26_0327-4.AS803-Add2 B4Elev 523A5-18-371.pdf

PDF 2 MB Posted

Attached to
Z2DA--523A5-18-371 Building 4 Elevator Replacement (Brockton)
Solicitation number
36C24126Q0250
Issued by

About this file

This is an architectural construction drawing document that provides detailed specifications for building and elevator system replacements at a federal facility under the Office of Real Estate and Facilities Management, U.S. Department of Veterans Affairs. The drawing set (designated 4.AS803) includes typical construction details for roof access doors, exhaust louvers, and exterior wall penetrations at a penthouse level with elevations referenced at 334'-2½" (Penthouse Low Roof) and 339'-11¼" (Penthouse Roof).

The specifications detail hollow metal door frame installations with associated structural modifications including saw-cut brick openings, new loose lintels per structural requirements, ice and water shield membrane wrapping around openings, brake metal angle flashing at full wall width, sealant joints, and existing brick veneer patching and repair. Additional work includes installation of extruded aluminum mechanical louvers, control dampers, elevator shaft exhaust louvers, and condenser units with cowling as referenced in mechanical drawings. All work requires field verification of existing conditions by the contractor, with wall penetrations to maintain proper brick coursing and integration with existing waterproofing systems. The construction documents are scaled at 3"=1'-0" and reference coordination with structural, mechanical, and other trade drawings for complete system integration.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXSITING BRICK

EXSITING STRUCTURE

HOLLOW METAL

DOOR FRAME

CUT WALL AS REQ. TO

SIZE FOR DOOR

NOTE:

CONTRACTOR SHALL VERIFY ALL CONDITIONS IN FIELD

DOOR AS SCHEDULED

WRAP ICE AND WATER

SHIELD STRIP MEMBRANE

AROUND NEW OPENING

AND ADHERE TO EXIST.

WATERPROOFING

SAW CUT BRICK AS REQ.

FOR NEW DOOR WIDTH

SEALANT JOINT

BRAKE METAL ANGLE

FLASHING AT FULL WIDTH OF

EXISTING EXPOSED WALL

EXSITING BRICK

VENEER, PATCH AND

REPAIR AS REQ. FOR

NEW LOOSE LINTEL

EXSITING

STRUCTURE

SEALANT JOINT

NEW LOOSE LINTEL, SEE

STRUCTURAL FOR SIZE

HOLLOW METAL

DOOR FRAME

NOTE:

CONTRACTOR SHALL VERIFY ALL CONDITIONS IN FIELD

WRAP ICE AND WATER

SHIELD STRIP MEMBRANE

AROUND NEW OPENING

AND ADHERE TO EXIST.

WATERPROOFING

DOOR AS SCHEDULED

INFILL GAP AT U/S OF

STRUCTURE AS REQ.

BRAKE METAL ANGLE

FLASHING AT FULL WIDTH

OF EXISTING EXPOSED

WALL

EXSITING

STRUCTURE

EXSITING BRICK

NOTE:

CONTRACTOR SHALL VERIFY ALL CONDITIONS IN FIELD

DOOR AS SCHEDULED

METAL FLASHING

DOOR JAMB BEYOND

WRAP ICE AND WATER

SHIELD STRIP MEMBRANE

AROUND NEW OPENING

AND ADHERE TO EXIST.

WATERPROOFING

FACE OF CMU BEYOND

BRAKE METAL CLOSURE

PANEL, DEPTH OF WALL, VIF.

METAL DOOR THRESHOLD,

MATCH FULL DEPTH OF

WALL, MECHANICALLY

FASTENED, FULL BED OF

SEALANT BELOW

EXTRUDED ALUMINUM

MECHANICAL LOUVERS,

TYP.

EXISTING STRUCTURE

NOTE:

CONTRACTOR SHALL VERIFY ALL CONDITIONS IN FIELD

EXSITING BRICK VENEER,

PATCH AND REPAIR AS REQ.

FOR NEW LOOSE LINTEL

WRAP ICE AND WATER

SHIELD STRIP MEMBRANE

AROUND NEW OPENING AND

ADHERE TO EXIST.

WATERPROOFING

SEALANT JOINT

NEW LOOSE LINTEL, SEE

STRUCTURAL FOR SIZE

NEW FLASHING W/

DRIP EDGE

CONTROL DAMPER

NOTE:

CONTRACTOR SHALL VERIFY ALL CONDITIONS IN FIELD

EXTRUDED ALUMINUM

MECHANICAL LOUVERS,

TYP.

EXISTING STRUCTURE

EXSITING BRICK VENEER,

PATCH AND REPAIR AS REQ.

FOR NEW LOOSE LINTEL

SEALANT JOINT

NOTE:

CONTRACTOR SHALL VERIFY ALL CONDITIONS IN FIELD

EXTRUDED ALUMINUM

MECHANICAL LOUVERS,

TYP.

EXISTING STRUCTURE

EXSITING BRICK

VENEER, PATCH AND

REPAIR AS REQ. FOR

NEW LOOSE LINTEL

SEALANT JOINT

METAL SILL FLASHING SET

INTO SEALANT BED AT

T.O. NEW SILL

WRAP ICE AND WATER

SHIELD STRIP MEMBRANE

AROUND NEW OPENING

AND ADHERE TO EXIST.

WATERPROOFING

CONTROL DAMPER

Penthouse Low Roof 334' - 2 1/2"

19b

Elevator Machine Floor

330' - 6 1/2"

Penthouse Roof 339' - 11 1/4"

4.AS803

4.AS803

4.AS803

5'

- 8 1/

2" 2'

- 0

CONTROL DAMPER

Roof / Penthouse Floor

324' - 1 1/2"

Penthouse Low Roof 334' - 2 1/2"

H

4.AS803

4.AS803

4.AS803

COORD. W/ EQUIPMENT FOR

SIZE OF NEW DOOR OPENING

6'

- 3

1'

- 1 0"

I

4.AS803

4.AS803

4.AS803

NEW ELEVATOR SHAFT EXHAUST LOUVERS,

SEE MECHANICAL DRAWINGS

NEW CONDENSOR W/ COWLING,

SEE MECHANICAL DRAWINGS

COWLING FOR WALL PENETRATIONS

ALIGN CUT OPENING W/ COURSING

2' - 0"

21b

PHC04a

OUTLINE OF EXIST. DOOR

TO BE REMOVED

CUT WALL THIS SIDE OF DOOR AS

REQ. FOR NEW 40" DOOR WIDTH

SIZE DOOR HEIGHT TO BE ALIGNED

W/ HORIZ. BRICK COURSING

APPROX. LINE OF ROOF DECK

4.AS80321b

4.AS803

PHC04a

EXIST. CMU

BLOCK WALL

CUT WALL THIS SIDE OF DOOR AS

REQ. FOR NEW 40" DOOR WIDTH.

SAW CUT NEW OPENING FOR

CLEAN & UNIFORM APPEARANCE

REMOVE CMU ABOVE DOOR

TO U/S OF EXISTING BEAM

FINISH FLOOR

APPROX. LINE OF ROOF DECK

EXIST. STRUCTURE

OUTLINE OF EXIST. DOOR

TO BE REMOVED

4.AS803

4.AS803

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT STAMPCONSULTANTS

321 4 5 6 7 8 9 10

523A5-18-371

VAMC BROCKTON

940 BELMONT STREET

BROCKTON, MA 02301

BUILDING 4 ELEVATOR

REPLACEMENT

872 Massachusetts Avenue, Suite 2-9 Cambridge, MA 02139

T: 617.335.5186

William Pevear Architects, Inc.

63 Pleasant Street

T: 617.926.9300

RSE Associates, Inc.

STRUCTURAL:

101 Summer Street

T: 617.574.5099

Van Deusen & Associates

ELEVATOR CONSULTANT:

142 Hanlon Road

T: 508.397.5417

Hastings Consulting, Inc.

CODE CONSULTANT:

Watertown, MA 02472Boston, MA 02210 Holliston, MA 01746

Drawing Scale

08/16/2019

63 Franklin Street

T: 617.542.0810

Architectural Engineers, Inc.

MECH / ELEC / PLUMBING:

Boston, MA 02110

C :\U se rs

\a do rn .W

PA

\D oc um en ts

\V A_

Br oc kt on

_B

El ev at or

U pg ra de

-2

5_ ad or n@ w illi am pe ve ar

.c om

.rv t

3/

/2

2:

:1

PM

As indicated

4.AS803

Typical Exterior Details

SCALE: 3" = 1'-0"

21 TYPICAL DETAIL - ROOF ACCESS DOOR JAMB

SCALE: 3" = 1'-0"

31 TYPICAL DETAIL - ROOF ACCESS DOOR HEAD

SCALE: 3" = 1'-0"

11 TYPICAL DETAIL - ROOF ACCESS DOOR SILL

SCALE: 3" = 1'-0"

32 TYPICAL DETAIL - EXHAUST LOUVERS AT HEAD

SCALE: 3" = 1'-0"

22 TYPICAL DETAIL - EXHAUST LOUVERS AT JAMB

SCALE: 3" = 1'-0"

12 TYPICAL DETAIL - EXHAUST LOUVERS AT SILL

1/2" = 1'-0"5 Exterior Penthouse Wall Section - Exhaust Louvers

1/2" = 1'-0"3 Exterior Penthouse Wall Section - Roof Access Door

1/2" = 1'-0"4 Exterior Penthouse Elevation - 1

1/2" = 1'-0"2 Exterior Penthouse Elevation - 2 1/2" = 1'-0"1 PHC04a Door Elevation

Revisions: Date:

Addendum #2 03/27/2026

File details come from the government source that posted it. Updated .