Boiler report July 2023 7-28-2023.PDF
PDF 812 KB Posted
- Solicitation number
- 36C24223Q1082
About this file
This document summarizes a boiler report from Barclay Water Management regarding chemical treatment services at the VA Albany Stratton Building in Albany, New York. Key details include:
-
Barclay Water Management provides chemical treatment and water management services for four boilers at the site. Boilers 1 and 3 were offline at the time of inspection, while Boilers 2 and 4 were online, with Boiler 4 running as the lead boiler.
-
Water quality measurements for the boilers and condensate returns were within normal ranges. Polymer levels in Boiler 4 were slightly elevated after a treatment the previous day.
-
The related federal contract opportunity is for chemical treatment services at VA boiler and chiller plants in Veterans Integrated Service Network 2, including the Albany site. The solicitation number is 36C24223Q1082 and is issued by the Department of Veterans Affairs Veterans Health Administration.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Albany SOW 2024 - Boiler-Chiller Chemical Treatment.doc | DOC document | |
| C03. 36C24223Q1082_3.pdf | ||
| Questions II.docx | DOCX document | |
| 36C24223Q1082_2.pdf | ||
| 2 cooling service July 2023 7-28-2023.PDF | ||
| 36C24223Q1082_1.docx | DOCX document | |
| Cooling report June 2023 6-7-2023.pdf | ||
| June Boiler Service 2023 6-23-2023.PDF | ||
| P07. Wage (ALBANY).pdf | ||
| 36C24223Q1082.docx | DOCX document | |
| VAAR 819 219 77 VA Notice of Limitation on subcontracting.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Test Boiler 2 Boiler 4 Soft Water Feedwater Condensate Small Condensate Large
Conductivity (as uS/cm) 1163 750 - 3200
750 - 3200
175 - 250
61.5 0 - 50
4.5 0 - 25
2.4 0 - 25
Polymer, ppm 28.7 20 - 30
42.5 20 - 30 pH 11.75 10 - 12
11.87 10 - 12
7 - 9.5
9.2 8 - 10
8.5
8.3 - 9.5
9.3
8.3 - 9.5
Sulfite (ppm as SO3) 50 30 - 60
30 - 60
Hardness, total (ppm as CaCO3) 1 0 - 0
0 - 0
0 - 0
0 - 0
Test Low & Med Cond High Cond
Conductivity (as uS/cm) 2.4 0 - 25
2.8 0 - 25 pH 8.4
8.3 - 9.5
8.3 - 9.5
Hardness, total (ppm as CaCO3) 0 0 - 0
0 - 0
Opening Comment I have calibrated the new in house Myron meter for pH and conductivity with the supplied calibration standards.
All bulk chemicals and testing reagent inventories are OK at this time.
Service Report Boiler report July 2023
Friday, July 28, 2023 7:54 AM EDT
VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208
(518) 626-5000
Report Number: 588927 Recorded By: Logan Cote
(800) 253-2908 lcote@barclaywater.com
Stratton Bldg - Boiler Room
Barclay Water Management, Inc. - 55 Chapel Street, Newton MA 02458 (800) 253-2908
Service Report Boiler report July 2023
Friday, July 28, 2023 7:54 AM EDT
VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208
(518) 626-5000
Report Number: 588927 Recorded By: Logan Cote
(800) 253-2908 lcote@barclaywater.com
Stratton Bldg - Boiler Room
Service Report Boiler report July 2023
Friday, July 28, 2023 7:54 AM EDT
VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208
(518) 626-5000
Report Number: 588927 Recorded By: Logan Cote
(800) 253-2908 lcote@barclaywater.com
Stratton Bldg - Boiler Room
Boiler 1 Offline Boiler 1 is Offline.
Boiler 2 Online Is in standby all residuals were within normal operating range.
Boiler 3 Offline Boiler 3 is Offline in wet lay up.
Boiler 4 Online Running in lead. The polymer was fed yesterday and was slightly elevated at the time of the sampling. Sulfite was within normal operating range.
Closing Comment All condensate returns are returning good quality condensate. Please keep up with regular operator rounds and testing.
Keep up the good work. Thank you.
Service Report Boiler report July 2023
Friday, July 28, 2023 7:54 AM EDT
VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208
(518) 626-5000
Report Number: 588927 Recorded By: Logan Cote
(800) 253-2908 lcote@barclaywater.com
Stratton Bldg - Boiler Room
How are we doing? Let us know at feedback@barclaywater.com. We recommend that our customers perform routine water testing between service visits, to assure the proper performance of the water treatment program on a continuous basis. For supplemented potable water systems, it’s important to remember that monochloramine, like all oxidants, will degrade based on several factors, including but not limited to residence time, temperature, pH and presence of organic material. The iChlor system is designed to increase the monochloramine levels measured at the discharge of the unit. However, monochloramine residuals at distal outlets will vary based on the aforementioned factors in the building water system. Flushing may be required, under low/no flow conditions, to increase monochloramine level at distal points. REV. 07/05/2023