This document is a Mechanical Schedules drawing (M-601) for the Hunter Holmes McGuire VA Medical Center's Improve Patient Privacy 4B project. The detailed mechanical drawing provides specifications for various HVAC equipment, including a ductless split condensing unit (4B-CU-1) with 12,000 BTU/h cooling capacity for the OIT Closet, a corresponding indoor wall-mounted unit (4B-SS-1), and a HEPA air filter (4B-EF-HEPA-1) for the isolation room. The drawing includes electrical specifications, mounting instructions, and notes for installation requirements, such as coordinating with roofing contractors and using standard wall thermostats and condensate pumps. The project is part of a Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside contract for improving patient privacy at the Richmond VA Medical Center, with the mechanical design prepared by Apogee Consulting Group.
View the file
Other files for this federal contract opportunity
Show all 38
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project NumberCONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date# 06/12/2019
IMPROVE PATIENT
PRIVACY 4B
652-14-106
HUNTER HOLMES MCGUIRE VAMC
1201 BROAD ROCK BLVD
RICHMOND, VA 23249
18-083
BID DOCUMENTS
FULLY SPRINKLERED
2/
/2
:2 7:
A
M
M-601
MRASPG
MECHANICAL SCHEDULES
16 16
DUCTLESS SPLIT CONDENSING UNIT SCHEDULE
MARK LOCATION
AREA AND/OR ROOM
SERVED
COOLING CAPACITY
RANGE (BTU) COMPRESSOR TYPE POWER MCA MOCP REMARKS
4B-CU-1 4B-ROOF OIT CLOSET 12,000 Btu/h DC INVERTER-DRIVEN TWIN ROTARY 208/230, 1, 60 14 30 1, 2, 3
DUCTLESS SPLIT INDOOR UNIT SCHEDULE
TAG LOCATION
AREA AND/OR ROOM
SERVED TYPE AIRFLOW CAPACITY EAT DB ELECTRICAL DATA REMARKS
4B-SS-1 OIT OIT CLOSET WALL-MOUNTED 300 12,000.0 Btu/h 75 °F 208/230, 1, 60 1
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE WITH STANDARD WALL THERMOSTAT AND FILTER ALONG WITH CONDENSATE PUMP.
3. INDOOR UNIT POWERED THROUGH CONDENSING UNIT.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. INDOOR UNIT POWERED THROUGH CONDENSING UNIT.
3. PROVIDE WITH CONDENSING UNIT PAD FOR MOUNTING ON ROOF. COORIDNATE WITH ROOFING CONTRACTOR TO MEET ROOF WARRANTY REQUIREMENTS.
AIR FILTER SCHEDULE
MARK LOCATION
AREA AND/OR BLDG
SERVED SYSTEM AND/OR SERVICE MERV RATING MAX AIRFLOW
APD
HOUSING TYPE # - CARTRIDGES
CARTRIDGES
REMARKSINITIAL CHANGEOVER SIZE ARRANGEMENT
4B-EF-HEPA-1 4B-115A 4B-115A ISOLATION ROOM 4B-EF-1 HEPA 525 CFM 1.00 in-wg 2.25 in-wg BAG-IN / BAG-OUT 1 27" x 30" x 24" 1 WIDE BY 1 HIGH 1
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
NOTES:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. VENTURI TYPE PRESSURE INDEPENDENT AIR VALVE PROVIDE WITH DDC CONTROLLER WITH BIASING TO OFFSET DOOR OPENINGS AND SETPOINT ADJUSTMENT VIA BAS.
3. PROVIDE WITH 120V-24V TRANSFORMER.
ADDENDUM02 2/28/25
F
R P
O
SS
E
OI LNA
GNE
IN
E R
E
N
SILAS PERRY GEORGE
M O
C O
M
OHL
EA T
W
I N
A
V F
I
G I
R
Lic. No. 0402056110
Docusign Envelope ID: 29D5A0F9-09BE-425A-A5D7-BA060626AFF0
3/3/2025
| Sheets and Views |
| M-601 |
| 2025-03-03T14:56:49-0800 | |
| Digitally verifiable PDF exported from www.docusign.com |