11 - 630A4-22-700 DWGS 2-STRUCT.pdf

PDF 652 KB Posted

Attached to
Y1BG--Brooklyn EHRM Infrastructure Upgrades Construction VA Medical Center Brooklyn, NY 630A4-22-700
Solicitation number
36C77626B0002
Issued by

About this file

This is a structural engineering drawing (S-500) from the U.S. Department of Veterans Affairs for typical allowable penetrations through existing structural walls and decks, part of the EHRM Infrastructure Upgrades project in Brooklyn. The detailed technical drawing provides comprehensive guidelines for creating openings and penetrations in concrete structures, including specific requirements such as: maximum hole sizes (6" for round openings, 1'-0" for square/rectangular), minimum spacing between penetrations, restrictions on drilling through beams or damaging existing reinforcement, and protocols for identifying and documenting existing reinforcing steel before any work begins. The drawing includes multiple detailed views and annotations covering various scenarios like penetrations in post-tension slabs, existing concrete slabs, ribbed slabs, and walls, with explicit instructions to prevent structural damage and maintain structural integrity during modifications.

View the file

Other files

File Type Posted
0010 - 630A4-22-700 Responses to Tech Questions - 4-6-26.pdf PDF
36C77626B0002 0010.pdf PDF
0009 - 630A4-22-700 Responses to Tech Questions - 4-2-26.pdf PDF
0009 - 630A4-22-700 Brand Name Justification.pdf PDF
36C77626B0002 0009.pdf PDF
36C77626B0002 0008.pdf PDF
36C77626B0002 0007.pdf PDF
36C77626B0002 0006.pdf PDF
36C77626B0002 0005.pdf PDF
0005 - 630A4-22-700 Responses to Tech Questions - 3-3-26.pdf PDF
36C77626B0002 0004.pdf PDF
0003 - 630A4-22-700 Change Summary and Spec 01 32 16.15.pdf PDF
0003 - 630A4-22-700 Responses to Tech Questions - 2-24-26.pdf PDF
36C77626B0002 0003.pdf PDF
0002 - 630A4-22-700 Site Visit Sign-in Sheet - 2-3-26.pdf PDF
36C77626B0002 0002.pdf PDF
0002 - 630A4-22-700 DBA Wages - Kings County - 01-30-2026.pdf PDF
36C77626B0002 0001.pdf PDF
IFB 36C77626B0002 - 1-15-26.pdf PDF
06 - 630A4-22-700 Appx C-Topo Survey 2 of 2.pdf PDF
17 - 630A4-22-700 DWGS 7-TELECOM 1 of 2.pdf PDF
07 - 630A4-22-700 Appx D-Asbestos Inspection Report.pdf PDF
08 - 630A4-22-700 Appx E-XRF Lead Report.pdf PDF
10 - 630A4-22-700 DWGS 1-CIVIL.pdf PDF
12 - 630A4-22-700 DWGS 3-ARCH.pdf PDF
15 - 630A4-22-700 DWGS 6-ELEC 1 of 2.pdf PDF
18 - 630A4-22-700 DWGS 7-TELECOM 2 of 2.pdf PDF
19 - 630A4-22-700 PCRA.pdf PDF
20 - 630A4-22-700 ICRA.pdf PDF
01 - 630A4-22-700 SPECS-R2-251030.pdf PDF
02 - 630A4-22-700 Spec Section 01 31 00.01.pdf PDF
03 - 630A4-22-700 Appx A-CFD Analysis.pdf PDF
04 - 630A4-22-700 Appx B-Utilities Locate Survey.pdf PDF
05 - 630A4-22-700 Appx C-Topo Survey 1 of 2.pdf PDF
09 - 630A4-22-700 DWGS 0-GENERAL.pdf PDF
21 - 630A4-22-700 DBA Wages - Kings County - 01-02-2026.pdf PDF
22 - 630A4-22-700 VAAR 852.219-75 LOS - Construction.pdf PDF
13 - 630A4-22-700 DWGS 4-ENVIRO.pdf PDF
14 - 630A4-22-700 DWGS 5-MECH.pdf PDF
16 - 630A4-22-700 DWGS 6-ELEC 2 of 2.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOTES:

1. DO NOT CORE IN THE SHADED AREAS.

2. SEE FOR MORE INFORMATION.

TOC EL

PER PLAN

WALL CORNER

OR EDGE

2' - 0" 2' - 0" 2' - 0" 2' - 0" 2' - 0"

1'

1'

/B6 S-500

NOTES:

1. LOCATE EXISTING REINFORCEMENT PRIOR TO DRILLING AND

DO NOT CUT OR DAMAGE EXISTING REINFORCEMENT.

2. DO NOT DRILL MORE THAN 2 HOLES WITHIN 3'-0" UNLESS

APPROVED BY COR AND SUBMITTED TO SEOR.

3. DO NOT DRILL THROUGH BEAMS.

T d=4" MAX MIN

5D

EXIST CONC SLAB OR WALL

3'-0" MIN

PENETRATIONS FARTHER THAN 8 TIMES THE

PENETRATIONS DIA OR WIDTH, BUT NOT LESS

THAN 24" MIN FROM ANCHOR, DO NOT REQUIRE

STEEL PIPE INSERT

8d O

R w T

YP

d w

SLAB EDGE

NOTES:

1. LOCATE ALL EXISTING REINFORCEMENT, TENDONS, AND PT ANCHOR HEADS PRIOR TO DRILLING

SUCH THAT CORING AND CUTTING DO NOT DAMAGE ANY EXISTING ANCHOR HEADS, PT

TENDONS OR REINFORCEMENT.

2. NEW PENETRATIONS @ 8'-0" OC MIN.

3. NEW ROUND OPENINGS TO BE 6" MAX. NEW SQUARE OR RECTANGULAR OPENING LENGTH/

WIDTH TO BE 1'-0" MAX. CORNERS SHALL BE SMOOTH. DO NOT OVERCUT.

4. BEFORE ANY WORK STARTS: LOCATE AND DOCUMENT EXISTING REINFORCING THAT HAS THE

POTENTIAL TO INTERFERE W/ CONSTRUCTION. IDENTIFY AND DOCUMENT ALL THIS

REINFORCEMENT IN A SHOP DRAWING SUBMITTAL AND SUBMIT TO ARCHITECT FOR STANDARD

SHOP DRAWING REVIEW AND APPROVAL TWO WEEKS BEFORE START OF ANY WORK..

L

D E

C K

S

P A

N

6 1/4"

MIN 3x LARGEST HOLE SIZE.

SPACE SO ADJACENT WEB IS NOT

CUT. DO NOT DAMAGE WEB IF

ADJACENT WEB HAS AN EXIST CUT

HOLES LESS THAN 6" DO NOT REQUIRE REINF

PROVIDED THEY DO NOT CUT MORE THAN ONE WEB

(E) BEAM

(E) BEAM

(E

B E

A M

EXIST CONC

COLUMN PER PLAN

ABOVE OR BELOW

6'

0"

SLAB PENETRATION 5"Ø OR

LESS MAY BE PLACED

OUTSIDE RADIUS SHOWN

WITHOUT PRIOR APPROVAL.

FOR ADDL INFO REFER TO

DO NOT DRILL THROUGH OR

DAMAGE DROPPED SLABS

/B6 S-500

DO NOT DAMAGE OR DRILL

THROUGH WEBS (HATCHED AREA).

FOR ADDL INFO REFER TO /B6 S-500

EXIST FINISHED FLOOR

REMOVE BOTH 8X16 BLOCKS IN

EACH BAY IF MORE THAN ONE

PENETRATION PASSES THROUGH IT

ALL PENETRATIONS MUST

BE THROUGH BLOCKS

FIRE PROOFING PER ARCH. DO NOT

DAMAGE EXISTING CONCRETE BEAM REINF

SEE NOTE, TYPSEE NOTE, TYP

NOTE:

DO NOT DAMAGE OR PLACE PIPES

THROUGH CONC JOIST AND BEAM.

NON-LOAD BEARING WALL PER ARCH.

DO NOT DAMAGE EXISTING

CONCRETE BEAM REINF.

3/4" = 1'-0" C1

PENETRATIONS IN EXISTING CONCRETE OR CMU WALL

1" = 1'-0" B6

PIPING & CONDUIT AT EXISTING FLAT SLAB OR WALL

1" = 1'-0"

B8

PENETRATIONS AT EXIST POST TENSION SLABS

1" = 1'-0" F5

OPENINGS LESS THAN 6" IN COMP DECK & ROOF DECK

3/4" = 1'-0"

F1

PENETRATIONS IN EXISTING CONCRETE SLABS WITH NO BEAMS

1" = 1'-0" E5

OPENINGS IN EXIST RIBBED SLABS

WSP USA Inc.

1201 Pacific Ave, Suite 550 Tacoma WA, 98402

TEL: (206) 431-2300

FAX: (206) 431-2250

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ ENGINEER OF RECORD

A/E:

STAMPCONSULTANT/ DISCIPLINE

321 4 5 6 7 8 9 10

DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/1

/2

:4

:3

A

M

A u to d e s k D o c s

/6

A

-2

-7

V A

N Y

B ro o k ly n E

H R

M

IU

/V A

B K

S

T R

.r v t

S-500

TYPICAL ALLOWABLE PENETRATIONS

THROUGH EXISTING STRUCTURAL WALLS

AND DECKS

NRT JKM

100% CONSTRUCTION

DOCUMENTS

08/29/2025

630A4-22-700EHRM INFRASTRUCTURE

UPGRADES - BROOKLYN

1" = 1'-0" C6

OPENINGS IN EXIST SLABS WITH BLOCKS BETWEEN JOISTS

Revisions: Date:

IN

Sheets
S-500 - TYPICAL ALLOWABLE PENETRATIONS THROUGH EXISTING STRUCTURAL WALLS AND DECKS

File details come from the government source that posted it. Updated .