3. 19-035903_VTD Upgrades-100%Type B Drawings_240402_REV.pdf
PDF 34 MB Posted
- Attached to
- VTD Upgrades Federal contract opportunity
- Solicitation number
- 6973GH-24-R-00121
About this file
This document is a set of 100% type B drawings for the VTD Upgrades project, which is a federal contract opportunity solicited by the Department of Transportation Federal Aviation Administration Franchise Acquisition Services.
The key details are:
The solicitation number is 6973GH-24-R-00121 for the VTD Upgrades project at the Mike Monroney Aeronautical Center in Oklahoma City, OK. The project involves upgrading the heating, ventilating, and air-conditioning (HVAC) systems in the 24,531 SF VTD facility, including replacing two 100-ton air-cooled chillers, primary and secondary chilled water pumps, variable air volume air handling units, computer room air-conditioning units, and updating the existing energy management control system. Site drainage rework, new natural gas piping, and replacement of the existing diesel engine generator with a natural gas engine generator are also required. Proposals must be submitted by 5:00 p.m. Central Time on June 28, 2024 to the Contracting Officer, Elizabeth Fikes.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Oklahoma City, Oklahoma 73169FAA-MMC: VOR/TACAN/DME (VTD) UPGRADES
SHEET INDEX
GENERAL
G000 COVER SHEET / INDEX
G001 LOCATION PLAN
G002 GENERAL NOTES, ABBREVIATIONS, & SYMBOLS
CIVIL EXHIBITS
C100 GENERAL NOTES
C200 SURVEY
C300 DEMOLITION & EROSION CONTROL PLAN
C400 SITE PLAN
C401 UTILITY PLAN
C500 GRADING PLAN
C600 DETAILS
ARCHITECTURAL
D201 DEMOLITION FLOOR PLAN
D202 DEMOLITION ROOF PLAN
A201 FLOOR PLAN
A202 REFLECTED CEILING PLAN
A203 ROOF PLAN
A204 ENLARGED CANOPY PLANS AND DETAILS
A205 PLAN DETAILS
A301 WALL SECTIONS AND DETAILS
A302 ROOF DETAILS
A303 ENLARGED DETAILS
A401 DOOR & WINDOW ELEVATIONS & DETAILS
A402 PARTIAL BUILDING ELEVATIONS
STRUCTURAL
S.000 GENERAL NOTES
S.001 ENLARGED CANOPY FOUNDATION PLAN & DETAILS
S.101 ENLARGED CANOPY FOUNDATION PLAN AND DETAILS
S.201 ENLARGED CANOPY FRAMING PLAN AND DETAILS
MECHANICAL
M001 MECHANICAL LEGEND, SYMBOLS, AND NOTES
M002 MECHANICAL SCHEDULES
M003 MECHANICAL SCHEDULES
M100 MECHANICAL DEMOLITION PLAN - HVAC
100% Type "B" Design - Issued For Construction Contract # 6973GH-21-D-00044 Work Order # 2019-035909
Structural Engineers:MEP Engineers:Civil Engineers:
www.SA.Studio
8101 S. MacArthur Blvd.
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
Fire Protection Engineer:
MECHANICAL (CONTINUED)
M101 MECHANICAL DEMOLITION PLAN - ROOF
M102 MECHANICAL DEMOLITION PLAN -PIPING
M103 ENLARGED MECHANICAL DEMOLITION PLANS
M200 MECHANICAL PLAN - HVAC
M201 MECHANICAL PLAN - ROOF
M202 MECHANICAL PLAN - CHW, HW, & REFRIGERANT PIPING
M203 ENLARGED MECHANICAL PLANS
M300 MECHANICAL SECTIONS
M400 MECHANICAL DETAILS
M401 MECHANICAL PIPING DIAGRAM AND DETAILS HEATING WATER
SYSTEM
M402 MECHANICAL PIPING DIAGRAM AND DETAILS CHILLED WATER
SYSTEM
M500 MECHANICAL CONTROLS LEGEND OF SYMBOLS, ABBREVIATIONS
AND SCHEDULES
M501 MECHANICAL CONTROLS - FIRST FLOOR PLAN
M502 MECHANICAL CONTROLS - ROOF PLAN
M503 MECHANICAL CONTROLS - VAV AIR HANDLING UNIT
M504 MECHANICAL CONTROLS AIR TERMINAL UNITS AND EXHAUST
FANS
M505 MECHANICAL CONTROL - HEATING WATER SYSTEM
M506 MECHANICAL CONTROL - CHILLED WATER SYSTEM
ELECTRICAL
E.100 SINGLE-LINE DIAGRAM
E.201 EXTERIOR LIGHTING DEMOLITION PLAN
E.202 ELECTRICAL DEMOLITION PLAN
E.203 LIGHTING DEMOLITION PLAN - FIRST FLOOR
E.204 LIGHTING DEMOLITION PLAN UPPER LEVELS
E.301 LIGHTING PLAN EXTERIOR
E.302 ELECTRICAL POWER PLAN
E.303 LIGHTING PLAN -FIRST FLOOR
E.304 LIGHTING PLAN - UPPER LEVELS
E.401 LIGHTING CONTROL SCHEME PLAN - FIRST FLOOR
E.501 LIGHTING SCHEDULE AND DETAIL
FIRE PROTECTION
FA-1 FIRE ALARM PLAN - DEMOLITION
FA-2 FIRE ALARM PLAN - NEW
FA-3 FIRE ALARM PLAN - RISER & MATRIX
FA-4 FIRE ALARM PLAN - TESTING
02/08/2024
SPECIAL
CIVIL INSTITUTE
1 SCALE: NOT TO SCALE
LOCATION PLAN
NORTH
SCREENING
FACILITY.
BADGE AND
PASSES
LOCATION NOTES:
1. ALL CONSTRUCTION VEHICLES MUST GO
THROUGH THE CONSTRUCTION GATE AT THE
SCREENING FACILITY BEFORE THEY ARE
ABLE TO ENTER THE MMAC CAMPUS.
2. THE REAL ID ENFORCEMENT IS SCHEDULED
TO GO INTO EFFECT IN OKLAHOMA ON MAY 7,
2025. ALL CONTRACTORS AND
SUB-CONTRACTORS WHO DO NOT HAVE A
FAA BADGE WILL BE REQUIRED TO HAVE
VALID/ACCEPTABLE IDENTIFICATION TO
ENTER THE MMAC CAMPUS.
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
63G001 2
VTD GUARD SHACK (220).
ALL CONSTRUCTION
TRAFFIC ENTERS THRU THIS
GATE.
PROJECT
LOCATION
PROPOSED AREA FOR
CONTRACTOR STAGING.
CONTRACTOR TO COORDINATE
WITH FAA AND BUILDING USER
FINAL LOCATION AND LAYOUT
CAUTION
NOTICE TO CONTRACTOR
THE CONTRACTOR IS SPECIFICALLY CAUTIONED
THE LOCATION AND ELEVATION OF EXISTING
UTILITIES AS SHOWN ON THESE PLANS ARE BASED
ON RECORDS OF THE VARIOUS UTILITY COMPANIES
AND MEASUREMENTS TAKEN IN THE FIELD.
THE INFORMATION IS NOT TO BE RELIED ON AS
BEING EXACT OR COMPLETE. THE CONTRACTOR
MUST CALL THE LOCAL UTILITY LOCATION CENTER
AT LEAST 72 HOURS BEFORE ANY EXCAVATION TO
REQUEST EXACT FIELD LOCATIONS OF THE UTILITIES
exp date 06/30/23
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
GENERAL:
OKIE:
SURVEY:
GEOTECHNICAL:
SITE WORK AND GRADING:
ALL DISTURBED EARTH SURFACES WHICH ARE NOT PAVED OR BUILDING PADS SHALL
BE LANDSCAPED OR REVEGETATED WITH A TEMPORARY COVER, DEPENDING ON THE
PLANTING SEASON, AS OUTLINED BELOW.
PRIOR TO SEEDING, NEEDED EROSION CONTROL PRACTICES SHALL BE INSTALLED.
THE SUBGRADE SHALL BE LOOSENED EVENLY TO A DEPTH OF 2 TO 3 INCHES AND
10-20-10 FERTILIZER (10 LBS. PER 1000 SQ. FT. OR 450 LBS. PER ACRE) SHALL
BE MIXED WITH THE LOOSENED SOIL BY DISKING OR OTHER SUITABLE MEANS.
SOIL SHALL BE TESTED AND LIME TREATED IF REQUIRED BY TESTING FIRM.
SEEDS MAY BE DRILLED OR BROADCAST UNIFORMLY.
SEEDING IMPLEMENTS SHOULD BE USED AT RIGHT ANGLES TO THE SLOPE TO
MINIMIZE EROSION.
MULCH SHALL BE USED ON ALL SLOPES GREATER THAN 5 PERCENT OR AS NEEDED.
THE AREA SHALL BE WATERED DAILY OR AS OFTEN AS NECESSARY TO MAINTAIN
ADEQUATE SOIL MOISTURE UNTIL THE PLANTS EXCEED 1 INCH IN HEIGHT.
THE CONTRACTOR SHALL KEEP ON SITE A CURRENT SET OF THE APPROVED
CONSTRUCTION WORKING DRAWINGS AT ALL TIMES. THE CONTRACTOR SHALL
MARK (IN RED INK) ALL APPROVED CHANGES INCURRED FOLLOWING PUBLIC WORKS
DEPARTMENT APPROVAL OF THE INITIAL DRAWINGS. THESE CHANGES MAY BE
INITIATED FROM FIELD CONDITIONS OR CHANGES MADE BY THE DESIGN
ENGINEER OR THE PUBLIC WORKS ENGINEER. EXCEPT FOR MINOR FIELD
ADJUSTMENTS, ALL CHANGES SHALL BE REVIEWED AND AGREED TO BY THE
DESIGN ENGINEER AND THE PUBLIC WORKS ENGINEER PRIOR TO FINAL APPROVAL
OF THE PROJECT. THE CONTRACTOR SHALL SUBMIT THE WORKING DRAWINGS TO
THE ENGINEER OF RECORD (DESIGN ENGINEER) AFTER FINAL INSPECTION OF
PROJECT TO SERVE AS A BASIS FOR DEVELOPMENT OF FINAL AS-BUILT RECORD
DRAWINGS.
EROSION CONTROL NOTES:
TEMPORARY EROSION CONTROL:
AS-BUILTS:
PERMANENT EROSION CONTROL PRACTICES:
ANNUAL RYEGRASS
ELBON RYE
WHEAT
OATS
SORGHUMS
SUDAN GRASS
PLANT TYPE
PER
ACRE
40 LBS.
2 BU.
2 BU.
3 BU.
60 LBS.
60 LBS.
PER 1000
SQ. FT.
0.9 LBS.
3.0 LBS.
3.0 LBS.
2.5 LBS.
1.4 LBS.
1.4 LBS.
PLANTING
DATE
DEPTH OF
SEEDING
09/05-11/30 08/15-11/30 08/15-11/30 08/15-11/30 03/01-09/15 04/01-09/15
4 INCH
2 INCH
2 INCH
2 INCH
2 INCH
2 INCH
BERMUDA GRASS SOLID SLAB SOD OR SEEDING SHALL BE USED ON THIS PROJECT
IN ALL DISTURBED AREAS.
LAWN AREAS SHALL BE FERTILIZED ACCORDING TO TIME OF INSTALLATION
MAY 1 - AUGUST 31: APPLY 16-8-8 FERTILIZER AT A
RATE OF SIX (6) POUNDS PER 1000 SQ FT TO LAWN AREAS
SEPTEMBER 1 - APRIL 30: APPLY 10-20-10 FERTILIZER
AT A RATE OF TEN (10) POUNDS PER 1000 SQ FT TO LAWN AREAS
SOIL SHALL BE LOOSENED EVENLY TO A DEPTH OF 2 TO 3 INCHES AND FERTILIZER
SHALL BE MIXED WITH THE LOOSENED SURFACE SOIL BY DISKING OR OTHER
SUITABLE MEANS.
SOIL SHALL BE TESTED FOR pH AND SHALL BE TREATED WITH LIME AS REQUIRED.
THE AREA SHALL BE WATERED DAILY OR AS OFTEN AS NECESSARY TO MAINTAIN
ADEQUATE SOIL MOISTURE UNTIL FINAL ACCEPTANCE OR ONE MONTH.
SODDED AND SEEDED AREAS SHALL BE PREPARED AND PLACED IN ACCORDANCE WITH
CITY OF OKLAHOMA CITY STANDARDS AND SPECIFICATIONS. SEED SLOPES LESS THAN 5%.
SOD SLOPES BETWEEN 5% AND 4:1. STAKE SOD ON SLOPES GREATER THAN 4:1.
LAND DISTURBANCE PERMIT AND STORMWATER CONSTRUCTION PERMIT SHALL BE OBTAINED
FROM THE CITY OF OKLAHOMA CITY PUBLIC WORKS DEPARTMENT, STORMWATER DIVISION.
ALL EROSION CONTROL WORK SHALL BE DONE IN STRICT ACCORDANCE WITH THE
STORMWATER POLLUTION PREVENTION PLAN AND CITY OF OKLAHOMA CITY STANDARDS AND
SPECIFICATIONS.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A STABILIZED
CONSTRUCTION ENTRANCE, AND FOR CLEANING OF VEHICLE WHEELS IN ACCORDANCE
WITH THE CITY OF OKLAHOMA CITY STANDARDS AND SPECIFICATIONS.
SILT FENCES: PLACEMENT OF SILT FENCES SHALL BE AS SHOWN ON THE
DEMOLITION & EROSION CONTROL PLAN. FENCING WHICH BECOMES DAMAGED SHALL
BE REPLACED PROMPTLY. DEPOSITS OF SILT WHICH BUILD UP BEHIND DIKES MAY
BE DISKED INTO THE SITE BEFORE PLACEMENT OF TEMPORARY COVER. AFTER
TEMPORARY COVER IS PLACED OR AFTER LANDSCAPING COMMENCES, SILT SHALL
BE REMOVED AND DISPOSED OF IN A MANNER APPROVED BY THE ENGINEER.
CONDUCT SITE CLEARING OPERATIONS TO ENSURE MINIMUM INTERFERENCE
WITH ROADS,STREETS,WALKS AND OTHER ADJACENT OCCUPIED OR USED
FACILITIES. DO NOT CLOSE OR OBSTRUCT STREETS, WALKS, OR OTHER
OCCUPIED OR USED FACILITIES WITHOUT PERMISSION FROM AUTHORITIES
HAVING JURISDICTION. STREETS AND ROADWAYS SHALL BE THOROUGHLY
CLEANED AND/OR SWEPT ON A DAILY BASIS OR MORE FREQUENTLY AS
REQUIRED BY THE GOVERNING AUTHORITY. RESTORE DAMAGED IMPROVEMENTS
TO ORIGINAL CONDITION AS ACCEPTABLE TO PARTIES HAVING JURISDICTION.
THE CONTRACTOR SHALL PROVIDE DUST CONTROL MEASURES IN ACCORDANCE
WITH LOCAL AUTHORITIES.
ALL STREET SURFACES, DRIVEWAYS, CULVERTS, ROADSIDE DRAINAGE DITCHES
AND OTHER STRUCTURES THAT ARE DISTURBED OR DAMAGED IN ANY MANNER AS
A RESULT OF CONSTRUCTION SHALL BE REPLACED IN ACCORDANCE WITH THE
SPECIFICATIONS.
UNLESS SPECIFIED OTHERWISE, ALL MATERIAL AND WORKMANSHIP SHALL BE
IN ACCORDANCE WITH THE CITY OF OKLAHOMA CITY STANDARDS, OKLAHOMA DEPARTMENT
OF ENVIRONMENTAL QUALITY STANDARDS AND OKLAHOMA DEPARTMENT OF
TRANSPORTATION SPECIFICATIONS FOR HIGHWAY CONSTRUCTION AND/OR THE
APPROPRIATE LOCAL AUTHORITIES.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PERMITS, PERMIT FEES,
LICENSES, LICENSE FEES, AND TAP FEES, ETC.
ALL ELEVATIONS IN PAVED AREAS ARE TOP OF FINISHED PAVEMENT UNLESS
OTHERWISE NOTED.
RELOCATION OF ANY UTILITIES SHALL BE PERFORMED IN ACCORDANCE WITH
THE PROVISIONS OF THE APPROPRIATE UTILITY COMPANY AND/OR REGULATORY
AGENCY. CONTRACTOR SHALL OBTAIN WRITTEN APPROVAL FROM ENGINEER
BEFORE ANY UTILITY RELOCATION.
NO DIMENSION MAY BE SCALED. REFER UNCLEAR ITEMS TO THE ENGINEER FOR
INTERPRETATION.
ALL CONTRACTORS SHALL NOTIFY UTILITY COMPANIES AND GOVERNMENT
AGENCIES IN WRITING OF THE INTENT TO EXCAVATE NO LESS THAN 72 HOURS
PRIOR TO SUCH EXCAVATION (EXCLUSIVE OF SATURDAYS, SUNDAYS AND HOLIDAYS)
AND CALL "OKIE" AT 1-800-522-6543.
EXISTING UTILITY LOCATIONS SHOWN SHALL BE FIELD VERIFIED BY
CONTRACTOR PRIOR TO CONSTRUCTION. LOCATIONS OF UNDERGROUND UTILITIES
ON THESE DRAWINGS ARE APPROXIMATE ONLY AND BASED ON ACTUAL FIELD
LOCATIONS OF VISIBLE STRUCTURES AND PLAN COMPUTATIONS.
ALL FEATURES OF THIS PROJECT INCLUDING, BUT NOT LIMITED TO, SIDEWALKS
AND CURB RAMPS SHALL COMPLY WITH THE AMERICAN DISABILITIES ACT (ADA)
ACCESSIBILITY GUIDELINES, AND THE INTERIM FINAL RULES FOR PUBLIC
RIGHT-OF-WAY, PUBLISHED IN THE FEDERAL REGISTER, SEPTEMBER 2010.
WHERE SPATIAL LIMITATIONS OR EXISTING FEATURES WITHIN THE LIMITS OF
THE PROJECT PREVENT FULL COMPLIANCE WITH THIS ACT, THE CONTRACTOR
SHALL IMMEDIATELY NOTIFY THE ENGINEER UPON DISCOVERY OF SUCH FEATURES.
THE CONTRACTOR SHALL NOT PROCEED WITH ANY ASPECT OF THE WORK WHICH
IS NOT IN FULL COMPLIANCE WITH THE ADA WITHOUT PRIOR, WRITTEN
PERMISSION FROM THE ENGINEER. ANY WORK WHICH IS NOT PERFORMED WITHIN
THE GUIDELINES OF THE ADA, FOR WHICH THE CONTRACTOR DOES NOT HAVE
WRITTEN APPROVAL, SHALL BE CORRECTED AT THE CONTRACTOR'S EXPENSE.
CROSS SLOPES FOR SIDEWALKS SHALL NOT EXCEED 1:50
RAMP SLOPES SHALL NOT EXCEED 1:12
GRADES EXCEEDING 5% WILL BE TREATED AS A RAMP SLOPE
FINISHED SUBGRADE SURFACE SHALL NOT BE MORE THAN 0.1 FEET ABOVE OR
BELOW ESTABLISHED FINISHED SUBGRADE ELEVATIONS AND ALL GROUND
SURFACES SHALL VARY UNIFORMLY BETWEEN INDICATED ELEVATIONS. FINISHED
DITCHES SHALL BE GRADED TO ALLOW FOR PROPER DRAINAGE WITHOUT PONDING
AND IN A MANNER THAT WILL MINIMIZE EROSION.
EXISTING TOPOGRAPHY IS BASED ON AN ACTUAL FIELD SURVEY PERFORMED BY
LEMKE LAND SURVEYING SURVEYING, DATED AUGUST 4, 2021.
NONE PROVIDED
LEGEND
PROPOSED GRADE ELEVATIONG
TOP OF BANK ELEVATIONTBK
TOE OF BANK ELEVATIONTOE
LINEAR FEETL.F.
BACK OF CURB ELEVATIONBC
FINISHED FLOOR ELEVATIONFF/FFE
SIDEWALK ELEVATIONS/W
RIGHT OF WAY
EDGE OF CONCRETE ELEVATIONEC
EXISTINGEX./EXIST.
R/W
SQUARE FEETS.F.
TOP OF GRATE ELEVATIONTG
TOP OF PAVEMENT ELEVATIONTP
TOP OF RIM ELEVATIONTR
TOP OF STEP ELEVATIONTS
TOP OF WALL ELEVATIONTW
NOT A PARTN.A.P.
UTILITY EASEMENTU/E
TOP OF BANK/DIKE
TOE OF BANK/DIKE
GRADE BREAKLINE
CUT/FILL EXTENTS-TIE TO EXISTING
EXISTING STORM (DRAIN) PIPE
PROPOSED STORM (DRAIN) PIPE
EXISTING MAJOR CONTOUR (5 FT INT.)
EXISTING MINOR CONTOUR (1 FT INT.)
PROPOSED MAJOR CONTOUR (5 FT INT.)
PROPOSED MINOR CONTOUR (1 FT INT.)
SD
SD
EXISTING GRAVEL
PROPOSED GRAVEL
EXISTING ASPHALT
SF SILT FENCE
POWER POLE
GUY ANCHOR
COMMUNICATIONS PEDESTALC
ELECTRIC BOX
ELECTRIC TRANSFORMER
LIGHT POLE
EB
XFMR
BENCHMARK
GM GAS METER
SIGN
TREE
FIRE HYDRANT
WATER METER
WATER VALVE
S
SEWER CLEAN-OUT
SANITARY SEWER MANHOLE
FIRE DEPARTMENT CONNECTION
> > > FLOWLINE
CIVIL SHEET INDEX:
C100 GENERAL NOTES
C200 SURVEY
C300 DEMOLITION & EROSION CONTROL PLAN
C400 SITE PLAN
C401 UTILITY PLAN
C500 GRADING PLAN
C600 DETAILS
OKLAHOMA COUNTY
OKLAHOMA
THE CITY OF OKLAHOMA CITY
PUBLIC WORKS DEPARTMENT
ENGINEERING
420 W. MAIN STREET,SEVENTH FLOOR
OKLAHOMA CITY,OKLAHOMA
405-297-2581
405-297-2117 FAX
STORMWATER
GAS AND ELECTRIC
THE CITY OF OKLAHOMA CITY
PUBLIC WORKS DEPARTMENT
DEVELOPMENT CENTER
420 W. MAIN STREET,EIGHTH FLOOR
OKLAHOMA CITY,OKLAHOMA
405-297-3835
405-297-1651 FAX
BUILDING PERMITS AND INSPECTIONS
THE CITY OF OKLAHOMA CITY
PUBLIC WORKS DEPARTMENT
SUBDIVISION AND ZONING
420 W. MAIN STREET,EIGHTH FLOOR
OKLAHOMA CITY,OKLAHOMA
405-297-2623
ZONING
OKLAHOMA CITY AIRPORT TRUST (OCAT)
7100 TERMINAL DRIVE,
3RD FLOOR TERMINAL BUILDING, ROOM 301,
OKLAHOMA CITY, OKLAHOMA.
405-316-3266
NOTE COORDINATE ALL UTILITIES THROUGH
OKLAHOMA CITY AIRPORT TRUST-MMAC
OKLAHOMA CITY AIRPORT TRUST (OCAT)
7100 TERMINAL DRIVE,
3RD FLOOR TERMINAL BUILDING, ROOM 301
OKLAHOMA CITY, OKLAHOMA.
405-316-3266
BEFORE YOU DIG CALL OCAT FOR
UTILITY LOCATE AT FAA-MMAC
SURVEY CONTROL
POINT NUMBER NORTHING EASTING ELEVATION DESCRIPTION
OFF-SITE SURVEY CONTROL
100 140033.90 2081274.84 1275.06 #4 BAR W/LEMKE CAP
101 139360.62 2081264.05 1269.96 #4 BAR W/LEMKE CAP
ON-SITE SURVEY CONTROL
102 141754.33 2080376.96 1286.46 #4 BAR W/LEMKE CAP
103 142074.22 2080633.63 1283.25 #4 BAR W/LEMKE CAP
HORIZONTAL AND VERTICAL DATUM BASED ON OKLAHOMA CITY SURVEY CONTROL
HORIZONTAL DATUM: NAD83 (2011), OKLAHOMA STATE PLANE, NORTH ZONE
VERTICAL DATUM: NAVD88
WATER
OKLAHOMA CITY AIRPORT TRUST (OCAT)
7100 TERMINAL DRIVE,
3RD FLOOR TERMINAL BUILDING, ROOM 301,
OKLAHOMA CITY, OKLAHOMA.
405-316-3266
SANITARY SEWER
OKLAHOMA CITY AIRPORT TRUST (OCAT)
7100 TERMINAL DRIVE,
3RD FLOOR TERMINAL BUILDING, ROOM 301,
OKLAHOMA CITY, OKLAHOMA.
405-316-3266 exp date 06/30/23
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
THIS SHEET WAS PRODUCED FOR THE CONVENIENCE OF
THE CONTRACTOR. IT IS INTENDED FOR GENERAL SURVEY
INFORMATION ONLY. WALLACE DESIGN COLLECTIVE HAS
NOT CONFIRMED ITS ACCURACY. SURVEY INFORMATION
WAS REPRODUCED BY ELECTRONIC TRANSFER FROM THE
SURVEYOR. ORIGINAL SURVEY DRAWINGS AVAILABLE
UPON REQUEST FROM THE SURVEYOR.
REMOVE RIPRAP
APRON TYP.
SIDEWALK REMOVAL TO
NEAREST PAVING JOINT TYP.
CONC. WASHOUT
CONTRACTOR SHALL RELOCATE
AS NEEDED THROUGHOUT
CONSTRUCTION
RE: 6/C.600
REMOVE EX.
STORM DRAINS
RE: C500
87 12 86 12
83 12
-2.49% -2
.5 5%
-3.06%
-4.27%
-3 .2
5%
-2.73%
-2.39%
12831282
12821283
12831283
ROCK CHECK DAMN
TYP. RE: 7/C600
SILT FENCE TYP.
FLUSH/CLEAN
STORM DRAIN
FLUSH/CLEAN
STORM DRAIN
REMOVE EX. STORM
DRAIN
RE: C500
12.29'
4.67'
REMOVE AND REPLACE 4'
WIDE PAVEMENT TO
CONSTRUCT PROPOSED GAS
LINE IMPROVEMENTS
REMOVE EX.
LANDSCAPING AREA
REMOVE EX.
LANDSCAPING AREA
REMOVE AND RELOCATE
EX. LIGHT TO CONSTRUCT
PROP. CANOPY
REMOVE AND RELOCATE
EX. LIGHT TO CONSTRUCT
PROP. CANOPY
100'
100'
EX. GAS VALVE
CONTRACTOR SHALL PROTECT
THROUGHOUT CONSTRUCTION
EX. GAS LINE
CONTRACTOR SHALL PROTECT
THROUGHOUT CONSTRUCTION
EX. WATER LINE
CONTRACTOR SHALL PROTECT
THROUGHOUT CONSTRUCTION
7.5' min.
7.5' min.
100'X100' STAGING AREA SHOWN
DASHED
CONTRACTOR SHALL DETERMINE
FINAL SIZE REQUIRED FOR EQUIPMENT
AND MATERIAL STAGING AND
COORDINATE WITH FAA PRIOR TO
CONSTRUCTION
RE: C500 FOR GRADING OF THIS AREA
INSTALL CURB PROTECTION AT ENTRANCE TO
STAGING AREA
CURB AND GUTTER SHALL BE REPLACED IF
DAMAGED DURING CONSTRUCTION
CITY OF OKLAHOMA CITY 2-FT
CONTOUR DATA SHOWN AT
STAGING AREA
CONTRACTOR SHALL FIELD
VERIFY ELEVATIONS PRIOR TO
DISTURBANCE
128812
128512
84 12
CAUTION
NOTICE TO CONTRACTOR
THE CONTRACTOR IS SPECIFICALLY CAUTIONED
THE LOCATION AND ELEVATION OF EXISTING
UTILITIES AS SHOWN ON THESE PLANS ARE BASED
ON RECORDS OF THE VARIOUS UTILITY COMPANIES
AND MEASUREMENTS TAKEN IN THE FIELD.
THE INFORMATION IS NOT TO BE RELIED ON AS
BEING EXACT OR COMPLETE. THE CONTRACTOR
MUST CALL THE LOCAL UTILITY LOCATION CENTER
AT LEAST 72 HOURS BEFORE ANY EXCAVATION TO
REQUEST EXACT FIELD LOCATIONS OF THE UTILITIES
exp date 06/30/23
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
GENERAL DEMOLITION NOTES
1. ALL CONCRETE AND ASPHALT NOTED FOR REMOVAL SHALL BE SAW CUT FULL
DEPTH AND REMOVED OFF SITE.
2. CONTRACTOR SHALL PROTECT ALL SURVEY CONTROL POINTS.
3. CONTRACTOR SHALL REMOVE ALL WASTE MATERIALS OFF SITE.
4. ALL EXISTING STRUCTURES, UNLESS OTHERWISE NOTED TO REMAIN, FENCING,
TREES, ETC., WITHIN CONSTRUCTION AREA SHALL BE REMOVED & DISPOSED
OF OFF SITE. ALL COST SHALL BE INCLUDED IN BASE BID.
5. WITH PRIOR APPROVAL, CONTRACTOR MAY ESTABLISH AN ON-SITE STAGING
AREA. CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING STAGING AREA
TO ITS ORIGINAL CONDITION. SECURITY OF STAGING AREA SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR.
6. ON-SITE VEGETATION SHALL BE PROTECTED AS NOTED. IN DESIGNATED
PROTECTION AREAS WHERE THE CONTRACTOR DOES NOT PROTECT
VEGETATION AS NOTED, CONTRACTOR SHALL RESTORE VEGETATION TO
EXISTING CONDITION AT NO ADDITIONAL EXPENSE TO THE OWNER, TO THE
SATISFACTION OF THE ARCHITECT.
7. CONTRACTOR SHALL PROTECT ALL ABOVE GROUND UTILITY FEATURES NOT
BEING REMOVED INCLUDING, BUT NOT LIMITED TO, MANHOLES, VALVES, AND
INLETS. IF ANY EXISTING STRUCTURES TO REMAIN ARE DAMAGED DURING
CONSTRUCTION, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REPAIR
OR REPLACE THE EXISTING STRUCTURE AS NECESSARY.
8. TOPSOIL STOCKPILES AND DISTURBED PORTIONS OF THE SITE, WHERE
CONSTRUCTION ACTIVITY TEMPORARILY CEASES FOR AT LEAST 14 DAYS
SHALL BE STABILIZED IMMEDIATELY WITH TEMPORARY SEED AND MULCH PER
SPECIFICATIONS ON THE GENERAL NOTES AND STORMWATER POLLUTION
PREVENTION PLAN.
9. CONTRACTOR SHALL ENSURE CONSTRUCTION SITE HAS POSITIVE DRAINAGE
THROUGHOUT THE DURATION OF CONSTRUCTION.
0 10 2020
1" = 20'
LEGEND
REMOVE EX. SIDEWALK TO NEAREST PAVING JOINT
SILT FENCE (RE: 1/C600)
STRIP SOD AND RE-GRADE (RE: C500)
ROCK CHECK DAM (RE: 2/C600)
REMOVE RIPRAP APRON AND DISPOSE OFF-SITE
FLOW ARROW
REMOVE AND REPLACE CONCRETE PAVEMENT
AND CURB & GUTTER (RE: 9/C600)
OKLAHOMA CITY AIRPORT TRUST (OCAT)
7100 TERMINAL DRIVE,
3RD FLOOR TERMINAL BUILDING, ROOM 301
OKLAHOMA CITY, OKLAHOMA.
405-316-3266
BEFORE YOU DIG CALL OCAT FOR
UTILITY LOCATE AT FAA-MMAC
TRICKLE CHANNEL TYP.
RE: 7/C600
SIDEWALK DRAIN TYP.
RE: 5/C600
RIPRAP APRON TYP.
RE: 6/C600
CONSTRUCT TRICKLE CHANNEL
IN FL OF EXISTING SWALE
RE: 7/C600
N: 141,776.15 E: 2,080,672.41
N: 141,855.40 E: 2,080,678.04
N: 142,011.24 E: 2,080,683.02
N: 142,088.87 E: 2,080,688.86
CONCRETE SLOPE
END TREATMENT
RE: 8/C600
2'
2'
N: 141,928.28 E: 2,080,345.84
N: 141,973.07 E: 2,080,353.92
N: 142,042.76 E: 2,080,423.21
N: 142,049.91 E: 2,080,469.73
N: 141,808.12 E: 2,080,467.04
N: 141,816.38 E: 2,080,512.36
CONCRETE APRON
TYP. RE: 4/C600
CONSTRUCT TRICKLE CHANNEL
IN FL OF EXISTING SWALE
RE: 7/C600
CONSTRUCT TRICKLE CHANNEL
IN FL OF EXISTING SWALE
RE: 7/C600
CONSTRUCT TRICKLE CHANNEL
IN FL OF EXISTING SWALE
RE: 7/C600
CONSTRUCT TRICKLE CHANNEL
IN FL OF EXISTING SWALE
RE: 7/C600
CONSTRUCT
CONCRETE FLUME
RE: 10/C600
CONSTRUCT TRICKLE CHANNEL
IN FL OF EXISTING SWALE
RE: 7/C600
CONSTRUCT TRICKLE CHANNEL
IN FL OF EXISTING SWALE
RE: 7/C600
PROP. GENERATOR
RE: MEP
RE: C401
RELOCATED
LIGHT POLE
RELOCATED
LIGHT POLE
PROPOSED CANOPY
RE: ARCH & STRUCT
CAUTION
NOTICE TO CONTRACTOR
THE CONTRACTOR IS SPECIFICALLY CAUTIONED
THE LOCATION AND ELEVATION OF EXISTING
UTILITIES AS SHOWN ON THESE PLANS ARE BASED
ON RECORDS OF THE VARIOUS UTILITY COMPANIES
AND MEASUREMENTS TAKEN IN THE FIELD.
THE INFORMATION IS NOT TO BE RELIED ON AS
BEING EXACT OR COMPLETE. THE CONTRACTOR
MUST CALL THE LOCAL UTILITY LOCATION CENTER
AT LEAST 72 HOURS BEFORE ANY EXCAVATION TO
REQUEST EXACT FIELD LOCATIONS OF THE UTILITIES
exp date 06/30/23
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
0 10 2020
1" = 20'
1. ALL WORK AND MATERIALS SHALL COMPLY WITH ALL MUNICIPAL REGULATIONS
AND CODES, WHICHEVER IS MORE STRINGENT.
2. ALL WORK AND MATERIALS SHALL COMPLY WITH O.S.H.A. STANDARDS.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RELOCATIONS, INCLUDING BUT
NOT LIMITED TO, ALL UTILITIES, STORM DRAINAGE, SIGNS, TRAFFIC SIGNALS &
POLES, ETC. AS REQUIRED. ALL WORK SHALL BE IN ACCORDANCE WITH
GOVERNING AUTHORITIES SPECIFICATIONS AND SHALL BE APPROVED BY
SUCH. ALL COST SHALL BE INCLUDED IN BASE BID.
4. ALL DIMENSIONS AND COORDINATES ARE FROM BACK OF CURB UNLESS
SHOWN OTHERWISE..
5. BUILDING COORDINATES ARE TO OUTSIDE FACE OF WALL.
GENERAL NOTES
LEGEND
CONCRETE SIDEWALK
BERMUDA SOD
RIPRAP
CONCRETE PAVEMENT
2'
2' VERTICAL CLEARANCE
AT UTILITY CROSSING
TAP EX. 3" GAS MAIN
COORDINATE WITH FAA
AND OCAT PRIOR TO
CONSTRUCTION
GENERATOR
RE: MEP
CONTRACTOR SHALL FIELD
VERIFY ALL EXIST. UTILITIES
INSIDE MECHANICAL
COURTYARD AND PROVIDE 2'
MIN. VERTICAL CLEARANCE
AT ALL UTILITY CROSSINGS
RELOCATED
LIGHT POLE
RE: ELECTRICAL
RELOCATED
LIGHT POLE
RE: ELECTRICAL
2" GAS LINE
PROVIDE SHUT-OFF VALVE AND
NATURAL GAS PRESSURE REGULATOR
4,000 CFH, 40 PSIG TO 11 IN WG.
PROVIDE DIELECTRIC FITTING AND
3-INCH ABOVE-GROUND PAINTED STEEL
PIPE FROM REGULATOR TO
GENERATOR CONNECTION
CAUTION
NOTICE TO CONTRACTOR
THE CONTRACTOR IS SPECIFICALLY CAUTIONED
THE LOCATION AND ELEVATION OF EXISTING
UTILITIES AS SHOWN ON THESE PLANS ARE BASED
ON RECORDS OF THE VARIOUS UTILITY COMPANIES
AND MEASUREMENTS TAKEN IN THE FIELD.
THE INFORMATION IS NOT TO BE RELIED ON AS
BEING EXACT OR COMPLETE. THE CONTRACTOR
MUST CALL THE LOCAL UTILITY LOCATION CENTER
AT LEAST 72 HOURS BEFORE ANY EXCAVATION TO
REQUEST EXACT FIELD LOCATIONS OF THE UTILITIES
exp date 06/30/23
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
0 10 2020
1" = 20'
1. ALL TRENCHING, PIPE LAYING AND BACKFILLING SHALL BE IN ACCORDANCE
WITH FEDERAL OSHA REGULATIONS.
2. PRIOR TO CONSTRUCTION, LOCATION OF SITE UTILITIES SHALL BE VERIFIED BY
CONTRACTOR WITH THE PROPER UTILITY COMPANY PROVIDING SERVICE.
3. CONTRACTOR SHALL NOTIFY THE UTILITY AUTHORITIES' INSPECTORS BEFORE
CONNECTING TO ANY EXISTING LINE IN ACCORDANCE WITH LOCAL
REQUIREMENTS.
4. CONTRACTOR IS TO COORDINATE WITH ALL UTILITY COMPANIES FOR
INSTALLATION REQUIREMENTS AND SPECIFICATIONS.
5. CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH THE SPECIFICATIONS OF
THE LOCAL AUTHORITIES REGARDING TO MATERIALS AND INSTALLATION OF
THE WATER AND SEWER LINES.
6. TERMINATE SERVICE PIPING 5' FROM BUILDING WALL UNTIL BUILDING PIPING
SYSTEMS ARE INSTALLED. TERMINATE PIPING WITH VALVE AND CAP PLUG OR
FLANGE AS REQUIRED FOR PIPING MATERIAL. MAKE CONNECTIONS TO
BUILDING PIPING SYSTEMS WHEN THOSE SYSTEMS ARE INSTALLED.
7. ALL PIPING SHALL BE INSTALLED WITH A MINIMUM OF 48" OF COVER, UNLESS
NOTED OTHERWISE.
8. UTILITY TRENCH DETAIL RE: C-700.
9. REFER TO MEP PLANS FOR CONTINUATION OF UTILITIES AT BUILDING.
10. CONTRACTOR TO FIELD VERIFY DEPTH AND LOCATION OF PUBLIC WATER AND
SANITARY SEWER LINES AT PROPOSED TAP LOCATIONS
10. REFER TO PLUMBING AND/OR FIRE PROTECTION SHEETS FOR FIRE LINE LEAD-IN
LOCATION AND DETAIL.
11. CONSTRUCT CLAY TRENCH PLUG THAT EXTENDS AT LEAST 5 FEET OUT FROM
THE FACE OF THE BUILDING EXTERIOR. THE PLUG MATERIAL SHALL CONSIST
OF CLAY COMPACTED AT A WATER CONTENT AT OR ABOVE THE SOILS OPTIMUM
WATER CONTENT. THE CLAY FILL SHALL BE PLACED TO COMPLETELY
SURROUND THE UTILITY LINE AND BE COMPACTED TO AT LEAST 95% STANDARD
PROCTOR DENSITY.
PROPOSED SANITARY SEWER
PROPOSED WATER LINE
PROPOSED COMMUNICATION LINE
PROPOSED ELECTRIC LINE
GENERAL NOTES
LEGEND
PROPERTY LINE
TC 12
.17
TP 12
.67
12811282
1282 1281
1286 1285 1284
12841285
8" FL PER AS-BUILTS 1281.25
PROP. 8" FL 1281.40
EX. 8" FL 1281.23
EX. 8" FL 1281.32
PROP. 8" FL 1281.85
co co
EX. 8" FL 1282.13
PROP. 8" FL 1281.75
EX. 8" FL 1282.44
TC 12
.07
TP 12
.57
TC 12
.05
TP 12
.55
TC 12
.00
TP 12
.50
TC 12
.03
TP 12
.53
TC 12
.08
TP 12
.58
FL 1
4.8
5FL 1
4.7
FL 1
4.7
FL 1
4.7
FL 1
4.8
FL 1
4.8
FL 1
4.7
1283 1282
1281CONSTRUCT 8" PVC STORM
SEWER AT 1.6% SLOPE
8" AS-BUILT FL 1283.00
CONTRACTOR SHALL FIELD
VERIFY FLOW LINE
CONSTRUCT 8" PVC STORM
SEWER AT 1.2% SLOPE
8" AS-BUILT FL 1282.75
CONTRACTOR SHALL
LOCATE AND FIELD VERIFY
FLOW LINES AT EXISTING
CLEAN OUTS
FL 1280.09
FL 1280.98
FL 1280.89
TP 1280.94
TP 1281.28
FL 1280.89
TP 1281.39
TP 1281.63
TP 1282.12
TP 1281.43
FL 1280.70
FL 1281.31
FL 1281.37
TP 1282.63 TP 1282.61
TP 1281.86FL 1281.57
FL 1281.76
TP 1281.88
FL 1282.12
TP 1282.13
TP 1282.83
TP 1282.84
TP 1282.35
FL 1282.06
FL 1282.22
FL 1282.43
FL 1282.85
TP 1284.05
FL 1282.88
TP 1284.22
FL 1282.91
TP 1284.74
TP 1282.85
TP 1282.80
FL 1282.74
TP 1284.24
FL 1282.29
FL 1281.81
TP 1281.89
TP 1282.87
TP 1282.38
FL 1281.70
TP 1281.96
FL 1281.50
FL 1
1.0
FL 1281.42
TP 1281.67
TP 1281.79
TP 1282.18
TP 1282.52
TP 1281.79
TP 1282.18
FG 1282.10
FG 1282.10
FL 1281.15
FL 1280.82
FG 1280.49
FL 1280.29
EG 1280.65
TP 1282.13
TP 1282.09
ME 1282.61
ME 1282.92
ME 1283.07
ME 1283.28
ME 1283.58
ME 1283.47
ME 1283.62
ME 1283.48
ME 1283.62
ME 1282.87
ME 1283.12
ME 1283.00
ME 1282.82
ME 1282.71
ME 1282.78
FL 1281.01
EG 1279.98
EG 1281.34
EG 1280.97
ME 1282.82
FL 1281.95
EXTENTS OF
GRADING (TYP.)
PROP. TRICKLE
CHANNEL AT 0.4% MIN.
PROP. TRICKLE
CHANNEL AT 0.4% MIN.
PROP. TRICKLE
CHANNEL AT 0.4% MIN.
ENSURE POSITIVE
DRAINAGE TO TRICKLE
CHANNEL TYP.
SEE NOTE 9 FOR
PERIMETER
GRADING TYP.
SEE NOTE 9 FOR
PERIMETER
GRADING TYP.
ENSURE POSITIVE
DRAINAGE TO TRICKLE
CHANNEL TYP.
EG 85.15
FG 85.15
EG 85
.45
FG 85
.19
EG 85
.16
FG 85
.16
EG 85
.17
FG 85
.17
EG 85
.24
FG 85
.19
EG 84
.82
FG 84
.82
FG 84.95
EG 85
.15
FG 85
.15
EG 85
.14
FG 85
.14
EG 85
.15
FG 85
.15
EG 85
.17
FG 85
.17
FG 84.95
EG 85
.32
FG 85
.18
EG 84
.76
FG 84
.76
EG 84
.79
FG 84
.79
EG 85
.39
FG 85
.19
EG 85
.10
FG 85
.10
EG 85.19
FG 85.15
EG 85
.29
FG 85
.19
FG 84.95
4" STORM SEWER TO
COLLECT CANOPY
DOWNSPOUT
RE: 11/C600
4" STORM SEWER TO
COLLECT CANOPY
DOWNSPOUT
RE: 11/C600
TP 12
.90
TP 12
.03
ENSURE POSITIVE
DRAINAGE TO TRICKLE
CHANNEL
ENSURE POSITIVE
DRAINAGE TO TRICKLE
CHANNEL
ENSURE POSITIVE
DRAINAGE TO TRICKLE
CHANNEL
EX. GAS VALVE
CONTRACTOR SHALL PROTECT
THROUGHOUT CONSTRUCTION
EX. GAS LINE
CONTRACTOR SHALL PROTECT
THROUGHOUT CONSTRUCTION
EX. WATER LINE
CONTRACTOR SHALL PROTECT
THROUGHOUT CONSTRUCTION
CONTRACTOR SHALL TRANSPORT AND SPREAD SPOILS
IN 100'X100' AREA SHOWN ON PLANS
ALL DISTURBED AREA SHALL BE SEEDED FOR
PERMANENT STABILIZATION
FINISHED GRADES ARE SHOWN FOR REFERENCE ONLY
TO ENSURE POSITIVE DRAINAGE OF AREA FOR +/- 240
CY OF SPOILS
CONTRACTOR SHALL COORDINATE WITH ENGINEER OF
RECORD PRIOR TO CONSTRUCTION WITH ESTIMATED
VOLUME OF SPOILS FOR PROJECT TO DETERMINE
FINAL GRADING OF AREA
100'
0'
FG 12
.97
FG 12
.52
FG 12
.07
FG 12
.61
FG 12
.15
FG 12
.53
FG 12
.77
FG 12
.47
FG 12
.99
FG 12
.52
FG 12
.88
FG 12
.86
FG 12
.83
FG 12
.29
FG 12
.76
FG 12
.24
SLOPE 3:1 TO
EXISTING GRADE TYP.
AT SPOILS AREA.
1283 12
CITY OF OKLAHOMA CITY 2-FT
CONTOUR DATA SHOWN AT
SPOILS AREA
CONTRACTOR SHALL FIELD
VERIFY ELEVATIONS PRIOR TO
DISTURBANCE
128312
12861286
85 128212
128812
128612
CAUTION
NOTICE TO CONTRACTOR
THE CONTRACTOR IS SPECIFICALLY CAUTIONED
THE LOCATION AND ELEVATION OF EXISTING
UTILITIES AS SHOWN ON THESE PLANS ARE BASED
ON RECORDS OF THE VARIOUS UTILITY COMPANIES
AND MEASUREMENTS TAKEN IN THE FIELD.
THE INFORMATION IS NOT TO BE RELIED ON AS
BEING EXACT OR COMPLETE. THE CONTRACTOR
MUST CALL THE LOCAL UTILITY LOCATION CENTER
AT LEAST 72 HOURS BEFORE ANY EXCAVATION TO
REQUEST EXACT FIELD LOCATIONS OF THE UTILITIES
exp date 06/30/23
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
0 10 2020
1" = 20'
1. SITE GRADING SHALL NOT PROCEED UNTIL EROSION CONTROL MEASURES
HAVE BEEN INSTALLED & INSPECTED AND APPROVED BY LOCAL AUTHORITIES.
2. ALL CUT OR FILL SLOPES SHALL BE 3:1 OR FLATTER UNLESS OTHERWISE
NOTED.
3. CONTRACTOR SHALL ASSURE POSITIVE DRAINAGE AWAY FROM BUILDINGS
AND STRUCTURES FOR ALL GRASSED AND PAVED AREAS.
4. CONSTRUCTION SHALL COMPLY WITH ALL APPLICABLE GOVERNING CODES
AND BE CONSTRUCTED TO THE SAME.
5. CONTRACTOR IS RESPONSIBLE FOR TEMPORARY ACCESS ROADS AND SHALL
MAINTAIN POSITIVE DRAINAGE OF ENTIRE SITE THROUGHOUT CONSTRUCTION
AND AVOID PONDING OR RUTTING. TEMPORARY DEWATERING, INCLUDING
PUMPING, MAY BE REQUIRED AND SHALL BE INCLUDED IN THE SCOPE OF
WORK.
6. ALL SIDEWALKS AND RAMPS TO HAVE MAXIMUM LONGITUDINAL SLOPE OF 5%
AND MAXIMUM CROSS SLOPE OF 2%.
7. EXISTING DRAINAGE STRUCTURES TO BE INSPECTED AND REPAIRED AS
NEEDED, AND EXISTING PIPES ARE TO BE CLEANED OUT TO REMOVE ALL SILT
AND DEBRIS.
8. IF ANY EXISTING STRUCTURES TO REMAIN ARE DAMAGED DURING
CONSTRUCTION IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO REPAIR
OR REPLACE THE EXISTING STRUCTURE AS NECESSARY.
9. ALL FINISHED GRADE SHALL BE MINIMUM 1' BELOW WEEPS. ENSURE COVER
ABOVE EXISTING PERIMETER INSULATION.
GENERAL GRADING NOTES
SURVEY CONTROL
POINT NUMBER NORTHING EASTING ELEVATION DESCRIPTION
OFF-SITE SURVEY CONTROL
100 140033.90 2081274.84 1275.06 #4 BAR W/LEMKE CAP
101 139360.62 2081264.05 1269.96 #4 BAR W/LEMKE CAP
ON-SITE SURVEY CONTROL
102 141754.33 2080376.96 1286.46 #4 BAR W/LEMKE CAP
103 142074.22 2080633.63 1283.25 #4 BAR W/LEMKE CAP
HORIZONTAL AND VERTICAL DATUM BASED ON OKLAHOMA CITY SURVEY CONTROL
HORIZONTAL DATUM: NAD83 (2011), OKLAHOMA STATE PLANE, NORTH ZONE
VERTICAL DATUM: NAVD88
1200 EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
PROPOSED MINOR CONTOUR
PROPOSED MAJOR CONTOUR
EXTENTS OF GRADING
OKLAHOMA CITY AIRPORT TRUST (OCAT)
7100 TERMINAL DRIVE,
3RD FLOOR TERMINAL BUILDING, ROOM 301
OKLAHOMA CITY, OKLAHOMA.
405-316-3266
BEFORE YOU DIG CALL OCAT FOR
UTILITY LOCATE AT FAA-MMAC
LEGEND
EXISTING GRADE
FINISHED GRADE
FLOWLINE
FINISHED FLOOR ELEVATION
MATCH EXISTING
TOP OF CURB
TOP OF PAVEMENT
TOP OF SIDEWALK
EG
FG
FL
ME
TC
TP
TS
FFE
GUTTER LINEGL
6" 4"
SCALE: NTS
SIDEWALK DRAIN
2" PREFORMED
EXPANSION JOINT
SIDEWALK REMOVE TO
NEAREST PAVING JOINT
8" GALV STEEL CHECKERED
PLATE ACROSS SIDEWALK
2" x 3" GALV SCREWS SEE
NOTE 1
#3 @ 18" OC EW
6" TYPE "A"
AGG BASE
SUBGRADE AT 90% MIN
DENSITY
NOTES:
1. INSTALL COUNTERSUNK SCREWS IN LEADWOOD MASONRY
ANCHORS AT 24" OC.
6" 8"
6" 2" CLR
4" 2' 4"
SCALE: NTS SCALE: NTS7
GALV AFTER
FORMING
CONCRETE SLOPE END TREATMENT8 SCALE: NTS
D
SECTION
PLAN VIEW
MESH SIZE: 0.3" x 0.3" GAUGE: 0.063 x 0.063 4"
4" 1' -6
1'
-6
D
TOWARDS DITCH/SLOPE
OF LATERAL WITH OPEN END
PRESS FIT INTO OUTLET END
RODENT SCREEN
#4 BARS AS SHOWN
AT MIDPOINT
WWF 6 x 6-W1.4 x W1.4
2'-0"
2'-0"
4"
1' -6
6"
D M
IN
D
/4
PROTECT EX. 8"
STORM SEWER
EX. FLUME SERVING
PARKING LOT
4" 3500 PSI
CONCRETE PAD
CONCRETE
TRICKLE CHANNEL
RE: PLAN FOR
TOP OF APRON
5'
TY
P.
SCALE: NTS
FLUME CONCRETE APRON4
SECTION A-A
CONCRETE
TRICKLE CHANNEL
4" 3500 PSI
CONCRETE PAD
SCALE: NTS
PAVEMENT REPAIR9
TIE BAR
SAW CUT THICKNESS
T+2" (8" MIN.)
SAW CUT
COMPACT SUBGRADE TO 95%
STANDARD PROCTOR DENSITY
REMOVE EXISTING CONCRETE PAVING, SAW CUT SHOULD BE INCLUDED IN
PRICE.
TIE BARS TO BE 1" DIA. DEFORMED BARS (1 14" DIA. FOR PAVEMENT 8"THICK
AND GREATER) 18" LENGTH AND SPACED AT 18" CENTERS. ANCHORED WITH
EPOXY.
FOR TRANSVERSE JOINTS, USE SMOOTH BARS WITH SAME DIMENSIONS AS
SHOWN ABOVE. ONLY ONE END ANCHORED WITH EPOXY.
CONCRETE PANEL TO BE DOUBLE SAWED 6" APART TO PROTECT THE
PAVEMENT EDGE DURING EXCAVATION.
T
6"
EXISTING PAVEMENT THICKNESS PER ASBUILTS = 6"
CONTRACTOR SHALL FIELD VERIFY PAVMENT THICKNESS.
PROTECT EX. 8"
STORM SEWER
EX. FLUME
SERVING
PARKING LOT
4" 3500 PSI
CONCRETE PAD
CONCRETE
TRICKLE CHANNEL
RE: PLAN FOR
TOP OF APRON
CONCRETE SLOPED
END TREATMENT
RE: 2/THIS SHEET
A A
1.
M
IN
WITH STORM DRAIN TYPICAL OUTLET
PA
R
KI
N
G L
O T
FLUME CURBCURB
APRON UP TO
PARKING LOT CURB
@ FLUME SLOPE
6"
8"APRON TO MATCH
FLUME FL
M.E. 6'-4" M.E.
M .E
PLAN VIEW
6" 6"
8" 6'-4" 8"
SECTION
SCALE: NTS
CONCRETE FLUME10
R M.E.R M .E
2"
1' -8
1'
-0
4"
6" 1'-0"6"
WELDED WIRE
MESH
#4 X 3'-8" @ 10" O.C.
#4 CONTINUOUS
SECTION
2'-0"
1"
2-0"
4"
TOP OF SOD
MIN. 1" ABOVE
CONCRETE
UNDISTURBED SOIL
OR ENGINEERED FILL
GRADE VARIES
(3 HORIZ:1 VERT
MAX)
NOTE: 3' CURTAIN WALL @
EACH END, 100' MAX INTERVAL,
& AS SHOWN ON PLANS
TRICKLE CHANNEL TO BE
SCORED 1" DEEP @ 10' C/C
4"
A A
SECTION
END VIEW CURTAIN WALL
WELDED WIRE
MESH
CURTAIN WALL THICKENED EDGE
DRAIN PIPE
COMPACTED SUBGRADE
RE: SPECS
5'
TY
P.
COMPACTED SUBGRADE
RE: SPECS
exp date 06/30/23
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
RIP RAP APRON
3'
SECTION A-A
COMPACT TO 95%
STANDARD PROCTOR
NON-WOVEN
FILTER FABRIC
NOTE:
TURN DOWN RIPRAP ALL
AROUND OUTSIDE
PERIMETER OF RIPRAP
PLAN
12'
SE
C
A
SE
C A3.
D50 = 12"
SCALE: NTS
DOWNSPOUT TO CURB OPENING CONNECTION
DOWNSPOUT
RE: ARCH
REDUCER
CAST IRON HUB
45° ELBOW
6" CAST IRON CURB
OPENING NEENAH
R-3262-2 OR EQUAL
NORTH
SCALE: 1/8"=1'-0"
DEMOLITION FLOOR PLAN1
VEST.
LOBBY
100A
INSTRUCTOR
BREAKOUT
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CBT
PARTS
PARTS
TELE
CLASSROOM
CLASSROOM
MAINT.
CLASSROOM
117A
EQUIP.
PARTS
ALARM
COPY RM
PARTS
JAN
108107
CLASSROOM
CLASSROOM
TELE.
CBT
PARTS
123JAN
PARTS
CLASSROOM
CLASSROOM
MECHANICAL
FAN ROOM
ELECT. ROOM
MEN
VEST
DME LAB
132A
ANTENNA LAB
140A
REPL. TACAN
VEST
WOMEN
VORTAC LAB
109A
VEST
MEN
VOR/DME LAB
112/118
VEST
WOMEN
GPS LAB
LORAN C/
ANTENNA LAB
VOR
VENDING
VEST
LOBBY
LOUNGE
ROOF ACCESS
PARTS
128B
102B
PARTS PARTS
PARTS
121B
ESTABLISHED
2nd GEN.
FIRE
ELECT.
141A
142A
143A
144A
1 2 3 4 5 6 8 9
E
J
H
G
F
D
C
B
A
1 2 3 4 5 6 7 8 9
E
J
H
G
F
D
C
B
A
5.74.3
4.3 5.7
E.7
D.3
E.7
D.3
8.4
8.41.6
1.6
H.4 H.4
A.6A.6
C.3
F.7 F.7
C.3
3.3 6.7
3.3 6.7
D.4
E.5
10 11 127
11 1210
6 6
6 6
EXISTING CMU WALL
1000kVA
PADMOUNT
XFRMR
JUNCTION
CABINET
1. REMOVE EXTERIOR CURTAIN WALL SYSTEM - REFER TO SHEET
A.201 FOR INFORMATION ON NEW WINDOW AND WALL.
2. MODIFY DOOR FRAMES FOR INSTALLATION OF CONCEALED
WIRING TO LIGHT SWITCH ON MULLION - RE: SHEET E3.03. PATCH
FRAME AND RE-PAINT TO MATCH EXISTING
3. REMOVE FOR REPLACEMENT OF EXTERIOR DOUBLE DOORS.
STORE EXISTING HARDWARE FOR RE- USE.
4. REMOVE PEELING WALL PAINT. PREP FOR PRIME, AND PAINT
ENTIRE WALL.
5. REPAIR BY REPLACEMENT OF METAL PANEL GASKET.
6. REMOVE EXISTING EJ SEALANT AND PREP FOR NEW SEALANT
7. CHILLERS AND CONCRETE PAD REMOVED BY SEPARATE
CONTRACT.
8. REMOVE EXISTING GENERATOR, FUEL TANK, AND PAD AND
ASSOCIATED CONNECTIONS AND PREP FOR NEW CONDUITS
INDICATED ON SHEET E302.
XPLAN DEMOLITION NOTES:
1. REFER TO SHEET A202 FOR ADDITIONAL DEMOLITION INFORMATION
AT ROOF FOR REPLACEMENT OF DAMAGED/STAINED CEILING
PANELS.
2. REFER TO SHEET A202 FOR LOCATION OF EXISTING SKYLIGHTS TO
BE REPLACED.
SHEET NOTES:
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
01 5/24/23 ADD-001: CHILLER PADS AND FENCE REMOVAL
ROOF DEMOLITION PLAN1
ACCESS
PLATFORM
EXISTING ACCESS
LADDER UP TO HATCH
ON CONTERPOISE.
EXISTING
TACAN
ANTENNA
EXISTING
TACAN
ANTENNA
LINE OF COUNTERPOISE ABOVE
EXISTING
VENT
LINE OF COUNTERPOISE ABOVE
LINE OF COUNTERPOISE ABOVE
1. REMOVE EXISTING PARAPET CAP, TYPICAL FOR ALL PARAPET CAPS
2. REMOVE SCUPPER FLASHING AND PREP FOR NEW THROUGH WALL SCUPPER AND
FLASHING
3. REMOVE EXISTING WALK TILES
4. REMOVE EXISTING SKYLIGHTS
5. REMOVE EXISTING COLLECTOR BOX AND DOWNSPOUT AS REQUIRED FOR
INSTALLATION OF NEW SCUPPER AND FLASHING
6. EXISTING ROOF DRAIN - PROTECT
7. REMOVE EXISTING DRIP EDGE
8. REMOVE FLASHING AT EXISTING FLUE TO REMAIN
9. REMOVE FLASHING AT EXISTING OUTSIDE AIR HOOD TO REMAIN
10. REMOVE EXISTING EXHAUST FAN AND CURB, IF NEW EXHAUST FAN REQUIRES
DIFFERENT SIZED CURB - SEE MECHANICAL DRAWINGS FOR ADDITIONAL
INFORMATION
11. REMOVE EXISTING FLUE PER SHEET M101
12. EXISTING OUTSIDE AIR UNIT TO REMAIN
13. REMOVE EXISITNG RELEIF HOOD AND CURB PER SHEET M101
14. REMOVE EXISTING PITCH PANS FROM RADAR SUPPORTS
15. REMOVE FLASHING AT VENT
16. REMOVE FLASHING AROUND COUNTERPOISE COLUMN
DEMOLITION NOTES:
1. EXISTING ROOFING IS 2 1/2" OF POLYISOCYANURATE INSULATION ON METAL DECK
WITH 1/2" WOOD FIBER COVERBOARD, FIBERGLASS REINFORCED BASE SHEET AND
MODIFIED BITUMEN CAP SHEET.
2. REMOVE ALL EXISTING ROOFING AND ASSOCIATED FLASHINGS NECESSARY FOR
INSTALLATION OF NEW ROOFING SYSTEM AND RIGID INSULATION.
3. CONTRACTOR SHALL INSPECT EXISTING ROOF DECKING FOR LIGHT OXIDATION OR
OTHER MORE SEVERE ISSUES SUCH AS SECTIONS WHERE DECK IS RUSTED
THROUGH OR OTHER OPENINGS IN THE DECK THAT MAY NOT NECESSITATE
REPLACEMENT OF DECK OR NESTING OF NEW DECK. CONTRACTOR SHALL NOTIFY
FAA AND ARCHITECT OF ANY ISSUES WITH THE EXISITNG METAL DECK BEFORE
ANY REPAIRS NOTED IN SPECIFICATION SECTION 01 22 00 - UNIT PRICES OR
INSTALLATION OF NEW ROOFING.
4. REMOVE EXISTING SKYLIGHT AND PREPARE EXISTING CURBS FOR NEW SKYLIGHT
GENERAL NOTES:
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
NORTH
FLOOR PLAN1
VEST.
LOBBY
100A
INSTRUCTOR
BREAKOUT
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CBT
PARTS
PARTS
TELE
CLASSROOM
CLASSROOM
MAINT.
CLASSROOM
117A
EQUIP.
PARTS
ALARM
COPY RM
PARTS
JAN
108107
CLASSROOM
CLASSROOM
TELE.
CBT
PARTS
123JAN
PARTS
CLASSROOM
CLASSROOM
MECHANICAL
FAN ROOM
ELECT. ROOM
MEN
VEST
DME LAB
132A
ANTENNA LAB
140A
REPL. TACAN
VEST
WOMEN
VORTAC LAB
109A
VEST
MEN
VOR/DME LAB
112/118
VEST
WOMEN
GPS LAB
LORAN C/
ANTENNA LAB
VOR
VENDING
VEST
LOBBY
LOUNGE
ROOF ACCESS
PARTS
128B
102B
PARTS PARTS
PARTS
121B
ESTABLISHED
2nd GEN.
FIRE
ELECT.
A204
NEW CANOPY
ABOVE.
NEW COLUMNS
FOR CANOPY.
TYP. - PAINT
1. NEW EXTERIOR WALL - REFER TO SHEET A3.01 FOR ADDITIONAL
INFORMATION. INSTALL GYP. WALL BOARD WHERE DAMAGED GYP
BOARD AT THE FLOOR WAS REMOVED. PAINT TO VISUAL
TERMINATION OR CORNER AND PROVIDE NEW RUBBER BASE FOR
NEW WALL AND AT REPAIR OF EXISTING WALL - SEE PHOTO 1
2. MODIFY DOOR FRAMES FOR INSTALLATION OF CONCEALED WIRING
TO LIGHT SWITCH ON MULLION - RE: SHEET E3.03. PATCH FRAME
AND RE-PAINT TO MATCH EXISTING
3. PROVIDE AND INSTALL 4'-0" WIDE AREA OF FOAM INSULATION IN
WALL CAVITY CENTERED ON EXTERIOR WINDOW FRAME - RE:
DETAIL 2/A205 FOR ADDITIONAL INFORMATION.
4. REMOVE PEELING WALL PAINT. PREP, PRIME, AND PAINT ENTIRE
WALL.
5. REMOVE AND REPLACE EXTERIOR DOUBLE DOORS. RE-USE
EXISTING HARDWARE.- PAINT TO MATCH EXISTING FRAME.
6. REPAIR METAL PANEL GASKET.
7. REMOVE EXISTING EJ SEALANT AND PROVIDE NEW SEALANT
8. CHILLERS AND PADS PROVIDED BY SEPERATE CONTRACT
9. REFER TO SHEET E202 FOR REMOVAL OF EXISTING GENERATOR,
PAD AND ASSOCIATED CONNECTIONS AND DETAIL 10/M400 FOR
NEW GENERATOR PAD INSTALLATION
10. NEW EXTERIOR WALL WITH WINDOW - REFER TO SHEET A401 FOR
ADDITIONAL INFORMATION.
XPLAN NOTES:
141A
142A
143A
144A
1 2 3 4 5 6 8 9
E
J
H
G
F
D
C
B
A
1 2 3 4 5 6 7 8 9
E
J
H
G
F
D
C
B
A
5.74.3
4.3 5.7
E.7
D.3
E.7
D.3
8.4
8.41.6
1.6
H.4 H.4
A.6A.6
C.3
F.7 F.7
C.3
3.3 6.7
3.3 6.7
D.4
E.5
10 11 127
11 1210
7 7
7 7
EXISTING CMU WALL
1000kVA
PADMOUNT
XFRMR
JUNCTION
CABINET
CONC. PAD FOR
NEW GENERATOR -
RE: 10/M400
4'-0"
6"
EQUIP (FV)
6"6"
EQUIP (F
V)
5'- 6"
3'-
A205
A205
A205
A205
SIM.
A205
A205
SIM.
O.H.
SIM.
A205
SIM.
A205
SIM.
SCALE: N.T.S.
PHOTO 1 @ CURTAIN WALL1
NEW RUBBER BASE FOR
NEW WALL
PATCH/REPAIR
DETERIORATED/DAMAGED GYPSUM
WALL BOARD NEAR EXISTING
CURTAIN WALL.
REPLACE RUBBER BASE AT
GYPSUM WALL BOARD REPAIR
WITH NEW RUBBER BASE
MATCHING EXISTING BASE TO
REMAIN
NOTE: THIS PHOTO SHOWS WORK TO BE DONE
AT ALL LOCATIONS ON PLAN IDENTIFIED BY
PLAN NOTE #1
A.402
A.402
A.402
2 SIM
A.402 1O.H.
A.402 2O.H.
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
01 5/24/23 ADD-001: CHILLER PADS AND FENCE REMOVAL
REFLECTED CEILING PLAN1
GENERAL NOTES:
1. REPLACE ALL EXISTING LIGHT FIXTURES WITH NEW LED FIXTURES.
RE: E.203 & E.303.
2. REPLACE WATER DAMAGED CEILING PANEL WHERE NOTED OR
HATCHED ON PLAN. ALL OTHER CEILING PANELS AND GRID TO
REMAIN EXISTING. CONTRACTOR SHALL PROVIDE NEW CEILING
PANELS IN A ROOM 139 AND RE-USE THE EXISTING PANELS TO
REPLACE THE PANELS REMOVED IN THE CORRIDORS. CONTRACTOR
MAY USE ROOM 101A IF ADDITIONAL CEILING PANELS ARE
REQUIRED
3. REPLACE ALL LIGHTING CONTROLS AND DIMMERS IN OFFICES. RE:
E4.01.
4. REPLACE ALL OCCUPANCY/VACANCY SENSORS. RE: E4.01.
5. REPLACE ALL EMERGENCY EXIT LIGHTS. RE: E4.01.
GUTTER
DOWNSPOUT
DOWNSPOUT
PREFINISHED ARCHITECTURAL
STANDING SEAM DECKING
LEGEND:
EXISTING CEILING GRID AND PANELS REMOVED
FOR MECHANICAL WORK AS INDICATED ON M1.00
EXISTING GRID AND PANELS STAINED SHALL BE
REPLACED.
2 x 4 LIGHT FIXTURES
T BAR LIGHT FIXTURE
WALL SCONCE
SPEAKER
SMOKE DETECTOR
HVAC SUPPLY DIFUSSER
HVAC RETURN GRILL
KEYED NOTES:
1. REMOVE AND REPLACE WATER DAMAGED GYPSUM BOARD CEILING
BACK TO FRAMING MEMBER. TAPE, BED, AND PAINT TO VISUAL
TERMINATION
2. STAINED CEILING PANELS TO BE REPLACED
3. NEW SKYLIGHT
VEST.
LOBBY
100A
INSTRUCTOR
BREAKOUT
101A
OFFICE
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CBT
PARTS
PARTS
TELE
CLASSROOM
CLASSROOM
MAINT.
CLASSROOM
117A
EQUIP.
PARTS
ALARM
COPY RM
PARTS
JAN
CLASSROOM CLASSROOM
TELE.
CBT
PARTS
JAN
PARTS
CLASSROOM
CLASSROOM
MECHANICAL
FAN ROOM
ELECT. ROOM
MEN
VEST
DME LAB
132A
ANTENNA LAB
140A
REPL. TACAN
VEST
WOMEN VORTAC LAB
109A
VEST
MEN
VOR/DME LAB
112/118
VEST
WOMEN
GPS LAB
LORAN C/
ANTENNA LAB
VOR
128B
VENDING
VEST
LOBBY
LOUNGE
ROOF ACCESS
PARTS
128B
PARTS
PARTS
121B
ESTABLISHED
2nd GEN.
FIRE
ELECT.
105 106
141A
142A
143A
144A
101B
OFFICE
ANTENNA LAB
VOR
128A
OFFICE
116A
102B
PARTS
STEEL COLUMN - PAINT,
TYPICAL
A205
A205
A205
A205
SIM.
A205
A205
SIM.
O.H.
SIM.
A205
SIM.
A205
SIM.
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
6312A202 1314
ROOF PLAN1
ACCESS
PLATFORM
NEW
SKYLIGHTS
NEW
SKYLIGHTS
NEW
SKYLIGHTS
NEW
SKYLIGHTS
EXISTING
TACAN
ANTENNA
EXISTING
TACAN
ANTENNA
EXISTING
TACAN
ANTENNA
EXISTING
TACAN
ANTENNA
NEW TRAFFIC PADS. TYP.
NEW
TRAFFIC
PADS. TYP.
NEW TRAFFIC
PADS. TYP.
NEW
TRAFFIC
PADS. TYP.
EXISTING
CONDENSING
UNIT.
EXISTING
CONDENSING
UNIT.
EXISTING ACCESS
LADDER UP TO HATCH
ON CONTERPOISE.
EXISTING
TACAN
ANTENNA
EXISTING
TACAN
ANTENNA
NEW PREFINISH STRUCTURAL STANDING
SEAM METAL ROOF
NEW MOD BIT ROOFING
SYSTEM ON COVER BOARD
ON RIGID INSULATION* ON
EXISTING DECK.
NEW MOD BIT ROOFING SYSTEM
ON COVERBOARD ON RIGID
INSULATION ON EXISTING DECK.
NEW PARAPET CAP.
TYP.
NEW PARAPET CAP.
TYP.
NEW PARAPET CAP.
TYP.
NEW PARAPET CAP.
TYP.
NEW PARAPET CAP.
TYP.
NEW PARAPET CAP.
TYP.
NEW PARAPET CAP.
TYP.
NEW PARAPET CAP.
TYP.
GENERAL NOTES:
1. CONTRACTOR SHALL REMOVE EXISTING MODIFIED BITUMEN
ROOFING SYSTEM, INSULATION, FLASHINGS, AND PARAPET CAPS
FOR INSTALLATION OF NEW RIGID INSULATION AND ROOFING
SYTEM.
2. CONTRACTOR SHALL NOTIFY ARCHITECT / FAA OF ROOF
DISCOVERED TO BE DAMAGED BY RUST OR NEED TO BE WIRE
BRUSHED, PRIMED, AND RUST INHIBITOR APPLIED BEFORE WORK IS
DONE.
3. REMOVE EXISTING TRAFFIC TILES AND REPLACE WITH NEW TRAFFIC
PADS
4. REFER TO M101 FOR MECHANICAL ROOF EQUIPMENT DEMOLITION
INFORMATION
5. REFER TO M201 FOR MECHANICAL ROOF EQUIPMENT INFORMATION
6. REFER TO SPECIFICATIONS FOR ROOFING THICKNESS AND R-VALUE
7. ADD NEW GALVANIZED CANOPY OVER MECHANICAL YARD AS NOTED
ON SHEET A204.
8. PROVIDE AND INSTALL LASTISEAL SEALER, OR OTHER APPROVED
PENETRATING SEALER WITH 15 YEAR WARRANTY ON CMU VENEER
INDICATED ON DRAWING 2/A303.
9. EXISTING ROOF DECK SHALL BE CLEANED AND PREPPED FOR NEW
INSULATION TO BE ADHERED TO DECK
A.204
A302
A302
A302
A302
A302
A302
2 SIM.
A302
2 SIM.
A302
2 SIM.
A302
2 SIM.
NEW PARAPET CAP.
TYP.
NEW PARAPET
CAP. TYP.
A302
A302
A302
A302
A302
A302
A301
A301
A301
A301
A301
A301
A303
EXISTING VENT
EXISTING ROOF DRAIN.
RE: 7/A.601 TYP.
EXISTING ROOF DRAIN.
RE: 7/A.601 TYP.
EXISTING ROOF DRAIN.
RE: 7/A.601 TYP.
EXISTING ROOF DRAIN.
RE: 7/A.601 TYP.
EXISTING ROOF DRAIN.
RE: 7/A.601 TYP.
EXISTING COLUMN
THRU ROOF. RE: 8/A.601
TYP.
EXISTING COLUMN THRU
ROOF. RE: 8/A.601 TYP.
EXISTING COLUMN
THRU ROOF. RE: 8/A.601
TYP.
EXISTING COLUMN
THRU ROOF. RE: 8/A.601
TYP.
A302
A302
A302
A302
LINE OF COUNTERPOISE
ABOVE
EXISTING EXHAUST
FAN - RE: M1.01
EXISTING EXHAUST FAN
EXISTING EXHAUST FAN
EXISTING EXHAUST FAN
EXISTING EXHAUST FAN
NEST METAL ROOF
DECK OVER OPENING
NEST METAL
ROOF DECK
OVER EXISTING
FLUE OPENING
EXISTING FLUE
HIGH
EXISTING VENT
EXISTING
VENT
EXISTING EXHAUST
FAN RE: M1.01
EXISTING EXHAUST FAN
RE: M1.01
EXISTING EXHAUST
FAN RE: M1.01
EXISTING
VENT
EXISTING EXHAUST
FAN RE: M1.01
LEGEND:
METAL DRIP EDGE. TYP.
METAL DRIP
EDGE, TYP.
TAPPERED INSULATION
EXISTING COLLECTOR AND
DOWNSPOUT - REMOVE AS
REQUIRED FOR NEW SCUPPER
FLASHING AND REINSTALL
EXISTING COLLECTOR AND
DOWNSPOUT - REMOVE AS
REQUIRED FOR NEW SCUPPER
FLASHING AND REINSTALL
SIM.
A302
A302
A302
A302
A302
NEW MOD BIT ROOFING
SYSTEM ON COVER BOARD
ON RIGID INSULATION* ON
EXISTING DECK.
NEW MOD BIT ROOFING
SYSTEM ON COVER BOARD
ON RIGID INSULATION ON
EXISTING DECK.
NEW MOD BIT ROOFING
SYSTEM ON COVER BOARD
ON RIGID INSULATION* ON
EXISTING DECK.
LINE OF COUNTERPOISE
ABOVE
LINE OF COUNTERPOISE
ABOVE
TRAFFIC PADS - CONTRACTOR TO USE THE
STANDARD WIDTH AND THE VARIOUS STANDARD
LENGTHS PROVIDED BY MANUFACTURER TO
ACHIEVE THE WALKPAD LAYOUT DEPICTED IN THIS
DRAWING
A302
A301
NEST METAL ROOF
DECK OVER OPENING
NEST METAL ROOF
DECK OVER OPENING
NEST METAL ROOF
DECK OVER OPENING
TUCKPOINT CMU VENEER FROM
PARAPET THAT IS NOT COVERED
BY ROOFING AND APPLY CLEAR
SEALANT - SEE GENERAL NOTE #8
TUCKPOINT CMU VENEER FROM
PARAPET THAT IS NOT COVERED BY
ROOFING AND APPLY CLEAR SEALANT -
SEE GENERAL NOTE #8
TUCKPOINT CMU VENEER FROM
PARAPET THAT IS NOT COVERED
BY ROOFING AND APPLY CLEAR
SEALANT - SEE GENERAL NOTE #8
TUCKPOINT CMU VENEER FROM
PARAPET THAT IS NOT COVERED
BY ROOFING AND APPLY CLEAR
SEALANT - SEE GENERAL NOTE #8
A402
A303
A301
A303
A303
RD
RD
RD RD
RD
RD
RD
EXISTING VENT
EXISTING VENT
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520. No part of this record may be disclosed to persons without a "need to know", as defined in 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR parts 15 and 1520.
ADDENDUM-00306/2023
E
G
C
D.4
E.5
10 11 12
10 11 12
1 SCALE: 1/4"=1'-0"
ENLARGED CANOPY FLOOR PLAN
E
G
C
D.4
E.5
10 11 12
10 11 12
2 SCALE: 1/4"=1'-0"
ENLARGED CANOPY ROOF PLAN
2'-0" 10'-4" 2'-4"
2"
2' -0
'-4
6' -0
6'
-0
'-4
2'
-0
NEW COLUMN WITH
CONCRETE BASE,
TYPICAL - RE: STRUCT.
EXISTING
BUILDING
EXISTING MECHANICAL
YARD SCREEN WALL
LINE OF CANOPY ABOVE
NEW PRE-FINISHED METAL
CAP
NEW ROOF - RE: A203
HOLD…