About this file
This document contains technical data sheets and installation instructions for the CBGCW1KS model heating blankets produced by Powerblanket. The heating blankets are designed to be installed on 1000-gallon gas cylinders and consist of two heating blankets and two insulated pads. The instructions detail the proper identification and placement of the left and right heating blankets, as well as the use of the insulated pads to cover the tank top. Key specifications for the heating blankets are provided, including voltage, wattage, amperage, and resistance ranges. Safety features and recommended GFCI circuit use are also noted.
This document supports the federal contract opportunity WRST 248940 - Replace Deficient Visitor Center / Headquarters Water Treatment System, issued by the Department of the Interior National Park Service. The solicitation requires the replacement of a deficient water treatment system, but does not provide further details on the specific products or services sought.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CBGCW1KS INSTRUCTIONS REV C
Technical data sheet and installation instructions. Jen Reyes at Powerblanket®, 801-506-0198
Model GCW1KS Rev C from Powerblanket®
Consists of:
Two heating blankets Two insulated pads
Heating blankets:
GCW1KSL GCW1KSR
Volts, AC, 60 Hz 120 120
Cold performance, up to 100 +/-10F
Watts, +/-10% 1440 1440 Amps, rms 12.0 12.0
Resistance, Ohms 10.0 10.0
Res. Range, Ohms 9.5-10.5 9.5-10.5
Low power performance, based on fill state of tank
Watts, +/-10% 720 720
Amps, rms 6.0 6.0
Resistance, Ohms 20.0 20.0
Res. Range, Ohms 19.0-21.1 19.0-21.1
Hot performance, over 100 +/-10F
Watts 0 0
Amps, rms 0 0
Resistance, Ohms ~infinite ~infinite
Safety features of both blankets:
ETL listed product
Internal switching thermostats, bimetal, creep type, Qty. 2 in each blanket
Thermal spreading and electrically conducting ground plane
Recommend each heating blanket is controlled with a GFCI circuit
CBGCW1KS INSTRUCTIONS REV C
GCW1KS Installation Instructions
Please identify:
GCW1KSL, the left hand heating blanket, it has only buckles on its outside (six on one edge and nine on the cord edge of the heating blanket).
GCW1KSR, the right hand heating blanket, it has only webbing straps on its outside (six are about 18" long and nine are about 60" long and are on the cord edge of the heating blanket).
GCW2x5PADS, quantity two insulated pads approximately 2 ft. x 5 ft. each.
The heating blankets have a "warm" and a "cold" face/side. The easiest way to identify which side of the blankets face the tank when it is all wrapped up is to find the side with NO STRAPS on it. The strapping system for these blankets is all positioned on the cold, outward pointing faces of the blankets when wrapped on the tank. When done, the cord edges of both blankets will be up near the top of the tank with both cords coming off the same end of the tank.
Step 1. Pick which end of the gas cylinder from which you would like the electrical cords to exit.
Position the left and right blankets, cold side down on the ground on either side of the tank, with their six strap edges abutting under the tank. Attach the six webbing straps to the six buckles along these edges. The blankets should be strapped so that the edges are close to each but do not overlap. This small opening along the bottom will allow moisture to drain out the bottom. Note, the cord edges of the blankets are away from each other and both cords point in the same direction.
Step 2. Bring the cord edges toward each other as you lift the blankets and wrap them gently around the sides of the tank. The nine long straps are designed to go up over the top of the tank and down to the nine buckles on the left heating blanket. Get all of the straps attached to the buckles but not yet tightened. There should be about two feet of the top of the tank that is not yet covered. The pads will be used to cover and insulate that area.
Step 3. Because there are numerous versions of 1000 gallon tanks with varying positions for the top mounted features, we supply two insulating pads for you to position lengthwise between the long straps and the top of the tank. The pads can overlap each other and/or the heating blankets. They can deform as needed to cover hooks, pipes, etc. without being damaged. They should be positioned to cover as much of the tank as is possible so long as they are held on with the long straps of the heating blankets.
Step 4. Progressively snug the long straps taking care to keep the six strap edges of the blankets at the bottom of the tank. That lower edge is needed to allow water to drain out of the system.
Jen Reyes @ Powerblanket®, 801-456-8012.