This Fire Hydrant Flow Report documents a water flow test conducted by Rapid Fire Protection, Inc. on 1/29/2021 at Devils Tower National Monument. The report details a hydrant flow test involving two hydrants (A and B) located at the North Seasonal Housing and South Permanent Housing areas, both using AD/533-G/2008 model hydrants. Test results show a single 2.5" outlet flow test yielded 474 gallons per minute (gpm) with a pitot pressure of 8 and a residual pressure of 54, while a test with two 2.5" outlets resulted in 0 gpm. The test procedure involved attaching a gauge to Hydrant B to obtain static pressure, removing the cap from Hydrant A, fully opening the hydrant to clear debris, and recording pressure measurements during water flow.
View the file
Other files for this federal contract opportunity
Show all 33
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Hydrant Flow Report
Rapid Fire Protection, Inc. Date: 1/29/2021 1530 Samco Rd.
Rapid City, SD 57702 Performed by: SB & BH p: (605) 348-2342 f: (605) 348-0108
Devils Tower National Monument, DETO Project
A B Flow Test Hydrant Pressure Test Hydrant
Pitot Gauge
Set Up A B
Location N. Seasonal Housing Location S. Permanent Housing
Make / Model / Year AD/ 533-G/ 2008 Make / Model / Year AD/ 533-G/ 2008
Nozzle Coefficient 0.9 Static Pressure 68
Nozzle Diameter 2.5 Notes
Test 1 - Flowing single 2 1/2" outlet on Hydrant A
Pitot Pressure 8 Residual Pressure 54
Calculated Flow 474 gpm
Test 2 - Flowing two 2 1/2" outlets on Hydrant A
Residual Pressure Residual Pressure
Total Calculated Flow 0 gpm
Test Procedure:
(1) Attach the gauge to Hydrant (B) and obtain static pressure.
(2) Remove cap from Hydrant (A) and record nozzle coefficient.
(3) Fully open Hydrant (A) and allow water to flow to clear debris. Obtain pitot pressure in stream of water.
(4) While water is flowing from Hydrant (A), record residual pressure on gauge located at Hydrant (B).
0.9 0.8 0.7