This document contains Computational Fluid Dynamics (CFD) simulation reports analyzing cooling system performance in extra small computer rooms for use within the Department of Veterans Affairs (VA). The reports evaluate two room configurations—a rectangular version (20 ft × 39.5 ft) and a square version (24 ft × 32.5 ft)—both with 12 ft ceiling heights and identical equipment configurations: 2 downflow CRACs (Computer Room Air Conditioning units), 10 server racks, 2 hot boxes, and partitioning elements. Both simulations assume one CRAC unit failure, with the operational CRAC (Liebert DS053AS/AD/DS/DD model) supplying 8,000 CFM against a total heat load demand of 45.5 kW and 7,497 CFM airflow requirement, achieving adequate cooling with all heat loads successfully managed by the single functioning downflow unit.

The rectangular configuration demonstrates marginally higher temperature concerns, with one rack exceeding 80°F maximum inlet temperature and two racks between 75–80°F, while nine racks remained below 70°F. The square configuration performs optimally, with all 12 racks (including hot boxes) maintaining inlet temperatures below 70°F. Both rooms maintain a heat load density of approximately 61–62 W/sq ft across net floor areas of 732–742 sq ft. Thermal visualization data at multiple heights (4 feet and 10.5 feet above floor) and three-dimensional temperature fog representations illustrate airflow patterns and temperature stratification. The reports provide detailed rack-by-rack temperature metrics, including inlet/outlet temperatures and airflow volumes, demonstrating the adequacy of the current cooling infrastructure under single-unit failure scenarios.

View the file

Other files

File Type Posted
08 Attachment No. 1 to GSA Form 1364 - TEMPLATE_15-20 Yr_1.xlsx XLSX spreadsheet
17 - Offering Entity Acknowledgement Form.pdf PDF
04B - Lease Exhibit - New Construction_FEB 2026.pdf PDF
05A10 Appendix A10 Generic Extra-Small CSC Design Narrative.pdf PDF
09 - VA Form 10091 - FSC Vendor File Request.pdf PDF
05A06 Appendix A.6 VA_Leased_CBOC_Standard Layout Guide 10_29_25.pdf PDF
00 Global RLP Template R100 - VA Version_MAY 2026_ Macon.pdf PDF
12 - GSA Standard Form 330 - Architect Engineer Qualifications.pdf PDF
14 - Operations and Maintenance Plan Acknowledgement_FEB 2026.pdf PDF
10 - Past Performance List of References_FEB 2026.docx DOCX document
A- RLP Exhibit - New Construction_FEB 2026.pdf PDF
03 - Offeror Compliance Matrix_BVTO_FEB 2026.xlsx XLSX spreadsheet
05B Appendix B_LSN_Lease Service Narrative 7.28.26.pdf PDF
05A01 Appendix A.1 ProjectRoomContents_FY25 MACON GA HCC Final Excel 2026.07.08.xlsx XLSX spreadsheet
16 - Certification and Commitment of Building Energy Performance and Green Globes_FEB 2026.pdf PDF
02 - Pre-Bid Conference Registration Form_FEB 2026.docx DOCX document
04 Global Lease Template L100 - VA Version_MAY 2026.pdf PDF
C - RLP Exhibit - Prospectus_FEB 2026.pdf PDF
04A - Exhibit Lease - Broker Project_MAY 2026.pdf PDF
05A09 Appendix A.9 2 Visio-Generic Extra Small Data Center Design Package 2.pdf PDF
05A041 Appendix 05A.4.1 OIT Data Center Design.pdf PDF
00 No Proposal_Market Response Form_MAR 2026.docx DOCX document
13 - GSA Form 527 - Contractors Qualifications and Financial Information.pdf PDF
01- 3516 Solicitation Provisions_Feb. 2025.pdf PDF
07 - GSA Form 1364 - Proposal to Lease Space.pdf PDF
11 - Past Performance Questionnaire - PPQ_FEB 2026.pdf PDF
05A04 Appendix A.4 VA CBOC Info Transp Sys Specs 5_29_2025.pdf PDF
05A07 Appendix A.7 Macon HCC 2 Floors.pdf PDF
21-Bibb County Davis Bacon.pdf PDF
05A2 Appendix A.2_4-1 VA_Leased_CBOC_Design_Narrative_LDN_9-23-2026.pdf PDF
05A PFD_FY25 MACON GA HCC_Final_ 2026.07.29.pdf PDF
05A03 Appendix A.3 Room_Data_Matrix_7_3_24 _1.xlsx XLSX spreadsheet
04C - Exhibit Lease - Prospectus_MAY 2026.pdf PDF
05A05 Appendix A.5 VA Security Requirements_FSL Level II_ Oct 2024.pdf PDF
05 Agency Specific Requirements_ASR - Cover Page.pdf PDF
20 - VA Handbook 6500.6 - 3.12.10 FOR RLP.pdf PDF
06 - GSA Form 1217 - Lessors Annual Cost Statement.pdf PDF
18 - FAR 52.204-24 Representation Regarding Certain Telecom.pdf PDF
36C10F26R0088.docx DOCX document
05A2_1 Addendum A to LDN- Macon - Oct 2026.pdf PDF
05A08 Appendix A.8 Macon HCC 3 floor.pdf PDF
15 - GSA Form 12000 for Prelease Fire Protection and Life Safety Evaluation for an Office Building_May 2015.pdf PDF
B - RLP Exhibit - Broker Project_MAY 2026.pdf PDF
19 - 3517B General Clauses_Apr. 2026.docx.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Computational Fluid Dynamics (CFD) Simulation - Extra Small Computer Room - Rectangle Version

This report contains the results and images from a CFD simulation. It shows the performance of the current cooling system in this representation of a generic extra small computer room for use within VA.

Data Center & Infrastructure Engineering Solution Delivery, DevSecOps, OIT

Geometry and Objects Data Center Dimensions

Item Value Floor Length 20.0 ft Floor Width 39.5 ft Tile Size 24.0 inch UF Plenum Height 0.0 inch Real Ceiling Height 12.0 ft

Object Count Object Count Downflow CRACs 2 Server Racks 10 Hot Boxes 2 Vertical Partitions 6 Horizontal Partitions 1

Downflow CRACs by Style Downflow CRAC Style Total Units Failed Units Total Airflow (CFM) Nominal Cooling (Ton) Nominal Cooling (kW)

Liebert DS053AS/AD/DS/DD 2 1 8,000 15.1 53.2

Racks by Style Rack Style Total Racks Turned Off Total Heat Load (kW) Total Airflow (CFM)

CPI TeraFrame 60 cm x 110 cm x 45 U (Ducted) 6 0 30.0 4,731

CPI TeraFrame NF8N with Chimney 4 0 11.2 1,766

Heat Load/Cooling Airflow Total Heat Load and Airflow

Item Value Net Floor Area 742 sq ft Heat Load Density 61.2 W/sq ft Total Heat Load 45.5 kW Total Airflow Demand 7,497 CFM Total Airflow Supplied 8,000 CFM

Cooling Airflow Supplied Source Value Downflow CRACs 8,000 CFM Special CRACs 0.0 CFM Upflow CRACs 0.0 CFM In-Row Coolers 0.0 CFM Overhead Coolers 0.0 CFM Spot Coolers 0.0 CFM UF Vents (Net) 0.0 CFM AF Inlet Vents 0.0 CFM

Summary of AF Results Total Heat Load and Cooling

Item Value Total Airflow Demand 7,497 CFM Total Airflow Supply 8,000 CFM Total Heat Load 45.5 kW Cooling by Cooling Units 45.5 kW

Heat Loads and Cooling Achieved Item kW Ton Server Rack Heat Load 41.2 11.7 Hot Box Heat Load 4.26 1.21 Cooling by Downflow CRACs 45.5 12.9 Cooling by Upflow CRACs 0.0 0.0 Cooling by RDHx 0.0 0.0 Cooling by In-Row Coolers 0.0 0.0 Cooling by Overhead Coolers 0.0 0.0 Cooling by Spot Coolers 0.0 0.0 Cooling by Inlet Vents 0.0 0.0

Rack Temperature Results Rack Statistics

Range of Max Inlet Temp Number of Racks Above 80 F 1 Between 75 F and 80 F 0 Between 70 F and 75 F 2 Below 70 F 9

Hot Boxes are included

Rack Temperatures in Detail No. Rack or HotBox Name Xref Yref Heat Load Nominal Airflow Actual Airflow TinMax ToutMax Tbot_F Tmid_F Ttop_F

1 Row 2 - HDA A_1 7.0 6.1 2.80 442 824 67.8 78.5 67.2 67.6 67.7

2 Row 2 - HDA A 10.4 6.1 2.80 442 782 68.6 79.9 67.4 67.7 67.8

3 Row 2 - Rack 8 SD 13.8 6.0 5.00 789 896 69.2 86.8 67.5 68.0 68.7

4 Row 2 - Rack 9 SD 15.8 6.0 5.00 789 854 69.0 87.5 67.8 67.9 68.5

5 Row 2 - Rack 10 SD 17.8 6.0 5.00 789 818 68.7 88.0 67.9 67.7 68.2

6 Row 2 - Rack 3 SD 19.8 6.0 5.00 789 791 68.2 88.1 67.9 67.7 67.9

7 Row 2 - Rack 1 SD 21.8 6.0 5.00 789 770 68.0 88.5 67.9 67.7 67.7

8 Row 2 - Rack 2 SD 23.8 6.0 5.00 789 750 68.0 89.1 68.0 67.8 67.7

9 Row 2 - HDA B_1 25.8 6.1 2.80 442 452 69.8 89.4 68.1 67.9 67.8

10 Row 2 - HDA B 29.1 6.1 2.80 442 446 71.4 91.2 68.8 68.1 67.9

11 Hot Box 1 25.3 16.4 2.13 500 500 88.6 90.9

12 Hot Box 1_1 7.3 16.4 2.13 500 500 70.5 83.1

Xref and Yref in ft; Heat Load in kW; Airflow in CFM; Temperatures in F.

Results for Cooling Units Downflow CRACs: Cooling & Temperatures

Name Xref Yref Airflow T_Return T_Supply Cooling (Ton) Cooling (kW)

CRAC 1 3.0 2.8 8,000 85.4 66.3 12.9 45.5

CRAC 1_1 36.5 11.0 turned off ----- ----- ----- -----

Xref and Yref in ft; Airflow in CFM; Temperatures in F; Cooling Produced in Ton and kW.

Four Feet Above Floor

Temperature Fog

X Axis View

One CRAC Failed

Y Axis View

One CRAC Failed

10.5 Feet Above the Floor

Computational Fluid Dynamics (CFD) Simulation - Extra Small Computer Room - Square Version

This report contains the results and images from a CFD simulation. It shows the performance of the current cooling system in this extra small computer room for use within VA.

Data Center and Infrastructure Engineering Solution Delivery, DevSecOps, OIT

Geometry and Objects Data Center Dimensions

Item Value Floor Length 24.0 ft Floor Width 32.5 ft Tile Size 24.0 inch UF Plenum Height 0.0 inch Real Ceiling Height 12.0 ft

Object Count Object Count Downflow CRACs 2 Server Racks 10 Hot Boxes 2 Vertical Partitions 6 Horizontal Partitions 2

Downflow CRACs by Style Downflow CRAC Style Total Units Failed Units Total Airflow (CFM) Nominal Cooling (Ton) Nominal Cooling (kW)

Liebert DS053AS/AD/DS/DD 2 1 8,000 15.1 53.2

Racks by Style Rack Style Total Racks Turned Off Total Heat Load (kW) Total Airflow (CFM)

CPI TeraFrame 60 cm x 110 cm x 45 U (Ducted) 6 0 30.0 4,731

CPI TeraFrame NF8N with Chimney 4 0 11.2 1,766

Heat Load/Cooling Airflow Total Heat Load and Airflow

Item Value Net Floor Area 732 sq ft Heat Load Density 62.1 W/sq ft Total Heat Load 45.5 kW Total Airflow Demand 7,497 CFM Total Airflow Supplied 8,000 CFM

Cooling Airflow Supplied Source Value Downflow CRACs 8,000 CFM Special CRACs 0.0 CFM Upflow CRACs 0.0 CFM In-Row Coolers 0.0 CFM Overhead Coolers 0.0 CFM Spot Coolers 0.0 CFM UF Vents (Net) 0.0 CFM AF Inlet Vents 0.0 CFM

Summary of AF Results Total Heat Load and Cooling

Item Value Total Airflow Demand 7,497 CFM Total Airflow Supply 8,000 CFM Total Heat Load 45.5 kW Cooling by Cooling Units 45.5 kW

Heat Loads and Cooling Achieved Item kW Ton Server Rack Heat Load 41.2 11.7 Hot Box Heat Load 4.26 1.21 Cooling by Downflow CRACs 45.5 12.9 Cooling by Upflow CRACs 0.0 0.0 Cooling by RDHx 0.0 0.0 Cooling by In-Row Coolers 0.0 0.0 Cooling by Overhead Coolers 0.0 0.0 Cooling by Spot Coolers 0.0 0.0 Cooling by Inlet Vents 0.0 0.0

Rack Temperature Results Rack Statistics

Range of Max Inlet Temp Number of Racks Above 80 F 0 Between 75 F and 80 F 0 Between 70 F and 75 F 0 Below 70 F 12

Hot Boxes are included

Rack Temperatures in Detail No. Rack or HotBox Name Xref Yref Heat Load Nominal Airflow Actual Airflow TinMax ToutMax Tbot_F Tmid_F Ttop_F

1 Row 2 - HDA B 10.7 17.7 2.80 442 657 68.0 81.5 67.9 68.0 68.0

2 Row 2 - HDA B_1 14.0 17.7 2.80 442 619 67.9 82.2 67.9 67.9 67.9

3 Row 2 - Rack 2 SD 16.0 18.0 5.00 789 841 68.2 86.9 68.1 68.0 67.9

4 Row 2 - Rack 1 SD 18.0 18.0 5.00 789 831 68.3 87.3 68.3 68.1 67.9

5 Row 2 - Rack 3 SD 20.0 18.0 5.00 789 820 68.4 87.6 68.4 68.3 68.0

6 Row 2 - Rack 10 SD 13.0 6.1 5.00 789 866 68.2 86.4 68.2 67.8 67.2

7 Row 2 - Rack 8 SD 15.0 6.0 5.00 789 845 68.3 87.0 68.3 68.0 67.4

8 Row 2 - Rack 9 SD 17.0 6.0 5.00 789 825 68.3 87.4 68.3 68.2 67.6

9 Row 2 - HDA A_1 19.0 6.4 2.80 442 568 68.1 83.7 68.1 67.9 67.6

10 Row 2 - HDA A 22.4 6.4 2.80 442 558 68.1 83.9 68.0 67.9 67.8

11 Hot Box 1 7.2 6.4 2.13 500 500 67.4 80.6

12 Hot Box 1_1 25.8 17.7 2.13 500 500 68.2 81.6

Xref and Yref in ft; Heat Load in kW; Airflow in CFM; Temperatures in F.

Results for Cooling Units Downflow CRACs: Cooling & Temperatures

Name Xref Yref Airflow T_Return T_Supply Cooling (Ton) Cooling (kW)

CRAC 1 3.0 8.0 8,000 85.3 66.4 12.9 45.5

CRAC 1_1 29.5 16.2 turned off ----- ----- ----- -----

Xref and Yref in ft; Airflow in CFM; Temperatures in F; Cooling Produced in Ton and kW.

Temperature Fog

Four Feet Above Floor

X Axis

Y Axis

10.5 Feet Above Floor

File details come from the government source that posted it. Updated .