17-Attachment E - Senior Center Roof Plans - A02-A000.pdf
PDF 457 KB Posted
- Attached to
- Senior Center Roof Project
- Solicitation number
- IFB-032-26-KM
- Issued by
- Leon County, Florida
About this file
This is a roofing plans and specifications document for the City of Tallahassee's Senior Center Roof Repairs project, located at 1400 N Monroe Street, Tallahassee, Florida. The project scope encompasses eight roof sections (A, B, C, D, E, F, G, and H) requiring comprehensive restoration work. The primary work includes high-pressure washing of existing roof surfaces, installation of new 80 mil fleece-backed single-ply polyvinyl chloride (PVC) membrane roofing with low-rise foam adhesive, heat-welding of seams and laps, replacement of wall base flashing and penetration flashings with 60 mil PVC membrane, removal and reinstallation of salvaged aluminum parapet coping, installation of new reinforced aluminum gutters and downspouts, cleaning and repainting of roof drains and accessories with stainless steel hardware replacement, and application of reinforced liquid-applied membrane flashing at low-profile skylights and wall bases. The contractor must provide infrared photography to locate wet areas verified by roof cores, remove abandoned rooftop equipment including solar panels and support sleepers, and patch deteriorated lightweight concrete deck areas. The project requires the facility to remain operational during all construction activities, with the contractor responsible for coordinating work sequencing to minimize operational disruptions and maintaining worker safety barricades in accordance with OSHA regulations.
The base bid includes 150 square feet of roofing replacement and 60 square feet of deteriorated lightweight deck replacement, with contractors required to submit unit cost additive/deductive pricing ($___/SF) for variations beyond these amounts. The roofing manufacturer must provide a 20-year non-prorated, no-penalty-sum, and no-dollar-limit warranty covering the complete roofing system, while the contractor and installer must provide a two-year unlimited labor and material warranty on membrane roofing systems. All work must comply with the Florida Building Code (8th Edition, 2023), OSHA and EPA regulations, NRCA roofing and waterproofing standards, and SMACNA architectural sheet metal manual requirements. The contractor bears full responsibility for water intrusion and interior water damage during construction, must maintain 24-hour emergency contact availability throughout the contract period, and is responsible for all site protection, material distribution load management, debris removal, and restoration of disturbed surfaces to original condition.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONSULTANTS
A000
PERMIT SET
PROJ. NO.
DATE
DRAWN
APPROVED
REVISION
REVISION DATE
08/12/2025
ROOFING
SCHEDULE &
NOTES
CHECKED
171824
KR
RB
JS
CONSULTANTS
TA
LL
A H
A
SS
EE
, F
LO
RI
D A
SE
N
IO
R
C
EN
TE
R
BU
IL
D
IN
G R
O O
F
RE
PA
IR
S
C
ITY
O F
TA
LL
A H
A
SS
EE
1 HIGH PRESSURE WASH THE EXISTING ROOF SURFACE TO BE FREE OF DEBRIS AND LOOSE
ROOFING GRANULES. FULLY ADHERE NEW 80 MIL FLEECE BACKED SINGLE-PLY POLYVINYL
CHLORIDE (PVC) MEMBRANE ROOFING WITH LOW RISE FOAM. HEAT WELD SEAMS AND
LAPS IN ACCORDANCE WITH ROOFING MANUFACTURER'S RECOMMENDATIONS.
REMOVE EXISTING WALL BASE FLASHING, SKYLIGHT ROOF HATCH AND EXHAUST FAN
CURB FLASHING AND FULLY ADHERE 60 MIL PVC MEMBRANE FLASHING.
APPLY LIQUID APPLIED FLASHING AT VTR BASE, INSTALL MANUFACTURER'S APPROVED
PVC BOOT WITH DRAW BAND. SEAL TOP EDGE OF BOOT AND APPLY TWO COATS
PREMIUM ACRYLIC PAINT ON EXPOSED PIPE.
CLEAN, PRIME AND PAINT 2 COATS ROOF DRAINS, BOWLS, CLAMPING RINGS AND METAL
BASKET STRAINERS. REPLACE EXISTING BOLTS WITH STAINLESS STEEL BOLTS.
APPLY REINFORCED LIQUID APPLIED MEMBRANE FLASHING PER THE MANUFACTURER'E
REQUIREMENT.
REINSTALL SALVAGED METAL COPING WITH SEALED JOINT COVERS.
INSTALL NEW REINFORCED ALUMINUM GUTTER AN DOWNSPOUTS.
THESE WORK ITEMS ARE TYPICAL AND MAY NOT BE ALL INCLUSIVE BUT INTENDED TO
SUPPLEMENT THE DRAWINGS AND DETAILS AND CLARIFY THE SCOPE OF WORK. WORK LEGEND
ITEMS ARE TYPICAL FOR SITUATIONS AND WORK SCOPE SHOWN. WORK LEGEND SYMBOLS ARE
NOT SHOWN AT EVERY SPECIFIC LOCATION WHICH SCOPE IS TO BE COMPLETED, UNLESS
OTHERWISE NOTED.
A500
VTR
LOW PARAPET WALL
EXHAUST FAN
ABANDONED CAPPED
ROOD CURB
EXISTING SKYLIGHT N.I.C.
NEW SKYLIGHT
VTR
SCUPPER
ABANDONED SLEEPERS TO
BE REMOVED
ROOF DRAIN
ABANDONED SOLAR PANEL
TO BE REMOVED
SLOPE
PHOTO MARKER
PHOTO # / SHEET #
CRICKET
SECTION #
SHEET #
LOW/HIGH
WORK LEGEND NOTE
NOT IN CONTRACT
SIAMESE FIRE HOSE
CONNECTION / STAND PIPE
CHIMNEY
EQUIPMENT HATCH
GUTTER & DOWNSPOUT
ANTENNA TO BE REMOVED
L
1/A700
EF
N.I.C.
S
EX
RD
DS
A
RENOVATION NOTESGENERAL NOTES DEMOLITION NOTES
CAUTION:
CONTRACTOR TO PROVIDE WORKER SAFETY BARRICADES AT ROOF EDGES IN ACCORDANCE
WITH OSHA REGULATIONS.
1. CONTRACTOR TO PROVIDE INFRARED PHOTOGRAPHY TO LOCATE WET AREAS. AREAS
INDICATED AS BEING WET ARE TO BE VERIFIED WITH ROOF CORES.
ROOF 'A', 'B', 'C', 'D', 'E', 'F', 'G', AND 'H',
2. HIGH PRESSURE WASH THE EXISTING ROOF SURFACE FREE OF DEBRIS AND LOOSE
ROOFING GRANULES.
3. CONTRACTOR TO COORDINATE AND VERIFY WITH THE OWNER TO REMOVE ABANDONED
ROOFTOP EQUIPMENT INCLUDING ABANDONED SOLAR PANELS, SUPPORT SLEEPERS, AND
REFRIGERANT LINE. REFRIGERANT LINE AND ABANDONED ROOF PENETRATIONS TO BE CUT
AND CAPPED BELOW THE ROOFING SYSTEM.
4. AS INDICATED ON THE INFRARED SCAN REMOVE WET OR DETERIORATING ROOFING
MATERIALS INCLUDING MEMBRANES, FLASHINGS AND INSULATION DOWN TO THE DECK.
BASE BID AMOUNT OF 150 SF OF REPLACEMENT AND THE CONTRACTOR TO PROVIDE A
$____/SF ADD/DEDUCT.
5. CUT OUT AND PATCH ALL BLISTERS AND WRINKLES IN THE EXISTING GRANULATED CAP
SHEET.
6. CONTRACTOR TO CAREFULLY REMOVE EXISTING PREFINISHED ALUMINUM PARAPET COPING.
COORDINATE WITH STRUCTURAL PLANS FOR THE NEW OPENING FOR THE EQUIPMENT ROOF
ACCESS HATCH. IDENTIFY LOCATION FOR NEW ROOF HATCH.
7. CONTRACTOR TO PROTECT INTERIOR FINISHES DURING ROOFING OPERATION INVOLVING
THE PENETRATION OF THE ROOFING SYSTEM OR OPENING ROOF DECK. EQUIPMENT AND
FACILITY TO REMAIN OPERATIONAL AT ALL TIMES.
ROOF 'B'
8. PATCH, CLEAN AND REPLACE WET/DAMP DAMAGED LIGHTWEIGHT ROOF DECK WHERE
IDENTIFIED TO RECEIVE NEW ROOFING SYSTEM. ALLOW DAMP LIGHTWEIGHT CONCRETE TO
DRY AS LONG AS POSSIBLE (MINIMUM 4 HOURS) PRIOR TO INSTALLING PATCH.
CONTRACTOR TO PROVIDE AN ADDITIVE/DEDUCTIVE UNIT COST ($___/SF) FOR
DETERIORATED LIGHTWEIGHT REPLACEMENT WITH ZONOPATCH OR ZONOLITE PREMIX
LIGHTWEIGHT CONCRETE. BASE BID AMOUNT OF 60 SF REPLACEMENT.
9. REMOVE AND SALVAGE PREFINISHED ALUMINUM COPING TO BE CLEANED AND
REINSTALLED. CONTRACTOR OPTION TO INSTALL NEW WITH SIMILAR PROFILE.
ROOF 'A', 'D', 'E', 'F', 'G', AND 'H',
1. REMOVE LOOSE GRANULES FROM EXISTING ROOF SURFACE. CLEAN SURFACE TO REMOVE
ALL LAITANCE, DIRT, OIL, GREASE, GRANULES AND MILDEW. PROVIDE A CLEAN, SOUND
SURFACE CONDITION. CONTRACTOR SHALL SEAL AND PROTECT INTERIOR FROM WATER
PENETRATION. OWNER SHALL FURNISH WATER AND UTILITIES READILY AVAILABLE ON SITE
TO COMPLETE THE WORK.
2. REMOVE ALL ABANDONED ROOF EQUIPMENT, SLEEPERS, AND SUPPLY LINES AS NOTED.
VERIFY USAGE AND REMOVAL WITH OWNER.
3. AFTER CLEANING EXISTING ROOF SURFACE MEMBRANE AS REQUIRED BY MANUFACTURER.
FULLY ADHERE NEW 80 MIL FLEECE BACKED SINGLE-PLY POLYVINYL CHLORIDE (PVC)
MEMBRANE ROOFING SYSTEM WITH LOW RISE FOAM ADHESIVE RECOMMENDED BY
MANUFACTURER. USE A HEAVY ROLLER TO ENSURE PROPER ADHERED DISPLACEMENT, HEAT
WELD SEAMS AND LAPS IN ACCORDANCE WITH ROOFING MANUFACTURER'S
SPECIFICATIONS AND RECOMMENDATIONS.
4. CUT OUT AND REMOVE EXISTING ROOFING SYSTEM DOWN TO THE STRUCTURAL WOOD
DECK WHERE INDICATED TO INSTALL NEW ROOF ACCESS HATCH. VERIFY OPENING SIZE AND
LOCATION WITH STRUCTURAL AND HVAC DOCUMENT PROVIDED BY THE OWNER. ONCE
ROOF ACCESS HATCH IS INSTALLED, ADHERE 60 MIL PVC MEMBRANE FLASHING SYSTEM
AT THE CURB. HEAT WELD ALL LAPS AND SEAMS, AS REQUIRED.
5. FULLY ADHERE 60 MIL PVC MEMBRANE FLASHING SYSTEM. EXTEND MEMBRANE WALL
FLASHING UP AND OVER PERIMETER PARAPET AND WALL BASE AND ANCHOR TO THE
OUTSIDE FACE OF THE COPING SUBSTRATE, HEAT WELD ALL SEAM AND LAPS AS REQUIRED.
INSTALL MANUFACTURER’S PVC BOOT FLASHING WITH DRAW BAND CLAMPING AT ROOF
PENETRATIONS. APPLY MANUFACTURER APPROVED SEALANT TO THE TOP EDGE OF THE PVC
FLASHING MEMBRANE.
6. REINSTALL SALVAGED PREFINISHED ALUMINUM PARAPET COPING FASTENED WITH A
CONTINUOUS CLEAT AND WITH STAINLESS STEEL SCREWS WITH NEOPRENE WASHERS TO
MEET ANSI/SPRI ES-1 REQUIREMENTS. CONTRACTOR'S OPTION TO INSTALL NEW IN LIEU OF
SALVAGED COPING. INSTALL NEW JOINT COVERS TO BE BLIND SEALED WITH BUTYL TAPE ON
BOTH SIDES OF THE JOINT.
7. CLEAN, PRIME AND PAINT 2 COATS ROOF DRAINS, BOWLS, CLAMPING RINGS AND METAL
BASKET STRAINERS. REPLACE EXISTING BOLTS WITH STAINLESS STEEL BOLTS.
CONTRACTOR TO ENSURE ROOF DRAINS AND DOWNLEADER PIPES ARE SEALED AND FREE
FLOWING. ANY DAMAGED OR CRACKED CLAMPING RING OR BOWLS SHALL BE IDENTIFIED
AND REPLACED.
8. ATTACH PVC COATED EDGE METAL WITH HEMMED DRIP EDGE TO MEET ANSI/ SPRI ES-1
REQUIREMENTS AT PERIMETER ROOF EDGES AND PARAPET WALLS, AS REQUIRED. INSTALL
GUTTER AND DOWNSPOUT SYSTEM TO MEET ANSI/APRI GS-1 REQUIREMENTS. SEAL ALL
GUTTER JOINTS AND CONNECTIONS WITH PREMIUM SILICONE SEALANT. ANCHOR
DOWNSPOUT TO THE EXTERIOR WALL AT THE TOP, MIDDLE AND BOTTOM. INSTALL
CONCRETE SPLASH BLOCK AT EACH DOWNSPOUT OUTFALL
9. APPLY REINFORCED LIQUID APPLIED FLASHING AT THE PERIMETER OF THE LOW PROFILE
SKYLIGHTS PANEL JOINTS, AND WALL BASE ON ROOF "1" TO MANUFACTURER'S
RECOMMENDATIONS AND REQUIREMENTS TO BE INCLUDED IN THEIR WARRANTY. APPLY
COMPATIBLE ROOF COATING TO THE REMAINING AREAS OF ROOF "1". APPLY REINFORCED
LIQUID APPLIED FLASHING AT JOINT, LAPS AND SEAMS TO SEAL THE EXISTING METAL BUILT-
IN GUTTER BETWEEN ROOF "1" AND ANNEX. ENSURE THERE IS NO PONDING AND THERE IS
ADEQUATE FLOW TO OUTLETS.
ROOF 'B' AND 'C'
10. CUT OUT AND PATCH BLISTERS IN THE MINERAL SURFACE BUILT-UP ROOFING (BUR) AND
FLASHING SYSTEMS FROM ROOFS. COMPLETELY CUT OUT AND REMOVE MINERAL SURFACE
‘BUR’ CAP SHEET AND NAILED BASE SHEET IN ALL WET/DAMP AREAS INDICATED BY
INFRARED SCAN. CLEAN THE EXISTING LIGHTWEIGHT CONCRETE DECK AND ALLOW TO DRY
AS LONG AS POSSIBLE (MINIMUM 4 HOURS). CONTRACTOR TO PROVIDE PULL TEST TO
VERIFY MINIMUM REQUIRED LIGHTWEIGHT STRENGTH. REMOVE AND REPLACE DAMAGED
AND/OR DETERIORATED LIGHTWEIGHT CONCRETE AS REQUIRED. CONTRACTOR TO PROVIDE
AN ADDITIVE/DEDUCTIVE UNIT COST (ADEQUATE/SF) WITH PREMIXED LIGHTWEIGHT
CONCRETE (ZONOPATCH) TO MATCH ADJACENT DECK HEIGHT AND PROVIDE A LEVEL
TRANSITION SURFACE.
11. CAREFULLY REMOVE ALUMINUM FOIL FACE FROM MODIFIED BITUMEN FLASHING MEMBRANE
ON PERIMETER PARAPETS AND ROOFTOP EQUIPMENT. CAREFULLY REMOVE AND REPLACE
EXISTING DAMAGED SKYLIGHTS AS DETAILED. SEAL ROOF PENETRATIONS WITH THE
MANUFACTURER APPROVED REINFORCED LIQUID APPLIED FLASHING MEMBRANE.
12. AT ROOF EYEBROW CAREFULLY REMOVE ALUMINUM FOIL FACE FROM MODIFIED BITUMEN
FLASHING ROOF 'C' MEMBRANE. APPLY REINFORCED WATERPROOFING/ ROOF COATING AND
EMBED REINFORCEMENT FABRIC INTO THE COATING WHILE STILL WET, REMOVING ALL
WRINKLES, FISH MOUTHS AND VOIDS. REINFORCEMENT FABRIC TO OVERLAP A MIN. 3".
IMMEDIATELY APPLY A SATURATION COAT AND ALLOW TO DRY. COMPLY WITH
MANUFACTURERS RECOMMENDATIONS. APPLY NEW HIGH SRI PREMIUM ROOF COATING.
13. REINSTALL SALVAGED PREFINISHED ALUMINUM COPING AND RESEAL JOINT COVERS WITH
BUTYL TAPE ON EITHER SIDE OF JOINTS. SEE NOTE #6
1. THE EXISTING OVERALL PLANS ARE FOR INFORMATIONAL PURPOSES ONLY. CONTRACTOR
SHALL FIELD VERIFY ALL DIMENSIONS, ALL PROJECTIONS THROUGH ROOFS, AND ALL
CONDITIONS.
2. BEFORE SUBMITTING PROPOSAL FOR THE WORK, EACH BIDDER WILL BE HELD TO HAVE
EXAMINED THE PREMISES AND SATISFIED HIMSELF AS TO THE EXISTING CONDITIONS UNDER
WHICH HE WILL BE OBLIGED TO OPERATE AND COMPLETE THE WORK UNDER THIS
CONTRACT. NO ALLOWANCE WILL BE MADE SUBSEQUENTLY IN THIS CONNECTION ON
BEHALF OF THE CONTRACTOR FOR ANY ERROR OR NEGLIGENCE ON HIS PART.
3. NORMAL OPERATIONS OF THE FACILITY SHALL CONTINUE DURING DEMOLITION AND
CONSTRUCTION. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THE
WORK WITH ALL SUBCONTRACTORS AND SEQUENCE DEMOLITION AND CONSTRUCTION TO
MINIMIZE INTERRUPTIONS TO NORMAL OPERATIONS OF THE FACILITY.
4. ALL PROPOSED INTERRUPTIONS TO OPERATIONS, SERVICES AND EQUIPMENT SHALL BE
REVIEWED WITH AND APPROVED BY THE OWNER PRIOR TO STARTING SUCH WORK. UNLESS
OTHERWISE APPROVED IN WRITING.
5. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING EXIT WAYS CLEAR. WHERE AN EXIT
MUST BE TEMPORARILY BLOCKED, CONTRACTOR SHALL PROVIDE THE REQUIRED
BARRICADES AND DIRECTIONAL SIGNS FOR TEMPORARY EXITING AND SAFETY.
6. CONTRACTOR SHALL ERECT AND MAINTAIN ALL REASONABLE SAFEGUARDS FOR SAFETY
AND HEALTH INCLUDING POSTING DANGER SIGNS, AND OTHER WARNING AGAINST
HAZARDS, AS WELL AS PROMULGATING SAFETY REGULATIONS.
7. CONTRACTOR SHALL BE RESTRICTED TO AREAS SPECIFIED BY THE OWNER FOR ON SITE
STORAGE OF CONSTRUCTION MATERIALS.
8. CONTRACTOR SHALL TAKE CARE TO DISTRIBUTE LOAD OF EQUIPMENT AND MATERIALS ON
ROOF DURING ALL PHASES OF CONSTRUCTION. CONTRACTOR'S RESPONSIBILITY NOT TO
EXCEED DESIGN LOAD OF EXISTING ROOF STRUCTURE. CONTRACTOR SHALL NOT USE ANY
ROOF AREA OUTSIDE AREA OF THE WORK AND COMPLETED ROOF AREAS FOR STORAGE,
STAGING, OR WORKING.
9. CONTRACTOR SHALL TAKE CARE NOT TO DAMAGE EXISTING SURFACES AND SHALL BE
RESPONSIBLE FOR RETURNING ALL DISTURBED SOD AND REPAIR ALL DAMAGED AREAS
(MATERIALS, FINISHES, LANDSCAPING, ETC..) TO THEIR ORIGINAL CONDITION. SURFACES
SHALL BE REPAIRED TO MATCH THE EXISTING ADJACENT UNDAMAGED SURFACES.
10. CONTRACTOR SHALL MAINTAIN A CLEAN WORK PREMISE AT ALL TIMES AND SHALL CLEAN
CONSTRUCTION SITE OF ALL DEBRIS AT COMPLETION OF THE JOB AND BEFORE FINAL
PAYMENT IS MADE.
11. ALL DOWN LEADERS SHALL BE INSPECTED, CLEANED, AND FREE FLOWING DURING, AND
UPON COMPLETION OF REROOFING.
12. CONTRACTOR SHALL INSPECT THE EXISTING ROOFING SYSTEM, AND COMPENSATE FOR ANY
PONDING CONDITIONS. THE CONTRACTOR SHALL BUILD UP LOW AREAS TO PROVIDE
ADEQUATE POSITIVE DRAINAGE.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WATER INTRUSION AND WATER DAMAGE TO
THE BUILDING INTERIOR DURING CONSTRUCTION.
14. ALL NEW ROOFING MEMBRANE, MEMBRANE FLASHING, AND ROOF ACCESSORIES PROVIDED
BY ROOFING MANUFACTURER SHALL BE CONSIDERED A "ROOFING SYSTEM" AND SHALL
PROVIDE FBC WIND UPLIFT CLASSIFICATION
15. ALL FLASHING SHALL CONFORM TO MANUFACTURER'S RECOMMENDATIONS, AND COMPLY
WITH RECOMMENDED DETAILS OF NRCA ROOFING AND WATERPROOFING MANUAL AND
ARCHITECTURAL SHEET METAL MANUAL, BY THE SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION, INC. (SMACNA).
16. ROOFING MANUFACTURER TO PROVIDE SPECIFIED 20 YEAR WARRANTY, WITH NON
PRORATED, NO PENAL SUM, AND NO DOLLAR LIMIT WARRANTY TO INCLUDE THE ROOF
SYSTEM.
17. CONTRACTOR AND INSTALLER SHALL PROVIDE 2 YEAR UNLIMITED LABOR AND MATERIAL
WARRANTY ON MEMBRANE ROOFING SYSTEMS.
18. CONTRACTOR SHALL SEPARATE ALL DISSIMILAR METALS WITH ASPHALT COATING.
19. ALL WORK SHALL COMPLY WITH APPLICABLE OSHA AND E.P.A. REGULATIONS AND
GUIDELINES.
20. ALL WORK SHALL COMPLY WITH THE FLORIDA BUILDING CODE 8TH EDITION (2023).
21. CONTRACTOR SHALL LIST AN EMERGENCY CONTACT INFORMATION WHERE HE OR SHE MAY
BE REACHED 24 HOURS A DAY, SEVEN DAYS A WEEK, DURING THE ENTIRE PERIOD OF
CONTRACT TIME. THIS INFORMATION SHALL BE PROVIDED AT THE PRECONSTRUCTION
CONFERENCE.
EXISTING ROOFING CONDITIONS
THE EXISTING ROOFING SYSTEM CONSISTS OF
ROOF 'A', 'D', 'E', 'F', 'G', AND 'H'
(FROM THE TOP DOWN)
1. GRANULATED MODIFIED BITUMEN ROOFING SYSTEM
2. TAPERED RIGID INSULATION SYSTEM
3. TEMPORARY MEMBRANE / VAPOR BARRIER
4. WOOD DECK
ROOF 'B'
(FROM THE TOP DOWN)
1. GRANULATED MODIFIED BITUMEN ROOFING SYSTEM
2. LIGHTWEIGHT CONCRETE INSULATION SYSTEM
3. TEMPORARY MEMBRANE / VAPOR BARRIER
4. CONCRETE DECK
ROOF 'C' (EYEBROW)
(FROM TOP DOWN)
1. GRANULATED MODIFIED BITUMEN ROOFING SYSTEM
2. INTERPLY MEMBRANE
3. CONCRETE DECK
ROOFING LEGEND
WORK NOTES
| 2025-08-13T12:42:13-0400 | |