2400867_Volusia_Co_Landfill_Loading_Station_Structural_Combined.pdf
PDF 1 MB Posted
- Solicitation number
- 26-B-51IF
- Issued by
- Volusia County, Florida
About this file
This is a structural design document for Volusia County, Florida, detailing the construction specifications for a truck loading station and pump station foundation as part of the Southeast Cell Expansion at Tomoka Farms Road Landfill. The project involves the construction of reinforced concrete slabs, foundations, and related structural elements to support landfill operations. The truck loading station features a 9-inch thick reinforced concrete slab with specifications for floor live loads of 250 PSF with equipment loads, while the pump station includes an 8-inch thick reinforced concrete slab with a 12-inch thick mat foundation designed for 4,000 PSI concrete compressive strength. All structural work must comply with the Florida Building Code 2023 8th Edition and ACI standards, with the design based on a maximum allowable soil bearing capacity of 2,000 PSF as established by a geotechnical report prepared by Tierra, Inc. (Report No. 6511-24-178, dated April 23, 2025). The structural engineer of record is Eduardo Aviles-Nieves, Florida Professional Engineer License No. 85877, who sealed the plans dated January 30, 2026.
The document establishes comprehensive requirements for materials, fabrication, and construction procedures, including specifications for reinforcing steel (ASTM A-615 Grade 60), concrete mix design per ACI 301 standards with 2 to 4 percent air entrainment, and mandatory special inspections for soils, concrete, and steel per Florida Building Code Section 110. The contractor bears sole responsibility for erection procedures, temporary bracing, shoring, safety procedures, and coordination of all specialty engineered products, which must be sealed by a Florida-licensed professional engineer. Shop drawings for concrete mix designs, reinforcing steel, welded wire fabric, and pre-engineered items must be submitted for review and approval prior to fabrication. Construction joint locations in structural slabs and beams must be positioned at mid-span with continuous reinforcing across joints, and all concrete test results must be submitted directly to the engineer of record by the testing agency.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BE, BUT ARE NOT LIMITED TO, THE FOLLOWING:
LATERAL LOADS TO ASSURE STABILITY. SPECIALTY ENGINEERED PRODUCTS SHALL
AND LATERAL LOADS. INTERIOR SPECIALTY PRODUCTS SHALL BE DESIGNED FOR
DESIGNED FOR THE APPROPRIATE GRAVITY LOADS AND WIND LOADS INCLUDING UPLIFT
RESUBMISSIONS AS REQUIRED. ALL SPECIALTY ENGINEERED PRODUCTS SHALL BE
SHOP DRAWINGS ARE SUBMITTED IN A TIMELY MANNER SO AS TO ALLOW REVIEWS AND
LOCATED. CONTRACTOR'S RESPONSIBILITY TO ASSURE THAT THE SPECIALTY ENGINEERED
SEALED BY A LICENSED PROFESSIONAL ENGINEER IN THE STATE WHERE THE PROJECT IS
OF SHOP DRAWINGS FOR SPECIALTY ENGINEERED PRODUCTS WHICH SHALL BE SIGNED AND
A. THE GENERAL CONTRACTOR IS RESPONSIBLE TO COORDINATE THE PROPER SUBMISSION
8. SPECIALTY ENGINEERED PRODUCTS
OTHERWISE SHOWN.
INTENDED TO BE TYPICAL AND SHALL APPLY TO SIMILAR SITUATIONS ELSEWHERE UNLESS
7. ALL DETAILS, SECTIONS AND NOTES INDICATED ON THE CONSTRUCTION DOCUMENTS ARE
DRAWINGS TO PROPERLY CONSTRUCT THE PROJECT.
INFORMATION INDICATED IN THESE CONSTRUCTION DOCUMENTS WITH THE STRUCTURAL
BUILDING, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS AND COORDINATE THE
GENERAL CONTRACTOR SHALL REFER TO THE ARCHITECTURAL, PRE-ENGINEERED METAL
REQUIRED TO PROPERLY COMPLETE THE PROJECT STRUCTURE. THE
AND DO NOT BY THEMSELVES CONTAIN ALL THE INFORMATION
6. THE STRUCTURAL DRAWINGS ARE ONE DISCIPLINE OF THE CONTRACT DOCUMENTS
GENERAL CONDITIONS:
1. MISCELLANEOUS STEEL
1. 250 PSF WITH EQUIPMENT LOADS FOR SLAB-ON-GRADE
A. DESIGN FLOOR LIVE LOAD:
9. DESIGN LOADS FOLLOWING FLORIDA BUILDING CODE 2023 8TH EDITION
3.
4. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE ERECTION
PROCEDURE AND SEQUENCE TO ENSURE THE SAFETY OF THE STRUCTURE AND ITS
COMPONENT PARTS DURING ERECTION. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
ADDITION OF WHATEVER TEMPORARY BRACING, GUYS, TIE-DOWNS OR SHORING MAY BE
NECESSARY. SUCH MATERIAL SHALL BE REMOVED AND SHALL REMAIN THE PROPERTY OF
THE CONTRACTOR AFTER THE COMPLETION OF THE PROJECT.
5. IT SHALL BE THE SOLE RESPONSIBILY OF THE CONTRACTOR FOR INITIATING,
MAINTAINING AND SUPERVISING ALL SAFETY PROCEDURES . THE STRUCTURAL ENGINEER OF
RECORD IS NOT RESPONSIBLE FOR MEANS AND METHODS OF CONSTRUCTION OR FOR
RELATED SAFETY PROCEDURES.
FOUNDATION:
BY A QUALIFIED GEOTECHNICAL ENGINEER.
3. ALL EXCAVATIONS AND BUILDING PADS SHALL BE INSPECTED BY
A QUALIFIED GEOTECHNICAL ENGINEER TO VERIFY THE DESIGN
4. WHERE FILL IS REQUIRED, IT SHALL BE PLACED IN ACCORDANCE
5. FOOTING ELEVATIONS GIVEN ARE FOR THE PURPOSE OF DESIGN.
SOIL BELOW FOOTING NOT MEETING DESIGN BEARING PRESSURE
WITH INSTRUCTIONS OF A QUALIFIED GEOTECHNICAL ENGINEER
PRESSURE AND BACKFILLED PER SOIL REPORT RECOMMENDATIONS
TO LEVEL OF FOUNDATION BEARING. THIS SHALL BE APPROVED
TO MAINTAIN DESIGN BEARING PRESSURE.
ASSUMPTIONS AND REPORT ADVERSE CONDITIONS.
SHALL BE EXCAVATED TO A DEPTH OF VERIFIABLE DESIGN
2. THE SITE SHALL BE PREPARED UNIFORM IN ACCORDANCE WITH
CIVIL DRAWINGS, SPECIFICATIONS, SOILS REPORT AND THE ALLOWABLE
BEARING PRESSURE.
OR DISPLACEMENT OF EXISTING FOUNDATION OR STRUCTURES.
7. PROVIDE ANY BRACING OR SHORING NECESSARY TO AVOID SETTLEMENT
PIPING, ETC.
ANY MOVEMENT OR SETTLEMENT OF ADJACENT STRUCTURES, UTILITIES,
DIMENSIONS INDICATED. TAKE EVERY PRECAUTION TO GUARD AGAINST
6. ALL EXCAVATION SHALL BE KEPT DRY. EXCAVATE TO DEPTHS AND
8. BACKFILL AGAINST WALLS SHALL BE PLACED EVENLY ON EACH SIDE UNLESS SHORING
IS PROVIDED BY THE CONTRACTOR. SHORING SHALL BE THE SOLE RESPONSIBILTY
OF THE CONTRACTOR AND SHALL REMAIN IN PLACE UNTIL STRUCTURAL
ELEMENTS BRACING THE WALL ARE IN PLACE AND HAVE REACHED FULL DESIGN
STRENGTH.
TO CONSTRUCTION.
JOINT LOCATIONS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL PRIOR
JOINT AND ADDITIONAL SHEAR FRICTION REINFORCING. CONSTRUCTION
MID-SPAN AND KEY JOINTED WITH REINFORCING CONTINUOUS ACROSS
15. CONSTRUCTION JOINTS IN STRUCTURAL SLABS AND BEAMS SHALL BE AT
ON DRAWINGS.
7. LAP ALL BARS MINIMUM 48 DIAMETERS UNLESS OTHERWISE NOTED
SHALL BE LAPPED AT LEAST 12 INCHES UNLESS NOTED OTHERWISE.
6. WELDED WIRE FABRIC SHALL CONFORM WITH ASTM A 185. WELDED WIRE FABRIC
ACI SPECIFICATIONS.
5. CONCRETE COVER FOR REINFORCING STEEL SHALL BE AS REQUIRED BY
CONFORMING TO ASTM A-615 GRADE 60. SUBMIT ALL REINFORCING STEEL
4. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC DEFORMED BILLET STEEL
CHAPTER 5 SECTION 5.3 OF ACI 318 LATEST EDITION.
CHAPTER 3, METHOD 1 OR METHOD 3. CONTRACTOR SHALL SUBMIT BACKUP DATA PER
3. CONCRETE MIX SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ACI 301
B. CONCRETE SHALL HAVE 2 TO 4 PERCENT AIR ENTRAINMENT.
A. CONCRETE SLUMP SHALL BE 4 INCHES PLUS OR MINUS 1".
2. ALL CONCRETE SHALL BE READY MIX AND MEET THE FOLLOWING REQUIREMENTS:
1. CONCRETE MEMBERS TO HAVE THE FOLLOWING MINIMUM COMPRESSIVE STRENGTHS
CONCRETE:
AT 28 DAYS:
SHOP DRAWINGS FOR APPROVAL PRIOR TO ANY FABRICATION.
8. PROVIDE ACI STANDARD HOOKS UNLESS NOTED OTHERWISE ON DRAWINGS.
9. ALL CONCRETE WORK SHALL CONFORM TO ACI 318 LATEST EDITION
"THE BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE STRUCTURES", AND
ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS."
UNLESS NOTED OTHERWISE ON THE DRAWINGS.
"MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES"
10. ALL CONCRETE DETAILS SHALL CONFORM TO ACI 315 LATEST EDITION
11. CONTRACTOR SHALL REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR
LOCATIONS AND SIZES OF SLEEVES, OPENINGS, EMBEDDED ITEMS, SLAB RECESSES,
SLOPES, ECT. THESE ITEMS SHALL BE COORDINATED WITH OTHER TRADES AND INSTALLED
PRIOR TO CONCRETE PLACEMENT.
12. CONTRACTOR SHALL VERIFY ANCHOR BOLT SIZES AND LOCATIONS PRIOR TO CONCRETE
PLACEMENT.
PROVIDED AT TOP BARS AT BEAM ENDS AND SLAB EDGES.
13. BAR LENGTHS PROVIDED ON DRAWINGS DO NOT INCLUDE HOOK LENGTH. HOOKS SHALL BE
14. CONTRACTOR SHALL PROVIDE CHAIRS, BOLSTERS, SPACERS, ETC. AS REQUIRED TO SECURELY
SUPPORT REINFORCEMENT. SUPPORT ITEMS ON EXPOSED CONCRETE SHALL BE PLASTIC
SUPPORT REINFORCEMENT. TIPPED OR STAINLESS STEEL. IN HIGHLY CORROSIVE
ENVIRONMENTS, SUPPORT ITEM SHALL BE PLASTIC.
16. A COPY OF THE "FIELD REFERENCE MANUAL" ACI SP-15 LATEST EDITION
SHALL BE KEPT BY THE CONTRACTOR ON SITE.
TESTING AGENCY DIRECTLY TO THE ENGINEER OF RECORD.
17. ONE COPY OF ALL THE CONCRETE TEST RESULTS SHALL BE SUBMITTED BY THE
DRAWINGS FOR ALL FABRICATED MATERIALS TO ARCHITECT FOR
REVIEW. REPRODUCTION OF CONTRACT DRAWINGS FOR SHOP DRAWINGS
B. REVIEW OF SHOP DRAWINGS BY THE ARCHITECT/ENGINEER DOES
NOT RELIEVE THE CONTRACTOR OF THE SOLE RESPONSIBILITY FOR
ERRORS AND OMISSIONS ASSOCIATED WITH THE PREPARATION OF
A. THE CONTRACTOR SHALL SUBMIT, AS REQUIRED, PRINTS OF SHOP
WILL NOT BE PERMITTED.
THOSE SHOP DRAWINGS.
10. SHOP DRAWINGS:
11. THE FOLLOWING SHOP DRAWINGS SHALL BE SUBMITTED:
A. CONCRETE MIX DESIGNS
B. CONCRETE REINFORCING STEEL AND WELDED WIRE FABRIC
SPECIALITY ENGINEER REGISTERED IN THE STATE OF FLORIDA.
12. PRE-ENGINEERED ITEMS SHALL BE SUBMITTED SIGNED AND SEALED BY A
C. 5000 PSI CONCRETE SHALL HAVE A MAXIMUM WATER/CEMENT RATIO OF 0.40.
ALL OTHER CONCRETE TO HAVE MAXIMUM WATER/CEMENT RATIO OF 0.54.
SPECIAL INSPECTIONS
A. SOILS - SECTION 1705.6 PER TABLE 1705.6.
B. CONCRETE - SECTION 1705.3 PER TABLE 1705.3.
C. STEEL - SECTION 1705.2 PER TABLE 1705.2.3.
1. SPECIAL INSPECTIONS SHALL BE PERFORMED IN ACCORDANCE WITH SECTION 110 OF
FBC 2023 AND THE OWNER SHALL EMPLOY ONE OR MORE SPECIAL INSPECTORS TO
PROVIDE INSPECTIONS DURING CONSTRUCTION ON THE TYPES OF WORK LISTED UNDER
SECTION 1704. THE FOLLOWING AREAS OF WORK REQUIRE SPECIAL INSPECTIONS IN
ACCORDANCE WITH THE LISTED 2021 IBC SECTIONS/LOCATIONS:
- ALL CONCRETE INCLUDING FOOTINGS, AND SLABS........4000 PSI
1. THE FOUNDATION DESIGN OF THE STRUCTURES WAS BASED ON THE
FOLLOWING CRITERIA:
A. MAXIMUM ALLOWABLE SOIL BEARING CAPACITY: 2,000 PSF
1. SOILS REPORT PREPARED BY TIERRA, INC.
AND TESTING INC. REPORT NO: 6511-24-178 DATED: APRIL 23, 2025
WHERE DRAWINGS, SPECIFICATIONS, CODES, OR THESE NOTES DIFFER, THE
MORE STRINGENT REQUIREMENT SHALL GOVERN. PROVIDE THE HIGHER
QUALITY/STRENGTH/QUANTITY AS APPLICABLE
1. THE FOLLOWING NOTES SHALL APPLY TO ALL STRUCTURAL DRAWINGS.
2. THE GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SITE CONDITIONS AND
NOTIFY THE ENGINEER OF RECORD PRIOR TO FABRICATION AND CONSTRUCTION. FOR DIMENSIONS
NOT SHOWN ON THE STRUCTURAL DRAWINGS, SEE THE CIVIL DRAWINGS.
9" THICK REINF.
CONC. SLAB
(f'c = 4000 psi) W/
#5 AT 10" O.C. E.W.
S2
#4 BAR x3'-0" LONG
(CENTERED ON
CORNER OF TRENCH
DRAIN) TYP.
S2
(2)ADD'L #5 TOP & BOTT.
BARS EA. SIDE OF OPENING
EA. DIRECTION. EXTEND A
MINIMUM OF 2'-0" PAST
OPENING EACH END (TYP.)
9" THICK REINF.
CONC. SLAB
(f'c = 4000 psi) W/
#5 AT 10" O.C. E.W.
C J
C J
C J
C J
C J
C J
C J
C J
C J
C J
SC1
BP1
SC1
BP1
S2
S2
5B S2
5B S2
S2
5B S2
5B S2
12" DIA. CONC.
FILLED STL. GUARD
POST (TYP. OF 5)
CJ
C J
C J
C J
2'-0"
CONC.
SPEED
BUMP
2'-0"
CONC.
SPEED
BUMP
S2
6" CONC.
CURB
6" CONC.
CURB
16'-6" 11'-0" 16'-6"
44'-0"
'-0
NEW LOADING ARM
3' -6
7' -9
1'
-6
6"
'-0
6"
3'-6" 9'-3" 9'-3" 9'-3" 9'-3"
'-0
22'-0"
M
IN
. 2
SL
O
PE
M
IN
. 2
SL
O
PE
M
IN
. 2
SL
O
PE
M
IN
. 2
SL
O
PE
CL
L22'-0"
3'-0" 38'-0"
C
6" THICK REINF. CONC. SLAB
(f'c = 4000 psi) W/ #5 AT 12" O.C. E.W.
5B S2
5B S2
6" CONC.
CURB
15'-0"
'-0
19'-6" 8'-0" 16'-6"
SIM.
NOTE:
REFER TO MECH. DRAWINGS
FOR CONCRETE SLAB FINAL
LOCATION
'-1
1"
TR
UC
K L
OA
DI
NG
ST
AT
IO
N
FO
UN
DA
TIO
N
PL
AN
Sheet No.
NOTE: THE SCALE OF THESE PLANS MAY HAVE CHANGED DUE TO REPRODUCTION
www.cphcorp.com A Full Service
A & E Firm
CPH Consulting, LLC.
Plans Prepared By :
THIS SHEET NOT VALID FOR
CONSTRUCTION WITHOUT COMPLETE
SET OF PLANS.
500 WEST FULTON STREET
SANFORD, FLORIDA 32771
Ph. (407) 322-6841
Drawn:
Designed:
Checked:
Project No.:
Issue Date:
TO
MO
KA
FA
RM
S R
OA
D
LA
ND
FIL
L
VO
LU
SI
A
CO
UN
TY
, F
LO
RI
DA
SO
UT
HE
AS
T C
EL
L E
XP
AN
SIO
N
State of Florida Licenses:
Engineer No. 3215
11-25-2025
2400867
E.A
EA
DAS
NO
DA
TE
RE
VI
SI
ON
ISSUED FOR
CONSTRUCTION
S11 S11/4" = 1'-0"
TRUCK LOADING STATION FOUNDATION PLAN
N
EDUARDO AVILES-NIEVES, STATE OF
FLORIDA, PROFESSIONAL ENGINEER,
LICENSE NO. 85877.
THIS ITEM HAS BEEN DIGITALLY
SIGNED AND SEALED BY EDUARDO
AVILES-NIEVES ON THE DATE
ADJACENT TO THE SEAL. SIGNATURE
MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
1/30/2026
EDUARDO AVILES-NIEVES, PE
ED
UA
RDO A V ILES-NIEVES
PR
O
FESSIONA
STATE OF
No. 85877
LIC
ENSE
FLO R IDA
L ENGIN
EE
R
SHEET 24 of 38
S23/4" = 1'-0"
SECTION
CL OF TRENCH DRAIN
AND THICKENED SLAB
SLOPE SLOPE
1'-6"
TYP.
1'-6"
TYP.
WIDTH OF
TRENCH DRAIN
+1'-0" MIN.
3" C
LR
3"CLR.
3"
CLR
10 MIL. VAPOR BARRIER
(3) #5 CONT. AT DRAIN
#5 AT 16" OC
8"
5B S2
1/2" JOINT SEALANT
5B S23/4" = 1'-0"
SECTION
CONC. SLAB, SEE PLAN
FOR THICKNESS & REINF.
3" C
LR
1' -4
8" 8"
8"
1#5 CONT.
6"
#5@12" O.C.
1#5 CONT.
6"
FILL SAW CUT
W/JOINT FILLER
SL
AB
SE
E
PL
AN
SAW CUT CONTROL
JOINT TO BE 1/4 THE
SLAB THICKNESS (SHALL
BE WITHIN 12 HOURS)
REBAR REINF.
(SEE PLAN)
S23/4" = 1'-0"
SECTION
CL
CL
1'-0"
2" 11
2"
1' -0
6" 6"
9"
11 2" 11 2"
SECTION MK'D "A-A"
BASE PLATE (BP1)
TYP. SLAB CORNER REINF.
NOTE:
INSTALL BELOW UPPER LAYER
OF SLAB REINFORCING
3'-6"
(2)#4
(CTR ON CORNER)
SEE NOTE ABOVE
2" 6"
SEE PLAN FOR ADD'L
SLAB REINF.
SLAB EDGE
(2)#4 X 6'-0"
(CTR ON CORNER)
SEE NOTE ABOVE
6"
6"
2'-6"
6" 4'
-8
5' -0
GRADE LEVEL
SLOPE TO GRADE
12" DIA CONC FILLED STEEL
GUARD POST W/ BOLLARD
COVER RE: SITE & STREET
FURNISHINGS SPEC
SEALANT
30" DIA CONC AT 12"
POST
24" LONG #6 REBARS
(4 EACH POST)
S21/2" = 1'-0"
BOLLARD DETAIL
SC1
BP1
2'-0" 2'-0"
1 2"
CL
CL
S21" = 1'-0"
SECTION
4' -0
4'-0"
S2
3' -1
1 2"
6"
(16) #5 REBAR VERT.
#3 TIES @ 6" O.C.
6" CONC. CURB
2B S2
1-1/2" NON-SHRINK GROUT
S.S. BASE PLATE: PL
3/4"x12"x12" w/ (4)-5/8" DIA.
SS TYPE 316 ANCHORS
MIN. EMBED 12"
(SC1)
HSS 6x6x3/8" S.S.
SEE PLAN
CL
S21" = 1'-0"
SECTION
AA
3' -0
4'-0"
3' -0
6"
6"
(16) #5 REBAR
VERT.
#3 TIES @ 6" O.C.
(1) #5 CONT.
S23/4" = 1'-0"
SECTION
CONC. SLAB, SEE PLAN
FOR THICKNESS & REINF.
3" C
LR
8" 8"
8"
1#5 CONT.
1' -4
6"
8"
2'-0"
1/2" JOINT SEALANT
CONCRETE SPEED BUMP
#5 @ 12" O.C.
(4)#5 CONT.
S23/4" = 1'-0"
SECTION
CONC. SLAB, SEE PLAN
FOR THICKNESS & REINF.
3" C
LR
1' -4
8" 8"
8"
1#5 CONT.
2B S21" = 1'-0"
SECTION
4'-0"
3' -0
6"
6"
(16) #5 REBAR
VERT.
#3 TIES @ 6" O.C.
(1) #5 CONT. 6"1'-6"
STANDARD ACI
HOOK (TYP.)
Sheet No.
NOTE: THE SCALE OF THESE PLANS MAY HAVE CHANGED DUE TO REPRODUCTION
www.cphcorp.com A Full Service
A & E Firm
CPH Consulting, LLC.
Plans Prepared By :
THIS SHEET NOT VALID FOR
CONSTRUCTION WITHOUT COMPLETE
SET OF PLANS.
500 WEST FULTON STREET
SANFORD, FLORIDA 32771
Ph. (407) 322-6841
Drawn:
Designed:
Checked:
Project No.:
Issue Date:
TO
MO
KA
FA
RM
S R
OA
D
LA
ND
FIL
L
VO
LU
SI
A
CO
UN
TY
, F
LO
RI
DA
SO
UT
HE
AS
T C
EL
L E
XP
AN
SIO
N
State of Florida Licenses:
Engineer No. 3215
11-25-2025
2400867
E.A
EA
DAS
NO
DA
TE
RE
VI
SI
ON
ISSUED FOR
CONSTRUCTION
S2
TR
UC
K L
OA
DI
NG
ST
AT
IO
N
SE
CT
IO
NS
AN
D
DE
TA
ILS
EDUARDO AVILES-NIEVES, STATE OF
FLORIDA, PROFESSIONAL ENGINEER,
LICENSE NO. 85877.
THIS ITEM HAS BEEN DIGITALLY
SIGNED AND SEALED BY EDUARDO
AVILES-NIEVES ON THE DATE
ADJACENT TO THE SEAL. SIGNATURE
MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
1/30/2026
EDUARDO AVILES-NIEVES, PE
ED
UA
RDO A V ILES-NIEVES
PR
O
FESSIONA
STATE OF
No. 85877
LIC
ENSE
FLO R IDA
L ENGIN
EE
SHEET 25 of 38
24'-3"
8' -4
(4)#5 BARS
RE-ENTRANT (TYP.)
8" THICK REINF. CONCRETE SLAB (f'c = 4000 psi) w/ #5 AT 12" O.C. E.W. ON COMPACTED
SUBGRADE PER GEOTECHNICAL ENGINEER'S
RECOMMENDATIONS
S3
8" CONC.
CURB
8" THICK REINF. CONCRETE SLAB
(f'c = 4000 psi) w/ #6 AT 10" O.C. E.W.
(BOTTOM)
(2)ADD'L #6 TOP & BOTT.
BARS EA. SIDE OF OPENING
D (TYP.)
Ø10'-0"
Ø11'-4"
8" CONC.
CURB
8" CONC.
CURB
8"
1' -6
1#5
3"
8" 8"
#5@12" 1'-6"
1' -6
1#5
8"
#5@12"
A
#5 HORIZ. AT 10" O.C. EA. FACE
#5 VERT. AT
10" O.C. EACH FACE
CONT. RIBBED-FLAT
WATERSTOP BY
GREENSTREAK OR
APPROVED EQUAL (TYP.)
T/WET WELL FLOOR
ELEV.:= SEE PLUMBING
STANDARD ACI
HOOK (TYP.)
1'-6"
1' -0
3" C
LR
2" C
LR
1'-6"
6"
1#5 8"
8"
1'-6"
8" 8"
DOWELS TO MATCH SIZE
& SPACING OF WALL VERT.
PROVIDE 62 BAR DIA.
LAP SPLICE (TYP.)
12" THICK REINF. MAT
FOUNDATION (f'c = 4000 psi) w/
#6 AT 8" O.C. E.W TOP AND
BOTTOM ON COMPACTED SOIL
FOLLOWING GEOTECHNICAL
REPORT RECOMMENDATIONS
TOP SLAB, SEE PLAN
FOR THICKNESS
AND REINF.
SLAP OPENING
FOR DOOR ACCESS
HATCH REFER
TO MECH.
CONT. RIBBED-FLAT
WATERSTOP BY
GREENSTREAK OR
APPROVED EQUAL (TYP.)
8"
8"
Sheet No.
NOTE: THE SCALE OF THESE PLANS MAY HAVE CHANGED DUE TO REPRODUCTION
www.cphcorp.com A Full Service
A & E Firm
CPH Consulting, LLC.
Plans Prepared By :
THIS SHEET NOT VALID FOR
CONSTRUCTION WITHOUT COMPLETE
SET OF PLANS.
500 WEST FULTON STREET
SANFORD, FLORIDA 32771
Ph. (407) 322-6841
Drawn:
Designed:
Checked:
Project No.:
Issue Date:
TO
MO
KA
FA
RM
S R
OA
D
LA
ND
FIL
L
VO
LU
SI
A
CO
UN
TY
, F
LO
RI
DA
SO
UT
HE
AS
T C
EL
L E
XP
AN
SIO
N
State of Florida Licenses:
Engineer No. 3215
11-25-2025
2400867
E.A
EA
DAS
NO
DA
TE
RE
VI
SI
ON
ISSUED FOR
CONSTRUCTION
S3
PU
MP
ST
AT
IO
N
CO
NC
RE
TE
SL
AB
S33/8" = 1'-0"
PUMP STATION FOUNDATION PLAN
S33/8" = 1'-0"
PUMP STATION FOOTING SECTION
EDUARDO AVILES-NIEVES, STATE OF
FLORIDA, PROFESSIONAL ENGINEER,
LICENSE NO. 85877.
THIS ITEM HAS BEEN DIGITALLY
SIGNED AND SEALED BY EDUARDO
AVILES-NIEVES ON THE DATE
ADJACENT TO THE SEAL. SIGNATURE
MUST BE VERIFIED ON ANY
ELECTRONIC COPIES.
1/30/2026
EDUARDO AVILES-NIEVES, PE
ED
UA
RDO A V ILES-NIEVES
PR
O
FESSIONA
STATE OF
No. 85877
LIC
ENSE
FLO R IDA
L ENGIN
EE
SHEET 26 of 38
| 2400867-S1 TRUCK LOADING STATION- FOUNDATION PLAN |
| Sheets and Views |
| S1 |
| OLE2 |
| 2400867-S2 TRUCK LOADING STATION- FOOTING SECTION AND DETAILS |