ATTACHMENT - RFI 58 and 87 - 65 Percent Design Development CIH Report.pdf

PDF 7 MB Posted

Attached to
Y1DZ--PROJECT 675-23-100, Bid-Build (BB) Renovate Lake Nona Building 2 for Emergency Department and Observation Unit
Solicitation number
36C24825R0025
Issued by

About this file

This document is a Limited Asbestos, Lead-Containing Paint, PCB-Containing Caulk, and Mold Assessment Survey Report for the Lake Nona VA Medical Center Emergency Department and Observation Unit in Orlando, Florida. Conducted by GLE Associates, Inc. on May 15, 2024, the comprehensive survey assessed multiple building materials for potential hazardous substances. The assessment included sampling and analysis of slab interstitial materials, drywall, vinyl flooring, ceiling tiles, grout, and mastic across the facility. Laboratory testing revealed no detectable asbestos, lead-containing paint, PCB-containing caulk, or visible mold in the sampled materials.

The survey was performed in preparation for a renovation project (Solicitation Number 36C24825R0025) to renovate the Lake Nona Emergency Department and Observation Unit, with a project magnitude between $5,000,000 and $10,000,000. The site visit for potential contractors is scheduled for February 12, 2025, at 3:00 PM EST. The project is set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) and requires compliance with Davis-Bacon wage determinations. Proposals are due to the VA Contracting Officer Elizabeth Romero via email, with a focus on technical approach, past performance, and pricing evaluation.

View the file

Other files

File Type Posted
ATTACHMENT - MEP.pdf PDF
ATTACHMENT - RFI 39.pdf PDF
ATTACHMENT - VOLUME 11C_Lighting Plans Updated 07.08.13-3.pdf PDF
ATTACHMENT - RFI 38.pdf PDF
ATTACHMENT - VOLUME 2C_Arch Construction Plans Updated 05.30.13-2.pdf PDF
ATTACHMENT - VOLUME 7A_Ductwork Updated 07.23.13.pdf PDF
ATTACHMENT - HVAC.pdf PDF
ATTACHMENT - RFI 61.pdf PDF
ATTACHMENT - Site Visit Sign-in Sheet.pdf PDF
ATTACHMENT - Sirca Examination Light.pdf PDF
ATTACHMENT - RFI 108_PL702 Plumbing Details and Schedule.pdf PDF
ATTACHMENT - G2022-10000717-001-001_Diamond_Pledge_NDL_Roof_Guarantee.pdf PDF
ATTACHMENT - VOLUME 11C_Lighting Plans Updated 07.08.13-2.pdf PDF
ATTACHMENT - VOLUME 9A_Plumbing Updated 07.11.13-3.pdf PDF
ATTACHMENT - VOLUME 12A_Power Updated 07.25.13-2.pdf PDF
ATTACHMENT - RFI 11 and 21_Sirca Exam Light Brochure.pdf PDF
ATTACHMENT - RFI 73.pdf PDF
ATTACHMENT - VOLUME 9A_Plumbing Updated 07.11.13.pdf PDF
ATTACHMENT - VOLUME 9A_Plumbing Updated 07.11.13-2.pdf PDF
S06 Amendment 36C24825R0025 0001.pdf PDF
ATTACHMENT - Emergency Department Lake Nona Addendum 1.pdf PDF
ATTACHMENT - VOLUME 7A_Ductwork Updated 07.23.13-2.pdf PDF
Solicitation 36C24825R0025.pdf PDF
ATTACHMENT 6 - Experience Information Sheet.pdf PDF
ATTACHMENT 8 - Past Performance Questionnaire.docx DOCX document
ATTACHMENT 7 - Limitation of Subcontracting Certificate.docx DOCX document
ATTACHMENT 4 - Contract Progress Schedule.docx DOCX document
ATTACHMENT 1 - Construction Specifications.pdf PDF
ATTACHMENT 2 - Construction Drawings.pdf PDF
ATTACHMENT 9 - Base Offer Price Breakdown.xlsx XLSX spreadsheet
ATTACHMENT 3 - DBA Wage Determination 01.24.2025.pdf PDF
ATTACHMENT 5 - EMR.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Emergency Department Lake Nona Orlando VA Medical Center

Orlando, Florida

Contract 36C24819D0021, D.O. 36C24823N0249 Project 673-23-100

Asbestos, Lead-Containing Paint, PCB- Containing Caulk, and Mold Assessment

Survey Report

Prepared for

Department of Veterans Affairs Orlando VA Medical Center

13800 Veterans Way

Orlando, FL 32827

Prepared by

3603 NW 98th Street, Suite B

Gainesville, Florida 32606

June 4, 2024

Design, Inc.

1155 S. Semoran Boulevard, Suite 3-1111 Winter Park, FL 32792

888-453-4531 • Fax 407-658-4410

LIMITED ASBESTOS, LEAD-CONTAINING PAINT,

PCB-CONTAINING CAULK, AND MOLD ASSESSMENT

SURVEY REPORT

Lake Nona VA Medical Center Emergency Department (ED) and Observation Unit

Orlando, Florida 32827

GLE Project No.: 24000-29397

Prepared for:

Mr. Mike Tootle AKEA Design, Inc.

3603 Northwest 98th Street, Suite B

May 2024

Prepared by:

Limited Asbestos, Lead-Containing Paint, PCB-Containing Caulk, and Mold Assessment Survey Report

Conducted at:

Lake Nona VA Medical Center Emergency Department (ED) and Observation Unit

Orlando, Florida 32827

GLE Project No.: 24000-29397

Prepared for:

Mr. Mike Tootle AKEA Design, Inc.

3603 Northwest 98th Street, Suite B

Zac Klarich Junior Project Manager Signature

Paul S. Zak, CIH Environmental Services Manager Signature Florida Licensed Mold Assessor MRSA344

Robert B. Greene, PE, PG, CIH, LEED AP President Signature Florida LAC# EA 0000009

Prepared by:

GLE Associates, Inc.

1155 S. Semoran Boulevard, Suite 3-1111 Winter Park, FL 32792 Phone (888-453-4531) Facsimile (407-658-4151)

TABLE OF CONTENTS

1.0 EXECUTIVE SUMMARY

2.0 METHODOLOGY

2.1 Asbestos Survey

2.2 Lead-Containing Paint Screening

2.3 Polychlorinated Biphenyls (PCB) Survey

2.4 Visual Mold Assessment

3.0 SAMPLING

3.1 Asbestos Survey

Table 3.1 Summary of Asbestos Sampling Analytical Results

3.2 Lead-Containing Paint Screening

3.3 Polychlorinated Biphenyls (PCB) Survey

3.4 Visual Mold Assessment

4.0 CONCLUSIONS AND RECOMMENDATIONS

5.0 LIMITATIONS

APPENDICES

APPENDIX A - Personnel and Laboratory Certifications APPENDIX B - Photographs APPENDIX C - Asbestos Sample Laboratory Analytical Reports and Chain of Custody APPENDIX D - Lead Sample Laboratory Analytical Report and Chain of Custody APPENDIX E - PCB Sample Laboratory Analytical Report and Chain of Custody

1.0 EXECUTIVE SUMMARY

At the request of AKEA Design, Inc., GLE Associates, Inc. (GLE) conducted an assessment of the ED and Observation Unit at the Lake Nona VA Medical Center, located at 13800 Veterans Way, in Orlando, Florida on May 15, 2024. Specifically, the scope of services included the following:

Limited Asbestos-Containing Material (ACM) Survey Limited Lead-Containing Paint Screening Limited Poly-Chlorinated Biphenyls (PCB) survey Limited Mold Assessment

Consequently, this report is limited to the specified scope of services. While additional comments may be provided, the additional comments are submitted as a courtesy and are not intended to expand the original scope of this investigation. The scope of this survey did not include demolition of any building components, evaluation of architectural plans, or the quantification of materials for abatement purposes, or removal cost estimating. This report outlines the background information, our procedures and methodology, sample results, findings, conclusions, and recommendations.

The assessment was conducted by Mr. Brandon Christensen and Mr. Andy Fuentes of GLE. The asbestos survey was conducted pursuant to National Emission Standards for Hazardous Air Pollutants (NESHAP, 40 CFR 61) requirements. The lead-based paint survey was conducted using a modified version of the Department of Housing and Urban Development (HUD) survey methodology and in general accordance with Environmental Protection Agency (EPA) guidelines.

No asbestos was detected in the sampled materials:

Slab Interstitial Drywall with Joint Compound Wood Pattern Vinyl Floor Brown Vinyl Cove Base

2’x2’ White Ceiling Tile White Thinset White Grout Tan Mastic

No lead was detected above the laboratory’s reporting limit for the following sampled paint:

Tan paint on Drywall Brown paint on Drywall

Blue Paint on Columns

No PCBs were detected above the laboratory’s reporting limit for the following sampled caulk:

Beige caulking associated with the reception area wall.

No visible mold-impacted materials were observed.

2.0 METHODOLOGY

2.1 ASBESTOS SURVEY

The survey was performed by visually observing accessible areas within the scope of work. An EPA/AHERA accredited inspector performed the visual observations (refer to Appendix A for personnel qualifications).

After the overall visual survey was completed, representative sampling areas were determined.

The surveyor delineated homogeneous areas of suspect materials and samples of each material were obtained, in general accordance with regulations as established by the Occupational Safety and Health Administration (OSHA) and NESHAP. The field surveyor determined sample locations based on previous experience.

Both friable and non-friable materials were sampled. A friable material is one that can be crushed when dry by normal hand pressure. This survey did not include the demolition of building components to access suspect material.

After completion of the fieldwork, the samples were delivered to GLE’s National Voluntary Laboratory Accreditation Program (NVLAP) accredited laboratory, for analysis. The samples were analyzed by Polarized Light Microscopy (PLM) coupled with dispersion staining, in general accordance with EPA-600/R-93/116. Utilizing this procedure, the various asbestos minerals (chrysotile, amosite, crocidolite, actinolite, tremolite, and anthophyllite) can be determined. The percentages of asbestos minerals in the samples were visually determined by the microscopist.

Please note that the EPA designates all materials containing greater than one percent asbestos as an “asbestos-containing material” (ACM).

Regulated Asbestos-Containing Material (RACM) is defined as (a) Friable asbestos materials, (b) Category I non-friable ACM that has become friable, (c) Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or (d) Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations regulated by this subpart.

Category I and Category II non-friable ACM, as defined by the EPA:

Category I non-friable ACM means asbestos-containing packings, gaskets, resilient floor covering, asphalt roofing products, and pliable sealants and mastics that are in good condition and not friable, containing more than one percent asbestos, as determined using the method specified in Appendix E, Subpart E, 40 CFR Part 763, Section 1, PLM.

Category II non-friable ACM means any material, excluding Category I non-friable ACM, containing more than one percent asbestos as determined using the methods specified in Appendix E, Subpart E, 40 CFR Part 763 Section 1, PLM that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

2.2 LEAD-CONTAINING PAINT SCREENING

It is GLE’s understanding that the survey was conducted to provide information needed to comply with 29 CFR Part 1926 “Lead Exposure in Construction; Interim Final Rule” for future demolition and/or renovation activities. The Scope of the “Lead Exposure in Construction; Interim Final Rule” “…applies to all occupational exposure to lead in all construction work in which lead, in any amount, is present in an occupationally related context.” Due to the lack of a firm correlation between lead levels in paint and airborne lead levels during construction activities, OSHA has developed task-related triggers that require the implementation of the provisions required in 29 CFR Part 1926. Demolition and/or renovation activities involve tasks covered under this standard.

The limited survey was performed by observing and testing accessible painted component surfaces of the building. The sampling protocol used in this lead paint survey is a modified version of the survey methodology established by HUD. The protocol was modified to conform to the specific parameters of this project.

After the overall visual survey was completed, an inventory of painted surfaces was developed. The surveyor then subdivided the areas into homogeneous areas of apparent similar paint history.

Sampling of the paint surfaces was performed by collecting representative paint chips. All samples were submitted to EMSL Analytical, Inc., an accredited laboratory recognized under EPA’s National Lead Laboratory Accreditation Program (NLLAP). These samples were analyzed by EPA Method SW 846 3050B/7000B and the results are reported in percentage of lead by weight of the paint sample (% Wt).

2.3 PCB-CONTAINING CAULK SURVEY

GLE assessed immediately accessible areas of the subject location for visual evidence of suspect PCB-containing materials, such as caulking and/or sealants. The collected samples were submitted to EMSL, an accredited laboratory recognized under the National Environmental Laboratory Accreditation Program (NELAP). The samples were analyzed via EPA Method SW846 8082A for nine common Aroclors.

2.4 VISUAL MOLD ASSESSMENT

GLE assessed immediately accessible areas of the subject location for visual evidence of mold-impacted materials. Non-destructive visual observations were utilized for this task. Moisture content measurements were obtained through the use of a portable/hand-held moisture meter to perform in-situ testing as necessary to determine the extent of potentially water-damaged building materials. The meter gives a digital readout level in terms of a percentage of moisture (wood-equivalent) in the building material surveyed. In general, levels less than 20% represent an acceptable level of moisture. Levels in excess of 20% provide an environment conducive for the proliferation of microorganisms.

3.0 SAMPLING

Personnel and laboratory certifications are presented in Appendix A. Representative photographs are presented in Appendix B.

3.1 ASBESTOS SURVEY

A total of 24 samples of suspect building materials were collected from the facility during the survey, representing eight different identified homogeneous areas. The asbestos laboratory analytical report and chain of custody are presented in Appendix C.

A summary of the asbestos sampling analytical results and homogenous areas of suspect ACM determined to be present is outlined in the following table.

ASBESTOS CONTENT

Expressed as percent

* = The facility owner has the option of point-counting by Polarized Light Microscopy (PLM) those RACM whose asbestos content is less than 10% in order to more accurately determine the asbestos content therein.

FRIABILITY F = Friable Material NF = Non-Friable Material

ACM CATEGORY

RACM = Regulated ACM CAT I = Category I non-friable ACM CAT II = Category II non-friable ACM

ABBREVIATIONS:

PC = Results based on Point-Count analysis TEM NOB = Transmission Electron Microscopy of Non-Friable Organically Bound Material NA = Not Applicable ND = None Detected NIS = Not in Scope C = Chrysotile A = Amosite HA = Homogeneous Area SF = Square Feet LF = Linear Feet CF = Cubic Feet

TABLE 3.1: SUMMARY OF ASBESTOS SAMPLING ANALYTICAL RESULTS

DATE HA # HOMOGENEOUS MATERIAL

DESCRIPTION

HOMOGENEOUS MATERIAL

LOCATION

FRIABILITY

(F /NF) % ASBESTOS* # OF SAMPLES

COLLECTED

APPROXIMATE

QUANTITY ACM CATEGORY

05/15/24 M-01 Slab Interstitial Interstitial NF ND 3 NIS NA 05/15/24 DW-01 Drywall with Joint

Compound Walls Throughout NF ND 3 NIS NA

05/15/24 MSV-01 Wood Pattern Vinyl Floor Employee Office space Flooring NF ND 3 NIS NA

05/15/24 VB-01 Brown Vinyl Cove Base Employee Office Space Walls NF ND 3 NIS NA

05/15/24 CT-01 2’x2’ White Ceiling Tile Ceilings Throughout F ND 3 NIS NA 05/15/24 M-02 White Thinset Ceramic Flooring

Throughout NF ND 3 NIS NA

05/15/24 M-03 White Grout Bathroom Walls NF ND 3 NIS NA 05/15/24 MAS-01 Tan Mastic Reception Area Walls NF ND 3 NIS NA

3.2 LEAD-CONTAINING PAINT SCREENING

A total of three paint samples were collected and submitted for analysis:

Tan Paint on Drywall Brown Paint on Drywall Blue Paint on Columns

Analytical results indicate that the paint samples did not contain lead concentrations (% by weight) above the laboratory detection limit. The lead laboratory analytical report and chain of custody are presented in Appendix D.

3.3 PCB-CONTAINING CAULK SURVEY

One suspect beige caulk was observed and sampled associated with the receptionist area walls.

Analytical results indicate that the caulk sample did not contain PCB concentrations above the laboratory detection limit. The PCB laboratory analytical report and chain of custody are presented in Appendix E.

3.4 VISUAL MOLD ASSESSMENT

No visible mold-impacted materials were observed associated with Emergency Department (ED) and Observation Unit, and therefore, no microbial surface samples were collected. No visibly water-damaged materials, or materials exhibiting elevated moisture content, were observed.

4.0 CONCLUSIONS AND RECOMMENDATIONS

No asbestos-containing materials, lead-containing paints, PCB-containing caulks, or mold-impacted building materials were identified in the scope of this survey.

5.0 LIMITATIONS

GLE performed the scope of services as presented in our proposal. Reasonable effort has been made by GLE personnel to assess representative locations within the facility. Destructive sampling was not utilized as part of this assessment. GLE assumes no liability for existing conditions or damage within the subject facility or for any consequential effects that may result from our services and collection of field samples and measurements.

The information contained in this report was prepared based upon specific parameters requested by the Client. If additional information is available or becomes available, it should be forwarded for our review to determine if changes to our conclusions and recommendations are necessary. The data and evaluation in the report reflects conditions identified at the time of our site visit, and should not be construed as being representative of the site at a later date. GLE assumes no liability for any perceived or documented health effects of tenants, visitors, contractors, or any other individual that has or may come in contact with the building that may be attributable to the conditions present within the building.

The information contained in this report was prepared based upon specific parameters and regulations in force at the time of this report, and is only for the specific use of the Client and GLE.

GLE accepts no responsibility for the use, interpretation, or reliance by other parties on the information contained herein, unless written authorization has been obtained from GLE. This report is not intended to be used as a document to render health related opinions.

Because of the hidden nature of many building components (i.e. within mechanical chases), it may be impossible to determine if all of the suspect building materials have been located and subsequently tested. Destructive testing in some instances is not a viable option. We cannot, therefore, guarantee that all potential ACM, mold, PCBs or lead-containing paint has been located.

For the same reasons, estimates of quantities and/or conditions are subject to readily apparent situations, and our findings reflect this condition. We do warrant, however, that the investigations and methodology reflect our best efforts based upon the prevailing standard of care in the environmental industry.

Any materials found during construction activities, either not addressed in this survey report, or similar to the materials identified in this survey report, should be assumed to be hazardous until sampling and analysis documents otherwise.

APPENDIX A

Personnel and Laboratory Certifications

Melanie S. Griffin, SecretaryRon DeSantis, Governor

STATE OF FLORIDA

DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION

ASBESTOS LICENSING UNIT

THE ASBESTOS BUSINESS ORGANIZATION HEREIN IS LICENSED UNDER THE

PROVISIONS OF CHAPTER 469, FLORIDA STATUTES

GLE ASSOCIATES INC

Do not alter this document in any form.

ROBERT BLAIR GREENE

LICENSE NUMBER: ZA0000034

EXPIRATION DATE: NOVEMBER 30, 2025

This is your license. It is unlawful for anyone other than the licensee to use this document.

5405 CYPRESS CENTER DRIVE

SUITE 110

TAMPA FL 33609

Always verify licenses online at MyFloridaLicense.com

ISSUED: 11/02/2023

https://www.myfloridalicense.com/LicenseDetail.asp?SID=&id=2c9db36082555fee1afe88b159c9ca06 https://www.myfloridalicense.com/LicenseDetail.asp?SID=&id=2c9db36082555fee1afe88b159c9ca06

DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION

ASBESTOS LICENSING UNIT

THE ASBESTOS CONSULTANT - ENGINEER HEREIN IS LICENSED UNDER THE

PROVISIONS OF CHAPTER 469, FLORIDA STATUTES

GREENE, ROBERT BLAIR

Do not alter this document in any form.

GLE ASSOCIATES INC

LICENSE NUMBER: EA0000009

EXPIRATION DATE: NOVEMBER 30, 2024

This is your license. It is unlawful for anyone other than the licensee to use this document.

5405 CYPRESS CENTER DR

SUITE 110

TAMPA FL 33609

Always verify licenses online at MyFloridaLicense.com https://www.myfloridalicense.com/LicenseDetail.asp?SID=&id=10324f95ba50b55978623c96241000ac

RRRRcertifies

Zachary Klarich 5405 Cypress Center Drive Suite 110 Tampa FL 33609

Having passed a 25-question exam with a score of 70% or higher has successfully met training requirements for

Asbestos Refresher: Inspector FDBPR Asbestos Licensing Unit: Provider #0000995; Course #FL49-0004731 (½ Day; 3.40 Contact Hours)

(Reaccreditation for Inspector under TSCA Title II/AHERA) Conducted

4/16/2024

Certificate #: 0078 - 005-1713 Exam Date: 4/16/2024 EPA accreditation expires: 4/16/2025 Principal Instructor: Brian Duchene, PE, LAC CEUs: .4 FBPR LAC: #0000995; Course #0004731 FBPE CEHs: #0004021; Course #0009083/Educational Institutions: 4 CEHs AL Safe State: Teacher name on roster Last 4 of SSN: 6593

United States Department of Commerce National Institute of Standards and Technology

Certificate of Accreditation to ISO/IEC 17025:2017

NVLAP LAB CODE: 102003-0

GLE Associates, Inc.

Tampa, FL is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:

Asbestos Fiber Analysis

2024-04-01 through 2025-03-31

Effective Dates For the National Voluntary Laboratory Accreditation Program

This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017.

This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique dated January 2009).

has fulfilled the requirements of the Toxic Substances Control Act (TSCA) Section 402, and has received certification to conduct lead-based paint activities pursuant to 40 CFR Part 745.226

All EPA Administered Lead-based Paint Activities Program States, Tribes and Territories

This certification is valid from the date of issuance and expires March 03, 2027

Certification #

LBP-2060-3

Issued On

January 12, 2024

Michelle Price, Chief

Lead, Heavy Metals, and Inorganics Branch

AIHA Laboratory Accreditation Programs, LLC acknowledges that

EMSL Analytical, Inc.

3303 Parkway Center Ct Orlando, FL 32808-1040

Laboratory ID: LAP-163563 along with all premises from which key activities are performed, as listed above, has fulfilled the requirements of the AIHA Laboratory Accreditation Programs, LLC (AIHA LAP) accreditation to the ISO/IEC 17025:2017 international standard, General Requirements for the Competence of Testing and Calibration Laboratories in the following:

LABORATORY ACCREDITATION PROGRAMS

INDUSTRIAL HYGIENE Accreditation Expires: March 01, 2026

ENVIRONMENTAL LEAD Accreditation Expires: March 01, 2026

ENVIRONMENTAL MICROBIOLOGY Accreditation Expires: March 01, 2026

FOOD Accreditation Expires:

UNIQUE SCOPES Accreditation Expires:

BE FIELD/MOBILE Accreditation Expires:

Specific Field(s) of Testing/Method(s) within each Accreditation Program for which the above named laboratory maintains accreditation is outlined on the attached Scope of Accreditation. Continued accreditation is contingent upon successful on-going compliance with ISO/IEC 17025:2017 and AIHA LAP requirements. This certificate is not valid without the attached Scope of Accreditation. Please review the AIHA LAP website (www.aihaaccreditedlabs.org) for the most current Scope.

Revision21: 10/24/2023

Cheryl O Morton Managing Director, AIHA Laboratory Accreditation Programs, LLC

Date Issued: 03/01/2024

Effective: 10/24/2023 Revision: 9

SCOPE OF ACCREDITATION

EMSL Analytical, Inc. Laboratory ID: LAP-163563

Issue Date: 03/01/2024 3303 Parkway Center Ct Orlando, FL 32808-1040 Expire Date: 03/01/2026

The laboratory is approved for those specific field(s) of testing/methods listed in the table below. Clients are urged to verify the laboratory's current accreditation status for the particular field(s) of testing/Methods, since these can change due to proficiency status, suspension and/or withdrawal of accreditation.

The EPA recognizes the AIHA LAP, LLC ELLAP program as meeting the requirements of the National Lead Laboratory Accreditation Program (NLLAP) established under Title X of the Residential Lead-Based Paint Hazard Reduction Act of 1992 and includes paint, soil and dust wipe analysis. Air and composited wipes analyses are not included as part of the NLLAP.

Environmental Lead Laboratory Accreditation Program (ELLAP)

Initial Accreditation Date: 09/01/2007

Component, parameter, characteristic, material, or product tested Technology sub-type/Detector Method Method Description

(for internal methods only)

Airborne Dust AA NIOSH 7082 N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/APaint AA

EPA SW-846 7000B N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/ASettled Dust by Wipe AA

EPA SW-846 7000B N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/ASoil AA

EPA SW-846 7000B N/A

A complete listing of currently accredited ELLAP laboratories is available on the AIHA LAP, LLC website at:

http://www.aihaaccreditedlabs.org

DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION

MOLD-RELATED SERVICES LICENSING PROGRAM

THE MOLD ASSESSOR HEREIN IS CERTIFIED UNDER THE

PROVISIONS OF CHAPTER 468, FLORIDA STATUTES

ZAK, PAUL STANLEY

Do not alter this document in any form.

5405 CYPRESS CENTER DR

LICENSE NUMBER: MRSA344

EXPIRATION DATE: JULY 31, 2024

This is your license. It is unlawful for anyone other than the licensee to use this document.

SUITE 110

TAMPA FL 33609

Always verify licenses online at MyFloridaLicense.com https://www.myfloridalicense.com/LicenseDetail.asp?SID=&id=5d38157a3ee61ddf165b264dbdbc1925

Paul Zak

CIH-CP 9439

April 28, 2008

December 01, 2028

Powered by TCPDF (www.tcpdf.org) http://www.tcpdf.org acknowledges that

EMSL Analytical, Inc.

6340 Castleplace Drive Indianapolis, IN 46250

Laboratory ID: LAP-157245 along with all premises from which key activities are performed, as listed above, has fulfilled the requirements of the AIHA Laboratory Accreditation Programs (AIHA LAP), LLC accreditation to the ISO/IEC 17025:2017 international standard, General Requirements for the Competence of Testing and Calibration Laboratories in the following:

LABORATORY ACCREDITATION PROGRAMS

INDUSTRIAL HYGIENE Accreditation Expires: June 01, 2025

ENVIRONMENTAL LEAD Accreditation Expires: June 01, 2025

ENVIRONMENTAL MICROBIOLOGY Accreditation Expires: June 01, 2025

FOOD Accreditation Expires:

UNIQUE SCOPES Accreditation Expires:

Specific Field(s) of Testing (FoT)/Method(s) within each Accreditation Program for which the above named laboratory maintains accreditation is outlined on the attached Scope of Accreditation. Continued accreditation is contingent upon successful on-going compliance with ISO/IEC 17025:2017 and AIHA LAP, LLC requirements. This certificate is not valid without the attached Scope of Accreditation. Please review the AIHA LAP, LLC website (www.aihaaccreditedlabs.org) for the most current Scope.

Revision21: 05/15/2023

Cheryl O Morton Managing Director, AIHA Laboratory Accreditation Programs, LLC

Date Issued: 06/01/2023

Effective: 05/15/2023

SCOPE OF ACCREDITATION

EMSL Analytical, Inc. Laboratory ID: LAP-157245 6340 Castleplace Drive Indianapolis, IN 46250 Issue Date: 06/01/2023

The laboratory is approved for those specific field(s) of testing/methods listed in the table below. Clients are urged to verify the laboratory's current accreditation status for the particular field(s) of testing/Methods, since these can change due to proficiency status, suspension and/or withdrawal of accreditation.

The EPA recognizes the AIHA LAP, LLC ELLAP program as meeting the requirements of the National Lead Laboratory Accreditation Program (NLLAP) established under Title X of the Residential Lead-Based Paint Hazard Reduction Act of 1992 and includes paint, soil and dust wipe analysis. Air and composited wipes analyses are not included as part of the NLLAP.

Environmental Lead Laboratory Accreditation Program (ELLAP)

Initial Accreditation Date: 09/01/2002

Component, parameter or characteristic tested Technology sub-type/Detector Method Method Description

(for internal methods only)

Airborne Dust AA NIOSH 7082 N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/AAA

EPA SW-846 7000B N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/A

Paint

ICP

EPA SW-846 6010D N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/AAA

EPA SW-846 7000B N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/A

Settled Dust by Wipe

ICP

EPA SW-846 6010D N/A

EPA SW-846 3050B N/A

EPA SW-846 3051A N/ASoil AA

EPA SW-846 7000B N/A

Effective: 05/15/2023

Component, parameter or characteristic tested Technology sub-type/Detector Method Method Description

(for internal methods only)

EPA SW-846 3050B N/A

EPA SW-846 3051A N/AICP

EPA SW-846 6010D N/A

A complete listing of currently accredited ELLAP laboratories is available on the AIHA LAP, LLC website at:

http://www.aihaaccreditedlabs.org

APPENDIX B

Photographs

May 15, 2024

Job No.

24000-29397

Photograph Date:

Prepared By:

Upper Photo: Interstitial Overview

Lower Photo: M-01 Slab

Figure

Upper Photo: ED Overview

Lower Photo: DW-01 Drywall with Joint Compound

Upper Photo: CT-01 2’x2’ Ceiling Tile

Lower Photo: M-02 White Thinset

Upper Photo: M-03 White Grout

Lower Photo: MAS-01 Tan Mastic

Upper Photo: ED Overview

APPENDIX C

Asbestos Sample Laboratory Analytical Reports and

Chain of Custody

SUMMARY OF BULK SAMPLE ANALYSIS

AKEA Design; ORL VA-Emergency DEPT. Observ 24000-29397

Sample Sample Type Fiber Type

M-01A Slab Interstitial 100% Quartz, Calcite, Clay, Mica

M-01B Slab Interstitial 100% Quartz, Calcite, Clay, Mica

M-01C-QC Slab Interstitial 100% Quartz, Calcite, Clay, Mica

DW-01A Drywall & Joint

Compound 100% Gypsum, Quartz, Calcite, Clay

DW-01B Drywall & Joint

Compound 100% Gypsum, Quartz, Calcite, Clay

DW-01C Drywall & Joint

Compound 100% Gypsum, Quartz, Calcite, Clay

MSV-01A Wood Pattern Vinyl Floor 100% Polymer, Quartz, Calcite, Clay, Mica

MSV-01B Wood Pattern Vinyl Floor 100% Polymer, Quartz, Calcite, Clay, Mica

MSV-01C Wood Pattern Vinyl Floor 100% Polymer, Quartz, Calcite, Clay, Mica

VB-01A Brown Vinyl Cove Base 100% Polymer

VB-01B Brown Vinyl Cove Base 100% Polymer

VB-01C Brown Vinyl Cove Base 100% Polymer

CT-01A-QC 2' X 2' White Ceiling Tile 100% Mineral Wool

CT-01B 2' X 2' White Ceiling Tile 100% Mineral Wool

CT-01C 2' X 2' White Ceiling Tile 100% Mineral Wool

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020 as found in App. E to Sub.

E of 40 CFR Part 763, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 29345

Analyst / Approved

Signatory:

Feedback regarding laboratory performance should be addressed to lab@gleassociates.com.

Report Date: 5/20/2024

SUMMARY OF BULK SAMPLE ANALYSIS

AKEA Design; ORL VA-Emergency DEPT. Observ 24000-29397

Sample Sample Type Fiber Type

M-02A White Thinset 100% Quartz, Calcite, Clay, Mica

M-02B White Thinset 100% Quartz, Calcite, Clay, Mica

M-02C White Thinset 100% Quartz, Calcite, Clay, Mica

M-03A White Grout 100% Quartz, Calcite, Clay, Mica

M-03B White Grout 100% Quartz, Calcite, Clay, Mica

M-03C White Grout 100% Quartz, Calcite, Clay, Mica

MAS-01A Tan Mastic 100% Polymer

MAS-01B-QC Tan Mastic 100% Polymer

MAS-01C Tan Mastic 100% Polymer

Darryl Neldner

* Polarized Light Microscopy coupled with dispersion is the technique used for identification in accordance with EPA 600/M4-82-020 as found in App. E to Sub.

E of 40 CFR Part 763, EPA 600/R-93/116, and NIOSH Method 9002.

** The percentage of each component is visually estimated. The result of this analysis relate only to the material tested.

The report shall not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.

(>1% greater than one percent, <1% less than one percent) QC - Sample reanalyzed for QA/QC.

Analysis performed by GLE Associates, Inc. NVLAP Code 102003-0, CO AL-17485, TX 30-0337

*** This report shall not be reproduced except in full, without the written approval of the laboratory. GLE Report # 29345

Analyst / Approved

Signatory:

Feedback regarding laboratory performance should be addressed to lab@gleassociates.com.

Report Date: 5/20/2024

APPENDIX D

Lead Sample Laboratory Analytical Report and

Project Name:

Customer PO:

EMSL Sales Rep:

Reported:

GLE Associates [GLEA51D]

1155 South Semoran Boulevard, Suite 3-1111

Winter Park, FL 32792

EMSL Analytical, Inc.

3303 Parkway Center Court, Orlando, FL, 32808

Telephone: (407)-599-5887 Fax:(407)-599-9063

EMSL-OR-34

Daved McLouthAttention:

(407) 451-7300 dmclouth@gleassociates.com

24000-29397

Received: 05/15/2024 14:34

05/16/2024 15:18

Jason McDonald

EMSL Order ID: 342450041

LIMS Reference ID: JC50041

EMSL Customer ID: GLEA51D

Orlando VA Medical Center Building 2

Emegency Department And Observation

Analytical Results

Analyte Results RL Q DF Analysis Date

& AnalystWeight(g)

Prep Date

& Tech

Analytical

MethodPrep Method

Client Sample ID: PC - 01/Main Walls Date Sampled: 05/15/24

Matrix: Chips LIMS Reference ID: JC50041-01

1Lead 05/16/24 JS3 05/16/24 SM<0.008 % wt 0.008 % wt SW-846 3050B SW 846-7000B0.3073

Sample Comments:

Client Sample ID: PC - 02/Hallway Walls Date Sampled: 05/15/24

Matrix: Chips LIMS Reference ID: JC50041-02

1Lead 05/16/24 JS3 05/16/24 SM<0.009 % wt 0.009 % wt SW-846 3050B SW 846-7000B0.214

Sample Comments:

Client Sample ID: PC - 03/Colomns Date Sampled: 05/15/24

Matrix: Chips LIMS Reference ID: JC50041-03

1Lead 05/16/24 JS3 05/16/24 SM<0.008 % wt 0.008 % wt SW-846 3050B SW 846-7000B0.3087

Sample Comments:

[TOC_1]Sample Results[TOC]

Page 1 of 4Page 1 of 4

EMSL Sales Rep:

Reported:

GLE Associates [GLEA51D]

1155 South Semoran Boulevard, Suite 3-1111

Winter Park, FL 32792

EMSL Analytical, Inc.

3303 Parkway Center Court, Orlando, FL, 32808

Telephone: (407)-599-5887 Fax:(407)-599-9063

EMSL-OR-34

Daved McLouthAttention:

(407) 451-7300 dmclouth@gleassociates.com

24000-29397

Received: 05/15/2024 14:34

05/16/2024 15:18

Jason McDonald

EMSL Order ID: 342450041

LIMS Reference ID: JC50041

EMSL Customer ID: GLEA51D

Orlando VA Medical Center Building 2

Emegency Department And Observation

CertificationsAnalyte

Certified Analyses included in this Report

SW 846-7000B in Chips

34-AIHA ELLAP,34-LA,34-OHLead

[TOC_1]Certified

Analyses[TOC]

List of Certifications

Code Description Number Expires

34-LA 0519LA - Asbestos (PCM, PLM and TEM), Fungi and Bacteria, Lead and Metals 06/30/2024

34-AIHA ELLAP 163563American Industrial Hygiene Association (AIHA-LAP) - ELLAP 03/01/2026

34-AIHA EMLAP 163563American Industrial Hygiene Association (AIHA-LAP) - EMLAP 03/01/2026

34-AIHA IHLAP 163563American Industrial Hygiene Association (AIHA-LAP) - IHLAP 03/01/2026

34-A2LA Food 2845.49A2LA Food Microbiology Certificate 03/31/2026

34-OH E10057OH - Lead in Paint Chips, Wipes, Soil and Air 11/22/2024

Please see the specific Field of Testing (FOT) on www.emsl.com <http://www.emsl.com> for a complete listing of parameters for which EMSL is certified.

[TOC_1]Certifications[TOC]

Notes and Definitions

Item Definition

(Dig) For metals analysis, sample was digested.

[2C] Reported from the second channel in dual column analysis.

DF Dilution Factor

MDL Method Detection Limit.

ND Analyte was NOT DETECTED at or above the detection limit.

Q Qualifier

RL Reporting Limit

Wet Sample is not dry weight corrected.

Measurement of uncertainty and any applicable definitions of method modifications are available upon request. Per EPA NLLAP policy, sample results are not blank corrected.

[TOC_1]Qualifiers, Definitions and Disclaimer[TOC]

Page 2 of 4Page 2 of 4

EMSL Sales Rep:

Reported:

GLE Associates [GLEA51D]

1155 South Semoran Boulevard, Suite 3-1111

Winter Park, FL 32792

EMSL Analytical, Inc.

3303 Parkway Center Court, Orlando, FL, 32808

Telephone: (407)-599-5887 Fax:(407)-599-9063

EMSL-OR-34

Daved McLouthAttention:

(407) 451-7300 dmclouth@gleassociates.com

24000-29397

Received: 05/15/2024 14:34

05/16/2024 15:18

Jason McDonald

EMSL Order ID: 342450041

LIMS Reference ID: JC50041

EMSL Customer ID: GLEA51D

Orlando VA Medical Center Building 2

Emegency Department And Observation

EMSL maintains liability limited to coast of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. QC sample results are within quality control criteria and met method specifications unless otherwise noted.

Heather Ohye Laboratory Manager or other approved signatory

Analysis following EMSL SOP for the Determination of Environmental Lead by FLAA. The laboratory has a reporting limit of 0.008% by wt., based upon a minimum sample weight of

0.25g submitted to the lab, and is not responsible for any result or reporting limit provided in mg/cm2 since it is dependent upon an area value provided by non-lab personnel. A "<" (less than) result signifies that the analyte was not detected at or above the reporting limit. Measurement of uncertainty and definitions of modifications are available upon request. Results in this report are not blank corrected unless specified.

Page 3 of 4Page 3 of 4

APPENDIX E

PCB Sample Laboratory Analytical Report and

EMSL Sales Rep:

Reported:

GLE Associates [GLEA51D]

1155 South Semoran Boulevard, Suite

3-1111Winter Park, FL 32792

EMSL Order ID:

EMSL Customer ID:

EMSL Analytical, Inc.

6340 Castleplace Drive, Indianapolis, IN, 46250

Telephone: 317.803.2997 Fax:317.803.3047

IndianapolisLab@emsl.com / www.Emsl.com

CC52539

162452539

LIMS Reference ID:

GLEA51D

Daved McLouthAttention:

(407) 451-7300 dmclouth@gleassociates.com

24000-29397

Received: 05/17/2024 09:45

05/22/2024 08:23

ORLANDO VA MEDICAL CENTER BUILDING

2-EMERGENCY DEPARTMENT AND

OBSERVATION UNITJason McDonald

Analytical Results

Analyte Result

Analyzed

Date/TimeQ Units

Prep/Analyst

InitialsRL

Prepared

Date/Time

Analytical

Method

Prep

MethodDF

Sample: CC52539-01 Matrix: SolidPCB-01/BEIGE Lims Reference ID: Sampled: 05/15/24 00:00:00

Aroclor-1016 SW846-8082A05/20/24 18:12mg/kg<0.61 0.61 05/17/24 11:56 GB/GB SW846 35461

Aroclor-1221 SW846-8082A05/20/24 18:12mg/kg<0.61 0.61 05/17/24 11:56 GB/GB SW846 35461

Aroclor-1232 SW846-8082A05/20/24 18:12mg/kg<0.61 0.61 05/17/24 11:56 GB/GB SW846 35461

Aroclor-1242 SW846-8082A05/20/24 18:12mg/kg<0.61 0.61 05/17/24 11:56 GB/GB SW846 35461

Aroclor-1248 SW846-8082A05/20/24 18:12mg/kg<0.61 0.61 05/17/24 11:56 GB/GB SW846 35461

Aroclor-1254 SW846-8082A05/20/24 18:12mg/kg<0.61 0.61 05/17/24 11:56 GB/GB SW846 35461

Aroclor-1260 SW846-8082A05/20/24 18:12mg/kg<0.61 0.61 05/17/24 11:56 GB/GB SW846 35461

Aroclor-1262 SW846-8082A05/20/24 18:12mg/kg<0.61 0.61 05/17/24 11:56 GB/GB SW846 35461

Aroclor-1268 SW846-8082A05/20/24 18:12mg/kg<0.61 0.61 05/17/24 11:56 GB/GB SW846 35461

[TOC_1]Sample Results[TOC]

Sara A Dille Laboratory Manager or other approved signatory

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.”

EMSL Sales Rep:

Reported:

GLE Associates [GLEA51D]

1155 South Semoran Boulevard, Suite

3-1111Winter Park, FL 32792

EMSL Order ID:

EMSL Customer ID:

EMSL Analytical, Inc.

6340 Castleplace Drive, Indianapolis, IN, 46250

Telephone: 317.803.2997 Fax:317.803.3047

IndianapolisLab@emsl.com / www.Emsl.com

CC52539

162452539

LIMS Reference ID:

GLEA51D

Daved McLouthAttention:

(407) 451-7300 dmclouth@gleassociates.com

24000-29397

Received: 05/17/2024 09:45

05/22/2024 08:23

ORLANDO VA MEDICAL CENTER BUILDING

2-EMERGENCY DEPARTMENT AND

OBSERVATION UNITJason McDonald

CertificationsAnalyte

Certified Analyses included in this Report

CAS #

SW846-8082A in Solid

16-A2LA Chemistry,16-CA ELAP,16-FLDOH,16-NJDEP,16-NYDOHAroclor-1016 12674-11-2

16-A2LA Chemistry,16-CA ELAP,16-FLDOH,16-NJDEP,16-NYDOHAroclor-1221 11104-28-2

16-A2LA Chemistry,16-CA ELAP,16-FLDOH,16-NJDEP,16-NYDOHAroclor-1232 11141-16-5

16-A2LA Chemistry,16-CA ELAP,16-FLDOH,16-NJDEP,16-NYDOHAroclor-1242 53469-21-9

16-A2LA Chemistry,16-CA ELAP,16-FLDOH,16-NJDEP,16-NYDOHAroclor-1248 12672-29-6

16-A2LA Chemistry,16-CA ELAP,16-FLDOH,16-NJDEP,16-NYDOHAroclor-1254 11097-69-1

16-A2LA Chemistry,16-CA ELAP,16-FLDOH,16-NJDEP,16-NYDOHAroclor-1260 11096-82-5

16-A2LA Chemistry,16-CA ELAP,16-FLDOH,16-NJDEP,16-NYDOHAroclor-1262 37324-23-5

16-A2LA Chemistry,16-CA ELAP,16-FLDOH,16-NJDEP,16-NYDOHAroclor-1268 11100-14-4

[TOC_1]Certified

Analyses[TOC]

Sara A Dille Laboratory Manager or other approved signatory

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.”

EMSL Sales Rep:

Reported:

GLE Associates [GLEA51D]

1155 South Semoran Boulevard, Suite

3-1111Winter Park, FL 32792

EMSL Order ID:

EMSL Customer ID:

EMSL Analytical, Inc.

6340 Castleplace Drive, Indianapolis, IN, 46250

Telephone: 317.803.2997 Fax:317.803.3047

IndianapolisLab@emsl.com / www.Emsl.com

CC52539

162452539

LIMS Reference ID:

GLEA51D

Daved McLouthAttention:

(407) 451-7300 dmclouth@gleassociates.com

24000-29397

Received: 05/17/2024 09:45

05/22/2024 08:23

ORLANDO VA MEDICAL CENTER BUILDING

2-EMERGENCY DEPARTMENT AND

OBSERVATION UNITJason McDonald

List of Certifications

Code Description Number Expires

16-OHDOH E10040Ohio - Lead in Paint Chips, Wipes, Soil and Air 05/03/2025

16-NYDOH 12130New York Potable Water, Metals Solid and Hazardous Waste - Asbestos 04/01/2025

16-NJDEP IN002New Jersey Metals, Organics and Inorganics in DW PCBs 06/30/2024

16-MO 10180Missouri Drinking Water 03/31/2026

16-IN Metals/Asbestos C-49-09Indiana Lead and Metals and Asbestos in Drinking Water 12/31/2026

16-IN Colilert/HPC M-49-06Indiana Colilert and HPC 12/31/2026

16-FLDOH E871170Florida Asbestos and Metals in Drinking Water, PCBs 06/30/2024

16-CA ELAP 2575California Metals in DW, Chemistry and Bulk Asbestos in Hazardous Waste 06/30/2024

16-AIHA LAP 157245EMSL Analytical, Inc. Indianpolis, IN AIHA-LAP, LLC-ELLAP/IHLAP Accredited 06/01/2025

16-A2LA Food 2845.11A2LA Food Microbiology 07/31/2024

16-A2LA Chemistry 2845.25A2LA Environmental and Chemistry 07/31/2024

Please see the specific Field of Testing (FOT) on www.emsl.com <http://www.emsl.com> for a complete listing of parameters for which EMSL is certified.

Please see the specific Field of Testing (FOT) on www.emsl.com <http://www.emsl.com> for a complete listing of parameters for which EMSL is certified.

[TOC_1]Certifications[TOC]

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.”

EMSL Sales Rep:

Reported:

GLE Associates [GLEA51D]

1155 South Semoran Boulevard, Suite

3-1111Winter Park, FL 32792

EMSL Order ID:

EMSL Customer ID:

EMSL Analytical, Inc.

6340 Castleplace Drive, Indianapolis, IN, 46250

Telephone: 317.803.2997 Fax:317.803.3047

IndianapolisLab@emsl.com / www.Emsl.com

CC52539

162452539

LIMS Reference ID:

GLEA51D

Daved McLouthAttention:

(407) 451-7300 dmclouth@gleassociates.com

24000-29397

Received: 05/17/2024 09:45

05/22/2024 08:23

ORLANDO VA MEDICAL CENTER BUILDING

2-EMERGENCY DEPARTMENT AND

OBSERVATION UNITJason McDonald

Notes and Definitions

Item Definition

(Dig) For metals analysis, sample was digested.

[2C] Reported from the second channel in dual column analysis.

DF Dilution Factor

MDL Method Detection Limit.

ND Analyte was NOT DETECTED at or above the detection limit.

Q Qualifier

RL Reporting Limit

Wet Sample is not dry weight corrected.

Measurement of uncertainty and any applicable definitions of method modifications are available upon request. Per EPA NLLAP policy, sample results are not blank corrected.

[TOC_1]Qualifiers, Definitions and Disclaimer[TOC]

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.”

00 Cover
ACM-LBP-PCB-LMA - AKEA - Lake Nona ED - Report
GLE Project No.: 24000-29397
Mr. Mike Tootle
Prepared by:
GLE Project No.: 24000-29397
Mr. Mike Tootle
No asbestos-containing materials, lead-containing paints, PCB-containing caulks, or mold-impacted building materials were identified in the scope of this survey.
APPENDIX A
Personnel and Laboratory Certifications
APPENDIX B
Photographs APPENDIX C
Asbestos Sample Laboratory Analytical Reports and
Chain of Custody
APPENDIX D
Lead Sample Laboratory Analytical Report and
Chain of Custody
APPENDIX E
PCB Sample Laboratory Analytical Report and
Chain of Custody
PHOTOMaster.pdf
Upper Photo: Interstitial Overview
342450041_002 Lead.pdf
Sample Results
Certified Analyses