Asbestos - Lead-based Paint - Regulated Materials - 3-29-2019 report by Skelly and Loy - 92 pages.pdf
PDF 6 MB Posted
- Solicitation number
- 36C24221B0053
About this file
This report summarizes the results of an asbestos, lead-based paint, and environmentally regulated materials inspection conducted at the Donald J. Mitchell VA Outpatient Clinic in Rome, New York. Homogeneous materials were sampled and analyzed for asbestos and lead content. Materials identified to contain greater than one percent asbestos include HVAC duct insulation stick pin mastic, floor tile mastic, desktop, floor tile mastic, sink undercoating, generator exhaust insulation, and roof penetration tar. Previously identified asbestos-containing materials also remain on site. Lead-based paint was identified at levels exceeding 0.5% by weight.
The pre-solicitation notice describes an upcoming project to renovate approximately 25,000 square feet of existing second floor space at the Rome CBOC to create a new primary care clinic in accordance with PACT guidelines. The renovation will include abatement of asbestos and hazardous materials, as well as demolition and reconstruction of walls, mechanical, electrical and plumbing systems. The solicitation is expected to be issued on July 22, 2021 via https://beta.sam.gov/ with a site visit scheduled thereafter. The project value is estimated between $5-10 million.
View the file
Other files
Show 40 more
Latest 50 of 84 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Office Locations: Harrisburg, PA Morgantown, WV State College, PA Hagerstown, MD Hunt Valley, MD
March 29, 2019
Mr. Shane Goodman A│E Works Ltd.
209 Sandusky Street Pittsburgh, Pennsylvania 15212
RE: Asbestos, Lead-based Paint, and Environmentally Regulated Materials Inspection Donald J. Mitchell VA Outpatient Clinic 125 Brookley Road Rome, New York
Mr. Goodman:
On February 11 through 15, 2019, Skelly and Loy, Inc. conducted an asbestos, lead based paint, and environmentally regulated materials inspection of the Donald J. Mitchell VA Outpatient Clinic located in Rome, New York. This inspection was completed in accordance with appropriate Federal and New York state regulations. The objective of this inspection was to document the presence and condition of asbestos-containing material (ACM), lead-based paint (LBP), and environmental regulated materials that will be encountered during renovation activities.
ASBESTOS INSPECTION
Appropriate safety and hygiene protocols were observed during all site activities. A visual inspection was conducted in all accessible areas within the renovation area. Due to the building being occupied during the inspection activities, destructive measures were not used to gain access to inaccessible areas and discreet sampling methods were used. Suspect asbestos building materials were classified into homogeneous areas (HAs), and bulk samples of each HA were collected based on the United States Environmental Protection Agency (US EPA) random sampling protocol.
Appropriate precautions were taken when sampling friable materials. The bulk sampling areas were first wetted with amended water and a small portion was then removed using a razor knife or other means. All bulk samples were sealed in plastic vials and logged with an appropriate chain of custody (COC).
Site asbestos inspection activities were conducted by Mr. Dominick Dercole (NY inspector license #16-02379) and assisted by Mr. Nathaniel Ruhl. Mr. Dercole is EPA trained and licensed in compliance with 12 NYCRR 56, Subpart 56-5. A copy of the inspector’s licenses is enclosed.
A visual inspection was conducted for all accessible areas within the renovation area, including above the drop ceiling tile, for suspect ACM. Suspect ACM typically includes, but is not limited
Mr. Shane Goodman to, resilient flooring, mastics, ceiling tile, wallboard, building insulation, plaster, thermal system insulation (TSI), roofing material, cementitious sheet boards and siding, and cement flue patching.
Upon identification of a suspect material, a bulk sampling scheme was developed which included the collection of the appropriate number of bulk samples per homogeneous material. A homogeneous material is defined as a material that is consistent in appearance, texture, and age of installation. All bulk samples of suspect ACM found in the renovation area were documented on COC forms with results being presented on the analytical reports.
During the inspection, the quantity and condition of suspect ACM were also assessed.
Each suspect material was assessed as either friable or non-friable. By definition, friable material can be crumbled, pulverized, or reduced to powder by hand pressure. In addition, if non-friable material is disturbed or damaged, the material has the potential to become friable. Homogeneous materials were also categorized by condition as being good, damaged, or significantly damaged.
Asbestos bulk samples were analyzed using Polarized Light Microscopy (PLM) per 40 CFR 763 and the Stratified Point-Counting Method approved by the New York State Department of Health. Per 12NYCRR56, Subparts 56-4 and 56-5, non-friable, organically bound (NOB) materials such as floor tile, cove base, mastics and adhesives were analyzed by Item 198.6 (PLM- NOB with disclaimers) and Item 198.4 (quantitative Transmission Electron Microscopy [TEM] with no disclaimers). The bulk samples were shipped to Batta Environmental Associates (BATTA), located in Newark, Delaware, for analysis using PLM with dispersion staining, as specified by the US EPA. Any sample determined to be less than 10 percent asbestos was subsequently re-analyzed using the EPA-Modified PC method. BATTA is accredited through the National Voluntary Laboratory Accreditation Program (NVLAP) and is an approved laboratory by the New York State Department of Health for analysis of asbestos in bulk samples through the Environmental Laboratory Approval Program (ELAP).
Table 1.1, Summary of Asbestos Analytical Results, lists and characterizes all samples collected and analyzed from the Donald J. Mitchell Outpatient Clinic. Bulk sample results are reported by percent and type of asbestos identified by laboratory analysis. Copies of the analytical reports and COC documentation are attached. Materials identified to contain greater than one percent asbestos are considered by definition to be ACM. Likewise, materials identified to contain asbestos equal to, or less than, one percent asbestos are considered by definition to be non- ACM. The location(s) of all ACM identified within the renovation area can be ascertained by cross-referencing the room numbers/descriptions listed in the “Location” column of the tables to the room number/descriptions designations on the enclosed figures. By law, the laboratory analyst is required to analyze all layers of a submitted sample if multiple layers exist, unless otherwise directed in the COC. Based on the information gathered, the following summary of asbestos and non-asbestos findings and conclusions is presented.
Table 1.1 Summary of Asbestos Analytical Results
Sampled Material Percent
Asbestos Quantity Location
HVAC Duct Insulation Stick Pin
Mastic
3.12% Chrysotile
500 SF
Above drop ceilings under HVAC duct insulation
12”x12” Cream Floor Tile
Previously Identified
14,000 SF
Basement Hall, Sub-Basement Stairs Rooms G100, G110, G113, G114, G117, G119 Stairs, G127, G128, G131, G136B, G139, G141, G145, 1005, 1006, 1007, 1008, 1009, 1018, 1033, 1051, 1068, 1069, 1069 Hall, 1070, 1074, 1076, 1081, 1110, 1113, 1157, 1165, 1166, 1193, 1195, 1196, 1198, 1200, 1202, 1203, 1204, 1205, 1206, 1207, 1209, 1210, 1213, 1214, 1222, 1224, 1225, 2016, 2017, 2029, 2031, 2032, 2034, 2046, 2047, 2049, 2062, 2064, 2065
12”x12” Cream Floor Tile Mastic
2.69% Chrysotile
14,000 SF
Basement Hall, Sub-Basement Stairs Rooms G100, G110, G113, G114, G117, G119 Stairs, G127, G128, G131, G136B, G139, G141, G145, 1005, 1006, 1007, 1008, 1009, 1018, 1033, 1051, 1068, 1069, 1069 Hall, 1070, 1074, 1076, 1081, 1110, 1113, 1157, 1165, 1166, 1193, 1195, 1196, 1198, 1200, 1202, 1203, 1204, 1205, 1206, 1207, 1209, 1210, 1213, 1214, 1222, 1224, 1225, 2016, 2017, 2029, 2031, 2032, 2034, 2046, 2047, 2049, 2062, 2064, 2065
Black Desktop 30.8%
Chrysotile 1 Unit Room 1014
12”x12” White and Black Floor Tile
3.26% Chrysotile
200 SF Room 1014
12”x12” White and Black Floor Tile
Mastic
Previously Identified
200 SF Room 1014
White Sink Undercoating
3.29% Chrysotile
16 Units Rooms 1022, 1077, 1078, 1085
Generator Exhaust Insulation
40% Chrysotile 300 SF Room G134
Roof Penetration Tar
6.23% Chrysotile
2 SF Corridor 2107
Fire Doors Assumed 75 Units Installed and Stockpiled Doors
• Of 83 suspect homogeneous materials encountered, 133 bulk samples were collected and submitted to the laboratory to be analyzed.
• Confirmatory samples were taken of previously analyzed materials to ensure that the material on-site was the same material previously sampled.
• Of these, HVAC Duct Insulation Stick Pin Mastic (HA 07), 12”x12” Cream Floor Tile Mastic (HA 09A), Black Desktop (HA 22), 12”x12” White and Black Floor Tile Mastic (HA 23A), White Sink Undercoating (HA 27), Generator Exhaust Insulation (HA 32), and Roof Penetration Tar (HA
42) were identified to contain asbestos at a concentration greater than one percent, making them ACM by definition.
• Previously identified materials; 12”x12” Cream Floor Tile (HA 09) and 12”x12” White and Black Floor Tile Mastic (HA 23A) remain on site.
• Due to limited accessibility for sampling, Fire Door Insulation (HA 37) was assumed to be an asbestos containing material.
• All ACM was observed to be in good condition.
LEAD-BASED PAINT INSPECTION
The lead-based paint (LBP) inspection was conducted concurrently with the asbestos inspection. The LBP inspection was completed in accordance with applicable Federal and New York state laws, rules, and regulations with the objective of documenting the presence of LBP that would likely be disturbed during renovation efforts.
The inspection included an assessment of accessible painted surfaces suspected of being LBP. Lead was commonly added to paint as a pigment, drying agent, and to add durability and corrosion resistance. Lead shielding was also identified during the course of the inspection.
All bulk paint samples were collected and sealed in plastic vials and logged with an appropriate COC. Paint samples were analyzed using Atomic Absorption Spectrophotometry (AAS) - EPA Method SW846-(3050B:7420M). The paint samples were shipped to Batta Environmental Associates located in Newark, Delaware, for analysis using AAS, as specified by the EPA with results being presented in the analytical report. The analytical report and corresponding COC documentation are enclosed.
Table 2.1, Summary of Lead Analytical Results, lists and characterizes all samples collected and analyzed from the structure. Sample results are reported in percent lead by weight identified via laboratory analysis. Samples identified to be greater than 0.5 percent lead by weight are considered to be LBP in accordance with EPA/HUD guidelines. Likewise, samples identified to be less than 0.5 percent lead by weight are not considered LBP.
Table 2.1 Summary of Lead Analytical Results
Sample Numbers Results
(% Lead by Weight)
Regulatory Limit (% Lead by
Weight) Location
L01 DD 021319 <0.0063 0.5% Room 1002
L02 DD 021319 0.090 0.5% Room 1127
L03 DD 021319 0.17 0.5% Mechanical Room
L04 DD 021319 0.17 0.5% Room 2028
L05 DD 021319 0.21 0.5% Room 2097
L06 DD 021319 8.1 0.5% Penthouse
L07 DD 021319 <0.0088 0.5% Penthouse
L08 DD 021319 2.0 0.5% Stairs near Penthouse
L09 DD 021319 0.026 0.5% Room 1082
L10 DD 021319 <0.0063 0.5% Corridor 1103
L11 DD 021319 <0.0063 0.5% Room 136B
L12 DD 021319 <0.0063 0.5% Corridor near Room 1082
• Of 12 suspect paints encountered, 12 paint samples were collected and submitted to the laboratory to be analyzed.
• Of these, the Red Structural Steel (HA 06) and Brown Handrail (HA 08) were identified to contain lead at concentrations greater than 0.5% by weight.
• In addition, lead shielding located in Rooms 1022, 1077, 1078, and 1085 was also identified during the inspection. Location and quantities of the lead shielding is located in Table 2.2.
Table 2.2 Summary of Lead Containing Materials
Identified Materials Quantity Location
Lead Shielding 1,700 SF 1022, 1077, 1078, 1085
HAZARDOUS MATERIALS SURVEY
The hazardous materials inventory was conducted concurrently with the asbestos inspection. The hazardous/environmentally regulated materials portion of this investigation involved the identification of any items, components, and containers potentially containing hazardous/environmentally regulated materials. These materials include, but are not limited to, polychlorinated biphenyls (PCBs), mercury thermostats and lighting, fluorescent lighting, PCB light ballasts, lead acid batteries, ozone-depleting components, refrigerants (CFCs), petroleum or hazardous materials drums, pesticides, chemicals, paints, etc. Additionally, electronic wastes, household chemicals, etc. were cataloged. Actual sampling of these items and/or contents of these items potentially containing hazardous/environmentally regulated materials did not occur and the assumption of the presence of hazardous/environmentally regulated materials is based on inspector experience and knowledge.
The survey of the Donald J. Mitchell Outpatient Clinic identified potentially hazardous/environmentally regulated materials as being present. These materials are listed in Table 3.1 and in the enclosed “Summary of Hazardous/Environmentally Regulated Materials”.
Table 3.1 Summary of Hazardous/Environmentally Regulated Materials
Material Estimated Quantities Location
Fluorescent bulbs 1,200 Units Throughout Building
Ballasts 1,200 Units Throughout Building
Fire Extinguishers 30 Units Throughout Building
Exit Signs 52 Units Throughout Building
Bed Lighting Units 43 Units 2nd Floor Storage (previously inpatient) Wing
Surgery Lighting Units 3 Units 2nd Floor Surgery Wing
Room Call Lights 40 Units 2nd Floor Storage (previously inpatient) Wing
Backup Lighting Lead Acid Battery
14 Units Throughout Building
This report is accurate to the best knowledge of the inspectors. It must be reiterated that the asbestos inspection was limited to visible and accessible portions of the Donald J. Mitchell Outpatient Clinic and that ACM not identified through this inspection may be present in inaccessible areas of the structure. Should suspect ACM beyond that identified through this inspection be encountered at any time in the future, Skelly and Loy recommends that it be treated as ACM until clarification by valid analytical methods is obtained. Skelly and Loy further recommends that all laws, regulations, and guidelines, governing waste disposal and the protection of human health and the environment be strictly adhered to when working with or near any confirmed or suspect ACM. The inspectors and Skelly and Loy assume no liability for financial or health consequences resulting from actions or lack of actions taken by clients as a result of this inspection.
If you have any questions or comments concerning the contents or interpretation of this letter report, please call Mr. Daniel Davis at (412) 828-1412.
Sincerely, SKELLY and LOY, Inc.
Nathaniel Ruhl Environmental Technician
NJR/rcm Enclosures cc:
File:
R19-0045.000 Rome VA ACM-Hazardous Materials Report
MASTER SUMMARY TABLE
Master Summary Table
Skelly and Loy
Donald J. Mitchell Outpatient Clinic
125 Brookley Road
Rome, New York
Structural Description Material Description/Location Quantity % Asbestos
125 Brookley Road
HVAC Duct Insulation Stick Pin Mastic 500 SF 3.12% Chrysotile
12”x12” Cream Floor Tile Mastic 14,000 SF 2.69% Chrysotile
Black Desktop 1 Unit 30.8% Chrysotile
12”x12” White and Black Floor Tile 200 SF 3.26% Chrysotile
White Sink Undercoating 16 Units 3.29% Chrysotile
Generator Exhaust Insulation 300 SF 40% Chrysotile
Roof Penetration Tar 2 SF 6.23% Chrysotile
Fire Doors 75 Units Assumed
Photographs
Skelly and Loy
Building Exterior
HVAC Duct Insulation Stick Pin Mastic
12”x12” Cream Floor Tile Mastic
Skelly and Loy
Black Desktop
12”x12” White and Black Floor Tile
Skelly and Loy
White Sink Undercoating
Generator Exhaust
Skelly and Loy
Roof Penetration Tar
Fire Doors (Stockpiled)
LIST OF ASBESTOS HOMOGENOUS AREAS
AND MAPS
Skelly and Loy, Inc. List of Homogeneous Areas
Skelly and Loy, Inc.
Project Name: Rome NY VA Project Number: R19-0045.000.01
Building Name: Donald J. Mitchell Outpatient Clinic Location: 125 Brookley Road
HA# Material Contain Asbestos?
Quantity Yes No Assumed
01 Plaster X
01A Skim Coat X
02 Black Sink Undercoating X
03 2’x4’ White Dot and Pit Ceiling Tile X
04 2’x4’ White Wormhole Ceiling Tile X
05 4” Black Cove Base X
05A 4” Black Cove Base Mastic X
06 4” Brown Cove Base X
06A 4” Brown Cove Base Mastic X
07 HVAC Duct Insulation Stick Pin Mastic X 500 SF
08 Vibration Dampener X
09 12”x12” Cream Floor Tile X 14,000 SF
09A 12”x12” Cream Floor Tile Mastic X 14,000 SF
10 Yellow Sheet Flooring X
11 12”x12” Tan Floor Tile X
11A 12”x12” Tan Floor Tile Mastic X
12 12”x12” Blue Floor Tile X
12A 12”x12” Blue Floor Tile Mastic X
13 12”x12” Purple Floor Tile X
13A 12”x12” Purple Floor Tile Mastic X
14 4” Tan Cove Base X
14A 4” Tan Cove Base Mastic X
15 Cementitious Wallboard X
16 Joint Compound X
17 12”x12” White Floor Tile X
17A 12”x12” White Floor Tile Mastic X
18 12”x12” Green Floor Tile X
Quantity Yes No Assumed
18A 12”x12” Green Floor Tile Mastic X
19 Black Epoxy Flooring X
20 Green Sheet Flooring X
21 12”x12” Purple Floor Tile X
21A 12”x12” Purple Floor Tile Mastic X
22 Black Desktop X 1 Unit
23 12”x12” White and Black Floor Tile X 200 SF
23A 12”x12” White and Black Floor Tile Mastic X 200 SF
24 4” Wall Tile Mastic X
25 4” Wall Tile Grout X
26 2’x4’ White Faux 2’x2’ Ceiling Tile X
27 White Sink Undercoating X 16 Units
28 2’x4’ White Smooth Ceiling Tile X
29 Tan and Purple Wallpaper X
30 Roof Drain Mudded Fitting over Fiberglass X
31 Tan Woven Wallpaper X
32 Generator Exhaust Insulation X 300 SF
33 Black Duct Caulk X
34 White Wrap on Fiberglass Breeching X
35 Plumber’s Paste X
36 Spray-on Fireproofing X
37 Fire Door Insulation X 75 Units
38 White Wrap on Pipe Insulation X
39 6” Black Cove Base X
39A 6” Black Cove Base Mastic X
40 1’x1’ White Wall Tile X
Quantity Yes No Assumed
41 1’x1’ White Wall Tile Mastic X
42 Roof Penetration Tar X 2 SF
43 4” Gray Cove Base X
44 Red Circle Stair Tread X
45 1” Ceramic Floor Tile Grout X
46 Beige Sheet Flooring (Under Red Circle Stair Tread) X
47 Black Underlayment (Under Red Circle Stair Tread) X
48 6” Brown Cove Base X
48A 6” Brown Cove Base Mastic X
49 Cream Sheet Flooring X
50 2nd Floor Renovation Area 12”x12” Tan Floor Tile X
50A 2nd Floor Renovation Area 12”x12” Tan Floor Tile
Mastic
X
51 2nd Floor Renovation Area 12”x12” Tan Floor Tile X
51A 2nd Floor Renovation Area 12”x12” Tan Floor Tile
52 2nd Floor Renovation Area 12”x12” Green Floor Tile X
52A 2nd Floor Renovation Area 12”x12” Green Floor Tile
53 1st Floor Corridor 12”x12” Light Tan Floor Tile X
53A 2nd Floor Renovation Area 12”x12” Green Floor Tile
54 1st Floor Corridor 12”x12” Dark Tan Floor Tile X
54A 1st Floor Corridor 12”x12” Dark Tan Floor Tile Mastic X
55 1st Floor Corridor 12”x12” Red Floor Tile X
55A 1st Floor Corridor 12”x12” Red Floor Tile Mastic X
56 Grey Speckled Sheet Flooring X
56A Grey Speckled Sheet Flooring Mastic X
57 12”x12” Pink Floor Tile X
Quantity Yes No Assumed
57A 12”x12” Pink Floor Tile Mastic X
58 4” Pink Cove Base X
58A 4” Pink Cove Base Mastic X
59 Carpet Mastic X
60 Stack Coating X
LEGEND
AE WORKS LTD.
ROME, NEW YORK 13441
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - HA-1A
FIRST FLOOR
HOMOGENOUS AREAS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
HA-27 - WHITE SINK UNDERCOATING
HA-23 - 12"x12" WHITE AND BLACK FLOOR TILE
HA-22 - BLACK DESKTOP
HA-09A - 12"x12" CREAM FLOOR TILE MASTIC
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - HA-1B
FIRST FLOOR
HOMOGENOUS AREAS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
LEGEND
HA-37 - FIRE DOORS
HA-07 - HVAC STICK PIN MASTIC
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - HA-2A
SECOND FLOOR
HOMOGENOUS AREAS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
LEGEND
HA-42 - ROOF PENETRATION TAR
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - HA-2B
SECOND FLOOR
HOMOGENOUS AREAS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
HA-32 - GENERATOR EXHAUST
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - HA-3A
BASEMENT
HOMOGENOUS AREAS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - HA-3B
BASEMENT
HOMOGENOUS AREAS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
LEGEND
SUSPECT ASBESTOS BULK SAMPLING
AND MAPS
Skelly and Loy, Inc. Suspect Asbestos Bulk Sampling Form
*If first or any sample in a supplied group is positive, then all are assumed positive ND – No Asbestos Detected
Building Name: Donald J. Mitchell Outpatient Clinic Address: 125 Brookley Road
Sampled By: DD Date: 02-15-19
Sample Number
Material HA # Location % Asbestos
01 DD
021319
Plaster – Base Coat 01 Room 2016 ND
02 DD
021319
Plaster – Base Coat 01 Room 2017 ND
03 DD
021319
Plaster – Base Coat 01 Basement Corridor ND
04 DD
021319
Plaster – Base Coat 01 Basement Corridor ND
05 DD
021319
Plaster – Base Coat 01 Basement Corridor ND
06 DD
021319
Plaster – Base Coat 01 1st Floor Corridor ND
07 DD
021319
Plaster – Base Coat 01 1st Floor Corridor ND
01A DD
021319
Plaster – Top Coat 01A Room 2016 ND
02A DD
021319
Plaster – Top Coat 01A Room 2017 ND
03A DD
021319
Plaster – Top Coat 01A Basement Corridor ND
04A DD
021319
Plaster – Top Coat 01A Basement Corridor ND
05A DD
021319
Plaster – Top Coat 01A Basement Corridor ND
06A DD
021319
Plaster – Top Coat 01A 1st Floor Corridor ND
07A DD
021319
Plaster – Top Coat 01A 1st Floor Corridor ND
08 DD
021319
Black Sink Undercoating 02 Room 2047 <0.05% Chrysotile
09 DD
021319
Black Sink Undercoating 02 Room 2070A <0.05% Chrysotile
10 DD
021319
2’x4’ White Dot and Pit Ceiling Tile 03 Room 2060 ND
11 DD
021319
2’x4’ White Wormhole Ceiling Tile 04 2nd Floor Reception Area 2012 ND
12 DD
021319
4” Black Cove Base 05 Room 2046 ND
Material HA # Location % Asbestos
12A DD
021319
4” Brown Cove Base Mastic 05A Room 2046 ND
13 DD
021319
4” Brown Cove Base 06 2nd Floor Reception Area 2012 ND
13A DD
021319
4” Brown Cove base Mastic 06A 2nd Floor Reception Area 2012 ND
14 DD
021319
HVAC Stick Pin Mastic 07 2nd Floor Corridor near Room
3.12% Chrysotile
15 DD
021319
HVAC Stick Pin Mastic 07 2nd Floor Corridor near Room
16 DD
021319
Vibration Dampener 08 G134 ND
17 DD
021319
Vibration Dampener 08 Penthouse ND
18 DD
021319
12”x12” Cream Floor Tile 09 Basement Corridor at G146 Previously Identified
18A DD
021319
12”x12” Cream Floor Tile Mastic 09A Basement Corridor at G146 2.69% Chrysotile
19 DD
021319
Yellow Sheet Flooring 10 Room 2040 ND
20 DD
021319
12”x12” Tan Floor Tile 11 Corridor 2107 ND
20A DD
021319
12”x12” Tan Floor Tile Mastic 11A Corridor 2107 Insufficient Material for Analysis
21 DD
021319
12”x12” Blue Floor Tile 12 Corridor 2107 ND
21A DD
021319
12”x12” Blue Floor Tile Mastic 12A Corridor 2107 0.09% Chrysotile
22 DD
021319
12”x12” Purple Floor Tile 13 Corridor 2107 ND
22A DD
021319
12”x12” Purple Floor Tile Mastic 13A Corridor 2107 0.08% Chrysotile
23 DD
021319
4” Tan Cove Base 14 Corridor 2107 ND
23A DD
021319
4” Tan Cove Base Mastic 14A Corridor 2107 ND
24 DD
Cementitious Wallboard 15 Room 2070A ND
Material HA # Location % Asbestos
25 DD
021319
Cementitious Wallboard 15 Room 1005 ND
26 DD
021319
Joint Compound 16 Room 2070A ND
27 DD
021319
Joint Compound 16 Room 1005 ND
28 DD
021319
12”x12” White Floor Tile 17 Corridor 2091 ND
28A DD
021319
12”x12” White Floor Tile Mastic 17A Corridor 2091 Insufficient Material for Analysis
29 DD
021319
12”x12” Green Floor Tile and Mastic 18 Corridor 2091 ND
29A DD
021319
12”x12” Green Floor Tile Mastic 18A Corridor 2091 Insufficient Material for Analysis
30 DD
021319
Black Epoxy Flooring 19 Corridor 2091 ND
31 DD
021319
Green Sheet Flooring 20 Corridor 2091 ND
32 DD
021319
12”x12” Purple Floor Tile 21 Corridor 2091 ND
32A DD
021319
12”x12” Purple Floor Tile Mastic 21A Corridor 2091 ND
33 DD
021319
Black Desktop 22 Room 1014 30.8% Chrysotile
34 DD
021319
Black Desktop 22 Room 1014 *
35 DD
021319
12”x12” White and Black Floor Tile 23 Room 1014 3.26% Chrysotile
35A DD
021319
12”x12” White and Black Floor Tile Mastic
23A Room 1014 Previously Identified
36 DD
021319
4” Wall Tile Mastic 24 Room 1014 ND
37 DD
021319
4” Wall Tile Grout 25 Room 1014 ND
38 DD
021319
2’x4’ White Faux 2’x2’ Ceiling Tile 26 1st Floor Corridor ND
39 DD
2’x4’ White Faux 2’x2’ Ceiling Tile 26 1st Floor Corridor ND
Material HA # Location % Asbestos
40 DD
021319
White Sink Undercoating 27 Room 1006 3.29% Chrysotile
41 DD
021319
White Sink Undercoating 27 Room 1009 *
42 DD
021319
2’x4’ White Smooth Ceiling Tile 28 Basement Corridor ND
43 DD
021319
2’x4’ White Smooth Ceiling Tile 28 Basement Corridor ND
44 DD
021319
Tan and Purple Wallpaper 29 Corridor 2107 ND
45 DD
021319
Tan and Purple Wallpaper 29 Corridor 2107 ND
46 DD
021319
Roof Drain Mudded Fitting over Fiberglass
30 Room 2027 ND
47 DD
021319
Tan Woven Wallpaper 31 Room 2034 ND
48 DD
021319
Tan Woven Wallpaper 31 Room 2029 ND
49 DD
021319
Generator Exhaust Insulation 32 Room G134 40% Chrysotile
50 DD
021319
Black Duct Caulk 33 Room G134 ND
51 DD
021319
Black Duct Caulk 33 Room G134 ND
52 DD
021319
White Wrap on Fiberglass Breeching 34 Room G134 ND
53 DD
021319
White Wrap on Fiberglass Breeching 34 Room G134 ND
54 DD
021319
White Wrap on Fiberglass Breeching 34 Room G134 ND
55 DD
021319
Plumber’s Paste 35 Room G134 ND
56 DD
021319
Plumber’s Paste 35 Room G134 ND
57 DD
021319
Spray-on Fireproofing 36 2nd Floor Corridor ND
58 DD
Fire Door Insulation 37 Room 2090 Assumed
Material HA # Location % Asbestos
59 DD
021319
Fire Door Insulation 37 Room 2033 – Stockpiled Doors Assumed
60 DD
021319
White Wrap on Pipe Insulation 38 Room G134 ND
61 DD
021319
White Wrap on Pipe Insulation 38 Room G134 ND
62 DD
021319
White Wrap on Pipe Insulation 38 Room G134 ND
63 DD
021319
6” Black Cove Base 39 Room GS2 ND
64 DD
021319
6” Black Cove Base 39 Room GS2
ND
63A DD
021319
6” Black Cove Base Mastic 39A Room GS2
ND
64A DD
021319
6” Black Cove Base Mastic 39A Room GS2
ND
65 DD
021319
1’x1’ White Wall Tile 40 Room 2022 ND
66 DD
021319
1’x1’ White Wall Tile 40 Room 2022 ND
67 DD
021319
1’x1’ White Wall Tile Mastic 41 Room 2022 ND
68 DD
021319
1’x1’ White Wall Tile Mastic 41 Room 2022 ND
69 DD
021319
Roof Penetration Tar 42 Corridor 2107 6.23% Chrysotile
70 DD
021319
Roof Penetration Tar 42 Corridor 2107 *
71 DD
021319
4” Gray Cove Base 43 Room 2011A ND
72 DD
021319
Red Circle Stair Tread 44 Stair S2 Landing ND
73 DD
021319
Red Circle Stair Tread 44 Stair S1 Landing ND
74 DD
021319
1” Ceramic Floor Tile Grout 45 Room 2020 ND
75 DD
1” Ceramic Floor Tile Grout 45 Room 1002 ND
Material HA # Location % Asbestos
76 DD
021319
Beige Sheet Flooring (Under Red Circle Stair Tread)
46 Stair S2 Landing ND
77 DD
021319
Beige Sheet Flooring (Under Red Circle Stair Tread)
46 Stair S2 Landing ND
78 DD
021319
Black Underlayment (Under Red Circle Stair Tread)
47 Stair S1 Landing ND
79 DD
021319
Black Underlayment (Under Red Circle Stair Tread)t
47 Stair S1 Landing ND
80 DD
021319
6” Brown Cove Base 48 Behavioral Health – Room 1211 ND
81 DD
021319
6” Brown Cove Base 48 Behavioral Health – Room 1201 ND
80A DD
021319
6” Brown Cove Base Mastic 48A Behavioral Health ND
81A DD
021319
6” Brown Cove Base Mastic 48A Behavioral Health ND
82 DD
021319
Cream Sheet Flooring 49 Room 1040 ND
83 DD
021319
Cream Sheet Flooring 49 Room 1040 ND
84 DD
021319
2nd Floor Renovation Area 12”x12” Dark Tan Floor Tile
50 Corridor 2114 ND
84A DD
021319
2nd Floor Renovation Area 12”x12” Dark Tan Floor Tile Mastic
50A Corridor 2114 Insufficient Material for Analysis
85 DD
021319
2nd Floor Renovation Area 12”x12” Tan Floor Tile
51 Corridor 2114 ND
85A DD
021319
2nd Floor Renovation Area 12”x12” Tan Floor Tile Mastic
51A Corridor 2114 ND
86 DD
021319
2nd Floor Renovation Area 12”x12” Green Floor Tile
52 Room 2127 ND
86A DD
021319
2nd Floor Renovation Area 12”x12” Green Floor Tile Mastic
52A Room 2127 Insufficient Material for Analysis
87 DD
021319
1st Floor Corridor 12”x12” Light Tan Floor Tile
53 1st Floor Corridor ND
87A DD
021319
2nd Floor Renovation Area 12”x12” Green Floor Tile Mastic
53A 1st Floor Corridor Insufficient Material for Analysis
88 DD
021319
1st Floor Corridor 12”x12” Dark Tan Floor Tile
54 1st Floor Corridor ND
Material HA # Location % Asbestos
88A DD
021319
1st Floor Corridor 12”x12” Dark Tan Floor Tile Mastic
54A 1st Floor Corridor Insufficient Material for Analysis
89 DD
021319
1st Floor Corridor 12”x12” Red Floor Tile
55 1st Floor Corridor ND
89A DD
021319
1st Floor Corridor 12”x12” Red Floor Tile Mastic
55A 1st Floor Corridor ND
90 DD
021319
Grey Speckled Sheet Flooring 56 Room 1102 ND
91 DD
021319
Grey Speck Sheet Flooring 56 Room 1102 ND
90A DD
021319
Grey Speckled Sheet Flooring Mastic 56A Room 1102 ND
91A DD
021319
Grey Speckled Sheet Flooring Mastic 56A Room 1102 ND
92 DD
021319
12”x12” Pink Floor Tile 57 Room 1038 ND
93 DD
021319
12”x12” Pink Floor Tile 57 Room 1100 ND
92A DD
021319
12”x12” Pink Floor Tile Mastic 57A Room 1093 Insufficient Material for Analysis
93A DD
021319
12”x12” Pink Floor Tile Mastic 57A Room 1100 Insufficient Material for Analysis
94 DD
021319
4” Pink Cove Base 58 Room 1093 ND
95 DD
021319
4” Pink Cove Base 58 Room 1100 ND
94A DD
021319
4” Pink Cove Base Mastic 58A Room 1093 ND
95A DD
021319
4” Pink Cove Base Mastic 58A Room 1100 ND
96 DD
021319
Carpet Mastic 59 Room 2084 ND
97 DD
021319
Carpet Mastic 59 Room 1038 0.33% Chrysotile
98 DD
021319
Stack Coating 60 G134 0.28% Chrysotile
99 DD
Stack Coating 60 G134 ND
POSITIVE SAMPLE
NEGATIVE SAMPLE
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - BS-1
FIRST FLOOR
BULK SAMPLE LOCATIONS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
25, 27
36, 37 97 82, 83
6, 6A, 39
87, 87A 7, 7A, 38 88, 88A
89, 89A
80, 80A
81, 81A
35A
BULK SAMPLE NUMBER FORMAT - ## DD 021319
92, 92A, 94, 94A
90, 90A, 91, 91A
93, 93A, 95, 95A
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - BS-2
SECOND FLOOR
BULK SAMPLE LOCATIONS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
LEGEND
POSITIVE SAMPLE
NEGATIVE SAMPLE
32, 32A
31 45 28, 28A
29, 29A, 30
24, 26, 09
11 59
13, 13A
02, 02A
72, 76, 77 65, 66, 67, 68
1001, 01A
0812, 12A
73, 78, 79
84, 84A, 85, 85A, 86, 86A
69, 70
BULK SAMPLE NUMBER FORMAT - ## DD 021319
20, 20A, 23, 23A
21, 21A, 22, 22A 47
NOTE: SAMPLE 17 DD 021319 LOCATED IN PENTHOUSE (NOT SHOWN)
BULK SAMPLE NUMBER FORMAT - ## DD 021319
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - BS-3
BASEMENT
BULK SAMPLE LOCATIONS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
5, 5A, 43 18
4, 4A, 42
54, 62
50, 51, 52, 55, 61
53, 56, 60
98, 99
03, 03A
18A
63, 63A, 64, 64A
ANALYTICAL RESULTS
AND CHAIN OF CUSTODY
ASBESTOS SITE PHOTOGRAPH
INFORMATION
Site Photograph Information
Project Name: Rome NY VA Project Number: R19-0045.000.01
Description: HVAC Duct Insulation Stick Pin Mastic Location:
Above Drop Ceilings Throughout Building
Photograph No: 01 Date: 2-12-19
Photographer: NJR
Description: 12”x12” Cream Floor Tile Mastic Location:
Basement Hall, Sub-Basement Stairs Rooms G100, G110, G113, G114, G117, G119 Stairs, G127, G128, G131, G136B, G139, G141, G145, 1005, 1006, 1007, 1008, 1009, 1018, 1033, 1051, 1068, 1069, 1069 Hall, 1070, 1074, 1076, 1081, 1110, 1113, 1157, 1165, 1166, 1193, 1195, 1196, 1198, 1200, 1202, 1203, 1204, 1205, 1206, 1207, 1209, 1210, 1213, 1214, 1222, 1224, 1225, 2016, 2017, 2029, 2031, 2032, 2034, 2046, 2047, 2049, 2062, 2064, 2065
Photograph No: 02 Date: 2-12-19
Project Name: Rome NY VA Project Number: R19-0045.000.01
Description: Black Desktop Location: Room 1014
Photograph No: 03 Date: 2-12-19
Description: 12”x12” White and Black Floor Tile Location: Room 1014
Photograph No: 04 Date: 2-12-19
Project Name: Rome NY VA Project Number: R19-0045.000.01
Description: White Sink Undercoating Location: Dental Suite
Photograph No: 05 Date: 2-12-19
Description: Generator Exhaust Location: Room G134
Photograph No: 06 Date: 2-12-19
Project Name: Rome NY VA Project Number: R19-0045.000.01
Description: Roof Penetration Tar Location: Room 2071
Photograph No: 07 Date: 2-12-19
Description: Fire Doors Location: Throughout Building
Photograph No: 08 Date: 2-12-19
LEAD BASED PAINT MASTER SUMMARY
Skelly and Loy
Donald J. Mitchell Outpatient Clinic
125 Brookley Road
Rome, New York
Structural Description Material Description/Location Quantity % Lead
125 Brookley Road
Red Structural Steel TBD 8.1
Brown Handrails 1,100 SF 2.0
Lead Wall Lining 1,700 SF Known Mateial
Photographs
Building Exterior
Red Structural Steel
Brown Handrail
Lead Wall Lining
LIST OF LEAD BASED PAINT
HOMOGENOUS AREAS AND MAPS
Contain Lead?
Quantity Yes No Assumed
01 Light Blue Doorframes X
02 Red Doorframes X
03 Tan Doorframes X
04 Mauve Doorframes X
05 Purple Doorframes X
06 Red Structural Steel X TBD
07 Red Pipes X
08 Brown Handrail X 1,100 SF
09 Off-white Walls X
10 Yellow Walls X
11 Blue Walls X
12 Green Walls X
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - HA-L-01
FIRST FLOOR
LEAD HOMOGENOUS AREAS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
AND ABOVE CEILING THROUGHOUT BUILDING
NOTE: HA-06 - RED STRUCTURAL STEEL BEHIND WALLS
LEAD WALL LINING
HA-08 - BROWN HANDRAIL
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - HA-L-2
SECOND FLOOR
LEAD HOMOGENOUS AREAS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
LEGEND
AND ABOVE CEILING THROUGHOUT BUILDING
NOTE: HA-06 - RED STRUCTURAL STEEL BEHIND WALLS
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - HA-L-3
BASEMENT
LEAD HOMOGENOUS AREAS
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
LEGEND
AND ABOVE CEILING THROUGHOUT BUILDING
NOTE: HA-06 - RED STRUCTURAL STEEL BEHIND WALLS
SUSPECT LEAD BASED PAINT BULK
SAMPLING AND MAPS
Skelly and Loy, Inc. Suspect Lead Based Paint Bulk Sampling Form
Sampled By: DD/NJR Date: 02-15-19
Material HA # Location % Lead by Weight
L01 DD
021319
Light Blue Doorframes 01 Room 1002 <0.0063
L02 DD
021319
Red Doorframes 02 Room 1127 0.090
L03 DD
021319
Tan Doorframes 03 Mechanical Room 0.17
L04 DD
021319
Mauve Doorframes 04 Room 2028 0.17
L05 DD
021319
Purple Doorframes 05 Room 2097 0.21
L06 DD
021319
Red Structural Steel 06 Penthouse 8.1
L07 DD
021319
Red Pipes 07 Penthouse <0.0088
L08 DD
021319
Brown Handrail 08 Stairs near Penthouse 2.0
L09 DD
021319
Off-white Walls 09 Room 1082 0.026
L10 DD
021319
Yellow Walls 10 Corridor 1103 <0.0063
L11 DD
021319
Blue Walls 11 Room 136B <0.0063
L12 DD
Green Walls 12 Corridor near Room 1082 <0.0063
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - BS-L-1
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
FIRST FLOOR
LEAD BULK SAMPLE LOCATIONS
L01
L02
L10
L09/L12
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
NOT TO SCALE
FIGURE - BS-L-2
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
SECOND FLOOR
LEAD BULK SAMPLE LOCATIONS
L05
L04
L08
L07
NOTE: L06 IN PENTHOUSE MECHANICAL ROOM (POSITIVE)
IN PENTHOUSE MECHANICAL ROOM (NEGATIVE)
BUILDING 510
125 BROOKLEY ROAD
ROME VA OUTPATIENT CLINIC
SKELLY LOY,
CONSULTANTS IN
ENVIRONMENT - ENERGY
ENGINEERING - PLANNING
and Inc.
BASEMENT
LEAD BULK SAMPLE LOCATIONS
NOT TO SCALE
FIGURE - BS-L-3
L03
L11
ANALYTICAL RESULTS
AND CHAIN OF CUSTODY
LEAD BASED PAINT SITE PHOTOGRAPH
INFORMATION
Project Name: Rome NY VA Project Number: R19-0045.000.01
Description: Red Structural Steel Location: Throughout Building
Photograph No: 01 Date: 2-12-19
Description: Brown Handrail Location: Stairwells
Photograph No: 02 Date: 2-12-19
Project Name: Rome NY VA Project Number: R19-0045-000-01
Description: Lead Wall Lining Location: Room 1022
Photograph No: 03 Date: 2-12-19
Project Name: Rome NY VA Project Number: R19-0045-000-01
Description: Lead Wall Lining Location: Room 1078, Room 1077
Photograph No: 04 Date: 2-12-19
Project Name: Rome NY VA Project Number: R19-0045-000-01
Description: Lead Wall Lining Location: Room 1022
Photograph No: 05 Date: 2-12-19
ENVIRONMENTALLY REGULATED
MATERIALS SUMMARY TABLE
PRE-RENOVATION ASBESTOS AND HAZARDOUS/
ENVIRONMENTALLY REGULATED MATERIALS INSPECTION
125 BROOKLEY ROAD
ROME, NEW YORK
SUMMARY OF HAZARDOUS/ENVIRONMENTALLY REGULATED MATERIALS
MATERIALS ESTIMATED QUANTITY LOCATION
Fluorescent bulbs 1,200 Units Throughout Building
Ballasts 1,200 Units Throughout Building
Fire Extinguishers 30 Units Throughout Building
Exit Signs 52 Units Throughout Building
Bed Lighting Units 43 Units 2nd Floor Storage (previously inpatient) Wing
Surgery Lighting Units 3 Units 2nd Floor Surgery Wing
Room Call Lights 40 Units 2nd Floor Storage (previously inpatient) Wing
Backup Lighting Lead Acid Battery
14 Units Throughout Building
Hazardous Materials Photographs
Fluorescent Light Bulbs and Ballasts
Fire Extinguishers
Exit Sign
Bed Lighting Units
Room Call Lights
Lead Acid Batteries in Backup Lights
INSPECTORS LICENSES
File details come from the government source that posted it. Updated .