This document provides specifications for access doors and frames to be installed as part of a Veterans Affairs project to renovate the second floor of the Rome, New York Community Based Outpatient Clinic. The specifications cover fire-rated and non-rated access doors and frames in steel and stainless steel. Requirements include door and frame thickness, materials, finishes, hardware, installation, and testing standards. Manufacturers must submit product data and samples, with steel and stainless steel components requiring minimum recycled content percentages. The related federal contract opportunity is for the full renovation project with an estimated value between $5-10 million. The solicitation will be issued on July 22nd via beta.sam.gov.

View the file

Other files

File Type Posted
Amendment 0017.docx DOCX document
Amendment 0016.docx DOCX document
EY121B - Rev 1.pdf PDF
Amendment 0015.docx DOCX document
EP121B - Rev 2.pdf PDF
E-604 - Rev 2.pdf PDF
Amendment 0014.docx DOCX document
AE601 - Rev 2.pdf PDF
EY121C - Rev 1.pdf PDF
08 36 16 Sliding Door and Frames - Rev 1.pdf PDF
E-501 - Rev 1.pdf PDF
E-605 - Rev 1.pdf PDF
EY111 - Rev 1.pdf PDF
EY121A - Rev 1.pdf PDF
AE801 - rev 1.pdf PDF
Amendment 0013.docx DOCX document
AE802 - rev 1.pdf PDF
Amendment 0012.docx DOCX document
EL121C - Rev 1 - 211101.pdf PDF
EL121A - Rev 1 - 211101.pdf PDF
AE701 - rev 2.pdf PDF
AE501 - rev 1 - with VA red-marks.pdf PDF
AE121.A - rev 1.pdf PDF
RFI - Electric RFI.pdf PDF
EL121B - Rev 1 - 211101.pdf PDF
spec revised section - 09 06 00 Schedule of Finishes - rev 1.pdf PDF
AE121.C - rev 1.pdf PDF
AE121.B - rev 1 - with VA red-marks.pdf PDF
AE405 - Rev 1.pdf PDF
AE404 - Rev 1 - with VA red-marks.pdf PDF
AE406 - Rev 1.pdf PDF
Amendment 0011.docx DOCX document
AE407 - Rev 1.pdf PDF
AE408 - Rev 1.pdf PDF
AE403 - Rev 1.pdf PDF
AE508 - Rev 1.pdf PDF
AE409 - Rev 1.pdf PDF
AE401 - rev 1.pdf PDF
Amendment 0010.docx DOCX document
AE402 - rev 1.pdf PDF
spec added section - 11 73 00 Ceiling Mounted Patient Lift System.pdf PDF
AE507 - rev 1.pdf PDF
AE601 - rev 1.pdf PDF
spec revised section - 10 21 23 Cubicle Curtain Tracks and Curtains - REV 1b.pdf PDF
Asbestos - Lead-based Paint - Regulated Materials - 3-29-2019 report by Skelly and Loy - 92 pages.pdf PDF
Amendment 0009.docx DOCX document
AE701 - rev 1.pdf PDF
EL111 - rev 1.pdf PDF
AE702 - rev 1.pdf PDF
Amendment 0008.docx DOCX document
Show 40 more

Latest 50 of 84 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Department of Veterans Affairs Project #528A7-20-705 Renovate 2nd Floor Rome CBOC for PACT Bid Documents Rome, New York August 6, 2021

01-01-21

08 31 13 - 1

SECTION 08 31 13

ACCESS DOORS AND FRAMES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Access doors and panels installed in walls and ceilings.

1.2 RELATED WORK

A. Section 05 50 00, METAL FABRICATIONS: Wire Mesh and Screen Access

Doors.

B. Section 08 71 00, DOOR HARDWARE: Lock Cylinders.

C. Section 09 91 00, PAINTING: Field Painting.

D. Section 09 06 00, SCHEDULE FOR FINISHES: Finish Color.

E. Section 21 13 13, WET-PIPE SPRINKLER SYSTEMS: Access Doors for Control or Drain Valves.

F. Section 21 12 16, DRY-PIPE SPRINKLER SYSTEMS: Access Doors for Control or Drain Valves.

G. Section 22 40 00, PLUMBING FIXTURES: Access Doors for Plumbing Valves.

H. Section 23 31 00, HVAC DUCTS AND CASINGS: Locations of Access Doors for

Ductwork Cleanouts.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. American Welding Society (AWS):

D1.3/D1.3M-2018.........Structural Welding Code - Sheet Steel

(6th Edition.

C. ASTM International (ASTM):

A653/A653M-20...........Steel Sheet, Zinc-Coated (Galvanized) or

Zinc-Iron Alloy-Coated (Galvannealed) by the

Hot-Sip Process.

A1008/A1008M-18.........Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength

Low-Alloy with Improved Formability, Solution

Hardened, and Bake Hardenable.

A666-15.................Annealed or Cold-Worked Austenitic Stainless

Steel sheet, Strip, Plate, and Flat Bar.

E119-20.................Fire Test of Building Construction and

Materials.

D. National Fire Protection Association (NFPA):

08 31 13 - 2

80-2019 Edition.........Fire Doors and Other Opening Protectives.

252-2017 Edition........Fire Tests of Door Assemblies.

E. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-06..............Metal Finishes Manual.

F. UL LLC (UL):

Listed..................Online Certifications Directory.

10B-08 (Edition 10).....Standard for Fire Tests of Door Assemblies.

263-11 (Edition 14).....Fire Tests of Building Construction and

Materials.

1.4 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings:

1. Show size, configuration, and fabrication and installation details.

C. Manufacturer's Literature and Data:

1. Description of each product.

2. Installation instructions.

D. Sustainable Construction Submittals:

1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.

1.5 DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

1.6 STORAGE AND HANDLING

A. Store products indoors in dry, weathertight facility.

B. Protect products from damage during handling and construction operations.

1.7 FIELD CONDITIONS

A. Field Measurements: Verify field conditions affecting access door fabrication and installation. Show field measurements on Submittal

Drawings.

1. Coordinate field measurement and fabrication schedule to avoid delay.

08 31 13 - 3

1.8 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

PART 2 - PRODUCTS

2.1 MATERIALS

A. Steel Sheet: ASTM A1008/A1008M.

B. Stainless Steel: ASTM A666; Type 302 or Type 304 in wet areas and ceramic tile surfaces.

2.2 PRODUCTS - GENERAL

A. Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

B. Provide each product from one manufacturer.

C. Sustainable Construction Requirements:

1. Steel Access Doors Recycled Content: 30 percent total recycled content, minimum.

2. Stainless Steel Access Doors Recycled Content: 70 percent total recycled content, minimum.

2.3 ACCESS DOORS, FIRE-RATED

A. Door Construction:

1. Ceiling Access Door Construction: ASTM E119 or UL 263.

2. Wall Access Doors: NFPA 252 or UL 10B.

B. Label: Class B opening according to UL 10B or test by another nationally recognized laboratory. 1-1/2 hour fire-rated in fire rated shaft walls, with maximum temperature rise of 120 degrees C

(216 degrees F).

C. Door Panel: Minimum 0.9 mm (0.0359 inch) thick steel sheet, with mineral-fiber insulation core, insulated sandwich type construction.

D. Frame: Minimum 1.5 mm (0.0598 inch) thick steel sheet, depth and configuration to suit material and construction type where installed.

1. Frame Flange: Provide at units installed in concrete, masonry, or gypsum board.

2. Exposed Joints in Flange: Weld and grind smooth.

3. Provide expanded galvanized metal lath perimeter wings when installed in plaster, except veneer plaster.

E. Provide automatic closing device.

F. Hinge: Continuous steel hinge with stainless steel pin.

08 31 13 - 4

G. Lock: Self-latching, mortise type with provision for fitting flush a standard screw-in type lock cylinder.

1. Lock cylinder specified in Section 08 71 00, DOOR HARDWARE.

2. Latch release device operable from inside of door.

H. Anchors for Fire-Rated Access Doors: Comply with requirements of applicable fire test.

2.4 ACCESS DOORS, FLUSH PANEL, NON-RATED

A. Door Panel:

1. 1.9 mm (0.07 inch) thick steel or 1.5 mm (0.06 inch) thick stainless steel sheet.

2. Reinforce to maintain flat surface.

B. Frame:

1. 1.5 mm (0.06 inch) thick steel or stainless steel sheet, depth and configuration to suit material and construction type where installed.

2. Frame Flange: Provide at units installed in concrete, masonry, and gypsum board.

3. Exposed Joints in Flange: Weld and grind smooth.

4. Provide expanded galvanized metal lath perimeter wings when installed in plaster, except veneer plaster.

C. Hinge:

1. Concealed spring hinge, 175 degrees of opening.

2. Removable hinge pin to allow removal of door panel from frame.

D. Lock:

1. Flush, screwdriver-operated cam lock.

2.5 FABRICATION - GENERAL

A. Size: Minimum 600 mm (24 inches) square door unless otherwise shown or required to suit opening in suspension system of ceiling.

B. Component Fabrication: Straight, square, flat and in same plane where required.

1. Exposed Edges: Slightly rounded, without burrs, snags and sharp edges.

2. Exposed Welds: Continuous, ground smooth.

3. Welding: AWS D1.3/D1.3M.

08 31 13 - 5

C. Locks and Non-Continuous Hinges: Provide in numbers required to maintain alignment of door panel with frame. For fire-rated doors, provide hinges and locks as required by fire test.

D. Anchoring: Make provisions in frame for anchoring to adjacent construction. Provide anchors in size, number and location on four sides to secure access door to substrate. Provide anchors as required by fire test.

2.6 FINISHES

A. Steel Paint Finish:

1. Powder-Coat Finish: Manufacturer's standard two-coat finish system consisting of the following:

a. One coat primer.

b. One coat thermosetting topcoat.

c. Dry-film Thickness: 0.05 mm (2 mils) minimum.

d. Color: Refer to Section 09 06 00, SCHEDULE FOR FINISHES.

B. Stainless Steel Exposed Surfaces: NAAMM AMP 500; No.06 Metal Finishes.

2.7 ACCESSORIES

A. Fasteners: Type and size recommended by access door manufacturer, to suit application.

1. Stainless Steel Access Doors: Stainless steel fasteners.

2. Other Access Doors: Galvanized steel fasteners.

PART 3 - EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

1. Verify access door locations and sizes provide required maintenance access to installed building services components.

B. Protect existing construction and completed work from damage.

3.2 INSTALLATION - GENERAL

A. Install products according to manufacturer's instructions and approved submittal drawings.

1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

B. Install access doors and panels permitting access to service valves, traps, dampers, cleanouts, and other mechanical, electrical and

08 31 13 - 6 conveyor control items concealed in walls and partitions, and concealed above gypsum board and plaster ceilings.

C. Install fire rated access door according to NFPA 80.

D. Install fire-rated doors in fire-rated partitions.

E. Install flush access panels in partitions and in gypsum board and plaster ceilings.

3.3 ACCESS DOOR AND FRAME INSTALLATION

A. Wall Installations: Install access doors in openings with sides vertical.

B. Ceiling Installations: Install access doors parallel to ceiling suspension grid or room partitions.

C. Frames without Flanges: Install frame flush with surrounding finish surfaces.

D. Frames with Flanges: Overlap opening, with face uniformly spaced from finish surface.

E. Recessed Panel Access Doors: Install with face of surrounding materials flush with door panel installed finish.

F. Secure frames to adjacent construction with fasteners.

G. Install type, size and quantity of anchoring device suitable for material surrounding opening to maintain alignment, and resist displacement, during normal use of access door.

H. Field Painting Primed Access Doors: Comply with the requirements of

Section 09 91 00, PAINTING.

3.4 ADJUSTMENT

A. Adjust hardware so door panel opens freely.

B. Adjust door when closed so door panel is centered in frame.

- - E N D - -