of Federal Regulations (CFR) Part 763, Subpart E, known as the Asbestos

Hazard Emergency Response Act (AHERA).

Specific to the subject renovation project areas and building systems indicated on Client-provided drawings (see Appendix E) and based on the analytical results of the collected samples, the materials listed below were identified to contain asbestos.

ACM Description Material Locations % and Type

Asbestos Condition

Estimated

Quantity*

12” x12” White Floor Tile with Black Specks and

Black Mastic Women’s Locker Room (Room 026)

Floor Tile: 2.6% Chrysotile, Mastic: 10% Chrysotile

Good 600 Square Feet (SF)

12” x12” White Floor Tile with Black Streaks and

Black Mastic Men’s Locker Room (Room 025A)

Floor Tile: 3.1% Chrysotile, Mastic: 10% Chrysotile

Good 450 SF

Black Mastic Under Non- Asbestos-Containing

12”x12” White Floor tile with Grey Specks

Linen Closet (Room 018) 4.2% Chrysotile Good 175 SF

*Estimated quantities listed above are based on a cursory field evaluation, and actual quantities may vary significantly, especially if

ACMs are present outside of the renovation areas, and in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document and contractors would be responsible for drawing their own conclusions on quantities present.

A sample summary is included in Appendix B and the laboratory analytical report is included in

Appendix C. Sample locations/renovation project drawings are included in Appendix E and example photos of the identified ACM are included in Appendix F.

If the identified ACM will be impacted by the renovation project, the materials will need to be removed prior to renovation by a state-licensed asbestos abatement contractor in accordance

Responsive ■ Resourceful ■ Reliable ii with applicable federal, state, and local asbestos regulations, as well as per the VA’s abatement specification requirements.

Please note that additional suspect ACM (not sampled as part of this survey) could be present in inaccessible/hidden areas.

Responsive ■ Resourceful ■ Reliable 1

ASBESTOS SURVEY

VA Project: Correct FCA Deficiencies –B64

VA Project No. 539-20-211

Fort Thomas VA Medical Center

1000 Fort Thomas Avenue

Fort Thomas, KY 41075

1.0 INTRODUCTION

Terracon Consultants, Inc. (Terracon) conducted an asbestos survey specifically limited to within the boundaries and intent of the planned renovation project entitled “VA Project: Correct FCA

Deficiencies- FTD Interior Deficiencies” in Building 64 (B64) of the Fort Thomas VA Medical

Center (FTAMC). The survey was performed at the site on January 14, 2019 by a Commonwealth of Kentucky Department of Environmental Protection, Division of Air Quality-licensed Asbestos

Management Planner. Accessible building components and areas intended to be renovated were surveyed based upon Client-provided renovation plans. Homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented. Although reasonable effort was made to survey accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids, or in other concealed areas. Suspect ACM samples were collected in general accordance with the sampling protocols outlined in USEPA 40

Code of Federal Regulations (CFR) Part 763, Subpart E, known as the Asbestos Hazard

Emergency Response Act (AHERA). Samples were delivered to an accredited laboratory for analysis by Polarized Light Microscopy (PLM).

1.1 Project Objective

We understand that this survey was requested for the purposes of a future planned renovation project. Please note that asbestos surveys are required prior to renovation or demolition to satisfy requirements of the USEPA 40 CFR Part 61, Subpart M, the National Emission Standards for

Hazardous Air Pollutants (NESHAP) regulation (as well as the state NESHAP equivalent).

1.2 Reliance

This report is for the exclusive use of FFE, Inc. (Client) for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and FFE, Inc. Reliance on this report by FFE, Inc. and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal and the agreement between Terracon and FFE, Inc.

Responsive ■ Resourceful ■ Reliable 2

2.0 PROJECT DESCRIPTION

In general, the planned renovation project includes replacement of the speaker system throughout the hallways; impacts to electrical closets, first floor bathrooms (108 and 165), basement bathrooms/locker rooms, and other various rooms; and the replacement of the basement walk-in coolers/freezers in B64 at the Fort Thomas VA Medical Center (FTVAMC). Client-provided drawings which indicate the areas and systems being impacted by the renovation are shown on the drawings included in Appendix E.

3.0 FIELD ACTIVITIES

The survey was conducted by Mr. Lemuel Weyer who is an EPA-accredited and Commonwealth of Kentucky Department of Environmental Protection, Division of Air Quality-licensed Asbestos

Management Planner. A copy of his current Kentucky Asbestos Management Planner credential is attached as Appendix D. The survey was conducted in general accordance with the sample collection protocols established in USEPA 40 CFR Part 763, Subpart E, Section 763.86, AHERA.

A summary of survey activities is provided below.

3.1 Visual Assessment

Survey activities were initiated with visual observation of accessible areas and accessible building components pertaining to the renovation project to identify homogeneous areas of suspect ACM.

A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color and texture with consideration given to the date of application.

Please note that additional suspect ACM (not sampled as part of this survey) may be present in

3.2 Physical Assessment

A physical assessment of each HA of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the USEPA as a material which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.

3.3 Sample Collection

Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with USEPA AHERA sampling protocols. Samples of suspect materials were collected from randomly selected locations in each homogeneous area. Bulk samples were

Responsive ■ Resourceful ■ Reliable 3 collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.

The selection of sample locations and frequency of sampling were based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content.

Terracon collected a total of 116 bulk samples from 38 homogeneous areas of suspect ACM. A summary of suspect ACM samples collected during the survey is included as Appendix B.

3.4 Sample Analysis

Bulk samples were submitted under chain of custody to International Asbestos Testing

Laboratories (IATL) of Mount Laurel, New Jersey for analysis by PLM with dispersion staining techniques per USEPA methodology 600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. For samples identified by PLM to contain <10% asbestos, the additional point count method was utilized. IATL is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP), accreditation number 101165-

0.

4.0 REGULATORY OVERVIEW

The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. The asbestos NESHAP regulation also requires the identification and classification of existing ACM according to friability prior to demolition or renovation activity. Friable ACM is a material containing more than 1% asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. All friable ACM is considered regulated asbestos containing material (RACM).

The asbestos NESHAP regulation classifies material subject to demolition or renovation as either

RACM, Category I non-friable ACM, or Category II non-friable ACM. RACM includes all friable

ACM (pre-disturbance), along with Category I non-friable ACM that becomes friable (during disturbance), and Category I non-friable ACM subject to sanding, grinding, cutting, or abrading, or Category II non-friable ACM with a high probability of becoming crumbled, pulverized, or reduced to powder by forces expected to act on the material during disturbance. Category I non-friable ACM are exclusively asbestos-containing packings, gaskets, resilient floor coverings, and asphalt roofing products that contain more than 1% asbestos. Category II non-friable ACM are all other non-friable materials (other than Category I non-friable ACM) that contain more than 1% asbestos. Category II non-friable ACM generally includes (but is not limited to) cementitious material such as: cement pipes, cement siding (Transite™), cement panels, glazing, mortar, and grouts.

Responsive ■ Resourceful ■ Reliable 4

In Kentucky, the federal NESHAP regulation has been delegated to the state EPA and is administered under 401 Kentucky Administrative Regulation (KAR) 58:025. The Kentucky

Department for Environmental Protection (DEP), Division for Air Quality (DAQ) is responsible for administering and enforcing the federal and state NESHAP regulations as well as administering accreditations for asbestos professionals. NESHAP pre-renovation and pre-demolition notifications (are sent to the regional state EPA office). NESHAP pre-renovation (where >160 SF

/ 260 LF of friable ACM is removed) and pre-demolition notifications must be submitted to the

DAQ office 10 business days prior to project commencement. The Kentucky local regional DAQ office for the subject site is the Florence Region; 8020 Veterans Memorial Drive, Suite 110, Florence, KY 41042; telephone (859-525-4157); contact Mr. Clay Redmond

(clay.redmond@ky.gov).

The United States Occupational Safety and Health Administration (USOSHA) asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The USOSHA standard requires that employee exposure to airborne asbestos must not exceed 0.1 fibers per cubic centimeter of air (0.1 f/cc) as an eight-hour time weighted average (TWA) and not exceed

1.0 fibers per cubic centimeter of air (1.0 f/cc) over a 30-minute time period known as an excursion limit (EL). The TWA and EL are known as USOSHA’s asbestos permissible exposure limits

(PELs). The USOSHA standard classifies construction and maintenance activities which could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work.

5.0 FINDINGS AND RECOMMENDATIONS

Specific to the subject renovation project areas and building systems indicated on Client-provided drawings (see Appendix E) and based on the analytical results of the collected samples, the materials listed below were identified to contain asbestos.

ACM Description Material Locations % and Type

Asbestos Condition

Estimated

Quantity*

12” x12” White Floor Tile with Black Specks and Black

Mastic

Women’s Locker Room (Room 026)

Floor Tile: 2.6% Chrysotile, Mastic: 10% Chrysotile

Good 600 Square Feet (SF)

12” x12” White Floor Tile with Black Streaks and Black

Mastic

Men’s Locker Room (Room 025A)

Floor Tile: 3.1% Chrysotile, Mastic: 10% Chrysotile

Good 450 SF

Black Mastic Under Non- Asbestos Containing 12” x 12”

White Floor Tile with Grey Specks

Linen Closet (Room 018) 4.2% Chrysotile Good 175 SF

*Estimated quantities listed above are based on a cursory field evaluation, and actual quantities may vary significantly, especially if

ACMs are present outside of the renovation areas, and in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document and contractors would be responsible for drawing their own conclusions on quantities present

Responsive ■ Resourceful ■ Reliable 5

A sample summary is included in Appendix B and the laboratory analytical report is included in

Appendix C. Sample locations/renovation project drawings are included in Appendix E and example photos of the identified ACM are included in Appendix F.

If the identified ACM will be impacted by the renovation project, the materials will need to be removed prior to renovation by a state-licensed asbestos abatement contractor in accordance with applicable federal, state, and local asbestos regulations, as well as per the VA’s abatement specification requirements.

Please note that additional suspect ACM (not sampled as part of this survey) could be present in

6.0 LIMITATIONS/GENERAL COMMENTS

The survey was project specific and limited to our understanding of the Client’s intended renovation project scope; this survey is not meant to be a comprehensive survey of the entire building/facility and may not have included all building systems/materials in the subject area. In addition, Terracon did not perform sampling which required demolition or destructive activities such as knocking large holes in walls, dismantling of equipment or removal of protective coverings

(including ceramic coverings, sampling would cause irreparable damage). Reasonable efforts to access suspect materials within known areas of restricted access (e.g., crawl spaces) were made;

however, confined spaces or areas which may pose a health or safety risk to Terracon personnel were not sampled. Sampling did not include suspect materials which could not be safely reached with available ladders/man-lifts.

This asbestos survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the building. The information contained in this report is relevant to the date on which this survey was performed and should not be relied upon to represent conditions at a later date. This report has been prepared on behalf of and exclusively for use by FFE, Inc. for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding quantities, further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories, or other third-parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.

Responsive ■ Resourceful ■ Reliable 6

APPENDIX A

VA Project: Correct FCA Deficiencies- FTD Interior Deficiencies

VA Project No. 539-20-211

Fort Thomas VA Medical Center

1000 Fort Thomas Avenue

Fort Thomas, KY 41075

IDENTIFIED ASBESTOS-CONTAINING MATERIALS BY HOMOGENEOUS AREA (HA)

HA

No.

ACM Description Material Location

% and Type

Asbestos

EPA NESHAP

Classification Condition

Estimated

Quantity*

12” x12” White Floor Tile with Black Specks and Black Mastic

Women’s Locker Room (Room 026) Floor Tile: 2.6% Chrysotile

Mastic: 10% Chrysotile Category I Non-Friable Good 600 SF

12” x12” White Floor Tile with Black Streaks and

Black Mastic Men’s Locker Room (Room 025A)

Floor Tile: 3.1% Chrysotile Mastic: 10% Chrysotile

Category I Non-Friable Good 450 SF

Black Mastic Under Non- Asbestos Containing 12” x 12” White Floor Tile with

Grey Specks

Linen Closet (Room 018) 4.2% Chrysotile Category I Non-Friable Good 175 SF

See Appendix B for a summary of samples collected, Appendix C for detailed analytical results, Appendix E for a sample location drawings/renovation plans, and

Appendix F for example photos of the identified ACM.

*Estimated quantities listed above are based on a cursory field evaluation, and actual quantities may vary significantly, especially if ACMs are present outside of the planned renovation areas, and in hidden and/or inaccessible areas not evaluated as part of this survey. This is not a bidding document and contractors would be responsible for drawing their own conclusions regarding quantities present.

It should be noted that inaccessible/concealed suspect materials, other than those identified during this survey, may exist. Should additional suspect materials be uncovered prior to or during renovation activities, those materials must be assumed asbestos-containing until sampled by a state-licensed asbestos inspector and analysis refutes the positive assumption.

If the identified ACM will be impacted by the renovation, such materials would need to be properly removed, handled, and disposed in accordance with applicable federal and state EPA regulations, OSHA regulations, and per VA project specifications.

Responsive ■ Resourceful ■ Reliable 7

APPENDIX B

VA Project: Correct FCA Deficiencies- FTD Interior Deficiencies

VA Project No. 539-20-211

Fort Thomas VA Medical Center

1000 Fort Thomas Avenue

Fort Thomas, KY 41075

ASBESTOS SURVEY SAMPLE & RESULTS SUMMARY

Sample # Sample Material

Description Sample Location HA Location(s)

Results (% /

Type of

Asbestos) HA # SEQ. #

Tan Duct Mastic

Electrical Closet –

Room 276

Associated with

2nd and 3rd Floor

Duct Work

None Detected

(ND)

Electrical Closet-

Room 242d

ND

Electrical Closet-

Room 356

ND

Red Fire-Stop

Caulking

Electrical Closet –

Room 276 Penetrations in

Electrical Closet

Walls on 2nd and

3rd Floors

ND

Electrical Closet-

Room 242d

ND

Electrical Closet-

Room 356

ND

Drywall System:

Gypsum Board with

Joint Compound

Doorway of Room

2nd and 3rd Floor

Electrical Closets

Gypsum Board:

ND, Joint

Compound: ND

Northwest Corner of 242d

Gypsum Board:

ND, Joint

Compound: ND

Doorway of Room

Gypsum Board:

ND, Joint

Compound: ND

2’ x 2’ White Plain

Ceiling Tiles

Hallway near

Electrical Closet

253 Throughout 2nd

Floor

ND

Hallway Outside

Room 244

ND

Responsive ■ Resourceful ■ Reliable 8

Hallway Outside

Room 232

ND

Grey Duct Mastic

Hallway Outside

Room 200 Associated with

Various

Locations of Duct

Work throughout the Building

ND

Hallway Outside

Room 329

ND

Hallway Outside

Room 129

ND

White Encapsulant

Hallway Outside

Room 200 Associated with

Fiberglass Pipes

Throughout

Building

Encapsulant: ND, Fiberglass: ND

Hallway Near

Room 307a

Encapsulant: ND, Fiberglass: ND

Hallway Outside

Room 029

Encapsulant: ND, Fiberglass: ND

2’ x 2’ Ceiling Tiles with Small Fissures

Outside Offices

Throughout 3rd

Floor

ND

Hallway Outside

Room 307

ND

Hallway Outside

Room 336

ND

2’ x 2’ Ceiling Tiles with Large Fissures

Hallway Outside

Room 113

Throughout 1st

Floor and

Basement

ND

Hallway Outside

Room 101

ND

Hallway Outside

Room 031

ND

Tan Duct Mastic

Hallway Outside

Room123 Associated with

1st and

Basement Duct

Work

ND

Hallway Outside

Room 023

ND

Hallway Outside

Room 029

ND

10 28

1” x 1” Red and White

Ceramic Floor Tile with Mastic and Grout

Room 108-

Doorway to

Shower Area

Bathrooms 108, 156, 025

Ceramic: ND, Mastic: ND, Grout: ND

Responsive ■ Resourceful ■ Reliable 9

Room 108- Main

Doorway to

Bathroom

Ceramic: ND, Mastic: ND, Grout: ND

Room 156- Main

Doorway to

Bathroom

Ceramic: ND, Mastic: ND, Grout: ND

4” x 4” Tan Wall Tile with Yellow Mastic

Room 108-

Northeast Corner of Bathroom Area

Bathrooms 108 and 156

Ceramic: ND, Mastic: ND

Room 108-

Northeast Corner of Bathroom Area

Ceramic: ND, Mastic: ND

Room 156-

Northwest Corner of Room

Ceramic: ND, Mastic: ND

2’ x 2’ Ceiling Tile with

Small Fissures

Room 108- Middle of Room

Bathrooms 108 and 156

ND

Room 156- Middle of Room

ND

Room 156-

Northwest Corner

ND

Drywall System:

Gypsum Board with

Joint Compound

Room 108-

Northeast Corner of Bathroom Area

Bathrooms 108 and 156

Gypsum Board:

ND

Room 108-

Northeast Corner of Shower Area

Gypsum Board:

ND, Joint

Compound: ND

Room 156-

Northwest Corner of Center Dividing

Wall

Gypsum Board:

ND, Joint

Compound: ND

2’ x 2’ Drywall Ceiling

Tiles

Room 108-

Northwest Corner

Bathrooms 108 and 156 Shower

Areas

ND

Room 156-

Southeast Corner

ND

Room 156-

Southwest Corner

ND

15 43 White Encapsulant with Mastic

Room 108- Middle of Shower Area

Associated with

Fiberglass Pipes

Throughout

Encapsulant: ND, Fiberglass: ND, Mastic: ND

Responsive ■ Resourceful ■ Reliable 10

Room 108- Middle of Shower Area

Bathrooms 108 and 156

Encapsulant: ND, Fiberglass: ND, Mastic: ND

Room 156 Middle of Bathroom Area

Encapsulant: ND, Fiberglass: ND

Pipe Insulation and

Hard Fittings

North End of

Center Divider Wall in Room 156 Behind Walls in

Pipe Chases of

Bathrooms 108 and 156

Insulation: ND, Wrap: ND

North End of

Center Divider Wall in Room 156

Insulation: ND, Wrap: ND

North End of

Center Divider Wall in Room 156

Insulation: ND, Wrap: ND

Red Fire-Stop

Caulking

Room 108- Middle

North Wall Associated with

Penetrations in

Walls of

Bathrooms 108 and 156

ND

Room 108- Middle

North Wall

ND

Room 156-

Northeast Corner

ND

Plaster Walls and

Ceilings

Middle North Wall

Bathroom 156

ND

53 Middle North Wall ND

54 Northeast Corner ND

Fiberglass Reinforced

Plastic (FRP) Board with White Mastic

Doorway of Cooler

Room 007 Basement Walk-in Coolers.

Rooms 006, 007, 008, 010, 010A

FRP Board: ND, Mastic: ND

Doorway of Cooler

Room 010

FRP Board: ND, Mastic: ND

Doorway of Cooler

Room 010A

FRP Board: ND, Mastic: ND

6” x 6” Red Ceramic

Floor Tile with Mortar

Doorway of Cooler

Basement Walk-in Coolers.

Rooms 006, 007, 008, 010, 010A

Ceramic: ND, Mortar: ND

Doorway of Cooler

Ceramic: ND, Mortar: ND

Doorway of Cooler

Ceramic: ND, Mortar: ND

Responsive ■ Resourceful ■ Reliable 11

Multi-Sized (1” x 1” and 1” x 2”) Blue

Ceramic Floor Tile with Mastic and Grout

Doorway

Room 022

Ceramic: ND, Grout: ND

62 Doorway Ceramic: ND, Grout: ND

63 Northeast Corner Ceramic: ND, Grout: ND

4” x 4” Blue Wall Tile with Mastic and Grout

Southwest Corner

Room 022

Ceramic: ND, Mastic: ND, Grout: ND

65 Southwest Corner

Ceramic: ND, Mastic: ND, Grout: ND

66 Southwest Corner

Ceramic: ND, Mastic: ND, Grout: ND

4” x 4” White Wall Tile with Mastic and Grout

Southwest Corner

Southwest

Corner of 017

Ceramic: ND, Mastic: ND, Grout: ND

68 Southwest Corner

Ceramic: ND, Mastic: ND, Grout: ND

69 Southwest Corner

Ceramic: ND, Mastic: ND, Grout: ND

Unfinished Gypsum

Board

Southwest Corner

West Wall in

Room 017

Sample Not

Analyzed

71 Southwest Corner

Gypsum Board:

ND, White

Texture: ND

72 Northwest Corner

Gypsum Board:

ND, White

Texture: ND

1” x 1” Grey Floor Tile with Mastic and Grout

Doorway

Room 024

Ceramic: ND, Mastic: ND, Grout: ND

74 Doorway

Ceramic: ND, Mastic: ND, Grout: ND

75 Doorway

Ceramic: ND, Mastic: ND, Grout: ND

26 76 Plaster Walls and

Ceilings

Room 022-

Northwest Corner

Skim Coat: ND, Plaster: ND

Responsive ■ Resourceful ■ Reliable 12

Room 023-

Northeast Corner

Rooms 017, 022, 023, 024, 025 &

Skim Coat: ND, Plaster: ND

Room 017-

Doorway

Skim Coat: ND, Plaster: ND

Room 024-

Southwest Corner of Locker Room

Skim Coat: ND, Plaster: ND

Room 026-

Northeast Corner

Skim Coat: ND, Plaster: ND

12” x 12” Pink Floor

Tile with Yellow

Mastic

Southwest Corner

Room 023

Ceramic: ND, Mastic: ND

82 Northwest Corner Ceramic: ND, Mastic: ND

83 Northeast Corner Ceramic: ND, Mastic: ND

8” Tan Cove Base with Tan Mastic

Southwest Corner

Room 023

Cove Base: ND, Mastic: ND

85 Northwest Corner Cove Base: ND, Mastic: ND

86 Northeast Corner Cove Base: ND, Mastic: ND

Black Sink

Undercoating

Southwest Corner

Sink

Room 023

Southwest Sink

ND

Southwest Corner

Sink

ND

Southwest Corner

Sink

ND

2’ x 2’ Drywall Ceiling

Tiles

Northwest Corner

Room 023

ND

91 Northeast Corner ND

92 Southeast Corner ND

31 93 Tan Duct Mastic Middle of Room

Associated with

Duct Work

ND

Responsive ■ Resourceful ■ Reliable 13

Middle of Room

Throughout

Rooms 017, 022, 023, 024, 025 &

ND

Middle of Room

ND

White Duct Sealant

Middle of Room

Associated with

Room 023 Duct

Work

ND

Middle of Room

ND

Middle of Room

ND

12” x 12” White Floor

Tile with Black Specks and Black Mastic

Southeast Corner

Women’s

Restroom- 026

Floor Tile: 2.2%

Chrysotile by

Point Count

(PC), Mastic:

7.3% Chrysotile

PC

100 Northeast Corner

Floor Tile: 2.6%

Chrysotile PC, Mastic: 10%

Chrysotile

101 Southwest Corner

Floor Tile: 1.9%

Chrysotile PC, Mastic: 2.4%

Chrysotile PC

8” Black Cove Base with Brown Mastic

Southeast Corner

Women’s

Restroom- 026

Cove Base: ND, Mastic: ND

103 Northeast Corner Cove Base: ND, Mastic: ND

104 Southwest Corner Cove Base: ND, Mastic: ND

1” x 1” Tan Ceramic

Floor Tile with Mastic and Grout

Southwest of 026

Southwest

Corner of

Women’s

Restroom- 026

Ceramic: ND, Grout: ND, Mastic: ND

106 Southwest of 026

Ceramic: ND, Grout: ND, Mastic: ND

107 Southwest of 026

Ceramic: ND, Grout: ND, Mastic: ND

Responsive ■ Resourceful ■ Reliable 14

12” x12” White Floor

Tile with Black

Streaks and Black

Mastic

Northeast Corner

Men’s Locker

Room- Room

025A

Floor Tile: 3.1%

Chrysotile PC, Mastic: 8.3%

Chrysotile PC

109 Northwest Corner

Floor Tile: 2.0%

Chrysotile PC, Mastic: 10%

Chrysotile

110 Southeast Corner

Floor Tile: 1.8%

Chrysotile PC, Mastic: 10%

Chrysotile

4” x 4” Aqua Wall Tile with Mastic and Grout

Northeast Corner

Men’s Restroom-

Room 025

Ceramic: ND, Mastic: ND, 112 Northeast Corner Ceramic: ND, Mastic: ND, 113 Northwest Corner Ceramic: ND, Mastic: ND, 12” x 12” White Floor

Tile with Grey Specks and Black Mastic

Southwest Corner

Linen Closet-

Room 018

Floor Tile: ND, Mastic: 4.2%

Chrysotile PC

115 Northwest Corner

Floor Tile: ND, Mastic: 3.7%

Chrysotile PC

116 Southeast Corner Floor Tile: ND

Responsive ■ Resourceful ■ Reliable

APPENDIX C

ASBESTOS ANALYTICAL LABORATORY DATA

Lab No.: 6953376 Client No.: 1-01

Analyst Observation: Tan Mastic Client Description: Tan Duct Mastic

Location: Electrical Closet- Room 276 Facility:

Percent Asbestos:

None Detected

Percent Non-Asbestos Fibrous Material:

Percent Non-Fibrous Material:

Lab No.: 6953377 Client No.: 1-02

Location: Electrical Closet- Room 242d

Lab No.: 6953378 Client No.: 1-03

Location: Electrical Closet- Room 356

Lab No.: 6953379 Client No.: 2-04

Analyst Observation: Red Firestop Client Description: Red Fire-Stop Caulking

5 Fibrous Glass

Lab No.: 6953379(L2) Client No.: 2-04

Analyst Observation: Off-White Insulation

10 Cellulose

Lab No.: 6953380 Client No.: 2-05

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Amy Latham

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Client: TER940

Dated : 1/29/2020 1:29:01 Page 1 of 43

Lab No.: 6953380(L2) Client No.: 2-05

Lab No.: 6953381 Client No.: 2-06

Lab No.: 6953381(L2) Client No.: 2-06

Lab No.: 6953382 Client No.: 3-07

Analyst Observation: White Drywall Client Description: Drywall System: Gypsum Board With Joint Compound

Location: Doorway Of Room 276

3 Fibrous Glass

Lab No.: 6953382(L2)

Analyst Observation: White Joint Compound

Lab No.: 6953382(L3)

Analyst Observation: Composite

5 Cellulose

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Amy Latham

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:01 Page 2 of 43

Lab No.: 6953383 Client No.: 3-08

Location: Northwest Corner Of 242d

3 Fibrous Glass

Lab No.: 6953383(L2)

Lab No.: 6953383(L3)

Lab No.: 6953384 Client No.: 3-09

Location: Doorway Of Room 365

Lab No.: 6953384(L2)

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Amy Latham

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:01 Page 3 of 43

Lab No.: 6953384(L3)

Lab No.: 6953385 Client No.: 4-10

Analyst Observation: Tan/White Ceiling Tile Client Description: 2'x2' White Plain Ceiling Tiles

Location: Hallway Near Electrical Closet Facility:

40 Cellulose 40 Mineral Wool

Lab No.: 6953386 Client No.: 4-11

Location: Hallway Outside Room 244

Lab No.: 6953387 Client No.: 4-12

Location: Hallway Outside Room 232

Lab No.: 6953388 Client No.: 5-13

Analyst Observation: Grey Mastic Client Description: Grey Duct Mastic

Location: Hallway Outside Room 200

Lab No.: 6953389 Client No.: 5-14

Location: Hallway Outside Room 329

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Amy Latham

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:01 Page 4 of 43

Lab No.: 6953390 Client No.: 5-15

Location: Hallway Outside Room 129

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Amy Latham

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:01 Page 5 of 43

Lab No.: 6953391 Client No.: 6-16

Analyst Observation: White Sealant Client Description: White Encapsulant

Lab No.: 6953391(L2) Client No.: 6-16

Analyst Observation: Yellow Insulation

95 Fibrous Glass

Lab No.: 6953392 Client No.: 6-17

Location: Hallway Near Room 307a

Lab No.: 6953392(L2) Client No.: 6-17

Location: Hallway Near Room 307a

Lab No.: 6953393 Client No.: 6-18

Location: Hallway Outside Room 029

Lab No.: 6953393(L2) Client No.: 6-18

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:01 Page 6 of 43

Lab No.: 6953394 Client No.: 7-19

Client Description: 2'x2' Ceiling Tile With Small Fissures

Location: Outside Offices 371

50 Cellulose 30 Mineral Wool

Lab No.: 6953395 Client No.: 7-20

Location: Hallway Outside Room 307

Lab No.: 6953396 Client No.: 7-21

Location: Hallway Outside Room 336

Lab No.: 6953397 Client No.: 8-22

Client Description: 2'x2 Ceiling Tile With Large Fissures

Location: Hallway Outside Room 113

Lab No.: 6953398 Client No.: 8-23

Location: Hallway Outside Room 102

Lab No.: 6953399 Client No.: 8-24

Location: Hallway Outside Room 031

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:01 Page 7 of 43

Lab No.: 6953400 Client No.: 9-25

Location: Hallway Outside Room 123

Lab No.: 6953401 Client No.: 9-26

Location: Hallway Outside Room 023

Lab No.: 6953402 Client No.: 9-27

Lab No.: 6953403 Client No.: 10-28

Analyst Observation: Tan/White Ceramic Client Description: 1"x1" Red And White Ceramic Floor Tile With Mastic And Grout

Location: Room 108- Doorway To Shower Area Facility:

Lab No.: 6953403(L2)

Analyst Observation: Tan Mastic / Paper

Facility:

Lab No.: 6953403(L3)

Analyst Observation: Dk Grey Grout

Facility:

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:01 Page 8 of 43

Lab No.: 6953404 Client No.: 10-29

Location: Room 108- Main Doorway To Bathroom Facility:

Lab No.: 6953404(L2)

Facility:

Lab No.: 6953404(L3)

Facility:

Lab No.: 6953405 Client No.: 10-30

Location: Room 156- Main Doorway To

Facility:

Lab No.: 6953405(L2)

Facility:

Lab No.: 6953405(L3)

Facility:

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 9 of 43

Lab No.: 6953406 Client No.: 11-31

Client Description: 4"x4" Tan Wall Tile With Yellow Mastic And Grout

Location: Room 108- Northeast Corner Of Bathroom Area Facility:

Lab No.: 6953406(L2) Client No.: 11-31

Facility:

Lab No.: 6953407 Client No.: 11-32

Facility:

Lab No.: 6953407(L2) Client No.: 11-32

Facility:

Lab No.: 6953408 Client No.: 11-33

Location: Room 156- Northwest Corner Of Room Facility:

Lab No.: 6953408(L2) Client No.: 11-33

Room Facility:

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 10 of 43

Lab No.: 6953409 Client No.: 12-34

Location: Room 108- Middle Of Room

Lab No.: 6953410 Client No.: 12-35

Location: Room 156- Middle Of Room

Lab No.: 6953411 Client No.: 12-36

Location: Room 156- Northwest Corner

Lab No.: 6953412 Client No.: 13-37

Analyst Observation: White/Tan Drywall

Facility:

11 Cellulose

Lab No.: 6953413 Client No.: 13-38

Shower Area Facility:

Lab No.: 6953413(L2)

Facility:

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 11 of 43

Lab No.: 6953413(L3)

Facility:

Lab No.: 6953414 Client No.: 13-39

Center Dividing Wall Facility:

Lab No.: 6953414(L2)

Facility:

Lab No.: 6953414(L3)

Facility:

Lab No.: 6953415 Client No.: 14-40

Analyst Observation: White/Tan Ceiling Tile Client Description: 2'x2' Drywall Ceiling Tiles

Location: Room 108- Northwest Corner

2 Fibrous Glass

Lab No.: 6953416 Client No.: 14-41

Location: Room 156- Southeast Corner

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 12 of 43

Lab No.: 6953417 Client No.: 14-42

Location: Room 156- Southwest Corner

Lab No.: 6953418 Client No.: 15-43

Location: Room 108- Middle Of Shower

Facility:

Lab No.: 6953418(L2)

Analyst Observation: Clear Mastic

Facility:

Lab No.: 6953418(L3)

Facility:

Lab No.: 6953418(L4)

Analyst Observation: Silver/White/Tan Wrap / Mastic

Facility:

30 Fibrous Glass

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 13 of 43

Lab No.: 6953418(L5)

Facility:

Lab No.: 6953418(L6)

Facility:

Lab No.: 6953419 Client No.: 15-44

Facility:

Lab No.: 6953419(L2)

Facility:

Lab No.: 6953419(L3)

Facility:

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 14 of 43

Lab No.: 6953419(L4)

Facility:

Lab No.: 6953420 Client No.: 15-45

Location: Room 156- Middle Of Bathroom

Facility:

Lab No.: 6953420(L2) Client No.: 15-45

Location: Room 156- Middle Of Bathroom

Facility:

Lab No.: 6953421 Client No.: 16-46

Analyst Observation: Lt Grey Insulation Client Description: Pipes Insulation And Hard Fittings

Location: North End Of Center Divider Wall In Room 156 Facility:

Lab No.: 6953421(L2) Client No.: 16-46

Analyst Observation: White Wrap

Facility:

95 Cellulose

Lab No.: 6953422 Client No.: 16-47

Facility:

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 15 of 43

Lab No.: 6953422(L2) Client No.: 16-47

Facility:

Lab No.: 6953423 Client No.: 16-48

Facility:

Lab No.: 6953423(L2) Client No.: 16-48

Facility:

Lab No.: 6953424 Client No.: 17-49

Location: Room 108- Middle North Wall

20 Fibrous Glass

Lab No.: 6953424(L2) Client No.: 17-49

Lab No.: 6953425 Client No.: 17-50

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 16 of 43

Lab No.: 6953425(L2) Client No.: 17-50

Lab No.: 6953426 Client No.: 17-51

Location: Room 156- Northeast Corner

Lab No.: 6953426(L2) Client No.: 17-51

Location: Room 156- Northeast Corner

Lab No.: 6953427 Client No.: 18-52

Analyst Observation: Lt Tan Plaster Client Description: Plaster Walls And Ceilings

Location: Middle North Wall

Lab No.: 6953428 Client No.: 18-53

Location: Middle North Wall

Lab No.: 6953429 Client No.: 18-54

Location: Northeast Corner

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 17 of 43

Lab No.: 6953430 Client No.: 19-55

Analyst Observation: White Covering Material Client Description: Fiberglass Reinforced Plastic Board With White Mastic

Location: Doorway Of Cooler Room 007

40 Fibrous Glass

Lab No.: 6953430(L2) Client No.: 19-55

Analyst Observation: White Mastic

Location: Doorway Of Cooler Room 007

Lab No.: 6953431 Client No.: 19-56

Location: Doorway Of Cooler Room 010

Lab No.: 6953431(L2) Client No.: 19-56

Location: Doorway Of Cooler Room 010

Lab No.: 6953432 Client No.: 19-57

Location: Doorway Of Cooler Room 010A

Lab No.: 6953432(L2) Client No.: 19-57

Location: Doorway Of Cooler Room 010A

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 18 of 43

Lab No.: 6953433 Client No.: 20-58

Analyst Observation: Red Brick Client Description: 6"x6" Red Ceramic Floor Tile With Mortar And Grout

Location: Doorway Of Cooler 006

Lab No.: 6953433(L2) Client No.: 20-58

Analyst Observation: Grey Mortar

Lab No.: 6953434 Client No.: 20-59

Lab No.: 6953434(L2) Client No.: 20-59

Lab No.: 6953435 Client No.: 20-60

Location: Doorway Of Cooler 010

Lab No.: 6953435(L2) Client No.: 20-60

Location: Doorway Of Cooler 010

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 19 of 43

Lab No.: 6953436 Client No.: 21-61

Analyst Observation: Blue/White Ceramic Client Description: Multi-Sized (1"x1" and 1'x2") Blue Ceramic Floor Tile With Mastic And Grout

Location: Doorway

Lab No.: 6953436(L2) Client No.: 21-61

Analyst Observation: Grey Grout

Lab No.: 6953437 Client No.: 21-62

Lab No.: 6953437(L2) Client No.: 21-62

Lab No.: 6953438 Client No.: 21-63

Lab No.: 6953438(L2) Client No.: 21-63

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 20 of 43

Lab No.: 6953439 Client No.: 22-64

Client Description: 4"x4" Blue Wall Tile With Mastic And Grout

Location: Southwest Corner

Lab No.: 6953439(L2)

Analyst Observation: Lt Tan Mastic

Lab No.: 6953439(L3)

Lab No.: 6953439(L4)

Analyst Observation: Off-White Cementitious

Lab No.: 6953440 Client No.: 22-65

Lab No.: 6953440(L2)

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Terracon

611 Lunken Park Drive Cincinnati OH 45226

1/29/2020Report Date:

Report No.: 607942 - PLM Project: Fort Thomas VAMC Project No.: N1197176

PLM BULK SAMPLE ANALYSIS SUMMARY

Dated : 1/29/2020 1:29:02 Page 21 of 43

Lab No.: 6953440(L3)

Lab No.: 6953440(L4)

Lab No.: 6953441 Client No.: 22-66

Lab No.: 6953441(L2)

Lab No.: 6953441(L3)

Lab No.: 6953441(L4)

Laboratory Director

Approved By:

Date Analyzed:

1/16/2020Date Received:

Analyst:

Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Christopher Riffe

01/28/2020 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email:…

This is the start of the file's text. The full file is on GovTribe.