093013 Ceramic Porcelain Tiling.pdf
PDF 49 KB Posted
- Solicitation number
- 36C24521B0008
About this file
This document package includes specifications for ceramic/porcelain tiling work and a related federal contract opportunity notice.
The specifications document provides detailed requirements for ceramic and porcelain tile, backer units, setting materials, grout, accessories, and installation methods for a renovation project at a VA medical center. Product standards, testing protocols, and qualifications for materials and installers are specified. The scope of work includes interior wall and floor tiling.
The related opportunity notice is for construction services for project no. 613-19-100 to renovate buildings 3A and 3B at the same VA medical center. This is a 100% set-aside for Service-Disabled Veteran Owned Small Businesses. The estimated cost range is $10-20 million. The pre-solicitation, pre-bid site visit will be held on June 9, 2021, and questions are due by June 17, 2021. The bid opening is scheduled for July 14, 2021. Interested parties must register on SAM, VIP, and other websites listed to be eligible for award.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Bldg. 500 – Renovate 3B 10-01-15 Project No. 613-19-101
09 30 13 - 1 Submission Bid Documents July 16, 2020
SECTION 09 30 13
CERAMIC/PORCELAIN TILING
PART 1 - GENERAL
1.1 DESCRIPTION:
A. This section specifies interior ceramic, porcelain tile, waterproofing membranes for thin-set applications, crack isolation membranes, and tile backer board.
1.2 RELATED WORK:
A. Sustainable Design Requirements: Section 01 81 13, SUSTAINABLE
CONSTRUCTION REQUIREMENTS.
B. Preformed expansion joints in tile flooring: Section 07 95 13, EXPANSION JOINT COVER ASSEMBLIES.
C. Sealing of Joints: Section 07 92 00, JOINT SEALANTS.
D. Color, Texture, Pattern, and Size of Field Tile and Trim Shapes, and
Color of Grout Specified: Section 09 06 00, SCHEDULE FOR FINISHES.
E. Metal and Resilient Edge Strips at Joints with New Resilient Flooring, and Carpeting: Section 09 65 19, RESILIENT TILE FLOORING and Section 09
68 00, CARPETING.
1.3 SUBMITTALS:
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT
DATA, AND SAMPLES.
B. Samples:
1. Base tile, each type, each color, each size.
2. Floor tile panels, Porcelain tile, each type, color, size and pattern.
3. Porcelain tile, each type, color, patterns and size.
4. Wall (or wainscot) tile, each color, size and pattern.
5. Trim shapes, bullnose cap and cove including bullnose cap and base pieces at internal and external corners of vertical surfaces, each type, color, and size.
C. Product Data:
1. Ceramic and porcelain tile, marked to show each type, size, and shape required.
2. Epoxy grout.
3. Cementitious backer unit.
4. Dry-set portland cement mortar and grout.
5. Divider strip.
09 30 13 - 2 Submission Bid Documents July 16, 2020
6. Waterproofing membrane.
7. Reinforcing tape.
8. Leveling compound.
9. Latex-portland cement mortar and grout.
10. Slip resistant tile.
11. Crack isolation membrane.
14. Fasteners.
E. Certification:
1. Master grade certificate, ANSI A137.1.
2. Manufacturer's certificates indicating that the following materials comply with specification requirements:
a. Epoxy grout
b. Modified epoxy emulsion.
c. Cementitious backer unit.
d. Dry-set portland cement mortar and grout.
e. Waterproofing membrane.
f. Reinforcing tape.
g. Latex-portland cement mortar.
h. Leveling compound.
i. Crack isolation membrane.
j. Factory back mounted tile documentation for suitability for application in wet area.
F. Installer Qualifications:
1. Submit letter stating installer’s experience.
1.4 DELIVERY AND STORAGE:
A. Deliver materials in containers with labels legible and intact and grade-seals unbroken.
B. Store material to prevent damage or contamination.
1.5 QUALITY ASSURANCE:
A. Installers to be from a company specializing in performing installation of products specified and have a minimum of three (3) years’ experience.
B. Each type and color of tile to be provided from a single source.
C. Each type and color of mortar, adhesive, and grout to be provided from the same source.
1.6 WARRANTY:
A. Construction Warranty: In accordance with contract.
09 30 13 - 3 Submission Bid Documents July 16, 2020
1.7 APPLICABLE PUBLICATIONS:
A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in text by basic designation only.
B. American National Standards Institute (ANSI):
A10.20-06(R2011)........Safe Operating Practices for Tile, Terrazzo and
Marble WorkA108/A118/A136-14 Installation of
Ceramic Tile
A108.01-13..............Subsurfaces and Preparations by Other Trades
A108.02-13..............Materials, Environmental, and Workmanship
A108.1A-14..............Installation of Ceramic Tile in the Wet-Set
Method with Portland Cement Mortar
A108.1B-10..............Installation of Ceramic Tile on a Cured
Portland Cement Mortar Setting Bed with Dry-Set or Latex-Portland Cement Mortar
A108.1C-10..............Contractors Option; Installation of Ceramic
Tile in the Wet-Set method with Portland Cement
Mortar or Installation of Ceramic Tile on a
Cured Portland Cement Mortar Setting Bed with
Dry-Set or Latex-Portland Cement Mortar
A108.6-10...............Ceramic Tile with Chemical Resistant, Water
Cleanable Tile-Setting and -Grouting Epoxy
A108.8-10...............Ceramic Tile with Chemical Resistant Furan
Resin Mortar and Grout
A108.10-10..............Grout in Tilework
A108.13-10..............Load Bearing, Bonded, Waterproof Membranes for
Thin-Set Ceramic Tile and Dimension Stone
A118.1-12...............Dry-Set Portland Cement Mortar
A118.3-13...............Chemical Resistant, Water Cleanable Tile-
Setting and –Grouting Epoxy and Water Cleanable
Tile-Setting Epoxy Adhesive
A118.4-12...............Latex-Portland Cement Mortar
A118.9-10...............Cementitious Backer Units
A118.10-14..............Load Bearing, Bonded, Waterproof Membranes for
Thin-Set Ceramic Tile and Dimension Stone
Installation
A118.12-14..............Crack Isolation Membranes for Thin-Set Ceramic
Tile and Dimension Stone Installations
09 30 13 - 4 Submission Bid Documents July 16, 2020
A137.1-12...............American National Standard Specifications for
Ceramic Tile
C. ASTM International (ASTM):
A666-10.................Annealed or Cold-Worked Austenitic Stainless
Steel Sheet, Strip, Plate and Flat Bar
A1064/A1064M-14.........Carbon-Steel Wire and Welded Wire
Reinforcement, Plain and Deformed, for Concrete
C109/C109M-13...........Standard Test Method for Compressive Strength of Hydraulic Cement Mortars (Using 2 inch. or
[50-mm] Cube Specimens)
C241/C241M-13...........Abrasion Resistance of Stone Subjected to Foot
Traffic
C348-14.................Standard Test Method for Flexural Strength of
Hydraulic-Cement Mortars
C627-10.................Evaluating Ceramic Floor Tile Installation
Systems Using the Robinson-Type Floor Tester
C954-11.................Steel Drill Screws for the Application of
Gypsum Board on Metal Plaster Base to Steel
Studs from 0.033 in (0.84 mm) to 0.112 in (2.84
mm) in thickness
C979/C979M-10...........Pigments for Integrally Colored Concrete
C1002-14................Steel Self-Piercing Tapping Screws for the
Application of Panel Products
C1027-09................Test Method for Determining Visible Abrasion
Resistance of Glazed Ceramic Tile
C1127-01(R2009).........Standard Guide for Use of High Solids Content, Cold Liquid-Applied Elastomeric Waterproofing
Membrane with an Integral Wearing Surface
C1178/C1178M-13.........Standard Specification for Coated Glass Mat
Water-Resistant Gypsum Backing Panel
C1325-14................Non-Asbestos Fiber-Mat Reinforced Cementitious
Backer Units
C1353/C1353M-09(R2013)..Abrasion Resistance of Dimension Stone
Subjected to Foot Traffic Using a Rotary
Platform, Double-Head Abraser
09 30 13 - 5 Submission Bid Documents July 16, 2020
D1204-14................Test Method for Linear Dimensional Changes of
Nonrigid Thermoplastic Sheeting or Film at
Elevated Temperature
D2240-05(R2010).........Test Method for Rubber Property – Durometer
Hardness
D2497-07(R2012).........Tolerances for Manufactured Organic-Base
Filament Single Yarns
D3045-92(R2010).........Heat Aging of Plastics Without Load
D4397-10................Standard Specification for Polyethylene
Sheeting for Construction, Industrial and
Agricultural Applications
D5109-12................Standard Test Methods for Copper-Clad
Thermosetting Laminates for Printed Wiring
Boards
D. Code of Federal Regulation (CFR):
40 CFR 59...............Determination of Volatile Matter Content, Water
Content, Density Volume Solids, and Weight
Solids of Surface Coating
E. Tile Council of North America, Inc. (TCNA):
Handbook for Ceramic Tile Installation (2014)
DCOF AcuTest-2012.......Dynamic Coefficient of Friction Test
PART 2 - PRODUCTS
2.1 TILE:
A. Comply with ANSI A137.1, Standard Grade, except as modified:
1. Inspection procedures listed under the Appendix of ANSI A137.1.
2. Abrasion Resistance Classification:
a. Tested in accordance with values listed in Table 1, ASTM C1027.
b. Class V, 12000 revolutions for floors in Corridors, Kitchens, Storage including Refrigerated Rooms
c. Class IV, 6000 revolutions for remaining areas.
3. Slip Resistant Tile for Floors:
a. Coefficient of friction, when tested in accordance with
ANSI A137.1 and measured per the TCNA DCOF AcuTest.
1) Equal to or greater than .42 for level interior tile floors that shall be walked on when wet.
4. Mosaic tile shall be mounted or joined together by a resinous bonding material along tile edges.
09 30 13 - 6 Submission Bid Documents July 16, 2020
5. Factory Blending: For tile with color variations, within the ranges selected during sample submittals blend tile in the factory and package so tile units taken from one (1) package show the same range in colors as those taken from other packages and match approved samples.
6. Factory-Applied Temporary Protective Coating:
a. Protect exposed face surfaces (top surface) of tile against adherence of mortar and grout by pre-coating with a continuous film of hot applied petroleum paraffin wax.
b. Do not coat unexposed tile surfaces.
c. Pre-wax tiles set or grouted with furan or epoxy.
B. Glazed Wall Tile: Cushion edges, glazing.
C. Porcelain Paver Tile: Nominal 8 mm (5/16 inch) thick, with cushion edges. Porcelain tile produced by the dust pressed method shall be made of approximately 50% feldspar; the remaining 50% is to be made up of various high-quality light firing ball clays yielding a tile with a water absorption rate of 0.5% or less and a breaking strength of between 176 to 181 kg (390 to 400 lbs.).
D. Trim Shapes:
1. Conform to applicable requirements of adjoining floor and wall tile.
2. Use trim shapes sizes conforming to size of adjoining field wall tile unless detailed on construction documents or specified otherwise.
3. Internal and External Corners:
a. Square internal and external corner joints are not acceptable.
b. External corners including edges: Use bullnose shapes.
c. Internal corners: Use cove shapes.
d. Base to floor internal corners: Use special shapes providing integral cove vertical and horizontal joint.
e. Base to floor external corners: Use special shapes providing bullnose vertical edge with integral cove horizontal joint. Use stop at bottom of openings having bullnose return to wall.
f. Wall top edge internal corners: Use special shapes providing integral cove vertical joint with bullnose top edge.
g. Wall top edge external corners: Use special shapes providing bullnose vertical and horizontal joint edge.
h. For unglazed ceramic mosaic and glazed wall tile installed in portland cement mortar setting bed, use cove and bullnose shapes
09 30 13 - 7 Submission Bid Documents July 16, 2020 as applicable. When ceramic mosaic wall and base tile is required, use C Series cove and bullnose shapes.
i. For unglazed ceramic mosaic and glazed wall tile installed in dry-set portland cement mortar, latex-portland cement mortar, and organic adhesive (thin set methods), use cove and surface bullnose shapes as applicable.
j. Provide cove and bullnose shapes for countertops, stools, saddles, where indicated in construction documents, and required to complete tile work.
2.2 BACKER UNITS:
A. Cementitious Backer Units:
1. Use behind wall tile.
2. Conform to ASTM C1325; Type A.
3. Use in maximum lengths available to minimize end to end butt joints.
2.3 JOINT MATERIALS FOR CEMENTITIOUS BACKER UNITS:
A. Reinforcing Tape: Vinyl coated woven glass fiber mesh tape, open weave, 50 mm (2 inches) wide. Tape with pressure sensitive adhesive backing shall not be permitted.
B. Tape Embedding Material: Latex-portland cement mortar complying with
ANSI A108.01.
C. Joint material, including reinforcing tape, and tape embedding material, shall be as specifically recommended by the backer unit manufacturer.
2.4 FASTENERS:
A. Screws for Cementitious Backer Units.
1. Standard screws for gypsum board are not acceptable.
2. Minimum 11 mm (7/16 inch) diameter head, corrosion resistant coated, with washers.
3. ASTM C954 for steel 1 mm (0.033 inch) thick.
4. ASTM C1002 for steel framing less than 0.0329 inch thick.
2.5 SETTING MATERIALS OR BOND COATS:
A. Conform to TCNA Handbook for Ceramic Tile Installation.
B. Portland Cement Mortar: ANSI A108.02.
C. Latex-Portland Cement Mortar: ANSI A118.4.
1. For wall applications, provide non-sagging, latex-portland cement mortar complying with ANSI A118.4.
2. Prepackaged Dry-Mortar Mix: Factory-prepared mixture of portland cement; dry, redispersible, ethylene vinyl acetate additive; and
09 30 13 - 8 Submission Bid Documents July 16, 2020 other ingredients to which only water needs to be added at Project site.
D. Dry-Set Portland Cement Mortar: ANSI A118.1. For wall applications, provide non-sagging, latex-portland cement mortar complying with
ANSI A118.1.
E. Chemical-Resistant Bond Coat:
1. Epoxy Resin Type: ANSI A118.3.
2. Furan Resin Type: ANSI A118.5.
F. Waterproofing Membrane:
1. Fluid-applied system complying with ANSI A118.10
2. Include reinforcement and accessories recommended by manufacturer.
G. Crack Isolation Membrane:
1. Composite sheet consisting of ASTM D5109, Type II, Grade I
Chlorinated Polyethylene (CM) sheet reinforced on both sides with a non-woven polyester fiber.
2. Designed for use as an isolation membrane for thin-set bonding of sheet to substrate and thin-set bonding of ceramic and porcelain tile to sheet. Suited for both horizontal and vertical applications.
3. Conform to the following additional physical properties:
Property Units Results Test Method
Service Requirements
Cycles 70-801-14 “Extra Heavy”
ASTM C627
Fungus and Microorganis m Resistance
No growth Pass ASTM A118.10
Crack Isolation Performance
>1/8 inch “High performance”.
ASTM A118.12
4. Manufacturer’s standard sheet size with prefabricated or preformed inside and outside corners.
5. Sheet manufacturer’s solvent welding liquid or xylene and edge sealant.
2.6 GROUTING MATERIALS:
A. Water-Cleanable Epoxy Grout: ANSI A118.3, with a VOC content of 65 g/L or less when calculated according to 40 CFR 59 (EPA Method 24).
09 30 13 - 9 Submission Bid Documents July 16, 2020
2.7 PATCHING AND LEVELING COMPOUND:
A. Portland cement base, polymer-modified, self-leveling compound, manufactured specifically for resurfacing and leveling concrete floors.
Products containing gypsum are not acceptable.
B. Provide a patching and leveling compound with the following minimum physical properties:
1. Compressive strength - 25 MPa (3500 psig) per ASTM C109/C109M.
2. Flexural strength - 7 MPa (1000 psig) per ASTM C348 (28 day value).
3. Tensile strength – 4.1 MPa (600 psi) per ANSI 118.7.
4. Density – 1.9.
C. Capable of being applied in layers up to 38 mm (1-1/2 inches) thick without fillers and up to 101 mm (4 inches) thick with fillers, being brought to a feather edge, and being trowelled to a smooth finish.
D. Primers, fillers, and reinforcement as required by manufacturer for application and substrate condition.
E. Ready for use in 48 hours after application.
2.8 METAL DIVIDER STRIPS:
A. Terrazzo type divider strips.
B. Heavy top type strip with 5 mm (3/16 inch) wide top and 38 mm
(1 1/2 inch) long leg. Height to match tile and setting-bed thickness.
C. Embedded leg perforated and deformed for keying to mortar.
D. Stainless-steel, ASTM A666, 300 Series exposed-edge material.
2.9 WATER:
A. Clean, potable and free from salts and other injurious elements to mortar and grout materials.
2.10 CLEANING COMPOUNDS:
A. Specifically designed for cleaning masonry and concrete and which shall not prevent bond of subsequent tile setting materials including patching and leveling compounds and elastomeric waterproofing membrane and coat.
B. Materials containing acid or caustic Material are not acceptable.
2.11 FLOOR MORTAR BED REINFORCING:
A. ASTM A1064/A1064M welded wire fabric without backing, MW3 x MW3
(2 x 2-W0.5 x W0.5).
PART 3 - EXECUTION
09 30 13 - 10 Submission Bid Documents July 16, 2020
3.1 ENVIRONMENTAL REQUIREMENTS:
A. Maintain ambient temperature of work areas at not less than
16 degrees C (60 degrees F), without interruption, for not less than 24 hours before installation and not less than three (3) days after installation.
B. Maintain higher temperatures for a longer period of time where required by manufacturer's recommendation and ANSI Specifications for installation.
C. Do not install tile when the temperature is above 38 degrees C
(100 degrees F).
D. Do not install materials when the temperature of the substrate is below
16 degrees C (60 degrees F).
E. Do not allow temperature to fall below 10 degrees C (50 degrees F) after third day of completion of tile work.
3.2 ALLOWABLE TOLERANCE:
A. Variation in plane of sub-floor, including concrete fills leveling compounds and mortar beds:
1. Not more than 6 mm in 3048 mm (1/4 inch in 10 feet) from required elevation where portland cement mortar setting bed is used.
2. Not more than 3 mm in 3048 mm (1/8 inch in 10 feet) where dry-set portland cement, and latex-portland cement mortar setting beds and chemical-resistant bond coats are used.
B. Variation in Plane of Wall Surfaces:
1. Not more than 6 mm in 2438 mm (1/4 inch in 8 feet) from required plane where portland cement mortar setting bed is used.
2. Not more than 3 mm in 2438 mm (1/8 inch in 8 feet) where dry-set or latex-portland cement mortar or organic adhesive setting materials is used.
3.3 SURFACE PREPARATION:
A. Cleaning New Concrete or Masonry:
1. Chip out loose material, clean off all oil, grease dirt, adhesives, curing compounds, and other deterrents to bonding by mechanical method, or by using products specifically designed for cleaning concrete and masonry.
2. Use self-contained power blast cleaning systems to remove curing compounds and steel trowel finish from concrete slabs where ceramic tile shall be installed directly on concrete surface with thin-set materials.
09 30 13 - 11 Submission Bid Documents July 16, 2020
3. Steam cleaning or the use of acids and solvents for cleaning shall not be permitted.
B. Patching and Leveling:
1. Mix and apply patching and leveling compound in accordance with manufacturer's instructions.
2. Fill holes and cracks and align concrete floors that are out of required plane with patching and leveling compound.
a. Thickness of compound as required to bring finish tile system to elevation shown on construction documents.
b. Float finish except finish smooth for elastomeric waterproofing.
c. At substrate expansion, isolation, and other moving joints, allow joint of same width to continue through underlayment.
3. Apply patching and leveling compound to concrete and masonry wall surfaces that are out of required plane.
4. Apply leveling coats of material compatible with wall surface and tile setting material to wall surfaces, other than concrete and masonry that are out of required plane.
C. Waterproofing Membrane:
1. Install waterproofing to comply with ANSI A108.13 and manufacturer's written instructions to produce waterproof membrane of uniform thickness that is bonded securely to substrate.
2. Transitions: Provide manufacturer’s recommended detail reinforcing fabric at all substrate transitions.
3. Install waterproofing membrane where indicated and as follows:
a. Toilet Rooms: If floor is slab-on-grade, the membrane shall extend 4 inches minimum vertically on wall surfaces and 4 inches minimum onto floor.
1) If walls are not tiled, the vertical height of the membrane shall be 1/2 inch less than the height of the wall base.
Waterproofing membrane shall never remain exposed.
4. Allow waterproofing to cure and verify by inspecting that it is watertight before installing tile or setting materials over it.
D. Mortar Bed for Slopes to Drains:
1. Slope compound to drain where drains are shown on construction documents.
2. Install mortar bed in depressed slab sloped to drains not less than
3.2 mm in 305 mm (1/8 inch per foot).
09 30 13 - 12 Submission Bid Documents July 16, 2020
3. Allow not less than 50 mm (2 inch) depression at edge of depressed slab.
4. Screed for slope to drain and float finish.
5. Cure mortar bed for not less than seven (7) days. Do not use curing compounds or coatings.
6. Perform flood test to verify mortar bed slopes to drain before installing tile. Contracting Officer Representative (COR) to be present during flood test.
E. Tiling for Slopes to Drains:
1. Slope tile to drain where drains are shown on construction documents.
2. Tile slope shall not exceed 1/4 inch per foot.
F. Walls:
1. Apply patching and leveling compound to concrete and masonry surfaces that are out of required plane.
2. Apply leveling coats of material compatible with wall surface and tile setting material to wall surfaces, other than concrete and masonry that are out of required plane.
G. Existing Floors and Walls:
1. Remove existing composition floor finishes and adhesive. Prepare surface by grinding, chipping, self-contained power blast cleaning or other suitable mechanical methods to completely expose uncontaminated concrete or masonry surfaces. Follow safety requirements of ANSI A10.20.
2. Remove existing concrete fill or topping to structural slab. Clean and level the substrate for new setting bed and waterproof membrane or cleavage membrane.
3. Where new tile bases are required to finish flush with plaster above or where they are extensions of similar bases in conjunction with existing floor tiles, cut channel in floor slab and expose rough wall construction sufficiently to accommodate new tile base and setting material.
3.4 CEMENTITIOUS BACKER UNITS:
A. Remove polyethylene wrapping from cementitious backer units and separate to allow for air circulation. Allow moisture content of backer units to dry down to a maximum of 35 percent before applying joint treatment and tile.
B. Install in accordance with ANSI A118.9 except as specified otherwise.
09 30 13 - 13 Submission Bid Documents July 16, 2020
C. Install units horizontally or vertically to minimize joints with end joints over framing members. Units with rounded edges; face rounded edge away from studs to form a “V” joint for joint treatment.
D. Secure cementitious backer units to each framing member with screws spaced not more than 203 mm (8 inches) on center and not closer than
13 mm (1/2 inch) from the edge of the backer unit or as recommended by backer unit manufacturer. Install screws so that the screw heads are flush with the surface of the backer unit.
E. Do not install joint treatment for seven (7) days after installation of cementitious backer unit.
F. Joint Treatment:
1. Fill horizontal and vertical joints and corners with latex-portland cement mortar. Apply fiberglass tape over joints and corners and embed with same mortar.
2. Leave 6 mm (1/4 inch) space for sealant at lips of tubs, sinks, or other plumbing receptors.
3.5 METAL DIVIDER STRIPS:
A. Install metal divider strips in floor joints between ceramic and quarry tile floors and between tile floors and adjacent flooring of other materials where the finish floors are flush unless shown otherwise on construction documents.
B. Set divider strip in mortar bed to line and level centered under doors or in openings.
3.6 CERAMIC TILE – GENERAL:
A. Comply with ANSI A108/A118/A136 series of tile installation standards applicable to methods of installation and TCNA Installation Guidelines.
B. Installing Mortar Beds for Floors:
1. Install mortar bed in a manner that does not damage crack isolation or waterproof membrane.
C. Setting Beds or Bond Coats:
1. Set floor tile in thin-set bond coat over elastomeric membrane per
ANSI 108.13, TCNA System F122-14 where indicated on construction documents.
2. Set wall tile installed over concrete or masonry in dry-set portland cement mortar, or latex-portland cement mortar, ANSI 108.1B and
TCNA System W211-14, W221-14 or W222-14.
3. Set wall tile installed over concrete backer board in latex-portland cement mortar, ANSI A108.1B.
09 30 13 - 14 Submission Bid Documents July 16, 2020
4. Set trim shapes in same material specified for setting adjoining tile.
D. Workmanship:
1. Lay out tile work so that no tile less than one-half full size is used. Make all cuts on the outer edge of the field.
2. Set tile firmly in place with finish surfaces in true planes. Align tile flush with adjacent tile unless shown otherwise on construction documents.
3. Form intersections and returns accurately.
4. Cut and drill tile neatly without marring surface.
5. Cut edges of tile abutting penetrations, finish, or built-in items:
a. Fit tile closely around electrical outlets, piping, fixtures and fittings, so that plates, escutcheons, collars and flanges shall overlap cut edge of tile.
b. Seal tile joints water tight as specified in Section 07 92 00, JOINT SEALANTS, around electrical outlets, piping fixtures and fittings before cover plates and escutcheons are set in place.
6. Completed work is to be free from hollow sounding areas and loose, cracked or defective tile.
7. Remove and reset tiles that are out of plane or misaligned.
8. Floors:
a. Extend floor tile beneath casework and equipment, except those units mounted in wall recesses.
b. Align finish surface of new tile work flush with other and existing adjoining floor finish where indicated in construction documents.
c. In areas where floor drains occur, slope tile to drains.
d. Push and vibrate tiles over 203 mm (8 inches) square to achieve full support of bond coat.
9. Walls:
a. Cover walls and partitions, including pilasters, furred areas, and freestanding columns from floor to ceiling, or from floor to nominal wainscot heights as indicated in construction documents with tile.
b. Finish reveals of openings with tile, except where other finish materials are indicated in construction documents.
09 30 13 - 15 Submission Bid Documents July 16, 2020
c. Finish wall surfaces behind and at sides of casework and equipment, except those units mounted in wall recesses, with same tile as scheduled for room proper.
10. Joints:
a. Keep all joints in line, straight, level, perpendicular and of even width unless shown otherwise on construction documents.
b. Make joints 2 mm (1/16 inch) wide for glazed wall tile and mosaic tile work.
c. Make joints in paver tile, porcelain type; maximum 3 mm
(1/8 inch) wide.
11. Back Buttering: For installations indicated below, obtain 100 percent mortar coverage by complying with applicable special requirements for back buttering of tile in referenced
ANSI A108/A118/A136 series of tile installation standards:
a. Tile wall installations in wet areas, including showers, tub enclosures, laundries and swimming pools.
b. Tile installed with chemical-resistant mortars and grouts.
c. Tile wall installations composed of tiles 203 by 203 mm
(8 by 8 inches) or larger.
3.7 CERAMIC TILE INSTALLED WITH PORTLAND CEMENT MORTAR:
A. Mortar Mixes for Floor, Wall and Base Tile: ANSI A108.1A. except specified otherwise.
B. Installing Wall and Base Tile: ANSI A108.1A, except specified otherwise.
C. Installing Floor Tile: ANSI A108.1A, except as specified otherwise.
Slope mortar beds to floor drains at a minimum of 3 mm in 305 mm
(1/8 inch per foot).
3.8 PORCELAIN TILE INSTALLED WITH LATEX PORTLAND CEMENT BONDING MORTAR:
A. Due to the denseness of porcelain tile use latex portland cement bonding mortar that meets the requirements of ANSI A108.01. Mix bonding mortars in accordance with manufacturer’s instructions. Provide liquid ratios and comply with dwell times during the placement of bonding mortar and tile.
3.9 THIN SET CERAMIC AND PORCELAIN TILE INSTALLED WITH DRY-SET PORTLAND
CEMENT AND LATEX-PORTLAND CEMENT MORTAR:
A. Installation of Tile: ANSI A108.1B, except as specified otherwise.
B. Slope tile work to drains at not less than 3 mm in 305 mm (1/8 inch per foot).
09 30 13 - 16 Submission Bid Documents July 16, 2020
3.10 THIN SET CERAMIC AND PORCELAIN TILE INSTALLED WITH ORGANIC ADHESIVE
A. Installation of Tile: ANSI A108.4.
3.11 GROUTING:
A. Grout Type and Location:
1. Grout for glazed wall and base tile, and unglazed mosaic tile, epoxy grout unless otherwise indicated.
B. Workmanship:
1. Install and cure grout in accordance with the applicable standard.
2. Water-Cleanable Epoxy Grout: ANSI A118.3.
3.12 MOVEMENT JOINTS:
A. Prepare tile expansion, isolation, construction and contraction joints for installation of sealant. Refer to Section 07 92 00, JOINT SEALANTS.
B. TCNA details EJ 171-14.
C. At expansion joints, rake out joint full depth of tile and setting bed and mortar bed. Do not cut waterproof or isolation membrane.
D. Rake out grout at joints between tile, where indicated in construction documents- not less than 6 mm (1/4 inch) deep.
3.13 CLEANING:
A. Thoroughly sponge and wash tile. Polish glazed surfaces with clean dry cloths.
B. Methods and materials used are not permitted to damage or impair appearance of tile surfaces.
C. The use of acid or acid cleaners on glazed tile surfaces is prohibited.
D. Clean tile grouted with epoxy grout as recommended by the manufacturer of the grout and bond coat.
3.14 PROTECTION:
A. Keep traffic off tile floor, until grout and setting material is fully set and cured.
B. Where traffic occurs over tile floor is unavoidable, cover tile floor with not less than 9 mm (3/8 inch) thick plywood, wood particle board, or hardboard securely taped in place. Do not remove protective cover until time for final inspection. Clean tile of any tape, adhesive and stains.
3.15 TESTING FINISH FLOOR:
A. Test floors in accordance with ASTM C627 to show compliance with codes
1 through 10.
- - - E N D - - -