This pre-solicitation notice is for a new MRI site preparation project set aside for Service-Disabled Veteran-Owned Small Businesses. The Department of Veterans Affairs Network Contracting Office 10 requires preparation of a new building site to house MRI equipment at the Dayton VA Medical Center in Dayton, Ohio, for project number 552-18-102. The contractor shall provide all labor, materials, equipment, and supervision to prepare the site according to drawings and specifications within 245 calendar days of receiving the notice to proceed. The solicitation documents will be posted on March 20, 2020 on FBO.gov, with proposals due approximately 30 days later. This $2-5 million project has a NAICS code of 236220 and is 100% set aside for verified SDVOSBs. The contractor must perform a minimum of 15% of construction work. Bid, payment, and performance bonds will be required. A one-time site visit will be scheduled. Amendments will be posted on FBO.gov. Questions should be emailed to the point of contact provided.

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXISTING FIRST FLOOR

0"

P.81

CONCRETE FOUNDATION,

REFER TO STRUCTURAL

DRAINGS

CONCRETE SLAB ON

GRADE, REFER TO

STRUCTURAL DRAWINGS

MIN. R13 BATT

INSULATION

/8

1 3/8"

1 3/8"

2" 5/8" 6" 5/8"

1'-6"

1'-0"

INSULATED SPANDREL

GLASS UNIT

WINDOW SILL FRAMING

MEMBER & SILL

RECEPTOR

BLOCKING AS

REQUIRED

5/8" GYPSUM BOARD

6" COLD-FORMED

METAL FRAMING

1 5/8" LIGHT GAUGE

METAL FRAMING

WATER-RESISTIVE

BARRIER

EXTERIOR GYPSUM

SHEATHING

THIN CALCIUM

SILICATE UNIT (TYP.)

RIGID INSULATION

ALUMINUM STARTER

CHANNEL

STAINLESS STEEL

FLASHING

SEALANT AND BACKER

ROD W/ WEEP VENTS

@ 24"O.C. TO ALIGN W/

CHANNEL WEEPS

FLEXIBLE FLASHING

SEALANT AND BACKER

ROD

STAINLESS STEEL

FLASHING

PLASTIC ISOLATING

SHIM AS REQUIRED

ALUMINUM

INTERMEDIATE

CHANNEL (TYP.)

(2'X2') 2" PERIMETER

INSULATION

PERIMETER FOUNDATION

DRAIN, REFER TO CIVIL

DRAWINGS

POROUS FILL

FLUID APPLIED

WATERPROOFING

P.81

SCHEDULED CEILING

MIN. R13 BATT

INSULATION

WINDOW HEAD

9'-0"

STAINLESS STEEL

FLASHING

WINDOW HEAD

FRAMING MEMBER

INSULATED GLAZING

UNIT

WINDOW HORIZONTAL

FRAMING MEMBER

INSULATED SPANDREL

GLASS UNIT

/8

/8

5/8" GYPSUM BOARD

6" COLD-FORMED

METAL FRAMING

SEALANT AND BACKER

ROD (TYP.)

SEALANT AND BACKER

ROD - BEHIND

CHANNEL WEEPS

ALUMINUM STARTER

CHANNEL

BLOCKING AS

REQUIRED

THIN CALCIUM

SILICATE UNIT (TYP.)

RIGID INSULATION

WATER-RESISTIVE

BARRIER

2" COLD-FORMED "Z"

EXTERIOR GYPSUM

SHEATHING

PLASTIC ISOLATING

SHIM AS REQUIRED

SEALANT AND BACKER

ROD (TYP.)

1 3/8"

1 3/8"

2" 5/8" 6" 5/8"

1'-0"

1'-6"

COLD-FORMED BOX

HEADER, SEE STRUCT.

DWGS.

MULLION EXTENSION

'J' BEAD

5/8" GYPSUM BOARD

1 5/8" LIGHT GAUGE

METAL FRAMING

EXISTING FIRST FLOOR

0"

8.8

RECESSED RF

FLOORING, REFER TO

RF FLOORING DETAIL

PARENT WALL, REFER

TO FLOOR PLAN FOR

WALL TYPE

RF WALL, REFER TO

RF WALL DETAIL

2" ISOLATION

SCHEDULED BASE

R F

W A

L L P

A N

E L

RECESSED REINFORCED

SLAB ON GRADE, REFER TO

STRUCTURAL DRAWINGS

CONCRETE SLAB ON

GRADE, REFER TO

STRUCTURAL DRAWINGS

SCHEDULED BASE

-1 7/8"

RECESSED FLOOR RF FLOOR PANEL 1

FINISH FLOOR, REFER

TO FINISH SCHEDULE

EXISTING FIRST FLOOR

0"

9.7

WALL FOOTING, REFER TO

STRUCTURAL DRAWINGS

RECESSED RF FLOORING,

REFER TO RF FLOORING DETAIL

RF SHIELDED WALL;

REFER TO RF WALL DETAIL

1" FILLER

2" ISOLATION SPACE

SCHEDULED BASE

CONCRETE SIDEWALK;

REFER TO CIVIL DRAWINGS

-1 7/8"

RECESSED FLOORRF FLOOR PANEL

FINISH FLOOR, REFER

TO FINISH SCHEDULER

F W

A L L P

A N

E L

/8

THIN CALCIUM

SILICATE UNIT (TYP.)

ALUMINUM

INTERMEDIATE

CHANNEL (TYP.)

SHIM AS REQUIRED

SEALANT AND BACKER

ROD (TYP.)

RIGID INSULATION

2" COLD-FORMED "Z"

FLEXIBLE FLASHING

ALUMINUM STARTER

CHANNEL

STAINLESS STEEL

FLASHING

WATER-RESISTIVE

BARRIER

3/4" PLYWOOD

6" COLD-FORMED

METAL FRAMING

6"3/4"2"

1 1/4"

1 3/8"

1'-6"

PERIMETER FOUNDATION

DRAIN

(2'X2') 2" PERIMETER

INSULATION

FLUID APPLIED

WATERPROOFING

POROUS FILL

CONCRETE SLAB ON

GRADE

BRONZE SPRAYED

STRUCT. AND ELECT.

SEAM CLAMP

1/4 - 20 FLAT HEAD SELF

THREADING SCREW

POLYETHYLENE

UNDERLAYMENT (2

LAYERS MIN. 4MIL EACH)

3/4" RF FLOOR PANEL

WITH 3OZ COPPER ON

TOP SIDE

1/8" SUB -FLOOR

1/8" VINYL FILLER TILE

1/8" HARDBOARD

LEVELING LAYER

COORDINATE OVERALL FLOOR DEPTH WITH RF

PANEL MANUFACTURER AND MRI MANUFACTURER

FINISH FLOOR, REFER

TO FINISH SCHEDULE

MRI EQUIPMENT

BASEPLATE AND

HARDBOARD LEVELING

LAYER, COORDINATE

WITH MRI EQUIPMENT

MANUFACTURER

8.8

R F

W A

L L P

A N

E L

SOLID SURFACE SILL,

COORDINATE WITH RF VENDOR

RF WINDOW

CONTROL ROOM COUNTER WITH

BACKSPASH, REFER TO INTERIOR

ELEVATIONS

2" ISOLATION SPACE

PARENT WALL, REFER TO

FLOOR PLAN FOR WALL TYPE

RF WALL, REFER TO RF WALL

WALL DETAIL

MRI ROOM COUNTER WITH

BACKSPASH; REFER TO

INTERIOR ELEVATIONS

SOLID SURFACE SILL,

COORDINATE WITH RF VENDOR

5/8" 3 5/8"

2"1 3/4"

3 1/2" 5/8"

SHIM AS REQ'D. BY RF

MANUFACTURER

8.8

R F

W A

L L P

A N

E L

MRI ROOM LAY-IN CEILING, REFER

TO REFLECTED CEILING PLAN AND

FINISH SCHEDULE

RF WINDOW

CONTROL ROOM LAY-IN

CEILING, REFER TO

REFLECTED CEILING PLAN AND

FINISH SCHEDULE

CLIPS & FASTENERS PER SHIELDING

MANUFACTURER'S RECOMMENDATION.

TYPICAL. DO NOT PENETRATE

THROUGH SHIELDING.

RF CEILING PANEL BY RF

SHIELDING MANUFACTURER

RADIATION SHIELDING (GAUSS LINE

SHIELDING). REFER TO SIEMENS

SHIELDING REPORT FOR ADDITIONAL

INFORMATION

SCHEDULED CEILING. REFER TO

FINISH SCHEDULE

SUPPORT SYSTEM TO STRUCTURE

ABOVE PER MANUFACTURER'S

RECOMMENDATION

C O

O R

D

IN

A T

E W

IT

H

M R

I M

A N

U F

RF SHIELD WALL PANEL

5/8" GYP. BD. ON 2X4 WOOD STUD

2" ISOLATION

6"X8" BOX HEADER, REFER TO

STRUCTURAL DRAWINGS

6" COLD-FORMED

METAL FRAMING

3/4" PLYWOOD

RIGID INSULATION

THIN CALCIUM

SILICATE UNIT (TYP.)

ALUMINUM

INTERMEDIATE

CHANNEL (TYP.)

WATER-RESISTIVE

BARRIER

RF KNOCK-OUT PANEL CONNECTION

BY RF MANUFACTURERSEALANT AND BACKER

ROD (TYP.)

AT KNOCK-OUT PANEL (TYP.):

9'-0"L REMOVABLE CHANNEL,

COORDINATE LENGTH WITH STONE

VENEER MANUFACTURER AND MRI

EQUIPMENT MANUFACTURER

T.O. KNOCK OUT PANEL

8'-6"

T.O. REMOVABLE PANELS

9'-0"

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :5

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

DETAILS

AE-511

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1 1/2" = 1'-0"AE-511

1 WINDOW - DETAIL @ SILL

SCALE: 1 1/2" = 1'-0"AE-511

2 WINDOW - DETAIL @ HEAD

SCALE: 1 1/2" = 1'-0"AE-511

3 ENLARGED RF FLOOR/WALL SHIELD SECTION

SCALE: 1 1/2" = 1'-0"AE-511

6 ENLARGED RF FLOOR SHIELD SECTION

SCALE: 6" = 1'-0"AE-511

8 RF FLOORING

SCALE: 1 1/2" = 1'-0"AE-511

4 ENLARGED RF WINDOW SILL SECTION

SCALE: 1 1/2" = 1'-0"AE-511

5 ENLARGED RF WINDOW HEAD SECTION

SCALE: 1 1/2" = 1'-0"AE-511

7 ENLARGED RF CEILING DETAIL

Revisions Date

95% CD SUBMISSION 10/07/2019

BID & CONSTRUCTION 12/19/2019

CAM REVIEW 02/21/2020

ADDENDUM #1 06/08/2020

Sheets
AE-401 - EXTERIOR ELEVATIONS
AE-410 - EXTERIOR ELEVATIONS - DEDUCT ALTERNATE #2
AE-411 - EXTERIOR ELEVATIONS - DEDUCT ALTERNATE #3
AE-511 - DETAILS
AE-800 - INTERIOR ELEVATIONS
AE-1001 - DOOR & WINDOW SCHEDULES AND DETAILS