21-Fire Suppression Building C 2.pdf
PDF 83 KB Posted
- Solicitation number
- 542713
- Issued by
- Wayne County, Detroit City, Michigan
About this file
This file is technical specification documentation for Viking Corporation Microfast and MicrofastHP Quick Response Upright and Conventional Sprinklers, relevant to the City of Detroit's DPD Oakman Renovation project for Buildings A and C at 1180 Oakman Boulevard. The document provides comprehensive technical data on fire suppression sprinkler products available in multiple configurations, finishes, and temperature ratings. The sprinklers are small, thermosensitive, glass-bulb spray sprinklers designed for Light and Ordinary Hazard occupancies, with various models offering nominal K-Factors ranging from 2.8 to 8.0 and temperature ratings from 135°F to 286°F. Available finishes include Brass, Chrome-Enloy, White Polyester, Black Polyester, and Black Teflon, with corrosion-resistant coatings available for specialized applications. The sprinklers are cULus Listed, FM Approved, and certified to multiple international standards including NYC, ABS, VdS, LPC, and CE certifications.
The technical specifications detail minimum operating pressures of 7 psi and maximum working pressures up to 250 psi for high-pressure models, with factory hydrostatic testing to 500 psi. Materials include brass or copper frame castings and deflectors, nickel-alloy sealing assemblies with Teflon coating, and glass bulbs rated to -65°F. The document provides ordering information requiring specification of finish suffix and temperature suffix to the base part number, along with available accessories including standard sprinkler wrenches and cabinets with six or twelve-head capacity. Installation must comply with NFPA 13 standards and applicable regional codes, with inspections and maintenance performed according to NFPA 25 requirements. The sprinklers are available through domestic and international distributors, with product availability dating back to 1987 and warranty details available through Viking's current price schedule.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
TECHNICAL DATA
January 22, 2010
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional (Old Style) Sprinklers are small, thermosensitive, glass-bulb spray sprinklers available in several different finishes, temperature ratings, and K-Factors to meet design requirements. The special Polyester and Teflon® coatings can be used in decorative applications where colors are desired. In addi-tion, these coatings have been investigated for installation in corrosive atmos-pheres and are cULus listed as corrosion resistant as indicated in Approval Chart 1. (Note: FM Global has no approval classification for Teflon® and Polyester coatings as corrosion resistant.)
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV FM Approved: Classes 2002 and 2020 NYC Approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16 ABS Certified: Certificate 04-HS407984B-PDA VdS Approved: Certificates G4060054, G4060056, G4880046, G4930039, and G4980020 LPC Approved: Ref. No. 096e/03, TE30401, and TE30872 CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, and
0786-CPD-40171
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 NOTE: Other International approval certificates are available upon request.
Refer to Approval Chart 1 and Design Criteria on pages 51c-d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 51e for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifi cations:
Available since 1987.
Minimum Operating Pressure: 7 psi (0.5 bar)* Maximum Working Pressure: Sprinklers VK315 and VK340 are rated for use with water working pressures ranging from the minimum 7 psi (0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres-sure (HP) sprinklers can be identified by locating “250” stamped on the deflector. All other Part Nos. not mentioned above are rated to a maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: Refer to the Approval Charts
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 06661B, 06766B, 07060, and 12281. Brass UNS-C84400 for all other sprinklers.
Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 06661B and 12281. Copper UNS-C19500 for Sprinklers
06665B, 06764B, 07060, and 14817. Brass UNS-C26000 for all other Sprinklers.
Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Screw: Brass UNS-C36000
Form No. F_080488
Viking Technical Data may be found on The Viking Corporation’s Web site at http://www.vikinggroupinc.com.
The Web site may include a more recent edition of this Technical Data Page.
Sprinkler 51a
Replaces page 51a-e, dated April 25, 2008. (Updated for Sprinkler 14817. Added VdS to Sprinklers 06665B, 06764B, and 14817. Updated FM Approvals and split the Approval Charts to separate UL Listing requirements from FM Approval requirements. Changed the metric K-factor for K4.2 sprinklers to 57.)
TECHNICAL DATA
January 22, 2010
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For Teflon® Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon® Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.)
Order Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester = M-/W, Black Polyester = M-/B, and Black Teflon® = N Temperature Suffix (°F/°C): 135°/57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK300 with a 1/2” thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 06661BAB Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)
Sprinkler Wrench: Standard Wrench: Part No. 10896W/B (available since 2000) Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Sprinkler 51b
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature
Classification Sprinkler Nominal
Temperature Rating1 Maximum Ambient
Ceiling Temperature2 Bulb Color
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon®
Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black Teflon®
Footnotes 1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 51c-e. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and Teflon® coatings.
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
TECHNICAL DATA
January 22, 2010
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Approval Chart 1 (UL) Microfast® and MicrofastHP® Quick Response
Upright and Conventional Sprinklers Maximum 175 PSI (12 bar) WWP
Base Part Number1 SIN
Thread Size Nominal K-Factor Overall Length Listings and Approvals3
(Refer also to Design Criteria on page 51d.)
NPT BSP U.S. metric2 Inches mm cULus4 NYC7 VdS LPCB
Upright-Standard Orifice 06661B VK300 1/2” 15 mm 5.6 80.6 2-3/16 56 A2 A2 -- -- -- -- 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 -- -- A3 A3 B311 B313
Conventional-Standard Orifice 06766B VK310 1/2” 15 mm 5.6 80.6 2-3/16 56 A3 A3 -- A3 B311 B313
Upright-Large Orifice
06665B VK350 3/4” -- 8.0 115.2 2-5/16 59 A2 A2 A3 A3 B311 --
14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2 A2 A3 A3 B311 --
06764B VK350 1/2” 15 mm 8.0 115.2 2-5/16 59 A2 A2 A3 -- -- -- Conventional-Large Orifice
06768B VK354 3/4” 20 mm 8.0 115.2 2-5/16 59 A2 A3 -- A3 B311 -- Upright-Small Orifice10
06717B10 VK325 1/2” 15 mm 2.8 40.3 2-3/16 56 A2 A2 -- -- -- -- 06719B10 VK327 1/2” 15 mm 4.2 57 2-3/16 56 A2 A2 -- -- -- -- 06931B10 VK327 -- 10 mm 4.2 57 2-3/16 56 -- -- A3 -- C112 --
Maximum 250 PSI (17 bar) WWP Upright-Standard Orifice
Base Part Number1 SIN
Thread Size Nominal K-Factor Overall Length Listings and Approvals3
(Refer also to Design Criteria on page 51d.)
NPT BSP U.S. metric2 Inches mm cULus4 NYC8 VdS LPCB
12281 VK315 1/2” 15 mm 5.6 80.6 2-3/16 56 A2 A2 -- -- -- -- Upright-Small Orifice9
1228610 VK340 1/2” 15 mm 2.8 40.3 2-3/16 56 A2 A2 -- -- -- --
Approved Temperature Ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and
286 °F (141°C) B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) C - 155 °F (68 °C)
Approved Finishes 1 - Brass and Chrome-Enloy®
2 - Brass, Chrome-Enloy®, White Polyester5,6, Black Polyester5,6, and Black Teflon®5
3 - Brass, Chrome-Enloy®, White Polyester5,6, and Black Polyester5,6
Footnotes 1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5 cULus Listed as corrosion resistant.
6 Other colors are available on request with the same Listings and Approvals as the standard colors.
7 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA.
8 Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 16.
9 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized.
10The sprinkler orifice is bushed.
11 Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003.
12 Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40131.
13 MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.
Sprinkler 51c
TECHNICAL DATA
January 22, 2010
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
Sprinkler 51d
Figure 1:
Standard Sprinkler Wrench 10896W/B
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 on page 51c) cULus Listing Requirements:
Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers, or old style (conventional) sprinklers.
Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only).
The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer to the installation guidelines for old style (conventional) sprinklers.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor-dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
RESPONSE UPRIGHT AND
CONVENTIONAL SPRINKLERS
TECHNICAL DATA
January 22, 2010
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Sprinkler 51e
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
FM Approval Requirements:
The sprinklers indicated in Approval Chart 2 are FM Approved as quick response Non-Storage upright sprinklers as indicated in the FM Approval Guide.
For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Approval Chart 2 (FM) Microfast® Quick Response Upright Sprinklers
Maximum 175 PSI (12 bar) WWP Base Part Number1 SIN
Thread Size Nominal K-Factor Overall Length FM Approvals3
(Refer also to Design Criteria below.)NPT BSP U.S. metric2 Inches mm Standard Orifice
06661B VK300 1/2” 15 mm 5.6 80.6 2-3/16 56 A2 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 A2
Large Orifice
06665B VK350 3/4” -- 8.0 115.2 2-5/16 59 A2
14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2
Small Orifice4
06717B6 VK325 1/2” 15 mm 2.8 40.3 2-3/16 56 A1
Approved Temperature Ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)
Approved Finishes 1 - Brass and Chrome-Enloy®
2 - Brass, Chrome-Enloy®, White Polyester5, and Black Polyester5
Footnotes 1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the FM Approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4 FM Approved as quick response Non-Storage pendent sprinklers. For specific application and installation requirements, reference the latest appli-cable FM Loss Prevention Data Sheets (including Data Sheet 2-0).
5 Other colors are available on request with the same Approvals as the standard colors.
6 The sprinkler orifice is bushed.
Form No. F_080488
THIS PAGE
INTENTIONALLY
LEFT BLANK
Replaces page 51a-e, dated April 25, 2008. (Updated for Sprinkler 14817. Added VdS to Sprinklers 06665B, 06764B, and 14817. Updated FM Approvals and split the Approval Charts to separate UL Listing requirements from FM Approval requirements. Changed the metric K-factor for K4.2 sprinklers to 57.)