11 - 630A4-22-700 DWGS 2-STRUCT.pdf
PDF 652 KB Posted
- Attached to
- Y1BG--Brooklyn EHRM Infrastructure Upgrades Construction VA Medical Center Brooklyn, NY 630A4-22-700
- Solicitation number
- 36C77626B0002
About this file
This is a structural engineering drawing (S-500) from the U.S. Department of Veterans Affairs for typical allowable penetrations through existing structural walls and decks, part of the EHRM Infrastructure Upgrades project in Brooklyn. The detailed technical drawing provides comprehensive guidelines for creating openings and penetrations in concrete structures, including specific requirements such as: maximum hole sizes (6" for round openings, 1'-0" for square/rectangular), minimum spacing between penetrations, restrictions on drilling through beams or damaging existing reinforcement, and protocols for identifying and documenting existing reinforcing steel before any work begins. The drawing includes multiple detailed views and annotations covering various scenarios like penetrations in post-tension slabs, existing concrete slabs, ribbed slabs, and walls, with explicit instructions to prevent structural damage and maintain structural integrity during modifications.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTES:
1. DO NOT CORE IN THE SHADED AREAS.
2. SEE FOR MORE INFORMATION.
TOC EL
PER PLAN
WALL CORNER
OR EDGE
2' - 0" 2' - 0" 2' - 0" 2' - 0" 2' - 0"
1'
1'
/B6 S-500
NOTES:
1. LOCATE EXISTING REINFORCEMENT PRIOR TO DRILLING AND
DO NOT CUT OR DAMAGE EXISTING REINFORCEMENT.
2. DO NOT DRILL MORE THAN 2 HOLES WITHIN 3'-0" UNLESS
APPROVED BY COR AND SUBMITTED TO SEOR.
3. DO NOT DRILL THROUGH BEAMS.
T d=4" MAX MIN
5D
EXIST CONC SLAB OR WALL
3'-0" MIN
PENETRATIONS FARTHER THAN 8 TIMES THE
PENETRATIONS DIA OR WIDTH, BUT NOT LESS
THAN 24" MIN FROM ANCHOR, DO NOT REQUIRE
STEEL PIPE INSERT
8d O
R w T
YP
d w
SLAB EDGE
NOTES:
1. LOCATE ALL EXISTING REINFORCEMENT, TENDONS, AND PT ANCHOR HEADS PRIOR TO DRILLING
SUCH THAT CORING AND CUTTING DO NOT DAMAGE ANY EXISTING ANCHOR HEADS, PT
TENDONS OR REINFORCEMENT.
2. NEW PENETRATIONS @ 8'-0" OC MIN.
3. NEW ROUND OPENINGS TO BE 6" MAX. NEW SQUARE OR RECTANGULAR OPENING LENGTH/
WIDTH TO BE 1'-0" MAX. CORNERS SHALL BE SMOOTH. DO NOT OVERCUT.
4. BEFORE ANY WORK STARTS: LOCATE AND DOCUMENT EXISTING REINFORCING THAT HAS THE
POTENTIAL TO INTERFERE W/ CONSTRUCTION. IDENTIFY AND DOCUMENT ALL THIS
REINFORCEMENT IN A SHOP DRAWING SUBMITTAL AND SUBMIT TO ARCHITECT FOR STANDARD
SHOP DRAWING REVIEW AND APPROVAL TWO WEEKS BEFORE START OF ANY WORK..
L
D E
C K
S
P A
N
6 1/4"
MIN 3x LARGEST HOLE SIZE.
SPACE SO ADJACENT WEB IS NOT
CUT. DO NOT DAMAGE WEB IF
ADJACENT WEB HAS AN EXIST CUT
HOLES LESS THAN 6" DO NOT REQUIRE REINF
PROVIDED THEY DO NOT CUT MORE THAN ONE WEB
(E) BEAM
(E) BEAM
(E
B E
A M
EXIST CONC
COLUMN PER PLAN
ABOVE OR BELOW
6'
0"
SLAB PENETRATION 5"Ø OR
LESS MAY BE PLACED
OUTSIDE RADIUS SHOWN
WITHOUT PRIOR APPROVAL.
FOR ADDL INFO REFER TO
DO NOT DRILL THROUGH OR
DAMAGE DROPPED SLABS
/B6 S-500
DO NOT DAMAGE OR DRILL
THROUGH WEBS (HATCHED AREA).
FOR ADDL INFO REFER TO /B6 S-500
EXIST FINISHED FLOOR
REMOVE BOTH 8X16 BLOCKS IN
EACH BAY IF MORE THAN ONE
PENETRATION PASSES THROUGH IT
ALL PENETRATIONS MUST
BE THROUGH BLOCKS
FIRE PROOFING PER ARCH. DO NOT
DAMAGE EXISTING CONCRETE BEAM REINF
SEE NOTE, TYPSEE NOTE, TYP
NOTE:
DO NOT DAMAGE OR PLACE PIPES
THROUGH CONC JOIST AND BEAM.
NON-LOAD BEARING WALL PER ARCH.
DO NOT DAMAGE EXISTING
CONCRETE BEAM REINF.
3/4" = 1'-0" C1
PENETRATIONS IN EXISTING CONCRETE OR CMU WALL
1" = 1'-0" B6
PIPING & CONDUIT AT EXISTING FLAT SLAB OR WALL
1" = 1'-0"
B8
PENETRATIONS AT EXIST POST TENSION SLABS
1" = 1'-0" F5
OPENINGS LESS THAN 6" IN COMP DECK & ROOF DECK
3/4" = 1'-0"
F1
PENETRATIONS IN EXISTING CONCRETE SLABS WITH NO BEAMS
1" = 1'-0" E5
OPENINGS IN EXIST RIBBED SLABS
WSP USA Inc.
1201 Pacific Ave, Suite 550 Tacoma WA, 98402
TEL: (206) 431-2300
FAX: (206) 431-2250
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ ENGINEER OF RECORD
A/E:
STAMPCONSULTANT/ DISCIPLINE
321 4 5 6 7 8 9 10
DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/1
/2
:4
:3
A
M
A u to d e s k D o c s
/6
A
-2
-7
V A
N Y
B ro o k ly n E
H R
M
IU
/V A
B K
S
T R
.r v t
S-500
TYPICAL ALLOWABLE PENETRATIONS
THROUGH EXISTING STRUCTURAL WALLS
AND DECKS
NRT JKM
100% CONSTRUCTION
DOCUMENTS
08/29/2025
630A4-22-700EHRM INFRASTRUCTURE
UPGRADES - BROOKLYN
1" = 1'-0" C6
OPENINGS IN EXIST SLABS WITH BLOCKS BETWEEN JOISTS
Revisions: Date:
IN
| Sheets |
| S-500 - TYPICAL ALLOWABLE PENETRATIONS THROUGH EXISTING STRUCTURAL WALLS AND DECKS |