Z1DA--ALBANY BOILER-CHILLER PLANTS CHEMICAL TREATMENT (VA-24-00002448)
Solicitation number
36C24223Q1082
Issued by

About this file

This document summarizes a boiler report from Barclay Water Management regarding chemical treatment services at the VA Albany Stratton Building in Albany, New York. Key details include:

  • Barclay Water Management provides chemical treatment and water management services for four boilers at the site. Boilers 1 and 3 were offline at the time of inspection, while Boilers 2 and 4 were online, with Boiler 4 running as the lead boiler.

  • Water quality measurements for the boilers and condensate returns were within normal ranges. Polymer levels in Boiler 4 were slightly elevated after a treatment the previous day.

  • The related federal contract opportunity is for chemical treatment services at VA boiler and chiller plants in Veterans Integrated Service Network 2, including the Albany site. The solicitation number is 36C24223Q1082 and is issued by the Department of Veterans Affairs Veterans Health Administration.

View the file

Other files

File Type Posted
Albany SOW 2024 - Boiler-Chiller Chemical Treatment.doc DOC document
C03. 36C24223Q1082_3.pdf PDF
Questions II.docx DOCX document
36C24223Q1082_2.pdf PDF
2 cooling service July 2023 7-28-2023.PDF PDF
36C24223Q1082_1.docx DOCX document
Cooling report June 2023 6-7-2023.pdf PDF
June Boiler Service 2023 6-23-2023.PDF PDF
P07. Wage (ALBANY).pdf PDF
36C24223Q1082.docx DOCX document
VAAR 819 219 77 VA Notice of Limitation on subcontracting.docx DOCX document
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Test Boiler 2 Boiler 4 Soft Water Feedwater Condensate Small Condensate Large

Conductivity (as uS/cm) 1163 750 - 3200

750 - 3200

175 - 250

61.5 0 - 50

4.5 0 - 25

2.4 0 - 25

Polymer, ppm 28.7 20 - 30

42.5 20 - 30 pH 11.75 10 - 12

11.87 10 - 12

7 - 9.5

9.2 8 - 10

8.5

8.3 - 9.5

9.3

8.3 - 9.5

Sulfite (ppm as SO3) 50 30 - 60

30 - 60

Hardness, total (ppm as CaCO3) 1 0 - 0

0 - 0

0 - 0

0 - 0

Test Low & Med Cond High Cond

Conductivity (as uS/cm) 2.4 0 - 25

2.8 0 - 25 pH 8.4

8.3 - 9.5

8.3 - 9.5

Hardness, total (ppm as CaCO3) 0 0 - 0

0 - 0

Opening Comment I have calibrated the new in house Myron meter for pH and conductivity with the supplied calibration standards.

All bulk chemicals and testing reagent inventories are OK at this time.

Service Report Boiler report July 2023

Friday, July 28, 2023 7:54 AM EDT

VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208

(518) 626-5000

Report Number: 588927 Recorded By: Logan Cote

(800) 253-2908 lcote@barclaywater.com

Stratton Bldg - Boiler Room

Barclay Water Management, Inc. - 55 Chapel Street, Newton MA 02458 (800) 253-2908

Service Report Boiler report July 2023

Friday, July 28, 2023 7:54 AM EDT

VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208

(518) 626-5000

Report Number: 588927 Recorded By: Logan Cote

(800) 253-2908 lcote@barclaywater.com

Stratton Bldg - Boiler Room

Service Report Boiler report July 2023

Friday, July 28, 2023 7:54 AM EDT

VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208

(518) 626-5000

Report Number: 588927 Recorded By: Logan Cote

(800) 253-2908 lcote@barclaywater.com

Stratton Bldg - Boiler Room

Boiler 1 Offline Boiler 1 is Offline.

Boiler 2 Online Is in standby all residuals were within normal operating range.

Boiler 3 Offline Boiler 3 is Offline in wet lay up.

Boiler 4 Online Running in lead. The polymer was fed yesterday and was slightly elevated at the time of the sampling. Sulfite was within normal operating range.

Closing Comment All condensate returns are returning good quality condensate. Please keep up with regular operator rounds and testing.

Keep up the good work. Thank you.

Service Report Boiler report July 2023

Friday, July 28, 2023 7:54 AM EDT

VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208

(518) 626-5000

Report Number: 588927 Recorded By: Logan Cote

(800) 253-2908 lcote@barclaywater.com

Stratton Bldg - Boiler Room

How are we doing? Let us know at feedback@barclaywater.com. We recommend that our customers perform routine water testing between service visits, to assure the proper performance of the water treatment program on a continuous basis. For supplemented potable water systems, it’s important to remember that monochloramine, like all oxidants, will degrade based on several factors, including but not limited to residence time, temperature, pH and presence of organic material. The iChlor system is designed to increase the monochloramine levels measured at the discharge of the unit. However, monochloramine residuals at distal outlets will vary based on the aforementioned factors in the building water system. Flushing may be required, under low/no flow conditions, to increase monochloramine level at distal points. REV. 07/05/2023