Attachment 3 Med Air System -Dental duplex Reciprocating.xlsx

XLSX spreadsheet 62 KB Posted

Attached to
J045--Medical Gas Preventative Maintenance and Inspection Services for Erie VA Medical Center
Solicitation number
36C24426Q0958
Issued by

About this file

This is a Medical Gas System Inspection Report documenting preventative maintenance performed on a RAMVAC dental air duplex compressor system at VA Medical Center Erie. The inspection was conducted on May 28, 2026, by technician R. Garmon on System Model OSP25 (Serial #4773030), which has accumulated 1,065 run hours since manufacture on July 1, 2019. The report details comprehensive system evaluation including two Gast OF1202 pump units, motor performance metrics (208V, approximately 9.3-9.7 amps), and component condition assessments using a standardized legend (A=Acceptable, U=Unacceptable, R=Repaired, NR=Needs Replaced, NA=Not Applicable). All major components including discharge check valves, unloaders, solenoids, inlet filters, after cooler drain valves, crankcase filters, piston rings, and relief valves were marked acceptable, with lead pressure switch readings of 80-100 psi and room temperature at 77°F.

The report notes that the customer facility is currently servicing dental units with patient backlog constraints and has installed an additional compressor system, requesting information and parts compatibility details for the new dental air system. The deficiencies section indicates that parts may be required for service depending on the specifications of the newly installed equipment. No CO Monitor or Dew Point Monitor was present on the current system, and auto blow-down line functionality was not assessed. This inspection documentation directly supports the VA's solicitation for Medical Gas Preventative Maintenance and Inspection Services (Solicitation 36C24426Q0958, a 100% SDVOSB set-aside with a September 25, 2026 quote deadline).

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Customer InformationSystem InformationJob Information
FacilityVA Medical Center ErieSystem DescriptionRAMVAC dental air duplexJob #627910
Address135 East 38th StreetSystem Model #OSP25SO #627910
Erie,PA 16504System Serial #4773030Trip #1
ContactDavvid DombkowskiManufacture Date07/01/19Year2026
Emaildavid.dombkowski@va.orgSystem LocationDental Mechanical roomDate05/28/26
Phone814-860-2924Customer System #TechRgarmon
Pump ##1#2#3#4
Model #OF1202OF1202
Serial #Gast Item#004822Gast Item#004822
Run Hours1065
Room Temperature77°F
Discharge Temperature
Discharge Check ValvesAA
Unloaders and SolenoidsAA
Inlet FiltersAA
After Cooler Drain ValvesAA
High Temp Shutdown
Crankcase Filter
Rider and Piston RingsAA
Starter ContactsAA
Thermal Overload Settings
Transformer Condition
Panel LampsALEGEND
Relief ValvesAA = Acceptable
Panel RelaysAU = Unacceptable
Lead Pressure Switch80-100psiLocal Lag AlarmR = Repaired
Lag 1 Pressure SwitchpsiAudibleNR = Needs Replaced
Lag 2 Pressure SwitchpsiVisualNA = Not Applicable
Lag 3 Pressure Switchpsi
Motor Information SectionMotor #1Motor # 2Motor # 3Motor #4
Volts L1 to L22089.50 AMPS9.30 AMPS
Volts L2 to L32089.40 AMPS9.50 AMPS
Volts L1 to L32089.40 AMPS9.70 AMPS
EfficiencyService FactorHorse PowerRPM1,650
Frame SizeVoltageFull Load Amps
CO MonitorDew Point Monitor
Manuf/Model/SN:NoneManuf/Model/SN:None
Test Gas ReadingGas Conc.=20 PPMD.P. Reading (as found)
Cal Performed ?FailMeasured D.P. (Medpipe)
Sensor Replaced ?Sensor Replaced ?
Reading after CalD.P. Reading (as left)
Dryers
Unit On Line (as found)Pre FiltersLamps
Unit On Line (as left)After FiltersSuction Pressure
Selector SwitchDischarge Check ValveBlow Down Valve
Purge SelectMufflersAuto Blow Down
Line RegulatorSolenoidsFloat Drain

Sheet2

Parts Used
QuantityPart NumberPart Description

Deficiencies

Comments
customer servicing units for dental due to patient backlog
Customer installed additional compressor system-
Customer would like information for the new dental air system. Will require parts for service if different from
current compressor.

Recommendations image1.png image2.png