ATTACHMENT - Emergency Department Lake Nona Addendum 1.pdf
PDF 16 MB Posted
- Solicitation number
- 36C24825R0025
About this file
This document is an architectural and engineering addendum for renovating the Emergency Department and Observation Unit at the Orlando VA Medical Center, located at Lake Nona, Florida. The project involves a comprehensive renovation of Building 2, spanning approximately 8,648 square feet, and includes two primary areas: a Fast Track section of 4,079 square feet and an Observation Unit of 4,675 square feet. The renovation will include electrical, mechanical, and architectural upgrades, with detailed specifications for HVAC piping, noise and vibration control, electrical systems, and medical equipment placement.
The addendum (Addendum 1) includes multiple technical drawings and specifications, specifically detailing electrical systems, panel schedules, power plans, and system layouts for the Fast Track and Observation Unit areas. Key technical components include electrical infrastructure modifications, medical equipment placement, wall and floor finishes, medical gas systems, and compliance with VA healthcare design standards. The project is part of solicitation number 36C24825R0025, with a site visit scheduled for February 12, 2025, and is targeted for Service-Disabled Veteran-Owned Small Business (SDVOSB) contractors with specific requirements for safety records, experience modification rates, and technical capabilities.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Renovate Lake Nona Building 2 for ED Orlando VA Medical Center
Orlando, Florida
Contract 36C24819D0021, D.O. 36C24823N0249 Project 673-23-100
Addendum 1
Prepared for
Department of Veterans Affairs Orlando VA Medical Center
13800 Veterans Way
Orlando, FL 32827
Prepared by
3603 NW 98th Street, Suite B
Gainesville, Florida 32606
February 7, 2025
Design, Inc.
THIS PAGE INTENTIONALLY LEFT BLANK
Renovate Lake Nona Building 2 for ED Addendum 1 Orlando VA Medical Center Orlando, FL Contract 36C24819D0021, Project 673-23-100
AKEA Design, Inc. Contents – Page 1 of 2
Contents
Specifications
232113 Hydronic Piping
230541 Noise and Vibration Control for HVAC Piping and Equipment
Drawings
02 - G-002 - LEVEL 1, AREA E2 & D5 - EMERGENCY DEPARTMENT PHASING &
TEMPORARY CONSTRUCTION PLAN
03 - G-003 - LEVEL 1, AREAS E2 & D5 - LIFE SAFETY PLAN
06 - AE-101 - LEVEL1, AREA E2 - FAST TRACK FLOOR PLAN
07 - AE-102 - LEVEL 1, AREA E2 - OBSERVATION UNIT FLOOR PLAN
68 - E003 ELECTRICAL DETAILS
69 - E004 ELECTRICAL DETAILS
76 - EL101B - ELECTRICAL LIGHTING PLAN - OBSERVATION UNIT
79 - EP101A - ELECTRICAL POWER PLAN - FAST TRACK
80 - EP101B - ELECTRICAL POWER PLAN - OBESERVATION UNIT
84 - EP102C ELECTRICAL PANEL SCHEDULES
86 - EP102E ELECTRICAL PANEL SCHEDULES
87 - EY101A - ELECTRICAL SYSTEMS PLAN - FAST TRACK
88 - EY101B - ELECTRICAL SYSTEMS PLAN - OBSERVATION UNIT
AKEA Design, Inc. Contents – Page 2 of 2
Specification Divisions/Sections
Specification 23 05 41
Specification 23 21 13 prepared by
Robert A. Haffeman, P.E.
FL PE No. 66321
This item has been electronically signed and sealed by the individual named above. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
AKEA Design, Inc. Contents – Page 2 of 2
Renovate Lake Nona Building 2 for ED Specifications – Bid Documents for Construction
23 05 41 - 1
SECTION 23 05 41
NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT
VERSION 02-01-20
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies the application of noise control measures and vibration control techniques to fans.
B. A complete listing of all common acronyms and abbreviations are included in Section 23 05 11, COMMON WORK RESULTS FOR HVAC. Noise criteria, vibration tolerance, and vibration isolation for HVAC and plumbing work.
1.2 RELATED WORK
A. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA and SAMPLES.
B. Section 23 05 10, COMMON WORK RESULTS FOR HVAC.
C. Section 23 31 00, HVAC DUCTS and CASINGS.
D. Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.
1.3 QUALITY ASSURANCE
A. Refer to article, QUALITY ASSURANCE in specification Section 23 05
11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION.
B. Noise Criteria:
1. Noise levels in all 8 octave bands due to equipment and duct systems shall not exceed following NC levels:
TYPE OF ROOM NC LEVEL
Audio Speech Pathology 25
Audio Suites 25
Bathrooms and Toilet Rooms 40
Corridors (Nurse Stations) 40
Corridors (Public) 40
Examination Rooms 35
Lobbies, Waiting Areas 40
Locker Rooms 45
Offices, Large Open 40
Offices, Small Private 35
Patient Rooms 35
Phono/Cardiology 25
SPD (Decontamination and Clean Preparation) 45
23 05 41 - 2
Therapeutic Pools 45
Treatment Rooms 35
X-Ray and General Work Rooms 40
2. For equipment which has no sound power ratings scheduled on the plans, the contractor shall select equipment such that the fore-going noise criteria, local ordinance noise levels, and OSHA re-quirements are not exceeded. Selection procedure shall be in accordance with ASHRAE Fundamentals Handbook, Chapter 8, Sound and Vibration.
3. An allowance, not to exceed 5db, may be added to the measured value to compensate for the variation of the room attenuating effect between room test condition prior to occupancy and design condition after occupancy which may include the addition of sound absorbing material, such as, furniture. This allowance may not be taken after occupancy. The room attenuating effect is defined as the difference between sound power level emitted to room and sound pressure level in room.
4. In absence of specified measurement requirements, measure equipment noise levels three feet from equipment and at an elevation of maximum noise generation.
C. Allowable Vibration Tolerances for Rotating, Non-reciprocating
Equipment: Not to exceed a self-excited vibration maximum velocity of 5 mm per second (0.20 inch per second) RMS, filter in, when measured with a vibration meter on bearing caps of machine in vertical, horizontal, and axial directions or measured at equipment mounting feet if bearings are concealed. Measurements for internally isolated fans and motors may be made at the mounting feet.
1.4 SUBMITTALS
A. Submit in accordance with specification Section 01 33 23, SHOP
DRAWINGS, PRODUCT DATA, and SAMPLES.
B. Manufacturer's Literature and Data:
1. Vibration isolators:
a. Floor mountings
b. Hangers
c. Snubbers
d. Thrust restraints
23 05 41 - 3
2. Bases.
3. Acoustical enclosures.
C. Isolator manufacturer shall furnish with submittal load calculations for selection of isolators, including supplemental bases, based on lowest operating speed of equipment supported.
1.5 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc. (ASHRAE):
Handbook 2017........Fundamentals Handbook, Chapter 8, Sound and
Vibration
C. American Society for Testing and Materials (ASTM):
A123/A123M-2017......Standard Specification for Zinc (Hot-Dip
Galvanized) Coatings on Iron and Steel
Products
D2240-05(2010).......Standard Test Method for Rubber Property -
Durometer Hardness
D. Manufacturers Standardization (MSS):
SP-58-2018...........Pipe Hangers and Supports-Materials, Design and
Manufacture
E. Occupational Safety and Health Administration (OSHA):
29 CFR 1960.95.......Occupational Noise Exposure
F. American Society of Civil Engineers (ASCE):
ASCE 7-2017..........Minimum Design Loads for Buildings and Other
Structures.
G. American National Standards Institute / Sheet Metal and Air
Conditioning Contractor’s National Association (ANSI/SMACNA):
001-2008.............Seismic Restraint Manual: Guidelines for
Mechanical Systems, 3rd Edition.
H. International Code Council (ICC):
IBC 2018.............International Building Code.
I. Department of Veterans Affairs (VA):
H-18-8 2016..........Seismic Design Requirements.
23 05 41 - 4
PART 2 - PRODUCTS
2.1 GENERAL REQUIREMENTS
A. Type of isolator, base, and minimum static deflection shall be as required for each specific equipment application as recommended by isolator or equipment manufacturer but subject to minimum requirements indicated herein and in the schedule on the drawings.
B. Elastomeric Isolators shall comply with ASTM D2240 and be oil resistant neoprene with a maximum stiffness of 60 durometer and have a straight-line deflection curve.
C. Exposure to weather: Isolator housings to be either hot dipped galvanized or powder coated to ASTM B117 salt spray testing standards. Springs to be powder coated or electro galvanized. All hardware to be electro galvanized. In addition, provide limit stops to resist wind velocity. Velocity pressure established by wind shall be calculated in accordance with section 1609 of the International
Building Code. A minimum wind velocity of 75 mph shall be employed.
D. Uniform Loading: Select and locate isolators to produce uniform loading and deflection even when equipment weight is not evenly distributed.
E. Color code isolators by type and size for easy identification of capacity.
2.2 VIBRATION ISOLATORS
A. Floor Mountings:
1. Double Deflection Neoprene (Type N): Shall include neoprene cov-ered steel support plated (top and bottom), friction pads, and necessary bolt holes.
2. Spring Isolators (Type S): Shall be free-standing, laterally stable and include acoustical friction pads and leveling bolts.
Isolators shall have a minimum ratio of spring diameter-to--operating spring height of 1.0 and an additional travel to solid equal to 50 percent of rated deflection.
3. Captive Spring Mount for Seismic Restraint (Type SS):
a. Design mounts to resiliently resist seismic forces in all directions. Snubbing shall take place in all modes with adjustment to limit upward, downward, and horizontal travel to a maximum of 6 mm (1/4-inch) before contacting snubbers.
Mountings shall have a minimum rating of one G coefficient of
23 05 41 - 5 gravity as calculated and certified by a registered structural engineer.
b. All mountings shall have leveling bolts that must be rigidly bolted to the equipment. Spring diameters shall be no less than 0.8 of the compressed height of the spring at rated load.
Springs shall have a minimum additional travel to solid equal to 50 percent of the rated deflection. Mountings shall have ports for spring inspection. Provide an all directional neoprene cushion collar around the equipment bolt.
4. Spring Isolators with Vertical Limit Stops (Type SP): Similar to spring isolators noted above, except include a vertical limit stop to limit upward travel if weight is removed and also to reduce movement and spring extension due to wind loads. Provide clearance around restraining bolts to prevent mechanical short circuiting.
5. Pads (Type D), Washers (Type W), and Bushings (Type L): Pads shall be natural rubber or neoprene waffle, neoprene and steel waffle, or reinforced duck and neoprene. Washers and bushings shall be reinforced duck and neoprene. Washers and bushings shall be reinforced duck and neoprene. Size pads for a maximum load of
345 kPa (50 pounds per square inch).
6. Seismic Pad (Type DS): Pads shall be natural rubber / neoprene waffle with steel top plate and drilled for an anchor bolt.
Washers and bushings shall be reinforced duck and neoprene. Size pads for a maximum load of 345 kPa (50 pounds per square inch).
B. Hangers: Shall be combination neoprene and springs unless otherwise noted and shall allow for expansion of pipe.
1. Combination Neoprene and Spring (Type H): Vibration hanger shall contain a spring and double deflection neoprene element in series. Spring shall have a diameter not less than 0.8 of compressed operating spring height. Spring shall have a minimum additional travel of 50 percent between design height and solid height. Spring shall permit a 15 degree angular misalignment without rubbing on hanger box.
2. Spring Position Hanger (Type HP): Similar to combination neoprene and spring hanger except hanger shall hold piping at a fixed elevation during installation and include a secondary adjustment
23 05 41 - 6 feature to transfer load to spring while maintaining same position.
3. Neoprene (Type HN): Vibration hanger shall contain a double deflection type neoprene isolation element. Hanger rod shall be separated from contact with hanger bracket by a neoprene grommet.
4. Spring (Type HS): Vibration hanger shall contain a coiled steel spring in series with a neoprene grommet. Spring shall have a diameter not less than 0.8 of compressed operating spring height.
Spring shall have a minimum additional travel of 50 percent between design height and solid height. Spring shall permit a 15 degree angular misalignment without rubbing on hanger box.
5. Hanger supports for piping 50 mm (2 inches) and larger shall have a pointer and scale deflection indicator.
6. Hangers used in seismic applications shall be provided with a neoprene and steel rebound washer installed ¼’ clear of bottom of hanger housing in operation to prevent spring from excessive upward travel
C. Snubbers: Each spring mounted base shall have a minimum of four all-directional or eight two directional (two per side) seismic snubbers that are double acting. Elastomeric materials shall be shock absorbent neoprene bridge quality bearing pads, maximum 60 durometer, replaceable and have a minimum thickness of 6 mm (1/4 inch). Air gap between hard and resilient material shall be not less than 3 mm (1/8 inch) nor more than 6 mm (1/4 inch). Restraints shall be capable of withstanding design load without permanent deformation.
D. Thrust Restraints (Type THR): Restraints shall provide a spring element contained in a steel frame with neoprene pads at each end attachment. Restraints shall have factory preset thrust and be field adjustable to allow a maximum movement of 6 mm (1/4 inch) when the fan starts and stops. Restraint assemblies shall include rods, angle brackets and other hardware for field installation.
2.3 BASES
A. Rails (Type R): Design rails with isolator brackets to reduce mounting height of equipment and cradle machines having legs or bases that do not require a complete supplementary base. To assure adequate stiffness, height of members shall be a minimum of 1/12 of longest base dimension but not less than 100 mm (4 inches). Where
23 05 41 - 7 rails are used with neoprene mounts for small fans extend rails to compensate overhang of housing.
B. Integral Structural Steel Base (Type B): Design base with isolator brackets to reduce mounting height of equipment which require a complete supplementary rigid base. To assure adequate stiffness, height of members shall be a minimum of 1/12 of longest base dimension, but not less than 100 mm (four inches).
C. Inertia Base (Type I): Base shall be a reinforced concrete inertia base. Pour concrete into a welded steel channel frame, incorporating prelocated equipment anchor bolts and pipe sleeves. Level the concrete to provide a smooth uniform bearing surface for equipment mounting. Provide grout under uneven supports. Channel depth shall be a minimum of 1/12 of longest dimension of base but not less than
150 mm (six inches). Form shall include 13-mm (1/2-inch) reinforcing bars welded in place on minimum of 203 mm (eight inch) centers running both ways in a layer 40 mm (1-1/2 inches) above bottom. Use height saving brackets in all mounting locations. Weight of inertia base shall be equal to or greater than weight of equipment supported to provide a maximum peak-to-peak displacement of 2 mm (1/16 inch).
D. Curb Mounted Isolation Base (Type CB): Fabricate from aluminum to fit on top of standard curb with overlap to allow water run-off and have wind and water seals which shall not interfere with spring action. Provide resilient snubbers with 6 mm (1/4 inch) clearance for wind resistance. Top and bottom bearing surfaces shall have sponge type weather seals. Integral spring isolators shall comply with Spring Isolator (Type S) requirements.
2.4 SOUND ATTENUATING UNITS
A. Refer to specification Section 23 31 00, HVAC DUCTS and CASINGS.
2.5 ACOUSTICAL ENCLOSURES IN MECHANICAL ROOMS
A. Provide where shown on the drawings. Enclosures shall be removable and sectional, of a size and weight that sections can be readily handled with typical lifting and moving equipment available in the equipment room. Enclosures must contain access openings, observation ports, lights, and ventilation where required for normal operation, observation, and servicing.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Vibration Isolation:
23 05 41 - 8
1. No metal-to-metal contact will be permitted between fixed and floating parts.
2. Connections to Equipment: Allow for deflections equal to or greater than equipment deflections. Electrical, drain, piping connections, and other items made to rotating or reciprocating equipment (pumps, compressors, etc.) which rests on vibration isolators, shall be isolated from building structure for first three hangers or supports with a deflection equal to that used on the corresponding equipment.
3. Common Foundation: Mount each electric motor on same foundation as driven machine. Hold driving motor and driven machine in positive rigid alignment with provision for adjusting motor alignment and belt tension. Bases shall be level throughout length and width. Provide shims to facilitate pipe connections, leveling, and bolting.
4. Provide heat shields where elastomers are subject to temperatures over 38 degrees C (l00 degrees F).
5. Extend bases for pipe elbow supports at discharge and suction connections at pumps. Pipe elbow supports shall not short circuit pump vibration to structure.
6. Non-rotating equipment such as heat exchangers and convertors shall be mounted on isolation units having the same static deflection as the isolation hangers or support of the pipe connected to the equipment.
B. Inspection and Adjustments: Check for vibration and noise transmis-sion through connections, piping, ductwork, foundations, and walls.
Adjust, repair, or replace isolators as required to reduce vibration and noise transmissions to specified levels.
3.2 ADJUSTING
A. Adjust vibration isolators after piping systems are filled and equipment is at operating weight.
B. Adjust limit stops on restrained spring isolators to mount equipment at normal operating height. After equipment installation is complete, adjust limit stops so they are out of contact during normal operation.
C. Attach thrust limits at centerline of thrust and adjust to a maximum of 1/4inch (6-mm) movement during start and stop.
D. Adjust active height of spring isolators.
23 05 41 - 9
E. Adjust snubbers according to manufacturer's recommendations.
F. Adjust seismic restraints to permit free movement of equipment within normal mode of operation.
G. Torque anchor bolts according to equipment manufacturer's recommendations to resist seismic forces.
3.3 COMMISSIONING
A. Provide commissioning documentation in accordance with the requirements of section 23 08 00 – COMMISSIONING OF HVAC SYSTEMS for all inspection, start up, and contractor testing required above and required by the System Readiness Checklist provided by the
Commissioning Agent.
B. Components provided under this section of the specification will be tested as part of a larger system. Refer to section 23 08 00 –
COMMISSIONING OF HVAC SYSTEMS and related sections for contractor responsibilities for system commissioning.
- - - E N D - - -
Renovate Lake Nona Building 2 for ED Specifications – Construction Documents – 95%
T-1
SELECTION GUIDE FOR VIBRATION ISOLATORS
EQUIPMENT ON GRADE 20FT FLOOR SPAN 30FT FLOOR SPAN 40FT FLOOR SPAN 50FT FLOOR SPAN
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
ROOF FANS
ABOVE OCCUPIED AREAS:
5 HP & OVER --- --- --- CB S 1.0 CB S 1.0 CB S 1.0 CB S 1.0
CENTRIFUGAL FANS
UP TO 50 HP:
UP TO 200 RPM B N 0.3 B S 2.5 B S 2.5 B S 3.5 B S 3.5
201 - 300 RPM B N 0.3 B S 2.0 B S 2.5 B S 2.5 B S 3.5
301 - 500 RPM B N 0.3 B S 2.0 B S 2.0 B S 2.5 B S 3.5
501 RPM & OVER B N 0.3 B S 2.0 B S 2.0 B S 2.0 B S 2.5
60 HP & OVER:
UP TO 300 RPM B S 2.0 I S 2.5 I S 3.5 I S 3.5 I S 3.5
301 - 500 RPM B S 2.0 I S 2.0 I S 2.5 I S 3.5 I S 3.5
501 RPM & OVER B S 1.0 I S 2.0 I S 2.0 I S 2.5 I S 2.5
COOLING TOWERS
UP TO 500 RPM --- --- --- --- SP 2.5 --- SP 2.5 --- SP 2.5 --- SP 3.5
501 RPM & OVER --- --- --- --- SP 0.75 --- SP 0.75 --- SP 1.5 --- SP 2.5
T-2
EQUIPMENT ON GRADE 20FT FLOOR SPAN 30FT FLOOR SPAN 40FT FLOOR SPAN 50FT FLOOR SPAN
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
AIR HANDLING UNIT PACKAGES
SUSPENDED:
UP THRU 5 HP --- --- --- --- H 1.0 --- H 1.0 --- H 1.0 --- H 1.0
7-1/2 HP & OVER:
UP TO 500 RPM --- --- --- --- H,
THR
1.5 --- H, THR
2.5 --- H, THR
2.5 --- H, THR
2.5
501 RPM & OVER --- --- --- --- H,
THR
0.8 --- H, THR
0.8 --- H,TH
R
0.8 --- H,TH
R
2.0
FLOOR MOUNTED:
UP THRU 5 HP --- D --- --- S 1.0 --- S 1.0 --- S 1.0 --- S 1.0
7-1/2 HP & OVER:
UP TO 500 RPM --- D --- R S,
THR
1.5 R S, THR
2.5 R S, THR
2.5 R S, THR
2.5
501 RPM & OVER --- D --- --- S,
THR
0.8 --- S, THR
0.8 R S, THR
1.5 R S, THR
2.0
IN-LINE CENTRIFUGAL AND VANE AXIAL FANS, FLOOR MOUNTED: (APR 9)
UP THRU 50 HP:
UP TO 300 RPM --- D --- R S 2.5 R S 2.5 R S 2.5 R S 3.5
301 - 500 RPM --- D --- R S 2.0 R S 2.0 R S 2.5 R S 2.5
501 - & OVER --- D --- --- S 1.0 --- S 1.0 R S 2.0 R S 2.5
60 HP AND OVER:
301 - 500 RPM R S 1.0 R S 2.0 R S 2.0 R S 2.5 R S 3.5
T-3
EQUIPMENT ON GRADE 20FT FLOOR SPAN 30FT FLOOR SPAN 40FT FLOOR SPAN 50FT FLOOR SPAN
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
BASE
TYPE
ISOL
TYPE
MIN
DEFL
501 RPM & OVER R S 1.0 R S 2.0 R S 2.0 R S 2.0 R S 2.5
NOTES:
1. Edit the Table above to suit where isolator, other than those shown, are used, such as for seismic restraints and position limit stops.
2. For suspended floors lighter than 100 mm (4 inch) thick concrete, select deflection requirements from next higher span.
3. For separate chiller building on grade, pump isolators may be omitted.
4. Direct bolt fire pumps to concrete base. Provide pads (D) for domestic water booster pump package.
5. For projects in seismic areas, use only SS & DS type isolators and snubbers.
6. For floor mounted in-line centrifugal blowers (ARR 1): use "B" type in lieu of "R" type base.
7. Suspended: Use "H" isolators of same deflection as floor mounted.
- - - END - - -
23 21 13 - 1
SECTION 23 21 13
HYDRONIC PIPING
VERSION 02-01-20
PART 1 - GENERAL
1.1 DESCRIPTION
A. Water piping to connect HVAC equipment, including the following:
1. Chilled water, condenser water, heating hot water and drain piping.
2. Extension of domestic water make-up piping for HVAC systems.
3. Glycol-water piping.
B. A complete listing of common acronyms and abbreviations are included in Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
1.2 RELATED WORK
A. Section 01 00 00, GENERAL REQUIREMENTS.
B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
C. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.
D. Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS.
E. Section 23 05 11, COMMON WORK RESULTS FOR HVAC: General mechanical requirements and items, which are common to more than one section of
Division 23.
F. Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND
EQUIPMENT.
G. Section 23 07 11, HVAC AND BOILER PLANT INSULATION: Piping insulation.
H. Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.
I. Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC:
Temperature and pressure sensors and valve operators.
J. Section 23 21 23, HYDRONIC PUMPS: Pumps.
1.3 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. Where conflicts occur these specifications and the VHA standard will govern.
B. American Society of Mechanical Engineers (ASME):
B1.20.1-2013.........Pipe Threads, General Purpose (Inch)
B16.3-2016...........Malleable Iron Threaded Fittings: Classes 150 and 300
23 21 13 - 2
B16.4-2016...........Gray Iron Threaded Fittings: (Classes 125 and
250)
B16.5-2017...........Pipe Flanges and Flanged Fittings: NPS 1/2 through NPS 24 Metric/Inch Standard
B16.9-2018...........Factory Made Wrought Buttwelding Fittings
B16.11-2016..........Forged Fittings, Socket-Welding and Threaded
B16.18-2018..........Cast Copper Alloy Solder Joint Pressure
Fittings
B16.22-2018..........Wrought Copper and Copper Alloy Solder-Joint
Pressure Fittings
B16.24-2016..........Cast Copper Alloy Pipe Flanges and Flanged
Fittings: Classes 150, 300, 600, 900, 1500, and 2500
B16.39-2014..........Malleable Iron Threaded Pipe Unions: Classes
150, 250, and 300
B16.42-2016..........Ductile Iron Pipe Flanges and Flanged Fittings
B31.9-2014...........Building Services Piping
B40.100-2013.........Pressure Gauges and Gauge Attachments
ASME Boiler and Pressure Vessel Code:
BPVC Section VIII-2015 Rules for Construction of Pressure Vessels
C. American Society for Testing and Materials (ASTM):
A47/A47M-2018........Standard Specification for Ferritic Malleable
Iron Castings
A53/A53M-2018........Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and
Seamless
A106/A106M-2019......Standard Specification for Seamless Carbon
Steel Pipe for High-Temperature Service
A126-2004(R2019).....Standard Specification for Gray Iron Castings for Valves, Flanges, and Pipe Fittings
A183-2014............Standard Specification for Carbon Steel Track
Bolts and Nuts
A216/A216M-2018......Standard Specification for Steel Castings, Carbon, Suitable for Fusion Welding, for
High-Temperature Service
A536-1984(R2019......Standard Specification for Ductile Iron
Castings
23 21 13 - 3
B62-2017.............Standard Specification for Composition Bronze or Ounce Metal Castings
B88-//2016...........Standard Specification for Seamless Copper
Water Tube
F439-2019............Standard Specification for Chlorinated Poly
(Vinyl Chloride) (CPVC) Plastic Pipe
Fittings, Schedule 80
F441/F441M-2015......Standard Specification for Chlorinated Poly
(Vinyl Chloride) (CPVC) Plastic Pipe, Schedules 40 and 80
D. American Welding Society (AWS):
B2.1/B2.1M-2014......Standard for Welding Procedure and Performance
Specification
E. Expansion Joint Manufacturer’s Association, Inc. (EJMA):
EJMA 2017............Expansion Joint Manufacturer’s Association
Standards, Tenth Edition
F. Manufacturers Standardization Society (MSS) of the Valve and Fitting
Industry, Inc.:
SP-67-2017...........Butterfly Valves
SP-70-2014...........Gray Iron Gate Valves, Flanged and Threaded
Ends
SP-71-2014...........Gray Iron Swing Check Valves, Flanged and
Threaded Ends
SP-80-2014...........Bronze Gate, Globe, Angle, and Check Valves
SP-85-2014...........Gray Iron Globe and Angle Valves, Flanged and
Threaded Ends
SP-110-2014..........Ball Valves Threaded, Socket-Welding, Solder
Joint, Grooved and Flared Ends
SP-125-2018..........Gray Iron and Ductile Iron In-line, Spring-
Loaded, Center-Guided Check Valves
G. Tubular Exchanger Manufacturers Association (TEMA):
TEMA Standards2015...9th Edition
1.4 SUBMITTALS
A. Submittals, including number of required copies, shall be submitted in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
23 21 13 - 4
B. Information and material submitted under this section shall be marked “SUBMITTED UNDER SECTION 23 21 13, HYDRONIC PIPING”, with applicable paragraph identification.
C. Manufacturer's Literature and Data including: Full item description and optional features and accessories. Include dimensions, weights, materials, applications, standard compliance, model numbers, size, and capacity.
1. Pipe and equipment supports. Submit calculations for variable spring and constant support hangers.
2. Pipe and tubing, with specification, class or type, and schedule.
3. Pipe fittings, including miscellaneous adapters and special fittings.
4. Flanges, gaskets and bolting.
5. Couplings and fittings.
6. Valves of all types.
7. Strainers.
8. Flexible connectors for water service.
9. Pipe alignment guides.
10. Expansion joints.
11. Expansion compensators.
12. All specified hydronic system components.
13. Water flow measuring devices.
14. Gauges.
15. Thermometers and test wells.
16. Electric heat tracing systems.
D. Submit the welder’s qualifications in the form of a current (less than one-year old) and formal certificate.
E. Coordination Drawings: Refer to paragraph, SUBMITTALS of Section 23
05 11, COMMON WORK RESULTS FOR HVAC.
F. As-Built Piping Diagrams: Provide drawing as follows for chilled water and heating hot water system and other piping systems and equipment.
1. One wall-mounted stick file with complete set of prints. Mount stick file in the chiller plant or control room along with control diagram stick file.
2. One complete set of reproducible drawings.
3. One complete set of drawings in electronic AutoCAD and pdf format.
23 21 13 - 5
G. Complete operating and maintenance manuals including wiring diagrams, technical data sheets, information for ordering replacement parts, and troubleshooting guide:
1. Include complete list indicating all components of the systems.
2. Include complete diagrams of the internal wiring for each item of equipment.
3. Diagrams shall have their terminals identified to facilitate installation, operation and maintenance.
H. Completed System Readiness Checklist provided by the Commissioning
Agent and completed by the contractor, signed by a qualified technician, and dated on the date of completion, in accordance with the requirements of Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.
I. Submit training plans and instructor qualifications in accordance with the requirements of Section 23 08 00, COMMISSIONING OF HVAC
SYSTEMS.
1.5 QUALITY ASSURANCE
A. Section 23 05 11, COMMON WORK RESULTS FOR HVAC, which includes welding qualifications.
B. Submit prior to welding of steel piping a certificate of Welder’s certification. The certificate shall be current and not more than one-year old.
C. All couplings, fittings, valves, and specialties shall be the products of a single manufacturer.
1. All castings used for coupling housings, fittings, valve bodies, etc., shall be date stamped for quality assurance and traceability.
1.6 AS-BUILT DOCUMENTATION
A. Submit manufacturer’s literature and data updated to include submittal review comments and any equipment substitutions.
B. Submit operation and maintenance data updated to include submittal review comments, VA approved substitutions and construction revisions shall be in electronic version on CD or DVD inserted into a three-ring binder. All aspects of system operation and maintenance procedures, including applicable piping isometrics, wiring diagrams of all circuits, a written description of system design, control logic, and sequence of operation shall be included in the operation and maintenance manual. The operations and maintenance manual shall include troubleshooting techniques and procedures for emergency
23 21 13 - 6 situations. Notes on all special systems or devices shall be included. A List of recommended spare parts (manufacturer, model number, and quantity) shall be furnished. Information explaining any special knowledge or tools the owner will be required to employ shall be inserted into the As-Built documentation.
C. The installing contractor shall maintain as-built drawings of each completed phase for verification; and, shall provide the complete set at the time of final systems certification testing. Should the installing contractor engage the testing company to provide as-built or any portion thereof, it shall not be deemed a conflict of interest or breach of the ‘third party testing company’ requirement.
Provide record drawings as follows:
1. Red-lined, hand-marked drawings are to be provided, with one paper copy and a scanned PDF version of the hand-marked drawings provided on CD or DVD.
D. The as-built drawings shall indicate the location and type of all lockout/tagout points for all energy sources for all equipment and pumps to include breaker location and numbers, valve tag numbers, etc. Coordinate lockout/tagout procedures and practices with local
VA requirements.
E. Certification documentation shall be provided to COR 21 working days prior to submitting the request for final inspection. The documentation shall include all test results, the names of individuals performing work for the testing agency on this project, detailed procedures followed for all tests, and provide documentation/certification that all results of tests were within limits specified. Test results shall contain written sequence of test procedure with written test results annotated at each step along with the expected outcome or setpoint. The results shall include all readings, including but not limited to data on device
(make, model and performance characteristics), normal pressures, switch ranges, trip points, amp readings, and calibration data to include equipment serial numbers or individual identifications, etc.
1.7 SPARE PARTS
A. For mechanical pressed sealed fittings provide tools required for each pipe size used at the facility.
23 21 13 - 7
PART 2 - PRODUCTS
2.1 PIPE AND EQUIPMENT SUPPORTS, PIPE SLEEVES, AND WALL AND CEILING PLATES
A. Provide in accordance with Section 23 05 11, COMMON WORK RESULTS FOR
HVAC.
2.2 PIPE AND TUBING
A. Chilled Water, Heating Hot Water, and Vent Piping:
1. Steel: ASTM A53/A53M Grade B, seamless or ERW, Schedule 40.
2. Copper water tube option: ASTM B88, Type L, hard drawn.
B. Extension of Domestic Water Make-up Piping: ASTM B88, Type L, hard drawn copper tubing.
C. Cooling Coil Condensate Drain Piping:
1. From air handling units: Copper water tube, ASTM B88, Type M piping.
2. From fan coil or other terminal units: Copper water tube, ASTM
B88, Type M for runouts and Type L for mains.
D. Pipe supports, including insulation shields, for above ground piping: Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
2.3 FITTINGS FOR STEEL PIPE
A. 50 mm (2 inches) and Smaller: Screwed or welded joints.
1. Butt welding: ASME B16.9 with same wall thickness as connecting piping.
2. Forged steel, socket welding or threaded: ASME B16.11.
3. Screwed: 150-pound malleable iron, ASME B16.3. 125-pound cast iron, ASME B16.4, may be used in lieu of malleable iron. Bushing reduction of a single pipe size, or use of close nipples, is not acceptable.
4. Unions: ASME B16.39.
5. Water hose connection adapter: Brass, pipe thread to 20 mm (3/4 inch) garden hose thread, with hose cap nut.
B. 65 mm (2-1/2 inches) and Larger: Welded or flanged joints.
1. Butt welding fittings: ASME B16.9 with same wall thickness as connecting piping. Elbows shall be long radius type, unless otherwise noted.
2. Welding flanges and bolting: ASME B16.5:
a. Water service: Weld neck or slip-on, plain face, with 3.2 mm
(1/8 inch) thick full-face neoprene gasket suitable for 104 degrees C (220 degrees F).
23 21 13 - 8
1) Contractor's option: Convoluted, cold formed 150-pound steel flanges, with Teflon gaskets, may be used for water service.
b. Flange bolting: Carbon steel machine bolts or studs and nuts.
C. Welded Branch and Tap Connections: Forged steel weldolets, or branchlets and threadolets may be used for branch connections up to one pipe size smaller than the main. Forged steel half-couplings, ASME B16.11 may be used for drain, vent and gauge connections.
2.4 FITTINGS FOR COPPER TUBING
A. Joints:
1. Solder Joints: Joints shall be made up in accordance with recommended practices of the materials applied. Apply 95/5 tin and antimony on all copper piping.
2. Mechanically formed tee connection in water and drain piping:
Form mechanically extracted collars in a continuous operation by drilling pilot hole and drawing out tube surface to form collar, having a height of not less than three times the thickness of tube wall. Adjustable collaring device shall ensure proper tolerance and complete uniformity of the joint. Notch and dimple joining branch tube in a single process to provide free flow where the branch tube penetrates the fitting.
B. Bronze Flanges and Flanged Fittings: ASME B16.24.
C. Fittings: ASME B16.18 cast copper or ASME B16.22 solder wrought copper.
2.5 FITTINGS FOR PLASTIC PIPING
A. Schedule 40, socket type for solvent welding.
B. Schedule 40 PVC drain piping: Drainage pattern.
C. Chemical feed piping for condenser water treatment: CPVC, Schedule
80, ASTM F439.
2.6 DIELECTRIC FITTINGS
A. Provide where copper tubing and ferrous metal pipe are joined.
B. 50 mm (2 inches) and Smaller: Threaded dielectric union, ASME
B16.39.
C. 65 mm (2-1/2 inches) and Larger: Flange union with dielectric gasket and bolt sleeves, ASME B16.42. Dielectric gasket material shall be compatible with hydronic medium.
D. Temperature Rating, 99 degrees C (210 degrees F).
23 21 13 - 9
E. Contractor’s option: On pipe sizes 50 mm (2 inch) and smaller, screwed end brass ball valves or dielectric nipples may be used in lieu of dielectric unions.
2.7 SCREWED JOINTS
A. Pipe Thread: ASME B1.20.1.
B. Lubricant or Sealant: Oil and graphite or other compound approved for the intended service.
2.8 VALVES
A. Asbestos packing is not acceptable.
B. All valves of the same type shall be products of a single manufacturer.
C. Provide chain operators for valves 150 mm (6 inches) and larger when the centerline is located 2.4 m (8 feet) or more above the floor or operating platform.
D. Shut-Off Valves:
1. Ball Valves (Pipe sizes 50 mm (2 inch) and smaller): MSS SP-110, screwed or solder connections, brass or bronze body with chrome-plated ball with full port and Teflon seat at 2758 kPa (400 psig) working pressure rating. Provide stem extension to allow operation without interfering with pipe insulation.
2. Butterfly Valves (Pipe Sizes 65 mm (2-1/2 inch) and larger):
Provide stem extension to allow 50 mm (2 inches) of pipe insulation without interfering with valve operation. MSS SP-67, flange lug type rated 1200 kPa (175 psig) working pressure at 93 degrees C (200 degrees F). Valves shall be ANSI Leakage Class VI and rated for bubble tight shut-off to full valve pressure rating. Valve shall be rated for dead end service and bi-directional flow capability to full rated pressure. Butterfly valves are prohibited for direct buried pipe applications.
a. Body: Cast iron, ASTM A126, Class B. Malleable iron, ASTM
A47/A47M electro-plated, or ductile iron, ASTM A536, Grade
65-45-12 electro-plated.
b. Trim: Bronze, aluminum bronze, or 300 series stainless steel disc, bronze bearings, 316 stainless steel shaft and manufacturer's recommended resilient seat. Resilient seat shall be field replaceable, and fully line the body to completely isolate the body from the product. A phosphate
23 21 13 - 10 coated steel shaft or stem is acceptable, if the stem is completely isolated from the product.
c. Actuators: Field interchangeable. Valves for balancing service shall have adjustable memory stop to limit open position.
1) Valves 150 mm (6 inches) and smaller: Lever actuator with minimum of seven locking positions, except where chain wheel is required.
2) Valves 200 mm (8 inches) and larger: Enclosed worm gear with handwheel, and where required, chain-wheel operator.
3) Gate Valves:
i. 50 mm (2 inches) and smaller: MSS SP-80, Bronze, 1035 kPa (150 psig), wedge disc, rising stem, union bonnet.
ii. 65 mm (2-1/2 inches) and larger: Flanged, outside screw and yoke. MSS SP-70, iron body, bronze mounted, 861 kPa
(125 psig) wedge disc.
E. Globe and Angle Valves:
1. Globe Valves:
a. 50 mm (2 inches) and smaller: MSS SP-80, bronze, 1035 kPa (150 psig) Globe valves shall be union bonnet with metal plug type disc.
b. 65 mm (2-1/2 inches) and larger: 861 kPa (125 psig), flanged, iron body, bronze trim, MSS SP-85 for globe valves.
2. Angle Valves:
a. 50 mm (2 inches) and smaller: MSS SP-80, bronze, 1035 kPa (150 psig) Angle valves shall be union bonnet with metal plug type disc.
b. 65 mm (2-1/2 inches) and larger: 861 kPa (125 psig), flanged, iron body, bronze trim, MSS SP-85 for angle.
F. Check Valves:
1. Swing Check Valves:
a. 50 mm (2 inches) and smaller: MSS SP-80, bronze, 1035 kPa (150 psig), 45-degree swing disc.
b. 65 mm (2-1/2 inches) and larger: 861 kPa (125 psig), flanged, iron body, bronze trim, MSS SP-71 for check valves.
2. Non-Slam or Silent Check Valve: Spring loaded double disc swing check or internally guided flat disc lift type check for bubble tight shut-off. Provide where check valves are shown in chilled
23 21 13 - 11 water and hot water piping. Check valves incorporating a balancing feature may be used.
a. Body: MSS SP-125 cast iron, ASTM A126, Class B, or steel, ASTM
A216/A216M, Class WCB, or ductile iron, ASTM 536, flanged or wafer type.
b. Seat, disc and spring: 18-8 stainless steel, or bronze, ASTM
B62. Seats may be elastomer material.
G. Water Flow Balancing Valves: For flow regulation and shut-off.
Valves shall be line size rather than reduced to control valve size.
1. Globe style valve.
2. A dual-purpose flow balancing valve and adjustable flow meter, with bronze or cast-iron body, calibrated position pointer, valved pressure taps or quick disconnects with integral check valves and preformed polyurethane insulating enclosure.
3. Provide a readout kit including flow meter, readout probes, hoses, flow charts or calculator, and carrying case.
H. Automatic Balancing Control Valves: Factory calibrated to maintain constant flow (plus or minus five percent) over system pressure fluctuations of 27 to 393 kPa (4 to 57 psig). Provide standard pressure taps and four sets of capacity charts. Valves shall be line size and be one of the following designs:
1. Gray iron ASTM A126 or brass body rated 1200 kPa (175 psig) at 93 degrees C (200 degrees F), with stainless steel piston and spring.
2. Brass or ferrous body designed for 2070 kPa (300 psig) service at
121 degrees C (250 degrees F), with corrosion resistant, tamper proof, self-cleaning piston/spring assembly that is easily removable for inspection or replacement.
3. Combination assemblies containing ball type shut-off valves, unions, flow regulators, strainers with blowdown valves and pressure temperature ports shall be acceptable.
4. Provide a readout kit including flow meter, probes, hoses, flow charts and carrying case.
2.9 WATER FLOW MEASURING DEVICES
A. Minimum overall accuracy plus or minus three percent over a range of
70 to 110 percent of design flow. Select devices for not less than
110 percent of design flow rate.
23 21 13 - 12
B. Venturi Type: Bronze, steel, or cast iron with bronze throat, with valved pressure sensing taps upstream and at the throat.
C. Wafer Type Circuit Sensor: Cast iron wafer-type flow meter equipped with readout valves to facilitate the connecting of a differential pressure meter. Each readout valve shall be fitted with an integral check valve designed to minimize system fluid loss during the monitoring process.
D. Self-Averaging Annular Sensor Type: Brass or stainless-steel metering tube, shutoff valves and quick-coupling pressure connections. Metering tube shall be rotatable so all sensing ports may be pointed down-stream when unit is not in use.
E. Insertion Turbine Type Sensor: Section 23 09 23, DIRECT-DIGITAL
CONTROL SYSTEM FOR HVAC.
F. Flow Measuring Device Identification:
1. Metal tag attached by chain to the device.
2. Include meter or equipment number, manufacturer's name, meter model, flow rate factor and design flow rate in /gpm.
G. Portable Water Flow Indicating Meters:
1. Minimum 150 mm (6 inch) diameter dial, forged brass body, beryllium-copper bellows, designed for 1200 kPa (175 psig) working pressure at 121 degrees C (250 degrees F).
2. Bleed and equalizing valves.
3. Vent and drain hose and two 3 m (10 feet) lengths of hose with quick disconnect connections.
4. Factory-fabricated carrying case with hose compartment and a bound set of capacity curves showing flow rate versus pressure differential.
5. Provide one portable meter for each range of differential pressure required for the installed flow devices.
H. Permanently Mounted Water Flow Indicating Meters: Minimum 150 mm (6 inch) diameter, or 457 mm (18 inch) long scale, for 120 percent of design flow rate, direct reading in gpm, with three valve manifold and two shut-off valves.
2.10 STRAINERS
A. Y Type.
1. Screens: Bronze, Monel metal or 18-8 stainless steel, free area not less than 2-1/2 times pipe area, with perforations as
23 21 13 - 13 follows: 1.1 mm (0.045 inch) diameter perforations for 100 mm (4 inches) and larger: 3.2 mm (1/8 inch) diameter perforations.
B. Suction Diffusers: Specified in Section 23 21 23, HYDRONIC PUMPS.
2.11 FLEXIBLE CONNECTORS FOR WATER SERVICE
A. Flanged Spool Connector:
1. Single arch or multiple arch type. Tube and cover shall be constructed of chlorobutyl elastomer with full faced integral flanges to provide a tight seal without gaskets. Connectors shall be internally reinforced with high strength synthetic fibers impregnated with rubber or synthetic compounds as recommended by connector manufacturer, and steel reinforcing rings.
2. Working pressures and temperatures shall be as follows:
a. Connector sizes 50 mm to 100 mm (2 inches to 4 inches), 1137 kPa (165 psig) at 121 degrees C (250 degrees F).
b. Connector sizes 125 mm to 300 mm (5 inches to 12 inches), 965 kPa (140 psig) at 121 degrees C (250 degrees F).
3. Provide ductile iron retaining rings and control units.
2.12 EXPANSION JOINTS
A. Factory built devices, inserted in the pipe lines, designed to absorb axial cyclical pipe movement which results from thermal expansion and contraction. This includes factory-built or field-fabricated guides located along the pipe lines to restrain lateral pipe motion and direct the axial pipe movement into the expansion joints.
B. Manufacturing Quality Assurance: Conform to Expansion Joints
Manufacturers Association (EJMA) Standards.
C. Bellows - Internally Pressurized Type:
1. Multiple corrugations of Type 304 or Type A240-321 stainless steel.
2. Internal stainless-steel sleeve entire length of bellows.
3. External cast iron equalizing rings for services exceeding 345 kPa (50 psig).
4. Welded ends.
5. Design shall conform to standards of EJMA and ASME B31.9.
6. External tie rods designed to withstand pressure thrust force upon anchor failure if one or both anchors for the joint are at change in direction of pipeline.
7. Integral external cover.
23 21 13 - 14
D. Bellows - Externally Pressurized Type:
1. Multiple corrugations of Type 304 stainless steel.
2. Internal and external guide integral with joint.
3. Design for external pressurization of bellows to eliminate squirm.
4. Welded ends.
5. Conform to the standards of EJMA and ASME B31.9.
6. Threaded connection at bottom, 25 mm (1 inch) minimum, for drain or drip point.
7. Integral external cover and internal sleeve.
E. Expansion Compensators:
1. Corrugated bellows, externally pressurized, stainless steel or bronze.
2. Internal guides and anti-torque devices.
3. Threaded ends.
4. External shroud.
5. Conform to standards of EJMA.
F. Expansion Joint (Contractor’s Option): 2413 kPa (350 psig) maximum working pressure, steel pipe fitting consisting of telescoping body and slip-pipe sections, PTFE modified polyphenylene sulfide coated slide section, with welded or flanged ends, suitable for axial end movement to 75 mm (3 inch).
G. Expansion Joint Identification: Provide stamped brass or stainless-steel nameplate on each expansion joint listing the manufacturer, the allowable movement, flow direction, design pressure and temperature, date of manufacture, and identifying the expansion joint by the identification number on the contract drawings.
H. Guides: Provide factory-built guides along the pipe line to permit axial movement only and to restrain lateral and angular movement.
Guides must be designed to withstand a minimum of 15 percent of the axial force which will be imposed on the expansion joints and anchors. Field-built guides may be used if detailed on the contract drawings.
I. Supports: Provide saddle supports and frame or hangers for heat exchanger. Mounting height shall be adjusted to facilitate gravity return of steam condensate. Construct supports from steel, weld joints.
23 21 13 - 15
2.13 HYDRONIC SYSTEM COMPONENTS
A. Pressure Reducing Valve (Water): Diaphragm or bellows operated, spring loaded type, with minimum adjustable range of 28 kPa (4 psig) above and below set point. Bronze, brass or iron body and bronze, brass or stainless-steel trim, rated 861 kPa (125 psig) working pressure at 107 degrees C (225 degrees F).
B. Pressure Relief Valve: Bronze or iron body and bronze or stainless-steel trim, with testing lever. Comply with ASME BPVC Section VIII and bear ASME stamp.
C. Automatic Air Vent Valves (where shown on drawings): Cast iron or semi-steel body, 1035 kPa (150 psig) working pressure, stainless steel float, valve, valve seat and mechanism, minimum 15 mm (1/2 inch) water connection and 6 mm (1/4 inch) air outlet. Air outlet shall be piped to the nearest floor drain.
2.14 WATER FILTERS AND POT CHEMICAL FEEDERS
A. See Section 23 25 00, HVAC WATER TREATMENT, paragraph, CHEMICAL
TREATMENT FOR CLOSED LOOP SYSTEMS.
2.15 GAUGES, PRESSURE AND COMPOUND
A. ASME B40.100, Accuracy Grade 1A, (pressure, vacuum, or compound for air, oil or water), initial mid-scale accuracy 1 percent of scale
(Qualify grade), metal or phenolic case, 115 mm (4-1/2 inches) in diameter, 6 mm (1/4 inch) NPT bottom connection, white dial with black graduations and pointer, clear glass or acrylic plastic window, suitable for board mounting. Provide red "set hand" to indicate normal working pressure.
B. Provide brass lever handle union cock. Provide brass/bronze pressure snubber for gauges in water service.
C. Range of Gauges: Provide range equal to at least 130 percent of normal operating range.
1. For condenser water suction (compound): 101 kPa (30 inches Hg) to
690 kPa (100 psig).
2.16 PRESSURE/TEMPERATURE TEST PROVISIONS
A. Pete's Plug: 6 mm (1/4 inch) MPT by 75 mm (3 inches) long, brass body and cap, with retained safety cap, nordel self-closing valve cores, permanently installed in piping where shown, or in lieu of pressure gauge test connections shown on the drawings.
23 21 13 - 16
B. Provide one each of the following test items to the COR:
1. 6 mm (1/4 inch) FPT by 3.2 mm (1/8 inch) diameter stainless steel pressure gauge adapter probe for extra-long test plug.
2. 90 mm (3-1/2 inch) diameter, one percent accuracy, compound gauge, 101 kPa (30 inches Hg) to 690 kPa (100 psig) range.
3. 0 to 104 degrees C (32 to 220 degrees F) pocket thermometer one-half degree accuracy, 25 mm (1 inch) dial, 125 mm (5 inch) long stainless-steel stem, plastic case.
2.17 THERMOMETERS
A. Mercury or organic liquid filled type, red or blue column, clear plastic window, with 150 mm (6 inch) brass stem, straight, fixed or adjustable angle as required for each in reading.
B. Case: Chrome plated brass or aluminum with enamel finish.
C. Scale: Not less than 225 mm (9 inches), range as described below, two-degree graduations.
D. Separable Socket (Well): Brass, extension neck type to clear pipe insulation.
E. Scale ranges:
1. Chilled Water and Glycol-Water: 0 to 38 degrees C (32 to 100 degrees F).
2. Hot Water and Glycol-Water: 38 to 93 degrees C (100 to 200 degrees F).
2.18 FIRESTOPPING MATERIAL
A. Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC.
2.19 ELECTRICAL HEAT TRACING SYSTEMS
A. Systems shall meet requirements of NFPA 70.
B. Provide tracing for outdoor piping subject to freezing temperatures below 3.3 degrees C (38 degrees F) as follows:
1. Chilled water and Hot water piping at units and all other areas exposed to the weather.
2. Domestic water lines exposed to weather.
C. Heat tracing shall be provided to the extent shown on the drawings
(Floor plans and…