A0003_Att_Hydrant_Flow_Chart_Graph_0003.pdf

PDF 26 KB Posted

Attached to
DETO 228872 - Replace Obsolete Housing with Multip
Solicitation number
140P2025R0002
Issued by

About this file

This Water Flow Test Report details a hydrant flow test conducted on January 29, 2021, at Devils Tower National Monument's Park Housing location. The test was performed using hydrants A1 and A2, with a gravity-fed water tank supplying water. Key technical measurements include a static reading of 68 PSI, a residual reading of 54 PSI, and a total flow during the test of 475 GPM. The test results indicate that at 20 PSI residual, the flow rate is 923 GPM, and at 0 PSI, the flow rate increases to 1,114 GPM. The test was conducted by RFP, SB & BH on a Friday morning at 9:00 AM, with hydrants having a 2.5-inch opening and a coefficient of 0.9. The report was provided by the Life Safety and Fire Protection Engineering Section located in Little Rock, Arkansas.

View the file

Other files

File Type Posted
B09_A0004_Att_01_91_14_Total_Building_Comm_8-27-25_0004.pdf PDF
B09_A0004_Att_Solicitation_QandA_as_of_9-3-2025_0004.pdf PDF
Sol_140P2025R0002_Amd_0004.pdf PDF
A0003_Att_StatementStructuralTestsSpecialInspections_0003.pdf PDF
A0003_Att_Hydrant_Test_Location_0003.pdf PDF
A0003_Att_Electrical_Report_of_Contact_0003.pdf PDF
A0003_Att_Hazmat_Report_0003.pdf PDF
A0003_Att_Hydrant_Flow_Report_0003.pdf PDF
A0003_Att_S101_Foundation_Plan_0003.pdf PDF
A0003_Att_Hydrant_Location_0003.pdf PDF
A0003_Att_Geotechnical_Report_0003.pdf PDF
Sol_140P2025R0002_Amd_0003.pdf PDF
A0003_Att_01_41_50_Special_Inspections_0003.pdf PDF
A0003_Att_32_33_00_Site_Furnishings_0003.pdf PDF
A0003_Att_01_91_14_Total_Building_Commissioning_0003.pdf PDF
Sol_140P2025R0002_Amd_0002.pdf PDF
B09_A0002_Att_Proposal_Submission_Package_DETO_228872_0002.docx DOCX document
B09_A0001_Att_Prebid_Sign-in_Sheet_(6-17-25)_0001.pdf PDF
Sol_140P2025R0002_Amd_0001.pdf PDF
B09_A0001_Att_Q-and-A_as_of_6-23-25_0001.pdf PDF
B09_A0001_Att_Prebid_Slides_(6-17-25)_0001.pdf PDF
B08_140P2025R0002_(7-31-25).pdf PDF
B08_Att_3_WD_WY20250003_(01-03-25).pdf PDF
B08_Att_4_Structural_Test_Special_Inspections_12-3-24.pdf PDF
B08_Att_6_Electrical_Report_of_Contact.pdf PDF
B08_Att_8_Hazmat_Report_2023-06-06.pdf PDF
B08_Att_10_Hydrant_Flow_Test_1-29-21.pdf PDF
B08_Att_7_Wildfire_Report_2023-06-06.pdf PDF
B08_Att_2_Drawings_(7-24-25).pdf PDF
Sol_140P2025R0002.pdf PDF
B08_Att_9_Floodplain_Hydrologic_Hydraulic_8-15-24.pdf PDF
B08_Att_5_Geotechnical_Report_2020_12_08.pdf PDF
B08_Att_1_Specs_(7-24-25).pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WATER FLOW TEST REPORT

HYDRANT # & LOCATION: 2, N & S Corners of Site Location DATE: 1/29/2021

TEST BY: RFP, SB & BH Day or Week: Friday TIME OF DAY: 9:00am MIN. OF FLOW:

WATER SUPPLIED BY: Gravity Fed Water Tank

PURPOSE OF TEST: Devils Tower National Monument, Park Housing

DATA

FLOW HYDRANT(S) A1 A2 A3

SIZE OPENING: 2.5 2.5

COEFFICIENT: 0.9 0.9

PITOT READING: 8

GPM: 475 0

TOTAL FLOW DURING TEST: 475 GPM

STATIC READING: 68 PSI RESIDUAL: 54 PSI

RESULTS: AT 20 PSI RESIDUAL 923 GPM AT 0 PSI 1114 GPM

ESTIMATED CONSUMPTION: GAL.

REMARKS:

0 68475 54923 201114 0 C = 0.9D = 2.5P = 8

11140

0 500 1000 1500 2000 2500

P re s s u re p s ig

Flow, gpm

Provided by the:

Life Safety and

Fire Protection Engineering

Section

101 S. Spring St

Little Rock, AR 72201

(501) 372-2900