This document contains specifications for signage for a Department of Veterans Affairs medical center renovation project. The specifications cover interior and exterior signage requirements, including room identification signs, directional signs, code-required signs, and temporary signs. Sign materials, types, fabrication, and installation requirements are defined. The related federal contract opportunity notices a $10-20 million pre-solicitation for construction services to renovate areas 3A and 3B of Building 500 at the VA medical center in Martinsburg, West Virginia, set aside entirely for Service-Disabled Veteran Owned Small Businesses. A pre-bid site visit will be held on June 9th and questions are due by June 17th, with solicitation documents available starting June 3rd. The bid opening will occur on July 14th.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bldg. 500 - Renovate 3B 01 - 06 Project No. 613-19-101
10 14 00 - 1
Submission Bid Documents July 16, 2020
SECTION 10 14 00
SIGNAGE
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies interior signage for room numbers, directional signs exterior signage, code required signs and temporary signs.
B. This section specifies exterior signage.
1.2 RELATED WORK
A. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE
CONSTRUCTION REQUIREMENTS.
B. Electrical Work: Division 26, ELECTRICAL.
C. Lighted EXIT signs for egress purposes are specified under Division 26, ELECTRICAL.
D. Color and Finish of Interior Signs: Section 09 06 00, SCHEDULE FOR
FINISHES.
1.3 QUALITY ASSURANCE
A. Manufacturer’s Qualifications: Provide signage that is the product of one manufacturer, who has provided signage as specified for a minimum of three (3) years. Submit manufacturer’s qualifications.
B. Installer’s Qualifications: Minimum three (3) years’ experience in the installation of signage of the type as specified in this Section. Submit installer’s qualifications.
1.4 SUBMITTALS
A. Submit in accordance with Section 01 33 00, SHOP DRAWINGS, PRODUCT DATA
AND SAMPLES.
B. Interior Sign Samples: Sign panels and frames, with letters and symbols, for each sign type.
1. Sign Panel, 203 x 254 mm (8 x 10 inches), with letters.
2. Color samples of each color, 152 x 152 mm (6 x 6 inches. Show anticipated range of color and texture.
3. Sample of typeface, arrow and symbols in a typical full size layout.
C. Manufacturer's Literature:
1. Showing the methods and procedures proposed for the anchorage of the signage system to each surface type.
2. Manufacturer’s printed specifications and maintenance instructions.
D. Sign Location Plan, showing location, type and total number of signs required.
10 14 00 - 2
E. Shop Drawings: Scaled for manufacture and fabrication of sign types.
Identify materials, show joints, welds, anchorage, accessory items, mounting and finishes.
F. Full size layout patterns for dimensional letters.
G. Manufacturer’s qualifications.
H. Installer’s qualifications.
1.5 DELIVERY AND STORAGE
A. Deliver materials to job in manufacturer's original sealed containers with brand name marked thereon. Protect materials from damage.
B. Package to prevent damage or deterioration during shipment, handling, storage and installation. Maintain protective covering in place and in good repair until removal is necessary.
C. Deliver signs only when the site and mounting services are ready for installation work to proceed.
D. Store products in dry condition inside enclosed facilities.
1.6 WARRANTY
A. Construction Warranty: Comply in accordance with contract.
1.7 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. American Architectural Manufacturers Association (AAMA):
611-14..................Anodized Architectural Aluminum
2603-13.................Voluntary Specification, Performance Requirements and Test Procedures for Pigmented Organic
Coatings on Aluminum Extrusions and Panels
C. American National Standards Institute (ANSI):
A117.1-09...............Accessible and Usable Buildings and Facilities
D. ASTM International (ASTM):
A36/A36M-14.............Carbon Structural Steel
A240/A240M-15...........Chromium and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure Vessels and for General Applications
A666-10.................Annealed or Cold-Worked Austenitic Stainless
Steel Sheet, Strip, Plate and Flat Bar
A1011/A1011M-14.........Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-
10 14 00 - 3
Strength Low-Alloy with Improved Formability, and
Ultra-High Strength
B36/B36M-13.............Brass Plate, Sheet, Strip, and Rolled Bar
B152/B152M-13...........Copper Sheet, Strip, Plate, and Rolled Bar
B209-14.................Aluminum and Aluminum-Alloy Sheet and Plate
B209M-14................Aluminum and Aluminum-Alloy Sheet and Plate
(Metric)
B221-14.................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes
B221M-13................Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes (Metric)
C1036-11(R2012).........Flat Glass
C1048-12................Heat-Treated Flat Glass-Kind HS, Kind FT Coated and Uncoated Glass
C1349-10................Architectural Flat Glass Clad Polycarbonate
D1003-13................Test Method for Haze and Luminous Transmittance of Transparent Plastics
D4802-10................Poly(Methyl Methacrylate) Acrylic Plastic Sheet
E. Code of Federal Regulation (CFR):
40 CFR 59...............Determination of Volatile Matter Content, Water
Content, Density Volume Solids, and Weight Solids of Surface Coating
F. Federal Specifications (Fed Spec):
MIL-PRF-8184F...........Plastic Sheet, Acrylic, Modified.
MIL-P-46144C............Plastic Sheet, Polycarbonate
G. National Fire Protection Association (NFPA):
70-14...................National Electrical Code
PART 2 - PRODUCTS
2.1 SIGNAGE GENERAL
A. Provide signs of type, size and design shown on the construction documents.
B. Provide signs complete with lettering, framing and related components for a complete installation.
C. Provide graphics items as completed units produced by a single manufacturer, including necessary mounting accessories, fittings and fastenings.
10 14 00 - 4
D. Do not scale construction documents for dimensions. Verify dimensions and coordinate with field conditions. Notify Contracting Officer
Representative (COR) of discrepancies or changes needed to satisfy the requirements of the construction documents.
2.2 INTERIOR SIGN MATERIALS
A. Aluminum:
1. Sheet and Plate: ASTM B209M (B209).
2. Extrusions and Tubing: ASTM B221M (B221).
B. Cast Acrylic Sheet: MIL-PRF-8184F; Type II, class 1, Water white non-glare optically clear. Matt finish water white clear acrylic shall not be acceptable.
C. Polycarbonate: MIL-P-46144C; Type I, class 1.
D. Vinyl: Premium grade 0.1 mm (0.004 inch) thick machine cut, having a pressure sensitive adhesive and integral colors.
E. Adhesives:
1. Adhesives for Field Application: Mildew-resistant, nonstaining adhesive for use with specific type of panels, sheets, or assemblies;
and for substrate application; as recommended in writing by signage manufacturer.
2. Adhesives to have VOC content of 50 g/L or less when calculated according to 40 CFR 59, (EPA Method 24).
F. Typography: Comply with VA Signage Design Guide.
1. Type Style: Helvetica Medium and Helvetica Medium Condensed. Initial caps or all caps, as indicated in drawings.
2. Arrow: Comply with graphic standards in construction documents.
3. Letter spacing: Comply with graphic standards in construction documents.
4. Letter spacing: Comply with graphic standards in construction documents.
5. Provide text, arrows, and symbols in size, colors, typefaces and letter spacing shown in construction documents. Text shall be a true, clean, accurate reproduction of typeface(s). Text shown in construction documents is for layout purposes only; final text for signs is listed in drawings.
2.3 INTERIOR SIGN TYPES
A. Conform to the VA Signage Design Guide.
1. Equal approved to the existing VA Martinsburg Medical Center VA
Bldg. 500 – Renovate 3A 10-01-15 Project No. 613-19-100
10 14 00 - 5 Submission 95% May 29, 2020
Signage Standard
B. Tactile Sign:
1. Tactile sign made from a material that provides for letters, numbers and Braille to be integral with sign. Photopolymer etched metal, sandblasted phenolic or embossed material. Do not apply letters, numbers and Braille with adhesive.
2. Numbers, letters and Braille to be raised 0.8 mm (1/32 inches) from the background surface. The draft of the letters, numbers and
Braille to be tapered, vertical and clean.
3. Braille Dots: Conform with ANSI A117.1 for Braille position and layout; (a) Dot base diameter: 1.5 mm (.059 inches) (b) Inter-dot spacing: 2.3 mm (.090 inches) (c) Horizontal separation between cells: 6.0 mm (.241 inches) (d) Vertical separation between cells:
10.0 mm (.395 inches)
4. Paint assembly specified color. After painting, apply white or other specified color to surface of the numbers and letters. Apply protective clear coat sealant to entire sign.
5. Finish: Eggshell, 11 to 19 degree on a 60 degree glossmeter.
C. Provide cork or felt on bottom or mounting bracket when sign is mounted on counter or desk.
D. For ceiling mounted signs, provide mounting hardware on the sign that allows for sign disconnection, removal, reinstallation, and reconnection.
E. Dimensional Letters:
1. Provide dimensional letters that are mill or laser cut acrylic in size and thickness indicated in construction documents.
2. Provide draft of letters perpendicular to letters face.
3. Fabricate letters with square corners, such as where a letter stem and bar intersect.
4. Paint letters with acrylic polyurethane.
F. Specialty Signs:
1. Small Freestanding Stanchion Sign: 57 mm (2.25 inches) polished aluminum tube mounted to weighted 356 mm (14 inches) diameter polished aluminum base. Sign bracket to hold a 6 mm (.25 inches)copy panel.
2. Freestanding Informational Sign: 57 mm (2.25 inches) polished aluminum tube vertical support mounted to a weighted 356 mm
(14 inches) diameter 57 mm (2.25 inches) polished aluminum base.
10 14 00 - 6 Submission 95% May 29, 2020
Provide rail back mechanically connected to vertical supports with copy panel attached to front and back.
G. Temporary Interior Signs:
1. Fabricated from 50 kg (110 pound) matte finished white paper cut to
101 mm (4 inch) wide by 305 mm (12 inch) long.
a. Punched 3.2 mm (.125 inch) hole with edge of hole spaced 13 mm
(.5 inch) in from edge and centered on 101 mm (4 inch) side.
b. Reinforce hole on both sides with suitable material that prevents tie from pulling through hole.
c. Ties: Steel wire 0.3 mm (0.120 inch) thick attached to tag with twist leaving 152 mm (6 inch) long free ends.
2. Mark architectural room number on sign, with broad felt marker in clearly legible numbers or letters that identify room, corridor or space as shown on construction documents.
3. Install temporary signs to rooms that have a room, corridor or space number. Attach to door frame, door knob or door pull.
a. Doors that do not require signs are: corridor doors in corridor with same number, folding doors or partitions, toilet doors, bathroom doors within and between rooms, closet doors within rooms, communicating doors in partitions between rooms with corridor entrance doors.
b. Replace and missing, damaged or illegible signs.
2.4 FABRICATION
A. Design interior signage components to allow for expansion and contraction for a minimum material temperature range of 38 degrees C
(100 degrees F), without causing buckling, excessive opening of joints or over stressing of adhesives, welds and fasteners.
B. Form work to required shapes and sizes, with true curve lines and angles. Provide necessary rebates, lugs and brackets for assembly of units. Provide concealed fasteners wherever possible.
C. Shop fabricate so far as practicable. Fasten joints flush to conceal reinforcement, or weld joints, where thickness or section permits.
D. Level and assemble contract surfaces of connected members so joints shall be tight and practically unnoticeable, without applying filling compound.
E. Signs: Fabricate with fine, even texture to be flat and sound.
1. Maintain lines and miters sharp, arises unbroken, profiles accurate and ornament true to pattern.
10 14 00 - 7 Submission 95% May 29, 2020
2. Plane surfaces to be smooth, flat and without oil-canning, free of rack and twist.
3. Maximum variation from plane of surface plus or minus 0.3 mm (0.015 inches). Restore texture to filed or cut areas.
F. Finish extruded members to be free from extrusion marks. Fabricate square turns, sharp corners, and true curves.
G. Finish hollow signs with matching material on all faces, tops, bottoms and ends. Mitere edge joints to give appearance of solid material.
H. Do not manufacture signs until final sign message schedule and location review has been completed by the COR and forwarded to contractor.
I. Drill holes for bolts and screws. Mill smooth exposed ends and edges with corners slightly rounded.
J. Form joints exposed to weather to exclude water.
K. Movable Parts, Including Hardware: Cleaned and adjusted to operate as designed without binding or deformation of members. Center doors and covers in opening or frame.
1. Align contact surfaces fit tight and even without forcing or warping components.
L. Pre-assemble items in shop to minimize field splicing and assembly.
Disassemble units only as necessary for shipping and handling limitations. Clearly mark units for re-assembly and coordinated installation.
M. Prime painted surfaces as required. Apply finish coating of paint for complete coverage with no light or thin applications allowing substrate or primer to show.
1. Finish surface smooth, free of scratches, gouges, drips, bubbles, thickness variations, foreign matter and other imperfections.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Locate signs as shown on the construction documents.
B. Conform to the VA Signage Design Guide for installation requirements.
C. At each sign location there are no utility lines behind each sign location that shall be affected by installation of signs.
1. Correct and repair damage done to utilities during installation of signs at no additional cost to Government.
D. Provide inserts and anchoring devices which shall be set in concrete or other material for installation of signs. Submit setting drawings, 10 14 00 - 8 Submission 95% May 29, 2020 templates, instructions and directions for installation of anchorage devices, which may involve other trades.
E. Refer to Sign Message Schedule for mounting method. Mount signs in proper alignment, level and plumb according to the Sign Location Plan and the dimensions given on elevation and Sign Location Plans. When exact position, angle, height or location is not clear, contact COR for resolution.
F. When signs are installed on glass, provide blank glass back up to be placed on opposite side of glass exactly behind sign being installed.
Provide blank glass back that is the same size as sign being installed.
G. Touch up exposed fasteners and connecting hardware to match color and finish of surrounding surface.
H. At completion of sign installation, clean exposed sign surfaces. Clean and repair adjoining or adjacent surfaces that became soiled or damaged as a result of installation of signs.
- - - END - - -