June Boiler Service 2023 6-23-2023.PDF

PDF 813 KB Posted

Attached to
Z1DA--ALBANY BOILER-CHILLER PLANTS CHEMICAL TREATMENT (VA-24-00002448)
Solicitation number
36C24223Q1082
Issued by

About this file

This document is a service report from Barclay Water Management detailing the results of a routine boiler and water treatment service visit conducted at the VA Albany Stratton Building located in Albany, New York. The report indicates that Boilers 1 and 3 were offline for wet layup and inspection respectively, while Boilers 2 and 4 were online at the time of the visit. Testing showed elevated sulfite and polymer levels in Boiler 2 which was in standby mode. Polymer residuals were slightly elevated but acceptable in Boiler 4, which was in the lead. Hardness levels were minimal in the soft water and feedwater systems. The report recommends that routine water testing be performed between service visits to ensure proper performance of the water treatment program. This service aligns with federal contract opportunity number 36C24223Q1082 issued by the Department of Veterans Affairs for chemical treatment services at the VA Albany boiler-chiller plants.

View the file

Other files

File Type Posted
Albany SOW 2024 - Boiler-Chiller Chemical Treatment.doc DOC document
C03. 36C24223Q1082_3.pdf PDF
Questions II.docx DOCX document
36C24223Q1082_2.pdf PDF
2 cooling service July 2023 7-28-2023.PDF PDF
36C24223Q1082_1.docx DOCX document
Cooling report June 2023 6-7-2023.pdf PDF
Boiler report July 2023 7-28-2023.PDF PDF
P07. Wage (ALBANY).pdf PDF
36C24223Q1082.docx DOCX document
VAAR 819 219 77 VA Notice of Limitation on subcontracting.docx DOCX document
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Test Boiler 2 Boiler 4 Soft Water Feedwater Condensate Large

Conductivity (as uS/cm) 1243 750 - 3200

750 - 3200

175 - 250

0 - 50

0 - 25

Polymer, ppm 46 20 - 30

20 - 30 pH 11.7 10 - 12

11.4 10 - 12

9.2 7 - 9.5

9.1 8 - 10

9.5

8.3 - 9.5

Sulfite (ppm as SO3) 85 30 - 60

30 - 60

Hardness, total (ppm as CaCO3) 2 0 - 0

0 - 0

0 - 0

Test Low & Med Cond High Cond

Conductivity (as uS/cm) 2 0 - 25

4.2 0 - 25 pH 8.3

8.3 - 9.5

8.3 - 9.5

Hardness, total (ppm as CaCO3) 0 0 - 0

0 - 0

Opening Comment I have calibrated the new in house Myron 6P meter for pH and conductivity with the supplied calibration standards. All bulk chemicals and testing reagent inventories are OK at this time.

Service Report June Boiler Service 2023

Friday, June 23, 2023 9:56 AM EDT

VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208

(518) 626-5000

Report Number: 586261 Recorded By: Logan Cote

(800) 253-2908 lcote@barclaywater.com

Stratton Bldg - Boiler Room

Barclay Water Management, Inc. - 55 Chapel Street, Newton MA 02458 (800) 253-2908

Service Report June Boiler Service 2023

Friday, June 23, 2023 9:56 AM EDT

VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208

(518) 626-5000

Report Number: 586261 Recorded By: Logan Cote

(800) 253-2908 lcote@barclaywater.com

Stratton Bldg - Boiler Room

Service Report June Boiler Service 2023

Friday, June 23, 2023 9:56 AM EDT

VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208

(518) 626-5000

Report Number: 586261 Recorded By: Logan Cote

(800) 253-2908 lcote@barclaywater.com

Stratton Bldg - Boiler Room

Boiler 1 Offline Boiler 1 is Offline in wet lay up

Boiler 2 Online Sulfite level are elevated due to boiler in standby. Polymer levels were also elevated in this boiler.

Boiler 3 Offline Boiler 3 is Offline for inspection

Boiler 4 Online Boiler 4 was online at the time of visit in lead the boiler the polymer residuals were slightly elevated but ok at this time.

Soft Water Online Showing a small trace of hardness.

Feedwater Online Showing minimal hardness.

Service Report June Boiler Service 2023

Friday, June 23, 2023 9:56 AM EDT

VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208

(518) 626-5000

Report Number: 586261 Recorded By: Logan Cote

(800) 253-2908 lcote@barclaywater.com

Stratton Bldg - Boiler Room

How are we doing? Let us know at feedback@barclaywater.com. We recommend that our customers perform routine water testing between service visits, to assure the proper performance of the water treatment program on a continuous basis. For supplemented potable water systems, it’s important to remember that monochloramine, like all oxidants, will degrade over time.

Flushing may be required, under low/no flow conditions, to increase monochloramine level at distal points. BWF 409-7 REV. 05/24/2023