This solicitation is for construction services to renovate designated areas of the second floor of Building 101 at the National Institute of Standards and Technology campus. Key details include that the magnitude of construction is estimated between $1 million to $5 million. A mandatory site visit is scheduled for January 22, 2024 from 10am to 12pm EST for offerors to survey site conditions. Questions for the record are due by January 29, 2024 and offers are due by February 27, 2024. The scope of work involves converting the existing second floor layout to a less restricted design intermingling closed offices, conference rooms, open work areas, collaboration spaces and exposed filing and copy spaces. Attachments include construction documents, specifications, asbestos inventory and addenda.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Wiring Legend:
QS WIRING AS REQUIRED BY CONTROL LINK LENGTH
(REFER TO QS SMART PANEL POWER SUPPLY WIRING GUIDE FOR SHADE WIRING NOTES):
TOTAL CONTROL
LINK LENGTH
WIRE GAUGE AVAILABLE FROM LUTRON IN ONE CABLE:
LESS THAN 500ft (152.4 m)
POWER (TERMINALS 1&2):
1 PAIR 18 AWG (1.0 mm²) GRX-CBL-346S (NON-PLENUM)
OR
GRX-PCBL-346S (PLENUM)DATA (TERMINALS 3&4):
1 PAIR 22 AWG (0.5 mm²), TWISTED AND SHIELDED*
500ft (152.4 m) TO 2,000ft (610 m)**
POWER (TERMINALS 1&2):
1 PAIR 12 AWG (4.0 mm²) GRX-CBL-46L (NON-PLENUM)
OR
GRX-PCBL-46L (PLENUM)DATA (TERMINALS 3&4):
1 PAIR 22 AWG (0.5 mm²), TWISTED AND SHIELDED*
*ALTERNATE DATA-ONLY CABLE: USE APPROVED DATA LINK CABLE (22 AWG [0.5 mm²]
TWISTED/SHIELDED) FROM BELDEN (MODEL # 9461).
**TOTAL LENGTH OF THE QS LINK MUST NOT EXCEED 2,000 ft (600 m).
DEVICES IN THE SAME DOTTED-LINE BOX ARE TO BE CONNECTED ON THE SAME
QS CONTROL LINK. CONSULT THE ONE-LINE DIAGRAM FOR DETAILED DEVICE
WIRING ORDER AND TOPOLOGY.
Q
1-WAY RF COMMUNICATION
2-WAY RF COMMUNICATION
INPUT POWER (NORMAL)
2 #12AWG (4 mm2)
INPUT POWER (NORMAL-EMERGENCY)
LUTRON SENSOR CABLE C-CBL-522S
OTHERWISE USE 3 #22 AWG (1.0 mm2)
3 #12AWG (4 mm2)
0-10V SIGNAL: 2 #18AWG (1.0 mm2) 2 #18AWG (1.0 mm2)
3 #18AWG (1.0 mm2)
LUTRON SENSOR CABLE C-CBL-522S
OTHERWISE USE 4 #22 AWG (1.0 mm2)
CAT5E OR BETTER CABLE FOR LUTRON
NETWORK TERMINATED WITH RJ45
CONNECTORS (TO BE PROVIDED BY
OTHERS). 328 ft (100 m) MAXIMUM RUN.
E
Wiring Notes:
QS LINK RULES
THE FOLLOWING LINK RULES MUST BE OBSERVED FOR PROPER OPERATION:
· THIS IS A TOPOLOGY-FREE LINK (T-TAP, HOME-RUN, ETC. IS OK); REFER TO TABLE BELOW FOR
WIRE RUN LIMITS.
· IF WIRED DIFFERENTLY THAN WHAT IS SHOWN, POWER DRAW UNIT REQUIREMENTS NEED TO
BE CONFIRMED; SEE POWER DRAW UNITS (PDUs) SPECIFICATION SHEET INCLUDED IN THIS
SUBMITTAL.
· MAXIMUM OF 512 OUTPUTS (BALLASTS, SHADES, CONTACT CLOSURES, ETC).
· MAXIMUM OF 100 OCCUPANCY SENSORS, 100 DAYLIGHT SENSORS/RADIO SHADOW SENSORS
AND 100 KEYPADS.
· MAXIMUM OF 100 QS DEVICES (SUCH AS A GRAFIK EYE® QS, SEETOUCH® QS KEYPAD, SMART
PANEL POWER SUPPLY [QSPS-Px-10-60], ESN, OR SIVOIA® QS SHADE / DRAPERY DRIVE UNIT).
QUANTUM PROCESSOR COUNTS AS 1 DEVICE PER LINK.
· MAXIMUM OF 100 ZONES - SUCH AS A SIVOIA QS SHADE / DRAPERY DRIVE UNIT, OR A LIGHTING
ZONE ON A GRAFIK EYE QS (DOES NOT APPLY TO QUANTUM SYSTEMS).
· THE 10 OUTPUTS ON A QSPS-Px-10-60 CANNOT EXCEED A COMBINED LENGTH OF 2,000 ft (600 m).
QUANTUM NETWORK
WHEN A LIGHTING MANAGEMENT NETWORK (LMN) IS REQUIRED TO ENABLE COMMUNICATIONS
BETWEEN INDIVIDUAL LIGHT MANAGEMENT HUBS (LMH) AND BETWEEN LMH AND THE SYSTEM
SERVER/DESKTOP/LAPTOP (Q-MANAGER). THE LMN REQUIRES A DEDICATED LAN OR VLAN. IT IS THE RESPONSIBILITY OF THE NETWORK PROVIDER TO ENSURE THE RELIABILITY AND SECURITY OF THE
LMN.
CAT5E OR BETTER ETHERNET CABLE TO BE RUN FOR DEDICATED LMN TERMINATED WITH RJ45
CONNECTORS (PROVIDED BY OTHERS). THE NUMBER OF ETHERNET HOPS/SEGMENTS BETWEEN THE SERVER/DESKTOP/LAPTOP (Q-MANAGER) AND ANY LMN NODE SHALL NOT EXCEED 6. TOTAL LENGTH
OF ETHERNET CABLE SHALL NOT EXCEED 328 FT (100M) POINT-TO-POINT.
IF LONGER RUNS ARE REQUIRED, MULTI-MODE FIBER OPTIC CABLE CAN BE USED INSTEAD WITH
APPROPRIATE FIBER OPTIC CONNECTORS (PROVIDED BY OTHERS). CONSULT WITH NETWORK
PROVIDER FOR STANDARD ETHERNET AND FIBER OPTIC WIRING RULES FOR DISTANCE AND
SEPARATION AS WELL AS FOR PLACEMENT OF SWITCHES, ROUTERS, HUBS, ETC.
FOR MORE INFORMATION REGARDING NETWORK EQUIPMENT REQUIREMENTS AND NETWORK
CONFIGURATION, PLEASE REFER TO THE QUANTUM LIGHTING MANAGEMENT NETWORK
SPECIFICATION SHEET OR CONTACT LUTRON.
CONCEPT DRAWING NOTES:
CONTROL SYSTEM DRAWING IS PROVIDED FOR CONCEPTUAL PURPOSES ONLY AND IS NOT
INTENDED FOR CONSTRUCTION. EXACT EQUIPMENT REQUIREMENTS, INCLUDING LOCATIONS AND
QUANTITIES, SHOULD BE VERIFIED IN ACCORDANCE WITH THE MOST UP-TO-DATE
LIGHTING/ELECTRICAL REFLECTED CEILING PLANS, LIGHTING FIXTURE SCHEDULES, PANEL
SCHEDULES, CONTROL INTENT AND SPECIFICATIONS. SHADE EQUIPMENT SHOULD BE VERIFIED IN
ACCORDANCE WITH ARCHITECTURAL PLANS, SPECIFICATIONS AND WINDOW
SCHEDULES/DETAILS.
LED DIMMING REQUIRES AN EXACT MATCH BETWEEN THE LED ARRAY, DRIVER AND CONTROL.
LUTRON CANNOT GUARANTEE COMPATIBILITY OR PERFORMANCE WITHOUT TESTING THIS
COMBINATION.
TO CONFIRM WHAT PRODUCTS LUTRON HAS AVAILABLE OR WHAT INTERFACES MAY BE
REQUIRED, CALL 1-877-DIM-LED8 OR CHECK LUTRON'S PRODUCT COMPATIBILITY MATRIX ON-LINE
AT WWW.LUTRON.COM/LED.
TO REQUEST THE TESTING OF AN LED PRODUCT BY LUTRON MANUFACTURERS CAN FILL OUT AN
LED EVALUATION REQUEST FORM ON-LINE AT WWW.LUTRON.COM/LED OR CONTACT
LEDS@LUTRON.COM.
LUTRON CAN GUARANTEE COMPATIBILITY AND PERFORMANCE OF LUTRON HI-LUME LED DRIVERS
USED WITH APPROPRIATE LUTRON CONTROLS. PLEASE REFER TO THE SPECIFICATION
SUBMITTAL SHEET FOR FURTHER INFORMATION.
IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING 0-10V CONTROL, PERFORMANCE AND
COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. PRODUCTS FOLLOWING THE IEC
STANDARD 60929 ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS.
DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER'S DISCRETION.
IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING PHASE CONTROL, PERFORMANCE
AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. HI-LUME OR ELV PRODUCTS
PROVIDING HIGH END AND LOW END TRIM ADJUSTMENTS ARE MORE LIKELY TO PROVIDE
ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO
THE USER'S DISCRETION.