Attachment 8-NIST Bldg 101 - Level 2 - Lutron Legend.pdf

PDF 84 KB Posted

Attached to
B101 2nd Floor Renovation
Solicitation number
1333ND24QNB190040
Issued by

About this file

This solicitation is for construction services to renovate designated areas of the second floor of Building 101 at the National Institute of Standards and Technology campus. Key details include that the magnitude of construction is estimated between $1 million to $5 million. A mandatory site visit is scheduled for January 22, 2024 from 10am to 12pm EST for offerors to survey site conditions. Questions for the record are due by January 29, 2024 and offers are due by February 27, 2024. The scope of work involves converting the existing second floor layout to a less restricted design intermingling closed offices, conference rooms, open work areas, collaboration spaces and exposed filing and copy spaces. Attachments include construction documents, specifications, asbestos inventory and addenda.

View the file

Other files

File Type Posted
1333ND24QNB190040 Amedment 002-SF-30.pdf PDF
Attachment 10-Final Dwgs_Reissued 02.16.24.pdf PDF
Attachment 5-Sustainable Design Manual.pdf PDF
Attachment 13-Pre-Bid RFIs.xlsx XLSX spreadsheet
Attachment 11-Final Specs_Reissued 02.16.24.pdf PDF
Attachment 1-SF-30.pdf PDF
Attachment 6-101-2-FE-Model.pdf PDF
Attachment 12-NIST Signage Specifications.pdf PDF
Attachment 4-Davis Bacon Wage Determinations.pdf PDF
Attachment 7-Building 101 2nd Floor Offices Building.pdf PDF
Attachment 14-Site Visit Sign In sheet.pdf PDF
Attachment 3- Amended Statement of Work.docx DOCX document
Attachment 2-Ammended_SF1442.pdf PDF
Attachment 9-Final Arch BOD_Reissued 02.16.24-.pdf PDF
Attachment 1-Standard Form 1442.pdf PDF
Attachment 6-NIST Bldg 101 2nd Flr Reno - Final Arch BOD.pdf PDF
Attachment 12-B101 2nd Floor Renovation_Addendum.docx DOCX document
Attachment 8-NIST Bldg 101 2nd Flr Reno - Final Hydraulic Calcs.pdf PDF
Attachment 10-NIST Bldg 101 2nd Flr Reno - Final Specs.pdf PDF
Attachment 11-M101 Induction Unit VLD Locations.pdf PDF
Attachment 5-Building 101 ACM Inventory - Sorted by Room.pdf PDF
Attachment 7-NIST Bldg 101 2nd Flr Reno - Final Dwgs.pdf PDF
Attachment 9-NIST Bldg 101 2nd Flr Reno - Final MEP FP BOD.pdf PDF
Attachment 2 - Key Personnel Resume Form.docx DOCX document
Attachment 4 - Past Performance Questionnaire.doc DOC document
Attachment 3 - Project Data Sheet.doc DOC document
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Wiring Legend:

QS WIRING AS REQUIRED BY CONTROL LINK LENGTH

(REFER TO QS SMART PANEL POWER SUPPLY WIRING GUIDE FOR SHADE WIRING NOTES):

TOTAL CONTROL

LINK LENGTH

WIRE GAUGE AVAILABLE FROM LUTRON IN ONE CABLE:

LESS THAN 500ft (152.4 m)

POWER (TERMINALS 1&2):

1 PAIR 18 AWG (1.0 mm²) GRX-CBL-346S (NON-PLENUM)

OR

GRX-PCBL-346S (PLENUM)DATA (TERMINALS 3&4):

1 PAIR 22 AWG (0.5 mm²), TWISTED AND SHIELDED*

500ft (152.4 m) TO 2,000ft (610 m)**

POWER (TERMINALS 1&2):

1 PAIR 12 AWG (4.0 mm²) GRX-CBL-46L (NON-PLENUM)

OR

GRX-PCBL-46L (PLENUM)DATA (TERMINALS 3&4):

1 PAIR 22 AWG (0.5 mm²), TWISTED AND SHIELDED*

*ALTERNATE DATA-ONLY CABLE: USE APPROVED DATA LINK CABLE (22 AWG [0.5 mm²]

TWISTED/SHIELDED) FROM BELDEN (MODEL # 9461).

**TOTAL LENGTH OF THE QS LINK MUST NOT EXCEED 2,000 ft (600 m).

DEVICES IN THE SAME DOTTED-LINE BOX ARE TO BE CONNECTED ON THE SAME

QS CONTROL LINK. CONSULT THE ONE-LINE DIAGRAM FOR DETAILED DEVICE

WIRING ORDER AND TOPOLOGY.

Q

1-WAY RF COMMUNICATION

2-WAY RF COMMUNICATION

INPUT POWER (NORMAL)

2 #12AWG (4 mm2)

INPUT POWER (NORMAL-EMERGENCY)

LUTRON SENSOR CABLE C-CBL-522S

OTHERWISE USE 3 #22 AWG (1.0 mm2)

3 #12AWG (4 mm2)

0-10V SIGNAL: 2 #18AWG (1.0 mm2) 2 #18AWG (1.0 mm2)

3 #18AWG (1.0 mm2)

LUTRON SENSOR CABLE C-CBL-522S

OTHERWISE USE 4 #22 AWG (1.0 mm2)

CAT5E OR BETTER CABLE FOR LUTRON

NETWORK TERMINATED WITH RJ45

CONNECTORS (TO BE PROVIDED BY

OTHERS). 328 ft (100 m) MAXIMUM RUN.

E

Wiring Notes:

QS LINK RULES

THE FOLLOWING LINK RULES MUST BE OBSERVED FOR PROPER OPERATION:

· THIS IS A TOPOLOGY-FREE LINK (T-TAP, HOME-RUN, ETC. IS OK); REFER TO TABLE BELOW FOR

WIRE RUN LIMITS.

· IF WIRED DIFFERENTLY THAN WHAT IS SHOWN, POWER DRAW UNIT REQUIREMENTS NEED TO

BE CONFIRMED; SEE POWER DRAW UNITS (PDUs) SPECIFICATION SHEET INCLUDED IN THIS

SUBMITTAL.

· MAXIMUM OF 512 OUTPUTS (BALLASTS, SHADES, CONTACT CLOSURES, ETC).

· MAXIMUM OF 100 OCCUPANCY SENSORS, 100 DAYLIGHT SENSORS/RADIO SHADOW SENSORS

AND 100 KEYPADS.

· MAXIMUM OF 100 QS DEVICES (SUCH AS A GRAFIK EYE® QS, SEETOUCH® QS KEYPAD, SMART

PANEL POWER SUPPLY [QSPS-Px-10-60], ESN, OR SIVOIA® QS SHADE / DRAPERY DRIVE UNIT).

QUANTUM PROCESSOR COUNTS AS 1 DEVICE PER LINK.

· MAXIMUM OF 100 ZONES - SUCH AS A SIVOIA QS SHADE / DRAPERY DRIVE UNIT, OR A LIGHTING

ZONE ON A GRAFIK EYE QS (DOES NOT APPLY TO QUANTUM SYSTEMS).

· THE 10 OUTPUTS ON A QSPS-Px-10-60 CANNOT EXCEED A COMBINED LENGTH OF 2,000 ft (600 m).

QUANTUM NETWORK

WHEN A LIGHTING MANAGEMENT NETWORK (LMN) IS REQUIRED TO ENABLE COMMUNICATIONS

BETWEEN INDIVIDUAL LIGHT MANAGEMENT HUBS (LMH) AND BETWEEN LMH AND THE SYSTEM

SERVER/DESKTOP/LAPTOP (Q-MANAGER). THE LMN REQUIRES A DEDICATED LAN OR VLAN. IT IS THE RESPONSIBILITY OF THE NETWORK PROVIDER TO ENSURE THE RELIABILITY AND SECURITY OF THE

LMN.

CAT5E OR BETTER ETHERNET CABLE TO BE RUN FOR DEDICATED LMN TERMINATED WITH RJ45

CONNECTORS (PROVIDED BY OTHERS). THE NUMBER OF ETHERNET HOPS/SEGMENTS BETWEEN THE SERVER/DESKTOP/LAPTOP (Q-MANAGER) AND ANY LMN NODE SHALL NOT EXCEED 6. TOTAL LENGTH

OF ETHERNET CABLE SHALL NOT EXCEED 328 FT (100M) POINT-TO-POINT.

IF LONGER RUNS ARE REQUIRED, MULTI-MODE FIBER OPTIC CABLE CAN BE USED INSTEAD WITH

APPROPRIATE FIBER OPTIC CONNECTORS (PROVIDED BY OTHERS). CONSULT WITH NETWORK

PROVIDER FOR STANDARD ETHERNET AND FIBER OPTIC WIRING RULES FOR DISTANCE AND

SEPARATION AS WELL AS FOR PLACEMENT OF SWITCHES, ROUTERS, HUBS, ETC.

FOR MORE INFORMATION REGARDING NETWORK EQUIPMENT REQUIREMENTS AND NETWORK

CONFIGURATION, PLEASE REFER TO THE QUANTUM LIGHTING MANAGEMENT NETWORK

SPECIFICATION SHEET OR CONTACT LUTRON.

CONCEPT DRAWING NOTES:

CONTROL SYSTEM DRAWING IS PROVIDED FOR CONCEPTUAL PURPOSES ONLY AND IS NOT

INTENDED FOR CONSTRUCTION. EXACT EQUIPMENT REQUIREMENTS, INCLUDING LOCATIONS AND

QUANTITIES, SHOULD BE VERIFIED IN ACCORDANCE WITH THE MOST UP-TO-DATE

LIGHTING/ELECTRICAL REFLECTED CEILING PLANS, LIGHTING FIXTURE SCHEDULES, PANEL

SCHEDULES, CONTROL INTENT AND SPECIFICATIONS. SHADE EQUIPMENT SHOULD BE VERIFIED IN

ACCORDANCE WITH ARCHITECTURAL PLANS, SPECIFICATIONS AND WINDOW

SCHEDULES/DETAILS.

LED DIMMING REQUIRES AN EXACT MATCH BETWEEN THE LED ARRAY, DRIVER AND CONTROL.

LUTRON CANNOT GUARANTEE COMPATIBILITY OR PERFORMANCE WITHOUT TESTING THIS

COMBINATION.

TO CONFIRM WHAT PRODUCTS LUTRON HAS AVAILABLE OR WHAT INTERFACES MAY BE

REQUIRED, CALL 1-877-DIM-LED8 OR CHECK LUTRON'S PRODUCT COMPATIBILITY MATRIX ON-LINE

AT WWW.LUTRON.COM/LED.

TO REQUEST THE TESTING OF AN LED PRODUCT BY LUTRON MANUFACTURERS CAN FILL OUT AN

LED EVALUATION REQUEST FORM ON-LINE AT WWW.LUTRON.COM/LED OR CONTACT

LEDS@LUTRON.COM.

LUTRON CAN GUARANTEE COMPATIBILITY AND PERFORMANCE OF LUTRON HI-LUME LED DRIVERS

USED WITH APPROPRIATE LUTRON CONTROLS. PLEASE REFER TO THE SPECIFICATION

SUBMITTAL SHEET FOR FURTHER INFORMATION.

IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING 0-10V CONTROL, PERFORMANCE AND

COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. PRODUCTS FOLLOWING THE IEC

STANDARD 60929 ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS.

DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER'S DISCRETION.

IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING PHASE CONTROL, PERFORMANCE

AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. HI-LUME OR ELV PRODUCTS

PROVIDING HIGH END AND LOW END TRIM ADJUSTMENTS ARE MORE LIKELY TO PROVIDE

ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO

THE USER'S DISCRETION.