This solicitation from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8 seeks design/build services to install fall protection guard rails and anchorage for Building 1 and Building 2 at the James A. Haley VA Medical Center in Tampa, Florida. The contractor shall provide engineered solutions utilizing roof anchor points for anyone needing to work on or from the roof, with a magnitude of construction between $2 million to $5 million. Interested parties must be registered in the System for Award Management and certified as a Service-Disabled Veteran-Owned Small Business. The site visit is scheduled for November 15, 2023 and requests for information are due by November 22. The wage determination FL20230208 applies to this project.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
1.9 2 3 4 5 6 7 8 8.1 9
B
C
D
E
F
G
2.5 4.3 new single ply-60 MIL-tpo fully adhered PEEL-N-STICK roofing system by GENFLEX or approved equal over 5"
UNIFORM rigid insulation. R=38 AVG
NEW WALK PAD PER MFG SPECS. PROVIDE TO
ALL EQUIPMENT AND ROOFTOP ROOMS
REQUIRING ACCESS
TYPICAL DOWN CONDUCTOR IN 1"
CONDUIT TO GROUND ROD SHALL
REMAIN. NEW SYSTEM SHALL
CONNECT TO EXISTING DOWN
CONDUCTOR
LIGHTNING PROTECTION SYSTEM SHALL BE
REMOVED AND REPLACED AND INSTALLED IN
SIMILAR LOCATION NEAR PREVIOUS
ATTACHMENT. TYPICAL ALL AREAS OF MAIN
AND ADJACENT ROOF WHERE REMOVAL IS
NECESSARY TO PERFORMT HE WORK.
REPLACE ALL LP NEAR ROOF MECH UNITS
NOTE:
1. AREAS SHOWN ARE HORIZONTAL PROJECTION. CONTRACTOR SHALL ADJUST AREA PER
CORRESPONDING SLOPE. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL
DIMENSIONS AND MEASUREMENTS PRIOR TO MATERIAL ORDERING AND INSTALLATION.
2. DIMENSIONS SHOWN FOR VERIFICATION AND REFERENCE ONLY.
3. PROVIDE 5" RIGID INSULATION ALL AREAS SO THAT AVERAGE R-VALUE IS EQUAL TO R-38.
REMOVE AND REPLACE ALL ROOF
DRAINS OR PROVIDE RETROFIT DRAIN
INSERT. FIELD VERIFY LOCATION AND
SIZE PRIOR TO START OF WORK
COORDINATE ROOF SLOPE WITH
TAPERED INSULATION LAYOUT.
REMOVE EXISTING AND INSTALL NEW ANODIZED ALUMINUM CAP AND
WALL FLASHING AND COUNTER FLASHING, UPPER AND LOWER DRIP
EDGES PER MFG DETAILS
02-A-1
02-A-2 02-A-3
02-A-402-A-5
02-A-6
ROOF TO REMAIN NOT IN SCOPE
BLDG 32
BLDG 23
BLDG 1
BLDG 42
BLDG 30
BLDG 36
BUILDING 2 PENTHOUSE BLDG 2
TPO MEMBRANE
SCOPE OF WORK (TPO MEMBRANE ROOF):
1. REMOVE EXISTING ROOFING SYSTEM TO BARE DECK ON ALL AREAS OF THE MAIN ROOF.
ALL FLASHING, INSULATION AND ADHESIVE SHALL BE REMOVED TO EXPOSE BARE
DECK SUBSTRATE.
2. PROVIDE NEW FULLY ADHERED 60 MIL WHITE TPO ROOFING SYSTEM OVER TAPERED
POLYISOCYANURATE INSULATION (SEE INSULATION LAYOUT R-38 AVG VALUE).
ATTACH INSULATION TO CLEAN SUBSTRATE WITH "GENFLEX" ONE STEP INSULATION
ADHESIVE. NOTE: INSULATION MUST BE ATTACHED TO SOUND ORIGINAL SUBSTRATE.
ATTACHMENT TO EXISTING MEMBRANE IS NOT PERMITTED. NEW ROOF MEMBRANE
INSTALLED BY CONTRACTOR SHALL ADHERE TO SUBMITTED AND APPROVED
SPECIFICATIONS.
3. REPLACE ALL CURB FLASHING. REMOVE ALL MECHANICAL EQUIPMENT STANDS PRIOR
TO START OF EACH PHASE OF WORK.
4. FURNISH AND INSTALL 1-PLY BASE FLASHING PER MFG SPECS
5. FURNISH AND INSTALL ALUMINUM ROOF COUNTER FLASHING AND COPING CAPS
6. FURNISH AND INSTALL 24 GAGE 2B STAINLESS STEEL PITCH PANS AND ROOF
PENETRATION FLASHING
7. FURNISH AND INSTALL DRAIN FLASHING AT DRAIN LOCATIONS. EXISTING DRAINS TO BE
REMOVED AND REPLACED WITH RETROFIT DRAINS.
8. EXISTING ROOF DECKING SHALL BE INSPECTED FOR SIGNS OF DETERIORATION OR
DAMAGE BY ON SITE FOREMAN. DAMAGED AREA SHALL BE DOCUMENTED ON PLAN
AND PHOTOGRAPHED PRIOR TO AND AFTER REPAIR. ENGINEER OF RECORD (EOR)
SHALL BE NOTIFIED IN WRITING OF ALL DAMAGED AREAS. ALL Damaged AREAS
SHALL BE EVALUATED FOR REPAIR OR REPLACEMENT.
9.
1. NO WORK SHALL COMMENCE UNTIL ALL SUBMITTALS HAVE BEEN
APPROVED IN WRITING BY THE COR OR VA AUTHORIZED
REPRESENTATIVE .
2.
ADDITIONAL NOTES
ROOF PLAN-MAIN ROOF
SCALE: 3/32" = 1'-0"1
ROOF PLAN - MAIN ROOF
20-Jul-17 A100
NORTH
CONSTRUCTION NOTES2
KEY PLAN
SCALE: 1:3003
NORTH
date sealed: 20-Jul-17
JAMES A. HALEY
VA HOSPITAL
13000 BRUCE B DOWNS BLVD
TAMPA, FL 33612
65% submittal
95% submittal abrams group construction, llc 3645 Highway 90 Pace, FL. 32571
Phone: (850) 994-7980 Fax: (850) 994-7981
REPLACE ROOF SYSTEMS
CAMPUS WIDE
N/A
05.17.17
100% submittal - REVIEW
(T) 813. 232 . 8448 (F) 800. 698 . 1945
200 2nd Ave South - #465 - St Petersburg, FL 33701 info@connellyengineering.com www. connellyengineering .com
C O N S U L T I N G E N G I N E E R S connelly groupC G 07.21.17
00.00.00 christopher r. connelly, pe pe-fl63886 / ca-fl 26841
S U
B M
IT
T A L C
O M
P L E T
IO
N : 9
N O
T F O
R C
O N
S T R
U C
T
IO
N
100% submittal - CONSTRUCTION SET 00.00.00
100% submittal - AS-BUILTS 00.00.00
35% submittal
CRC JJC
DESIGN PROFESSIONALPROJECT TEAM
FBC2014
5TH EDITION
S H
E E T S
A V E D
A T E
:4
P
M
:5 1:5
P
M S
H E E T P
L O
T D
A T E
673-14-604
REVISED 072117
AutoCAD SHX Text
DN
AutoCAD SHX Text
MECH. CHASE
AutoCAD SHX Text
FIXED ALUM.
AutoCAD SHX Text
LOUVERS
AutoCAD SHX Text
ALUM. LADDER
AutoCAD SHX Text
LOUVERS
AutoCAD SHX Text
FIXED ALUM.
AutoCAD SHX Text
LOUVERS
AutoCAD SHX Text
UP
AutoCAD SHX Text
ROOF WALKWAY
AutoCAD SHX Text
FD
AutoCAD SHX Text
FD
AutoCAD SHX Text
FD
AutoCAD SHX Text
FD
AutoCAD SHX Text
FANS
AutoCAD SHX Text
ROOF OF
AutoCAD SHX Text
SECOND
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
ROOF OF
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
4" RD
AutoCAD SHX Text
5" RD
AutoCAD SHX Text
5" RD
AutoCAD SHX Text
5" RD
AutoCAD SHX Text
5" RD
AutoCAD SHX Text
4" RD
AutoCAD SHX Text
4" RD
AutoCAD SHX Text
4" RD
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Print Date
AutoCAD SHX Text File Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PROJECT DIRECTOR
1.9 2 3 4 5 6 7 8 8.1 9
B
C
D
E
F
G
2.5 4.3 new single ply-60 MIL-tpo fully adhered PEEL-N-STICK roofing system by GENFLEX or approved equal over 5"
UNIFORM rigid insulation. R=38 AVG
NOTE:
1. AREAS SHOWN ARE HORIZONTAL PROJECTION. CONTRACTOR SHALL ADJUST AREA PER
CORRESPONDING SLOPE. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL
DIMENSIONS AND MEASUREMENTS PRIOR TO MATERIAL ORDERING AND INSTALLATION.
2. DIMENSIONS SHOWN FOR VERIFICATION AND REFERENCE ONLY.
3. PROVIDE 5" RIGID INSULATION ALL AREAS SO THAT AVERAGE R-VALUE IS EQUAL TO R-38.
LIGHTNING PROTECTION SYSTEM SHALL BE
REMOVED AND REPLACED AND INSTALLED IN
SIMILAR LOCATION NEAR PREVIOUS
ATTACHMENT. TYPICAL ALL AREAS OF MAIN
AND ADJACENT ROOF WHERE REMOVAL IS
NECESSARY TO PERFORMT HE WORK.
REPLACE ALL LP NEAR ROOF MECH UNITS
TYPICAL DOWN CONDUCTOR IN 1"
CONDUIT TO GROUND ROD SHALL
REMAIN. NEW SYSTEM SHALL
CONNECT TO EXISTING DOWN
CONDUCTOR
COORDINATE ROOF SLOPE WITH
TAPERED INSULATION LAYOUT.
REMOVE AND REPLACE ALL DAMGED
ROOF DRAINS OR PROVIDE RETROFIT
DRAIN INSERT. FIELD VERIFY LOCATION
AND SIZE PRIOR TO START OF WORK
REMOVE EXISTING AND INSTALL NEW
ANODIZED ALUMINUM CAP AND WALL
FLASHING AND COUNTER FLASHING,
UPPER AND LOWER DRIP EDGES PER
MFG DETAILS
02-B-1 02-B-2
BLDG 32
BLDG 23
BLDG 1
BLDG 42
BLDG 30
BLDG 36
BUILDING 2 PENTHOUSE BLDG 2
TPO MEMBRANE
SCOPE OF WORK (TPO MEMBRANE ROOF):
1. REMOVE EXISTING ROOFING SYSTEM TO BARE DECK ON ALL AREAS OF THE MAIN ROOF.
ALL FLASHING, INSULATION AND ADHESIVE SHALL BE REMOVED TO EXPOSE BARE
DECK SUBSTRATE.
2. PROVIDE NEW FULLY ADHERED 60 MIL WHITE TPO ROOFING SYSTEM OVER TAPERED
POLYISOCYANURATE INSULATION (SEE INSULATION LAYOUT R-38 AVG VALUE).
ATTACH INSULATION TO CLEAN SUBSTRATE WITH "GENFLEX" ONE STEP INSULATION
ADHESIVE. NOTE: INSULATION MUST BE ATTACHED TO SOUND ORIGINAL SUBSTRATE.
ATTACHMENT TO EXISTING MEMBRANE IS NOT PERMITTED. NEW ROOF MEMBRANE
INSTALLED BY CONTRACTOR SHALL ADHERE TO SUBMITTED AND APPROVED
SPECIFICATIONS.
3. REPLACE ALL CURB FLASHING. REMOVE ALL MECHANICAL EQUIPMENT STANDS PRIOR
TO START OF EACH PHASE OF WORK.
4. FURNISH AND INSTALL 1-PLY BASE FLASHING PER MFG SPECS
5. FURNISH AND INSTALL ALUMINUM ROOF COUNTER FLASHING AND COPING CAPS
6. FURNISH AND INSTALL 24 GAGE 2B STAINLESS STEEL PITCH PANS AND ROOF
PENETRATION FLASHING
7. FURNISH AND INSTALL DRAIN FLASHING AT DRAIN LOCATIONS. EXISTING DRAINS TO BE
REMOVED AND REPLACED WITH RETROFIT DRAINS.
8. EXISTING ROOF DECKING SHALL BE INSPECTED FOR SIGNS OF DETERIORATION OR
DAMAGE BY ON SITE FOREMAN. DAMAGED AREA SHALL BE DOCUMENTED ON PLAN
AND PHOTOGRAPHED PRIOR TO AND AFTER REPAIR. ENGINEER OF RECORD (EOR)
SHALL BE NOTIFIED IN WRITING OF ALL DAMAGED AREAS. ALL Damaged AREAS
SHALL BE EVALUATED FOR REPAIR OR REPLACEMENT.
9.
1. NO WORK SHALL COMMENCE UNTIL ALL SUBMITTALS HAVE BEEN
APPROVED IN WRITING BY THE COR OR VA AUTHORIZED
REPRESENTATIVE .
2.
ADDITIONAL NOTES
ROOF PLAN-MAIN ROOF
SCALE: 3/32" = 1'-0"1
ROOF PLAN - MAIN ROOF
20-Jul-17 A101
NORTH
CONSTRUCTION NOTES2
KEY PLAN
SCALE: 1:3003
NORTH
date sealed: 20-Jul-17
JAMES A. HALEY
VA HOSPITAL
13000 BRUCE B DOWNS BLVD
TAMPA, FL 33612
65% submittal
95% submittal abrams group construction, llc 3645 Highway 90 Pace, FL. 32571
Phone: (850) 994-7980 Fax: (850) 994-7981
REPLACE ROOF SYSTEMS
CAMPUS WIDE
N/A
05.17.17
100% submittal - REVIEW
(T) 813. 232 . 8448 (F) 800. 698 . 1945
200 2nd Ave South - #465 - St Petersburg, FL 33701 info@connellyengineering.com www. connellyengineering .com
C O N S U L T I N G E N G I N E E R S connelly groupC G 07.21.17
00.00.00 christopher r. connelly, pe pe-fl63886 / ca-fl 26841
S U
B M
IT
T A L C
O M
P L E T
IO
N : 9
N O
T F O
R C
O N
S T R
U C
T
IO
N
100% submittal - CONSTRUCTION SET 00.00.00
100% submittal - AS-BUILTS 00.00.00
35% submittal
CRC JJC
DESIGN PROFESSIONALPROJECT TEAM
FBC2014
5TH EDITION
S H
E E T S
A V E D
A T E
:4
P
M
:5 1:5
P
M S
H E E T P
L O
T D
A T E
673-14-604
AutoCAD SHX Text
PRECAST CONC.
AutoCAD SHX Text
COPING
AutoCAD SHX Text
MET. LADDER
AutoCAD SHX Text
5" RD
AutoCAD SHX Text
5" RD
AutoCAD SHX Text
INCINERATOR
AutoCAD SHX Text
STACK
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Print Date
AutoCAD SHX Text File Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COPPER CONDENSATE PIPE
SECURED WITH STAINLESS
STEEL CLAMP AND (2) #10 SS
SCREWS
PT BLOCK @ 72" C/C (AS NEEDED FOR SLOPE)
SECURED TO ROOF MEMBRANE WITH MASTIC
APPROVED BY THE ROOF MEMBRANE MFG.
CONTRACTOR SHALL CHECK FOR COMPATIBILITY
OF MATERIALS
PROVIDE CAP SHEET OVER SUPPORT BLOCKS TIED INTO
MAIN ROOFING MEMBRANE.
12"
ROOF DETAILS
20-Jul-1720-Jul-17 A400
COMMON R-VALUES OF MATERIALS
SCALE: NTS2
CONDENSATE DRAIN SUPPORT
SCALE: 1.5" = 1'-0"1
date sealed: 20-Jul-17
JAMES A. HALEY
VA HOSPITAL
13000 BRUCE B DOWNS BLVD
TAMPA, FL 33612
65% submittal
95% submittal abrams group construction, llc 3645 Highway 90 Pace, FL. 32571
Phone: (850) 994-7980 Fax: (850) 994-7981
REPLACE ROOF SYSTEMS
CAMPUS WIDE
N/A
05.17.17
100% submittal - REVIEW
(T) 813. 232 . 8448 (F) 800. 698 . 1945
200 2nd Ave South - #465 - St Petersburg, FL 33701 info@connellyengineering.com www. connellyengineering .com
C O N S U L T I N G E N G I N E E R S connelly groupC G 07.21.17
00.00.00 christopher r. connelly, pe pe-fl63886 / ca-fl 26841
S U
B M
IT
T A L C
O M
P L E T
IO
N : 9
N O
T F O
R C
O N
S T R
U C
T
IO
N
100% submittal - CONSTRUCTION SET 00.00.00
100% submittal - AS-BUILTS 00.00.00
35% submittal
CRC JJC
DESIGN PROFESSIONALPROJECT TEAM
FBC2014
5TH EDITION
S H
E E T S
A V E D
A T E
:4
P
M
:5
:2 P
M S
H E E T P
L O
T D
A T E
673-14-604
ROOF DRAIN RETROFIT
SCALE: NTS4
ROOF DRAIN RETROFIT - PREFERRED OPTION UNLESS REMOVAL
OF THE EXISTING DRAINAGE ASSEMBLY IS DEEMED NECESSARY.
EACH DRAIN SHALL BE INSPECTED FOR SUITABILITY OF RETROFIT
INSTALLATION.
PROVIDE DRAIN SIZE PER
SPECIFIC APPLICATION ON
EACH ROOF
EDGE FASCIA ATTACHMENT
SCALE: NTS3
AutoCAD SHX Text
20 GA. GALV. FORMED
AutoCAD SHX Text
RAIL, 12'-0" LENGTHS
AutoCAD SHX Text
NON-CURING
AutoCAD SHX Text
SEALANT
AutoCAD SHX Text
ROOF MEMBRANE
AutoCAD SHX Text PRE-PUNCHED 9/32" x 3/8"
AutoCAD SHX Text
SLOTS, 12" O.C.
AutoCAD SHX Text PRE-PUNCHED 9/32" x 3/8"
AutoCAD SHX Text
SLOTS, 24" O.C.
AutoCAD SHX Text 8"
AutoCAD SHX Text 6 "78"
AutoCAD SHX Text 1 "18"
AutoCAD SHX Text
WOOD NAILER
AutoCAD SHX Text
FASCIA COVER
AutoCAD SHX Text
(12'-0" LENGTHS)
AutoCAD SHX Text
ONE EDGE FASCIA - 8"
AutoCAD SHX Text
6" STAINLESS
AutoCAD SHX Text
STEEL SPRING @ 4'-0" O.C.
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Print Date
AutoCAD SHX Text File Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GenFlex Water Stop
See Note #3
Vertical substrate must be clean and suitable for flashing.
Alternate flashing substrates may be installed over existing vertical substrates if conditions prevent the substrate from meeting GenFlex flashing requirements.
Examples of alternate substrates are: 1/2" (13 mm) minimum thickness exterior grade plywood and 22 ga (0.76 mm) G-90 galvanized steel. Securement must be achieved with corrosion resistant fasteners and be sufficient to resist 125 lb
(556.03 N) of pullout pressure per square foot.
For compression details that utilize GenFlex Water Stop, the substrate must be bared in the compression area down to either a masonry or metal surface.
1.
2.
3.
As with any surface-mounted termination, the vertical substrate above the seal must be waterproofed and maintained by the property owner in order to ensure performance of the detail.
GenFlex EZ TPO
Bonding Adhesive
GenFlex EZ TPO Membrane
See Notes #1 & #2
GenFlex Bar Anchor with Approved Fasteners
12" o.c. (304.80 mm)
Existing Metal Counter-Flashing
3" Min. (76 mm)
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
10/20 Years
EZ-1.02
10-26-2015
All
Termination Bar with Counter-Flashing
GenFlex Water Stop
See Note #3
Vertical substrate must be clean and suitable for flashing.
Alternate flashing substrates may be installed over existing vertical substrates if conditions prevent the substrate from meeting GenFlex flashing requirements.
Examples of alternate substrates are: 1/2" (13 mm) minimum thickness exterior grade plywood or 22 ga (0.76 mm) G-90 galvanized steel. Securement must be achieved with corrosion resistant fasteners and be sufficient to resist 125 lb (556 N) of pullout pressure per square foot.
For compression details that utilize GenFlex Water Stop, the substrate must be bared in the compression area down to either a masonry or metal surface.
1.
2.
3.
GenFlex EZ TPO
Bonding Adhesive
GenFlex EZ TPO Membrane
See Notes #1 & #2
Existing Metal Counter-Flashing
GenFast Fasteners Spaced 12" o.c. (305 mm) on New Construction
GenFast Fasteners Spaced 8" o.c. (203 mm) on Reroofs & Recovers with Neoprene Washers or Sealed with an Appropriate Caulk
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-1.03
10-26-2015
All
Common Counter-Flashing & Membrane Securement
Membrane securement at 12" (305 mm) out from penetration and 12" o.c. (305 mm) required for Mechanically Attached Roof Systems. This can be accomplished with seam plates and fasteners overlaid with either TPO Cover Tape, a target patch of
TPO field membrane for the boot flange to be welded to, or with 6" (152 mm) TPO
Reinforced Flashing. When installation of the pipe boot would overlap a field seam, install a minimum 24" x 24" (610 mm x 610 mm) target patch centered on the penetration before installing the pipe boot. Membrane securement may also be installed close to the penetration and flashed with the pipe boot as shown here.
GenFlex EZ TPO
Membrane
GenFlex
ISO
Approved
Substrate
GenFlex Pre-Molded Pipe Boot -
Hot Air Weld standard boot flange to deck membrane, or apply the Peel & stick boot flange to the primed membrane, and roll into place with a
2" (51 mm) silicone roller.
Stainless Steel
Clamping Ring
GenFlex Water Stop Under
Pipe Boot Lip
GenFlex Termination Caulk
Pipe
Water Stop
Termination
Caulk
Stainless Steel
Clamp
Pre-Molded
Pipe Boot
Cut View
For MAS Systems, Read Note.
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-7.01
10-27-2015
All
Pre-Fabricated Pipe Boot
GenFlex EZ TPO
Membrane
GenFlex
ISO
Approved
Substrate
GenFlex Water Stop
(Use one tube per drain)
1/2" Min. (13 mm) of
Membrane inside
Compression Ring
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-8.01
10-27-2015
All
Roof Drain
GenFlex Edge Sealant Applied to
Splice Washed Edge of TPO
Reinforced Flashing. Caulk all Edges.
GenFlex Reinforced
TPO Flashing Hot Air
Welded to Pourable
Sealer Pocket Flange
Tight to Angle Change
GenFlex EZ TPO
Coated Metal
Field Fabricated Corner of
Unsupported TPO Flashing
Lap in Pourable Sealer Pocket to be
Pop Riveted to Prevent Movement that Could Affect Overlay Seal
GenFlex
Pourable Sealer
Mounded to
Shed Water
Refer to SMACNA for Pourable Sealer
Pocket Fabrication Directions - Must be sized to provide 1" (25. mm) of clearance between penetrations and between penetrations and sides of pocket. Job site conditions may require that the pocket be assembled onsite due to fixed, continuous penetrations.
1 1/2" Min. (38 mm) Hot
Air Weld
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-9.01
10-27-2015
All
Pourable Sealer Pocket Formed with TPO Coated Metal
GenFlex ISO
GenFlex EZ TPO Membrane
GenFlex EZ TPO
Bonding Adhesive
Approved Substrate
Any GenFlex Approved
Base Tie-In
GenFlex Water Stop
Counter-Flashing
HVAC Unit or
Skylight Assembly
Curb Flange Secured to the Structural Deck or Secured to a
Properly Installed
Wood Nailer
Equal in Height to the
Roof Insulation
Fasten Counter-Flashing with
Neoprene Washered Fasteners
6" o.c. (152 mm)
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-3.06
10-26-2015
Fully Adhered, MAS
Existing Curb Flashing
GenFlex EZ TPO Membrane
GenFlex EZ TPO
Bonding Adhesive
GenFlex ISO
Approved Substrate
Any GenFlex
Approved Base
Tie-In
HVAC Unit or
Skylight Assembly
Securement of
Membrane is Optional
Because Unit Will Rest on Membrane
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-3.07
10-26-2015
All Systems
New Curb Flashing
GenFlex ISO
GenFlex EZ TPO Membrane
GenFlex EZ TPO
Bonding Adhesive
Approved Substrate
Any GenFlex
Approved Base Tie-In
GenFlex Pre-Molded
Inside Corner
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-4.01
10-26-2015
All Systems
Pre-Molded Inside Corner
GenFlex EZ TPO Membrane
GenFlex EZ TPO
Bonding Adhesive
1 1/2" Min.
(38 mm) Hot
Air Weld
Approved Deck
GenFlex Seam Plate or
Metal Bar Anchor
Approved GenFast
(typical) Fastener
Spaced
Max. 12" o.c.
(305 mm)
Not to Exceed 6" (152
mm) in Length
GenFlex ISO
4" Max. (102 mm) Thickness without a Wood Nailer
Approved Substrate
NOTE: Deck membrane must extend minimum
1/2" (13 mm) above Bar Anchor or Seam Plate.
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-2.01
10-26-2015
All
Vertical Wall Base Flashing
GenFlex EZ TPO Coated
Metal Scupper Fabricated to
SMACNA Recommendations and Secured to the Substrate
6" o.c. (152 mm)
GenFlex EZ TPO Membrane
GenFlex EZ TPO
Non-reinforced
Flashing
T u r n
F l a s h i g i t o
S c u p p e
S l e e v e
½ m
GenFlex ISO
Wood Nailer Equal in Height to Insulation Thickness
Approved Substrate
Any GenFlex
Approved Base
Flashing
1 1/2" Min. (38 mm) Hot
Air Weld
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-10.01
10-27-2015
All
Scupper Fabricated with TPO Coated Metal
Flash wall in accordance with GenFlex specification and cut wall flashing at scupper opening. Mount scupper with 3" (76 mm) wide metal mounting flange and continuous, rounded corners onto the wall substrate with a bead of GenFlex Water Stop between the metal flange and the wall flashing membrane (be sure the metal joint in the sleeve is at the top of the scupper assembly).
Secure per SMACNA recommendations and as required to hold Water Stop under constant compression. Flash the scupper assembly with a large enough piece of TPO unreinforced flashing to cover the entire assembly and extend 3" (76 mm) beyond the flange in all directions. Cut the TPO unreinforced flashing at the scupper opening, and turn flashing 1 1/2" to 2" (38 mm to
51 mm) into the scupper outlet tube while welding the TPO unreinforced flashing to the interior of the TPO coated metal sleeve.
GenFlex Edge Sealant is required on all membrane cut edges with exposed scrim.
GenFlex ISO
Approved Substrate
Any GenFlex approved
Base Flashing
Unreinforced TPO Flashing or Peel & Stick Flashing from a TPO Flashing Kit*
T u
T
P
O u r e i n f o r c e d
F l a s h i g t o
S c u p p e r
S l e e v e
M
½
GenFlex Water Stop
Behind Metal Flange
See Note #3
Bonding
Adhesive
See Note #1
All parapet walls must be suitable for flashing, i.e. clean, tight, smooth, no cracks, acceptable substrate, etc.
1.
2.
3.
* Peel & Stick Flashing from a TPO Flashing Kit is black in color and will require an application of coating from the TPO Coating Kit in order to match the roof color.
TPO Coated Metal
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-10.04
10-27-2015
All
Overflow Scupper
GenFlex EZ TPO Membrane
Approved Fastener
Each 8" o.c. (203 mm) with Approved Caulk or Neoprene Washer
Wood Nailer
Masonry
Substrate
GenFlex
Water Stop
GenFlex ISO
GenFlex
Termination Bar
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-14.08
10-27-2015
TPO Systems (Not for use on Ballasted Roofs)
Roof Edge Termination
MANUFACTURER
ROOF DETAILS
TPO MEMBRANE
20-Jul-17 A500
ROOF MANUFACTURER DETAILS
SCALE: NTS1
ADDED AS-BUILT
09.21.16 date sealed: 20-Jul-17
JAMES A. HALEY
VA HOSPITAL
13000 BRUCE B DOWNS BLVD
TAMPA, FL 33612
65% submittal
95% submittal abrams group construction, llc 3645 Highway 90 Pace, FL. 32571
Phone: (850) 994-7980 Fax: (850) 994-7981
REPLACE ROOF SYSTEMS
CAMPUS WIDE
N/A
05.17.17
100% submittal - REVIEW
(T) 813. 232 . 8448 (F) 800. 698 . 1945
200 2nd Ave South - #465 - St Petersburg, FL 33701 info@connellyengineering.com www. connellyengineering .com
C O N S U L T I N G E N G I N E E R S connelly groupC G 07.21.17
00.00.00 christopher r. connelly, pe pe-fl63886 / ca-fl 26841
S U
B M
IT
T A L C
O M
P L E T
IO
N : 9
N O
T F O
R C
O N
S T R
U C
T
IO
N
100% submittal - CONSTRUCTION SET 00.00.00
100% submittal - AS-BUILTS 00.00.00
35% submittal
CRC JJC
DESIGN PROFESSIONALPROJECT TEAM
FBC2014
5TH EDITION
S H
E E T S
A V E D
A T E
:4
P
M
:5
:3
P M
S H
E E T P
L O
T D
A T E
673-14-604
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Print Date
AutoCAD SHX Text File Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GenFlex ISO
GenFlex EZ TPO
Membrane
Wood Nailer
Approved Substrate
Metalwork by others, fabricated and installed to SMACNA standards
(minimum fastening requirements shown below), must be installed in conjunction with a continuous metal cleat, securing fascia tightly to face of building in order to prevent or mitigate potential wind damage.
2"
(51 mm)
1 1/2"
(38 mm)
GenFlex Flashing Material
(Cover Tape Set in Primer or
TPO Flashing Welded to
TPO Coated Metal)
R o o f
E d g e
6" Max.
(152 mm)
1"
(25 mm)
1/2"
(13 mm)
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-14.12
10-27-2015
TPO Systems
Gravel Stop/Drip Edge Securement Pattern
When running gas line supports on a Mechanically Attached Roof System, care must be taken to run the supports on the lines of membrane securement in order to prevent movement caused by sheet flutter. The support area may be isolated from the main portion of the roof by installing a row of membrane securement on each side of the supports and then stripping them in with TPO Cover Tape installed to GenFlex specification.
GenFlex EZ TPO
Membrane
Membrane or Walkway
Pad Slip-Sheet Wood Block Support - Secure supported object to blocking to prevent dislodging. If supported load per block exceeds 25 lb (11.34 kg), see
Detail T-3.13.
1/4" Min. (6 mm)
3" Min.
(76.20 mm)
GenFlex ISO
Pipe or Conduit
Approved
Substrate
Clamps & Fasteners
(by Others)
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-16.03
10-27-2015
TPO Systems
Pipe Support
GenFlex EZ TPO Walkway Pad Hot Air
Welded in Place. Weld long sides only. Do not cross field seams. Start and stop walkway pad installation 2" (51 mm) from field seams.
GenFlex EZ TPO Membrane
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-16.04
10-27-2015
TPO Systems
Installation of Weldable Walkway Pad
1.
2.
3.
4.
5.
It is the responsibility of the building owner to ensure code compliance.
GenFlex Roofing Systems assumes no responsibility for attachment of lightning rods or damages to the roof system caused by failure or detachment of lightning rods.
Contact the GenFlex Technical Department for detail on mechanically attached systems.
3" Min.
(76 mm)
Sacrificial Sheet
(45 mil (1 mm)
GenFlex Membrane)
GenFlex Bonding
Adhesive
GenFlex EZ TPO
Membrane
GenFlex EZ
TPO Membrane
Precast Concrete
Paver per
Specifications
Lightning Rod
Base
Approved
Insulation
Approved
Substrate
GenFlex Pourable Sealer
Approved Caulk
Anchor Base through Bead of
Water Stop
When installing a vertically mounted lightning rod, first clean mounting area of membrane with TPO Cleaner, and apply a generous bead of GenFlex Water Stop to back of mounting plate in a pattern that crosses all holes in the plate. Position the plate in mounting location, and secure it to the wall, making certain that the fasteners penetrate the bead of Water Stop. Securement must be adequate to hold the bracket firmly to the substrate. Caulk the perimeter of the mounting plate with GenFlex Termination Caulk, and fill in all exposed holes on mounting plate with Termination Caulk. Install the lightning protection grounding cable as in Detail T-19.02.
Application of lightning protection on Mechanically Attached Systems requires the use of roof pavers to provide a stable surface to which the lightning rods can be mounted. Use minimum 24" x 24" x 2" (610 mm x 610 mm x 51 mm) pavers, weighing no less than 40 lb (18.14 kg) each. The pavers must be laid in the necessary pattern on slip-sheets of TPO membrane that extend 3" (76 mm) beyond paver in all directions. These slip-sheets should be secured to the paver with a dollop of Termination Caulk. Care must be taken to run the pavers along the lines of membrane securement because this type of roof system will produce some amount of sheet flutter when subjected to significant wind loads. Install the lightning protection grounding cable between pavers as in Detail T-19.02.
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-19.01
10-27-2015
TPO Systems
Lightning Rod
2" x 5"
(51 mm x 127 mm)
Coupling Set in
GenFlex Pourable
Pitch Pan Sealer
GenFlex 6" (152 mm) Reinforced EPDM Sacrificial Sheet
Fully Adhered to Membrane or GenFlex Bar Anchor Tape
(installed per specifications).
Approved
Substrate
GenFlex
ISO
Lightning
Rod
GenFlex
Pourable
Sealer
GenFlex Bar
Cover Tape Strip
GenFlex
Primer
24" Max.
(610 mm)
1.
2.
3.
Building codes or changes in direction may require more frequent straps.
It is the responsibility of the building owner to ensure code compliance.
GenFlex Roofing Systems assumes no responsibility for attachment of lightning rods or damages to the roof system caused by their failure or detachment.
GenFlex
Bonding
Adhesive
Lightning
Rod
GenFlex
Termination
Caulk
GenFlex
EZ TPO
Membrane
Base
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-19.02
10-27-2015
TPO Systems
Lightning Rod
4'
(1.2 m)
8'
(2.4 m)
4' (1.2 m)
For use on buildings up to 50' (15.2 m) high. If building height exceeds 50' (15.2 m), contact the GenFlex Technical Department for attachment pattern.
8"
(203 mm)
16"
(406 mm)
Repeat pattern below
Reduced fastening patterns are available for GenFlex
Isocyanurate Insulation. Minimum thickness restrictions apply. Refer to Insulation Securement Pattern for attachment options.
16"
(406 mm)
8"
(203 mm)
16"
(406 mm)
16"
(406 mm)
16"
(406 mm)
16"
(406 mm)
4'
(1.2 m)
4' (1.2 m)
8"
(203 mm)
8"
(203 mm)
16"
(406 mm)
16"
(406 mm)
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
N/A
EZ-S-41.05
10-27-2015
Fully Adhered
Insulation Securement
4'
(1.2 m)
8'
(2.4 m)
4' (1.2 m)
For use on buildings up to 50' (15.2 m) high. If building height exceeds 50' (15.2 m), contact the GenFlex Technical Department for attachment pattern.
8"
(203 mm)
16"
(406 mm)
Repeat pattern below
Reduced fastening patterns are available for GenFlex
Isocyanurate Insulation. Minimum thickness restrictions apply. Refer to Insulation Securement Pattern for attachment options.
16"
(406 mm)
8"
(203 mm)
16"
(406 mm)
16"
(406 mm)
16"
(406 mm)
16"
(406 mm)
4'
(1.2 m)
4' (1.2 m)
8"
(203 mm)
8"
(203 mm)
16"
(406 mm)
16"
(406 mm)
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
N/A
PS-41.05
6-18-2015
Fully Adhered
Standard Insulation Securement
GenFlex EZ TPO Membrane
GenFlex EZ TPO
Bonding Adhesive
Wood Nailer
GenFlex Bar Cover Tape applied to primed metal and membrane substrate centered on metal flange edge. Roll to ensure 100% contact, and caulk any exposed joints in the metal on the horizontal surface with GenFlex Termination
Caulk.
Metal Drip Edge fabricated and installed to SMACNA recommendations. Fascia portion must be cleated and extend to at least 1/2" ((13 mm) below wood nailer.
Flange securement must be at least 4" o.c. (152 mm) and be in staggered rows separated by no more than the fastener head width.
Metal work by others must be cleaned free of oil and contaminants and primed with
GenFlex Primer prior to application of TPO Cover Tape.
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-1.05
10-26-2015
All
Gravel Stop/Drip Edge Termination - Uncoated Metal
MANUFACTURER
ROOF DETAILS
20-Jul-17 A501
ROOF MANUFACTURER DETAILS
SCALE: NTS1
ADDED AS-BUILT
09.21.16 date sealed: 20-Jul-17
JAMES A. HALEY
VA HOSPITAL
13000 BRUCE B DOWNS BLVD
TAMPA, FL 33612
65% submittal
95% submittal abrams group construction, llc 3645 Highway 90 Pace, FL. 32571
Phone: (850) 994-7980 Fax: (850) 994-7981
REPLACE ROOF SYSTEMS
CAMPUS WIDE
N/A
05.17.17
100% submittal - REVIEW
(T) 813. 232 . 8448 (F) 800. 698 . 1945
200 2nd Ave South - #465 - St Petersburg, FL 33701 info@connellyengineering.com www. connellyengineering .com
C O N S U L T I N G E N G I N E E R S connelly groupC G 07.21.17
00.00.00 christopher r. connelly, pe pe-fl63886 / ca-fl 26841
S U
B M
IT
T A L C
O M
P L E T
IO
N : 9
N O
T F O
R C
O N
S T R
U C
T
IO
N
100% submittal - CONSTRUCTION SET 00.00.00
100% submittal - AS-BUILTS 00.00.00
35% submittal
CRC JJC
DESIGN PROFESSIONALPROJECT TEAM
FBC2014
5TH EDITION
S H
E E T S
A V E D
A T E
:4
P
M
:5
:3
P M
S H
E E T P
L O
T D
A T E
673-14-604
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Print Date
AutoCAD SHX Text File Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-S-3.01
10-27-2015
TPO Systems
Peel & Stick Wall Flashing
GenFlex Clear Primer
GenFlex Peel & Stick
TPO Membrane
GenFlex Standard or EZ Peel & Stick TPO
Membrane
Any GenFlex Approved
Base Securement Detail
Any GenFlex Vertical
Termination Detail
GenFlex ISO
GenFlex Approved Deck
Approved Substrate
Refer to
Seaming
Options
For use with Peel & Stick TPO (HW)
HOT AIR WELDED SEAMS
1 1/2" Min. (38.10 mm)
Hot Air Weld
For use with Peel & Stick TPO (HW)
3" WHITE SEAM TAPE SEAMS
Peel & Stick TPO (HW)
3" White Seam Tape
GenFlex Clear Primer
TPO Edge Caulk
SEAMING OPTIONS
Refer to detail PS-6.01 for seaming options.
10 Year Warranty
20 Year Warranty
Approved Substrate
GenFlex EZ Peel & Stick TPO Membrane
GenFlex Clear Primer
GenFlex Metal Bar Anchor or Seam Plates secured with Approved
GenFlex Fasteners spaced Max. 12" o.c. (305 mm). Fasteners not to exceed 6" (152 mm) in length. Fasteners may also be anchored vertically, tightly into the angle change.
Approved Deck
GenFlex Insulation 4" Max. (102 mm) Thickness without a Wood Nailer
GenFlex 6" (152 mm) Peel & Stick RPS bonded to the underside of the Peel & Stick
TPO deck membrane and rolled to ensure
100% contact
Leave 1" (25 mm) behind Bar Anchor or Seam Plate
GenFlex Clear Primer
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-S-3.02
10-26-2015
Fully Adhered
Peel & Stick RPS
TM
Position insulation to enable securement into the top flutes on steel decks to ensure positive attachment and to reduce fastener movement. Insulation should be installed with board edges resting on the top flutes.
GenFlex ISO
GenFlex Peel & Stick TPO
Membrane
Approved Substrate
Refer to detail # PS-6.01
For the Appropriate
Seaming Detail
SLOPE
Refer to detail PS-6.01 for seaming options.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
PS-41.02
5-20-2015
Self Adhered
Insulation Placement and Cross Section
Thermal Spacer
GenFlex TPO Membrane
Overlay Material
(Insulation or Cover Board)
Existing Metal Roof Panels
Structural Purlin
1.
2.
3.
Filler Insulation
Prime the backside of the TPO membrane with Clear Primer prior to attaching to the RMA strip.
GenFast Purlin Fasteners must penetrate the structural purlin a minimum of 1.5"
(38 mm) total.
If structural purlins are spaced every 5' (1.5 m), fastener spacing is not to exceed
12" (305 mm) o.c. If structural purlins are spaced every 6' (1.8 m), fastener spacing is not to exceed 6" (152 mm) o.c.
GenFast 2 3/8" (60 mm) Seam Plate or Bar Anchor
GenFast Purlin Fastener - See Note 3
GenFlex Clear Primer -
See Note 1
GenFlex TPO Peel & Stick RMA
1.5" (38 mm) Min.
See Note 2
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
15 Years
EZ-S-42.13
6-18-2015
Metal Building Recover
Peel & Stick TPO RMA Attachment
B
A
Peel & Stick EZ TPO (HW)
Peel & Stick EZ TPO (HW)
GenFlex EZ TPO Edge Caulk
(Required on all seam tape seams)
GenFlex Clear Primer
GenFlex 3" White Seam Tape
Refer to section 3.06 B1 for Peel & Stick TPO (HW) hot air weld seaming instructions.
1 1/2" min. (38.10 mm) Hot Air Weld
Peel & Stick EZ TPO (HW) & 3" White Seam Tape
Peel & Stick EZ TPO (HW) & Hot Air Welded Seams
NOTE: This detail replaces PS-6.01 & PS-6.02.
Position the upper membrane panel as required to achieve a 3" lap over the adjacent panel and mark the position of the upper membrane panel edge plus
1/4" (3 mm) with a crayon on the lower panel, prime the seaming areas of both panels and allow the primer to flash off, then position and apply the 3" White
Seam Tape along the marks as required to achieve 1/8" to 1/4" (3-6 mm) of exposure once the seam is assembled.
Refer to section 3.06 B2 for Peel & Stick TPO (HW) seam tape seaming instructions.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
10/20 Years
EZ-S-6.01
10-26-2015
Self Adhered
Seaming Methods for Peel & Stick EZ TPO
10 Year Warranty
20 Year Warranty
TM
GenFlex EZ Peel & Stick
Membrane Flashing Bonded to a
GenFlex Approved Substrate or
Standard TPO Membrane
Bonded to the Substrate with
TPO Bonding Adhesive in
Accordance with GenFlex
Specification
GenFlex White EZ TPO Edge Caulk - Apply around corner flashing and on all "HW" seams assembled with 3" White Seam Tape and "SA" seams.
GenFlex
Clear Primer
After inspection, coat the Outside Corner Flashing with GenFlex Ace Coating in order to match the installed system color.
TPO Flashing Kit
Material
Refer to detail PS-6.01 for seaming options.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-S-5.02
10-26-2015
Self Adhered
Peel & Stick Inside Corner
TM
Angle Change
Locate and cut deck flange even with corner.
Clear Primer
Turn membrane around corner without distorting the panel.
Clear Primer
Cut the bottom of the flap at a 45 degree angle
Clear Primer
Repeat Step 4 as required to wrap entire curb.
5.
6. Once the Peel & Stick membrane has been wrapped around the primed curb, prime the top of the membrane panel end in preparation for the flap to be wrapped around the corner and mated to the membrane surface. In keeping with good roofing practice, the flap should be oriented on the down-slope side of the penetration.
After the primer applied in Step 6 flashes-off, wrap the membrane flap around the corner and roll into place.
7.
Fold the excess flashing onto the top of the penetration, neatly creasing the corners and fasten.
8.
Apply TPO Edge Caulk to the
Peel & Stick TPO edges and around the corner flashing molded from the TPO Flashing
Kit Material.
10.
1.
2.
3.
4.
Install base securement at the angle change.
Prime vertical substrate with GenFlex Clear
Primer at the rate of 200 ft /gal (4.91 m /L).
Position Peel & Stick membrane (cut to fit the height of the curb by the diameter of the curb plus 6" (152 mm) into the angle change and lined up with a down-slope corner of the curb.
Locate the corner of the curb by feeling through the Peel & Stick membrane, and cut the deck flange portion of the membrane in order to wrap the Peel & Stick membrane around the corner.
After seaming the flashing flange to the deck sheet, prime the corner with
Clear Primer and apply a corner flashing molded from the TPO
Flashing Kit Material. Refer to detail
PS-6.01 for the appropriate seaming method.
9.
Refer to detail PS-6.01 for seaming options.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-S-3.04
10-26-2015
All
Peel & Stick Curb Flashing
2 2
TM
Approved Substrate
White TPO
Edge Caulk
3"
(76 mm)
6"
(152 mm)
GenFlex EZ
TPO Flashing
Clear Primer
TPO Flashing
Kit Material
All vertical substrates require priming with GenFlex Clear Primer.
Porous, or highly absorbant substrates may require a second primer application after the initial application seals the substrate.
Peel & Stick EZ TPO (HW) may be seamed by hot air welding the selvedge edge of the flashing to the deck sheet (min. 1.5" wide welds) or with 3" White Seam Tape and clear primer.
Peel & Stick EZ TPO (SA) must be seamed in accordance with
"SA" seaming instructions - refer to 3.06.B3 in the Peel & Stick EZ
TPO specification.
The strip-in flashing must extend 3" (76.20 mm) beyond the seam edge onto the deck sheet and vertically to a point 3" (76 mm) above the angle change.
"SA" seams and "HW" seam tape seams require a continuous high profile bead of edge caulk the same day the seams are assembled.
Standard TPO membrane & Bonding Adhesive may be used as parapet flashing with no strip-in of vertical joints required when the seams are assembled with hot air welds.
1.
2.
3.
4.
5.
6.
Refer to detail PS-6.01 for seaming options.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
20 Years
EZ-S-3.03
10-26-2015
Self Adhered
Peel & Stick TPO Flashing Vertical Joints
TM
4'
(1.2 m)
8'
(2.4 m)
4' (1.2 m)
For use on buildings up to 50' (15.2 m) high. If building height exceeds 50' (15.2 m), contact the GenFlex Technical Department for attachment pattern.
8"
(203 mm)
16"
(406 mm)
Repeat pattern below
Reduced fastening patterns are available for GenFlex
Isocyanurate Insulation. Minimum thickness restrictions apply. Refer to Insulation Securement Pattern for attachment options.
16"
(406 mm)
8"
(203 mm)
16"
(406 mm)
16"
(406 mm)
16"
(406 mm)
16"
(406 mm)
4'
(1.2 m)
4' (1.2 m)
8"
(203 mm)
8"
(203 mm)
16"
(406 mm)
16"
(406 mm)
1.
ISSUE / REVISION
DATE:
NOT TO SCALE
ACCEPTABLE SYSTEMS:
DETAIL NO.
MAXIMUM WARRANTY:
EZ TPO Systems
N/A
PS-41.05
6-18-2015
Fully Adhered
Standard Insulation Securement
MANUFACTURER
ROOF DETAILS
PEEL-N-STICK DETAILS
20-Jul-17 A502
ROOF MANUFACTURER DETAILS
SCALE: NTS1
ADDED AS-BUILT
09.21.16 date sealed: 20-Jul-17
JAMES A. HALEY
VA HOSPITAL
13000 BRUCE B DOWNS BLVD
TAMPA, FL 33612
65% submittal
95% submittal abrams group construction, llc 3645 Highway 90 Pace, FL. 32571
Phone: (850) 994-7980 Fax: (850) 994-7981
REPLACE ROOF SYSTEMS
CAMPUS WIDE
N/A
05.17.17
100% submittal - REVIEW
(T) 813. 232 . 8448 (F) 800. 698 . 1945
200 2nd Ave South - #465 - St Petersburg, FL 33701 info@connellyengineering.com www. connellyengineering .com
C O N S U L T I N G E N G I N E E R S connelly groupC G 07.21.17
00.00.00 christopher r. connelly, pe pe-fl63886 / ca-fl 26841
S U
B M
IT
T A L C
O M
P L E T
IO
N : 9
N O
T F O
R C
O N
S T R
U C
T
IO
N
100% submittal - CONSTRUCTION SET 00.00.00
100% submittal - AS-BUILTS 00.00.00
35% submittal
CRC JJC
DESIGN PROFESSIONALPROJECT TEAM
FBC2014
5TH EDITION
S H
E E T S
A V E D
A T E
:4
P
M
:5
:4
P M
S H
E E T P
L O
T D
A T E
673-14-604
SPECIAL DETAILS FOR PEEL-N-STICK TPO
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text Project Title
AutoCAD SHX Text Print Date
AutoCAD SHX Text File Location
AutoCAD SHX Text Checked
AutoCAD SHX Text Building Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text Drawn
AutoCAD SHX Text Revisions:
AutoCAD SHX Text Date
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Wood Framing Notes Continued
Minimum Shall be Provided at The End of All Walls And at Each Side of All Openings, Solid Blocking
Studs at Mid-Height of All Stud Walls Over 8 ft in Height.
Plywood Edge Clips Centered Between Joist/Trusses at Unblocked Roof Sheathing Edges. All Floor
Unless Noted Otherwise on The Plans, APA Rated Roof And Floor Sheathing Shall be Placed With
Strength Axis Perpendicular to Supports And Nailed With 8d Nails at 6"o.c. to Framed Panel Edges
Blocking. Allow 1/8" Spacing at All Panel Edges And Ends of All Roof And Floor Sheathing. Toenail
And Over Stud Walls as Shown on Plans And at 12"o.c. to Intermediate Supports. Provide Approved
Simpson Metal Joist Hangers in Accordance with Schedule. Nail All Multi-Joist Beams Together With
Toenail Joist to Supports With Two 16d Nails. Attach Timber Joist to Flush Headers or Beams With
Sheathing Edges Shall Have Approved Tongue-And-Groove Joints or Shall be Supported With Solid
Blocking to Supports With 2-16d at Each End or at 12"o.c. Unless Otherwise Noted.
Otherwise. Provide Bridging a 8 ft o.c. And Solid Blocking at All Bearing Points.
Members of Built-Up Posts Shall be Nailed to Each Other With 16d at 12"o.c. Staggered.
Floor And Roof Framing: Provide Double Joist Under And Around All Openings in Floors or Roofs Unless Noted
With 8d at 4"o.c., And to All Intermediate Studs And Blocking With 8d at 8"o.c. Allow 1/8" Spacing at All
Sheathing on Exterior Surfaces Nailed at All Panel Edges (Block Unsupported Edges), Top And Bottom Plates
With Nails at 7"o.c. Use 5d Cooler Nails For 1/2" GWB And 6D Cooler Nails For 5/8" GWB. Provide 1/2" Plywood
Refer to The Plans And Shear Wall Schedule For Required Sheathing And Nailing. When Not Otherwise Noted, 12"o.c. Staggered or Bolted to Concrete With 1/4"X 3-1/4" Tap Cons at 16"o.c. Unless Otherwise Noted.
Provide Gypsum Wallboard on Interior Surfaces Nailed to Al Studs, Top And Bottom Plates, And Blocking
All Stud Walls Shall Have Their Lower Wood Plates Attached to Wood Framing Below With 16d Nails at
For Wood Columns Shall be Provided Through Floors to Supports Below. Provide Solid Blocking Between
Wall Framing: All Studs Walls Shown And Not Otherwise Noted Shall be 2X4 Studs at 16"o.c. Two Studs be Compatible in Size With Members Provided.
With The Length of The Member;
be Compatible in Size With Members Provided.
Fb= 3,100 psi, E=2,100,000 psi, Fv=290 psi (For 2.1E Members)
Fb= 2,900 psi, E=2,000,000 psi, Fv=290 psi (For 2.0E Members)
And Nuts of All Bolts And Lag Screws Bearing on Wood.
To Flush Beams With Joist Hangers, Unless Otherwise Noted.
WOOD
E= 1,600,000 psi
Fb= 1,200psi
Fc= 975 psi
Fv= 150psi
11% Maximum Moisture Content
Al…