June Boiler Service 2023 6-23-2023.PDF
PDF 813 KB Posted
- Solicitation number
- 36C24223Q1082
About this file
This document is a service report from Barclay Water Management detailing the results of a routine boiler and water treatment service visit conducted at the VA Albany Stratton Building located in Albany, New York. The report indicates that Boilers 1 and 3 were offline for wet layup and inspection respectively, while Boilers 2 and 4 were online at the time of the visit. Testing showed elevated sulfite and polymer levels in Boiler 2 which was in standby mode. Polymer residuals were slightly elevated but acceptable in Boiler 4, which was in the lead. Hardness levels were minimal in the soft water and feedwater systems. The report recommends that routine water testing be performed between service visits to ensure proper performance of the water treatment program. This service aligns with federal contract opportunity number 36C24223Q1082 issued by the Department of Veterans Affairs for chemical treatment services at the VA Albany boiler-chiller plants.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Albany SOW 2024 - Boiler-Chiller Chemical Treatment.doc | DOC document | |
| C03. 36C24223Q1082_3.pdf | ||
| Questions II.docx | DOCX document | |
| 36C24223Q1082_2.pdf | ||
| 2 cooling service July 2023 7-28-2023.PDF | ||
| 36C24223Q1082_1.docx | DOCX document | |
| Cooling report June 2023 6-7-2023.pdf | ||
| Boiler report July 2023 7-28-2023.PDF | ||
| P07. Wage (ALBANY).pdf | ||
| 36C24223Q1082.docx | DOCX document | |
| VAAR 819 219 77 VA Notice of Limitation on subcontracting.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Test Boiler 2 Boiler 4 Soft Water Feedwater Condensate Large
Conductivity (as uS/cm) 1243 750 - 3200
750 - 3200
175 - 250
0 - 50
0 - 25
Polymer, ppm 46 20 - 30
20 - 30 pH 11.7 10 - 12
11.4 10 - 12
9.2 7 - 9.5
9.1 8 - 10
9.5
8.3 - 9.5
Sulfite (ppm as SO3) 85 30 - 60
30 - 60
Hardness, total (ppm as CaCO3) 2 0 - 0
0 - 0
0 - 0
Test Low & Med Cond High Cond
Conductivity (as uS/cm) 2 0 - 25
4.2 0 - 25 pH 8.3
8.3 - 9.5
8.3 - 9.5
Hardness, total (ppm as CaCO3) 0 0 - 0
0 - 0
Opening Comment I have calibrated the new in house Myron 6P meter for pH and conductivity with the supplied calibration standards. All bulk chemicals and testing reagent inventories are OK at this time.
Service Report June Boiler Service 2023
Friday, June 23, 2023 9:56 AM EDT
VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208
(518) 626-5000
Report Number: 586261 Recorded By: Logan Cote
(800) 253-2908 lcote@barclaywater.com
Stratton Bldg - Boiler Room
Barclay Water Management, Inc. - 55 Chapel Street, Newton MA 02458 (800) 253-2908
Service Report June Boiler Service 2023
Friday, June 23, 2023 9:56 AM EDT
VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208
(518) 626-5000
Report Number: 586261 Recorded By: Logan Cote
(800) 253-2908 lcote@barclaywater.com
Stratton Bldg - Boiler Room
Service Report June Boiler Service 2023
Friday, June 23, 2023 9:56 AM EDT
VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208
(518) 626-5000
Report Number: 586261 Recorded By: Logan Cote
(800) 253-2908 lcote@barclaywater.com
Stratton Bldg - Boiler Room
Boiler 1 Offline Boiler 1 is Offline in wet lay up
Boiler 2 Online Sulfite level are elevated due to boiler in standby. Polymer levels were also elevated in this boiler.
Boiler 3 Offline Boiler 3 is Offline for inspection
Boiler 4 Online Boiler 4 was online at the time of visit in lead the boiler the polymer residuals were slightly elevated but ok at this time.
Soft Water Online Showing a small trace of hardness.
Feedwater Online Showing minimal hardness.
Service Report June Boiler Service 2023
Friday, June 23, 2023 9:56 AM EDT
VA Albany Stratton Bldg 113 Holland Ave Albany NY 12208
(518) 626-5000
Report Number: 586261 Recorded By: Logan Cote
(800) 253-2908 lcote@barclaywater.com
Stratton Bldg - Boiler Room
How are we doing? Let us know at feedback@barclaywater.com. We recommend that our customers perform routine water testing between service visits, to assure the proper performance of the water treatment program on a continuous basis. For supplemented potable water systems, it’s important to remember that monochloramine, like all oxidants, will degrade over time.
Flushing may be required, under low/no flow conditions, to increase monochloramine level at distal points. BWF 409-7 REV. 05/24/2023