Questions II.docx

DOCX document 13 KB Posted

Attached to
Z1DA--ALBANY BOILER-CHILLER PLANTS CHEMICAL TREATMENT (VA-24-00002448)
Solicitation number
36C24223Q1082
Issued by

About this file

This document contains questions and answers regarding chemical treatment services for cooling towers at an Albany, New York VA medical center. The facilities include three cooling towers, one at 1000 tons and two at 750 tons each. Liquid bromine injection is used for biocide treatment, rather than bromine tablets as stated in the original scope of work. Documentation of past legionella testing by the previous contractor could not be found, indicating testing may not be currently performed. Clarification was provided on the cooling tower sizes which were previously listed incorrectly.

The related federal contract opportunity is a solicitation from the Department of Veterans Affairs for chemical treatment services at the Albany VA medical center's boiler and chiller plants. Solicitation number 36C24223Q1082 has an opportunity type of solicitation and is being conducted by VA Networks 2 and 24.

View the file

Other files

File Type Posted
Albany SOW 2024 - Boiler-Chiller Chemical Treatment.doc DOC document
C03. 36C24223Q1082_3.pdf PDF
36C24223Q1082_2.pdf PDF
2 cooling service July 2023 7-28-2023.PDF PDF
36C24223Q1082_1.docx DOCX document
Cooling report June 2023 6-7-2023.pdf PDF
June Boiler Service 2023 6-23-2023.PDF PDF
Boiler report July 2023 7-28-2023.PDF PDF
P07. Wage (ALBANY).pdf PDF
36C24223Q1082.docx DOCX document
VAAR 819 219 77 VA Notice of Limitation on subcontracting.docx DOCX document
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions:

Q: Is the closed loop, chilled water using a pot feeder?

A: Yes, Pot feeder is used.

Q:There is a pot feeder for bromine tablets and liquid injection, SOW states tablets being used. Which is it, tablet or liquid?

A: Liquid injection to the 3 towers is being used.

( this last question prompts an SOW change also)

Q: Is the chilled water closed loop annually tested for legionella prevention A: I could not find documentation from the previous contractor (Barclave) to support correct information to be given for contractors proposal. (It appears that it not being currently tested)

In the answers, both the cooling towers are referenced as “12 tons” I am assuming they meant “120 tons” based on the make-up usage. Can you please clarify?

A: We have three cooling towers one is 1000 tons & the other two are 750 tons. I am so sorry for this mistake.