This document appears to be a set of construction drawings for an existing federal facility. It details the planned demolition and replacement of the existing sewer system, septic tank, and leach field at the Headquarters building in Wrangell-St. Elias National Park & Preserve. The drawings show the locations of the existing and proposed components, as well as provide specifications for the new septic tank, piping, and leach field installation. This work is part of a larger project to "Replace Deficient Visitor Center / Headquarters Water Treatment System" under solicitation number 140P2024R0034, issued by the Department of the Interior National Park Service. The drawings provide technical details to support this project requirement but do not contain information about the solicitation itself, such as response dates, award information, or contractual terms.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GARAGE/
UTILITY
HEADQUARTERS
EXISTING 6" SEWER PIPE
EXISTING CLEANOUT
PROTECT HEADQUARTERS SEWER SYSTEM
EXISTING SEWER FROM
GARAGE/UTILITY TO REMAIN
REMOVE EXISTING SEPTIC TANK
9.0-FT
CUT EXISTING SEWER AT 9.0-FT FROM
EXISTING CLEANOUT, SEE NOTE 1
REMOVE EXISTING CLEANOUT AND PIPING
EXISTING CLEANOUT
REMOVE EXISTING LEACH FIELD
APPROXIMATE LIMITS OF PROPOSED
LEACH FIELD EXCAVATION, REMOVAL OF
ITEMS IN NOTE 1, AND INSTALLATION OF
NEW SEPTIC TANK AND PIPING.
EXISTING SEWER FROM
GARAGE/UTILITY TO REMAIN
APPROXIMATE LIMITS OF EXCAVATION FOR
WATER STORAGE TANK AND PLUMBING
EXISTING 8" UTILIDOR, PROTECT IN PLACE
EXISTING ELECTRICAL EQUIPMENT, PROTECT IN PLACE
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
1204/2 4/2
4 1
:35 :04
P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\H
Q
- C op pe rC en ter \S
C2 0-
CS
-D
M-
HQ
.dw g U
SE
R:
NC
ON
W
AY
HQ
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L. CHMIELOWSKI
12/01/2023
EXISTING CONDITIONS
AND DEMOLITION
C1.1-
DEMOLITION NOTES
1. REMOVE ALL EXISTING SEWER SYSTEM COMPONENTS
DOWNSTREAM OF CONNECTION POINT. THE PIPING,
SEPTIC TANK, CLEANOUTS, INSPECTION PIPES, AND
LEACH FILED PIPES SHALL BE REMOVED AND DISPOSED
PER THE ADEC ONSITE WASTEWATER SYSTEM
INSTALLATION MANUAL, ARTICLE 3.17.
2. DO NOT DAMAGE THE HEADQUARTERS BUILDING SEWER
SYSTEM. THE HEADQUARTERS SYSTEM SHALL BE
PROTECTED IN PLACE
REVISIONS
04/24/2024 ADEC REVISIONS NMC
DATE COMMENT BY
GARAGE/
UTILITY
HEADQUARTERS
VISITOR CENTER
MUSEUM
T
H
E
A
T
R
E
E
X
H
I
B
I
T
S
~200-FT WELL RADIUS
PROJECT AREA;
SEE 2/C2.0
EXISTING 6" SEWER PIPE
CONCRETE PAD FOR 5000
GALLON WATER STORAGE
TANK, SEE 1/C2.0
DEEP TRENCH LEACH
FIELD; SEE C3.2
EDGE OF CLEARING
EXISTING CLEANOUT, TYP
CONNECT TO EXISTING
SYSTEM, SEE NOTE 2
HEADQUARTERS SEWER SYSTEM ,
PROTECT IN PLACE
PROJECT AREA;
SEE 1/C2.0
10.0-FT MINIMUM CLEARANCE
GARAGE/
UTILITY
CONCRETE PAD, SEE
NOTE 1 AND DETAIL 1/C3.0
WATER STORAGE TANK,
SEE PLUMBING SHEETS
FOR TANK AND
CONNECTIONS
A
A
10.0-FT
5.0-FT MAX.
SEE GENERAL CIVIL NOTE 4
4-IN PERFORATED PIPE,
DEEP TRENCH, TYP
92.0-FT
INSPECTION PIPE, TYP
DOUBLE CLEANOUT, TYP
20-LF 6-IN HDPE IN 15" ARCTIC PIPE
NEW 4,500 GALLON SEPTIC TANK
CLEANOUT AND
4-IN 90° BEND
4-IN 45° BEND, TYP
10.0-FT 4-IN HDPE ARCTIC PIPE
PROTECT IN PLACE
EXISTING SEWER FROM
GARAGE/UTILITY TO REMAIN
45° BEND
10-LF 6-IN HDPE IN 15" ARCTIC PIPE
CUT EXISTING SEWER AND INSTALL
CLEANOUT AND 45° BEND
DISTRIBUTION BOX
55.0-FT
C2.0
WATER STORAGE TANK PAD
1" = 20'
GENERAL CIVIL NOTES:
1. CONTRACTOR TO VERIFY LOCATION OF
WATER STORAGE TANK PAD WITH PARK
PERSONNEL PRIOR TO CONSTRUCTION.
LOCATE UTILITIES AND VERIFY
SEPARATION DISTANCES ARE MET. SET
ELEVATION OF PAD PER PLUMBING
REQUIREMENTS, AND HIGH ENOUGH SO
THAT SURROUNDING GROUND DRAINS
AWAY AT 5% FOR 5-FT MINIMUM. DO NOT
DIRECT RUNOFF TOWARDS
GARAGE/UTILITY BUILDING.
2. REMOVE ALL EXISTING SEWER SYSTEM
COMPONENTS DOWNSTREAM OF
CONNECTION POINT. DO NOT DAMAGE
THE HEADQUARTERS BUILDING SEWER
SYSTEM. THE HEADQUARTERS SYSTEM
SHALL BE PROTECTED IN PLACE.
3. ADDITIONAL SPACE FOR CONTRACTOR
STAGING MAY BE PROVIDED IN VISITOR
PARKING LOT. COORDINATE WITH PARK
STAFF.
4. RECORDS DO NOT INDICATE A CLEANOUT
ON THE EXISTING SEWER LINE WITHIN
5-FT OF THE BUILDING. CONTRACTOR
SHALL INSPECT UTILITY AND VERIFY IF A
CLEANOUT HAS BEEN INSTALLED. IF
THERE IS NO CLEANOUT THE
CONTRACTOR SHALL INSTALL ONE
WITHIN 5-FT OF THE BUILDING AND NOTE
ON RECORD DRAWINGS.
C2.0
SEPTIC SYSTEM
1" = 20'
LEACH FIELD NOTES:
1. SEE SHEETS C3.1 AND C3.2 FOR SEPTIC TANK AND LEACH
FIELD INSTALLATION.
2. THE CAPACITY OF THE PROPOSED LEACH FIELD IS 4,300
GPD USING AN APPLICATION RATE OF 0.88 GPD/SF.
3. CONTRACTOR SHALL EXCAVATE 6-FT BELOW BOTTOM OF
PROPOSED LEACH FIELD TO DETERMINE IF A CONFINING
LAYER IS PRESENT, DOCUMENT FINDINGS, AND REPORT
TO ENGINEER.
SITE PLAN
C2.0-
CONTRACTOR STAGING AND LAYDOWN
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
1204/2 4/2
4 1
:34 :59
P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\H
Q
- C op pe rC en ter \S
C2 0-
CS
-S
I-C
OP
PE
RC
EN
TE
R.
dw g U
SE
R:
NC
ON
W
AY
HQ
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L. CHMIELOWSKI
12/01/2023
REVISIONS
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
1204/2 4/2
4 1
:35 :06
P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\H
Q
- C op pe rC en ter \S
C2 0-
CS
-D
T-
HQ
.dw g U
SE
R:
NC
ON
W
AY
HQ
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L. CHMIELOWSKI
12/01/2023
6-IN
12-IN
BEDDING, 2-IN MINUS
CLASSIFIED MATERIAL
EXCAVATE AS REQUIRED
TO REMOVE ALL
UNSUITABLE MATERIAL
ARCTIC PIPE
CLEAN NATIVE MATERIAL,
COMPACTED TO 90%
ARFS
EXISTING GROUND = FINISH GRADE,
GRADE TO DRAIN
C3.1
TRENCH SECTION
NTS
6-IN
3.5-FT MINIMUM
4-IN RIGID INSULATION BOARD,
4-FT WIDE CENTERED OVER PIPE. (MAY BE
USED IN PLACE OF ARCTIC PIPE, SEE 3/C3.0)
SEWER LOCATE TAPE
2-FT MIN.
COMPACT BOTTOM OF TRENCH
C3.1
SEPTIC TANK INSTALLATION DETAIL
NTS
ANCHORS, (TYP OF 6)
CABLE, (TYP OF 3)
SLO
PE T
O D
RAIN
S
LO
P E
TO
D
R A
IN
24-IN MANWAY WITH
INSULATED FROST LID
COMPACTED BACKFILL
MUST BE MOUNDED
4-IN TO 6-IN TO ALLOW
FOR SETTLEMENT
ARFS
BACKFILL WITH EXCAVATED MATERIAL,
COMPACT TO 90%
FILL TANK 1/2 FULL OF WATER
PRIOR TO BACKFILLING
SEPTIC TANK FOUNDATION MUST BE
THOROUGHLY COMPACTED NON-FROST
SUSCEPTIBLE MATERIAL
2-FT MINIMUM
4,500 GALLON
STEEL TANK
NOTE:
1. ANCHORS SHALL BE SEATED AND PROOF
LOADED TO 120% OF DESIGN LOAD.
6-IN ARCTIC SEWER PIPE
FROM EXISTING SYSTEM,
SEE NOTE 4
FLEXIBLE LOW PRESSURE COUPLING WITH 2 EACH
SCREW CLAMPS, FERNCO 1056-54 (OR EQUAL) TO
PROVIDE SMOOTH TRANSITION (TYP OF 2)
BACKFILL IN 12" LIFTS,
COMPACT TO 90%
NOTE:
1. 4,500 GALLON, TWO COMPARTMENT STEEL SEPTIC TANK
MANUFACTURED IN COMPLIANCE WITH 18 AAC AND APP. H
OF THE UNIFORM PLUMBING CODE.
2. SEPTIC TANK MUST BE INSTALLED LEVEL.
3. SOLID PIPE WITH NO JOINTS TO SPAN 10 FEET FROM INLET
AND OUTLET OF TANK
4. THE SLOPE OF THE SEWER PIPE IMMEDIATELY PROCEEDING
THE SEPTIC TANK MUST BE BETWEEN 1% AND 2% FOR AT
LEAST 10-FT.
END VIEW
PROFILE
4-IN SEWER PIPE TO LEACH FIELD,
SEE 3/C3.0 FOR INSULATION
24-IN MANWAYS
WITH INSULATED
FROST LIDS
EXISTING 6" ARCTIC PIPE
PROPOSED CLEANOUT
AT CONNECTION
PROPOSED 6" ARCTIC PIPE
LEACH FIELD,
SEE SHEET C3.2
C3.1
SEWER SYSTEM OVERVIEW
NTS
DOUBLE CLEANOUT
10-FT
PROPOSED 4" ARCTIC PIPE
NOTE:
RIGID BOARD INSULATION SHALL BE DOW STYROFOAM HIGHLOAD 40 OR APPROVED EQUAL
4-IN URETHANE INSULATION, 30 PSI
MINIMUM COMPRESSIVE STRENGTH
MOUND TO DRAIN
C3.1-
DETAILS
4-IN URETHANE INSULATION, 30 PSI
MINIMUM COMPRESSIVE STRENGTH
6-IN PVC INLET TEE
4-IN PVC TEE WITH EFFLUENT FILTER
RATED FOR 4300 GPD MINIMUM
6-IN INSPECTION PIPE WITH CAP
DISTRIBUTION BOX
PERFORATED LEACH FIELD
PIPING BEYOND, TYP
2-FT MINIMUM
REVISIONS
4-IN RIGID BOARD
INSULATION
OVER LEACH
FIELD
DISTRIBUTION
PIPE
9-FT MINIMUM, TYP
2-FT COURSE GRADE SEWER ROCK, TYP
INSPECTION PIPE, TYP,
SEE 2/C3.2
B B
DISTRIBUTION BOX;
SEE DETAIL 3/C3.2
4-IN 90° BEND, TYP
4-IN PERFORATED PIPE, HOLES DOWN, TYP
92-FT MINIMUM, TYP
CLEANOUT AND
90° BEND, TYP
PIPE SLOPE
PER NOTE 1
THIS DETAIL
4.5-FT
EXISTING GROUND
4-IN RIGID INSULATION BOARD
2-FT MINIMUM
6-IN
2-FT COURSE GRADE SEWER ROCK
4-IN RIGID INSULATION BOARD,
SET 6-IN ABOVE PERF. PIPE
GRADE TO DRAIN
GRADE T
O D
RAIN
9-FT MIN,
TYP 4.5-FT
4-IN PERFORATED PIPE, HOLES DOWN, TYP
3.5-FT FROM EXISTING GROUND
EXCAVATED MATERIAL
COMPACTED TO 90%
EXISTING GROUND
FINISHED GRADE, SLOPE TO DRAIN
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
1204/2 4/2
4 1
:35 :06
P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\H
Q
- C op pe rC en ter \S
C2 0-
CS
-D
T-
HQ
.dw g U
SE
R:
NC
ON
W
AY
HQ
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L. CHMIELOWSKI
12/01/2023
C3.2
LEACH FIELD - TYPICAL
NTS
C3.2
INSPECTION PIPE
NTS
LEACH FIELD - PLAN
LEACH FIELD - SECTION B-B
DETAILS
C3.2-
NOTES:
1. TUF-TITE 9HDB (9-HOLE DISTRIBUTION BOX) USED AS BASIS FOR DESIGN, APPROVED
EQUALS ALLOWED.
2. DISTRIBUTION BOX SHALL BE INSTALLED LEVEL. MANUFACTURER SUPPLIED
"LEVELERS" MAY ONLY BE USED IF THE DIAMETER OF INLET AND OUTLET PIPES IS
NOT DECREASED.
INLET
C3.2
DISTRIBUTION BOX
NTS
REVISIONS
04/24/2024 ADEC REVISIONS NMC
DATE COMMENT BY
NOTES:
1. THE SLOPE OF THE SEWER PIPE IMMEDIATELY PROCEEDING THE LEACH FIELD MUST
BE BETWEEN 1% AND 2% FOR AT LEAST 10-FT.
File details come from the government source that posted it. Updated .