03 - 630A4-22-700 Appx A-CFD Analysis.pdf

PDF 2 MB Posted

Attached to
Y1BG--Brooklyn EHRM Infrastructure Upgrades Construction VA Medical Center Brooklyn, NY 630A4-22-700
Solicitation number
36C77626B0002
Issued by

About this file

This document is a Computational Fluid Dynamics (CFD) modeling study for the Brooklyn VA Data Hall, conducted by Resolved Analytics. The study examined airflow, temperature, and pressure distribution under four different scenarios involving the operation of three Computer Room Air Conditioning (CRAC) units. Each case simulated a different configuration: Case 1 with all three CRAC units active, and Cases 2-4 with one CRAC unit offline at a time.

The CFD modeling used a three-dimensional, turbulent, single-phase air model with the Realizable K-Epsilon turbulence model and an ideal gas model. The data hall contained 53 total racks (37 active), with a total room load of 125.3 kW. Consistent across all cases, the rack inlet temperatures averaged 75.0°F, and the CRAC return temperatures were consistently 95.0°F. The flow patterns consistently showed high-velocity cold air jets coming through floor tiles, with slight variations in pressure drop between cases ranging from 0.099" to 0.125" water column when operating at a design flow rate of approximately 20,100 CFM.

View the file

Other files

File Type Posted
36C77626B0002 0010.pdf PDF
0010 - 630A4-22-700 Responses to Tech Questions - 4-6-26.pdf PDF
0009 - 630A4-22-700 Brand Name Justification.pdf PDF
36C77626B0002 0009.pdf PDF
0009 - 630A4-22-700 Responses to Tech Questions - 4-2-26.pdf PDF
36C77626B0002 0008.pdf PDF
36C77626B0002 0007.pdf PDF
36C77626B0002 0006.pdf PDF
36C77626B0002 0005.pdf PDF
0005 - 630A4-22-700 Responses to Tech Questions - 3-3-26.pdf PDF
36C77626B0002 0004.pdf PDF
0003 - 630A4-22-700 Responses to Tech Questions - 2-24-26.pdf PDF
36C77626B0002 0003.pdf PDF
0003 - 630A4-22-700 Change Summary and Spec 01 32 16.15.pdf PDF
0002 - 630A4-22-700 Site Visit Sign-in Sheet - 2-3-26.pdf PDF
36C77626B0002 0002.pdf PDF
0002 - 630A4-22-700 DBA Wages - Kings County - 01-30-2026.pdf PDF
36C77626B0002 0001.pdf PDF
IFB 36C77626B0002 - 1-15-26.pdf PDF
07 - 630A4-22-700 Appx D-Asbestos Inspection Report.pdf PDF
08 - 630A4-22-700 Appx E-XRF Lead Report.pdf PDF
10 - 630A4-22-700 DWGS 1-CIVIL.pdf PDF
12 - 630A4-22-700 DWGS 3-ARCH.pdf PDF
15 - 630A4-22-700 DWGS 6-ELEC 1 of 2.pdf PDF
18 - 630A4-22-700 DWGS 7-TELECOM 2 of 2.pdf PDF
19 - 630A4-22-700 PCRA.pdf PDF
20 - 630A4-22-700 ICRA.pdf PDF
01 - 630A4-22-700 SPECS-R2-251030.pdf PDF
02 - 630A4-22-700 Spec Section 01 31 00.01.pdf PDF
04 - 630A4-22-700 Appx B-Utilities Locate Survey.pdf PDF
05 - 630A4-22-700 Appx C-Topo Survey 1 of 2.pdf PDF
09 - 630A4-22-700 DWGS 0-GENERAL.pdf PDF
11 - 630A4-22-700 DWGS 2-STRUCT.pdf PDF
21 - 630A4-22-700 DBA Wages - Kings County - 01-02-2026.pdf PDF
22 - 630A4-22-700 VAAR 852.219-75 LOS - Construction.pdf PDF
06 - 630A4-22-700 Appx C-Topo Survey 2 of 2.pdf PDF
17 - 630A4-22-700 DWGS 7-TELECOM 1 of 2.pdf PDF
13 - 630A4-22-700 DWGS 4-ENVIRO.pdf PDF
14 - 630A4-22-700 DWGS 5-MECH.pdf PDF
16 - 630A4-22-700 DWGS 6-ELEC 2 of 2.pdf PDF
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Brooklyn VA Data Hall Computational Fluid Dynamics Modeling Study

Results Rev.1 Highly Confidential

December 12, 2024

P R

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

• Spees Design Build contracted Resolved Analytics (RA) to perform CFD modeling in support of their Brooklyn VA Data Hall project.

• The CFD modeling will be used to evaluate the spatial distribution of airflow, temperature and pressure as additional CRAC units have been added to the existing data hall.

• Four CFD simulation cases will be run:

• Case 1: All three CRACs in service at a reduced load

• Case 2: CRAC 1 out of service with remaining two CRACs at 100% load

• Case 3: CRAC 2 out of service with remaining two CRACs at 100% load

• Case 4: CRAC 3 out of service with remaining two CRACs at 100% load

• Additional model simulation cases can be provided as needed. These are to be determined and are not covered under the present scope of work.

• Profiles of velocity, temperature, pressure will be reported along with the hot air return temperatures and rack inlet temperatures.

Background

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

• A fully three-dimensional, turbulent, single-phase (air), steady-state CFD model will be used to simulate the flow profile within the data hall.

• A steady-state modeling methodology will be used where the governing equations of fluid motion are iteratively solved to convergence ensuring mass, momentum, and energy conservation.

• The Realizable K-Epsilon turbulence model will be used.

• The air will be simulated using the ideal gas model to allow for density changes due to temperature and pressure.

Simulation Basics

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

• The CFD modeling will simulate the transfer of heat from the servers to the air and subsequent cooling by the CRAC Units.

• Underfloor cooling provided by Three (3) CRAC Units

• Cases 2-4: Underfloor cooling provided by Two (2) CRAC Units

• Two aisles of server racks [39 total racks]

• 27 Standard Density Racks

• 6 Main Distribution Racks

• 4 Active

• 2 Passive

• 6 Horizontal Distribution Racks

• Two Uninterruptable Power Supply Units

• Only one is active at a time

General Conditions – Cases 1-4

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Data Hall Layout – Plan View

CRACs (3 Total)

Cold Air Tile Openings (56%

Open Area)

UPS

(Active)

MDA Racks (Active)

MDA Racks (Passive)

MDA Racks (Passive)

SD Racks (Between Arrows)

HDA Racks

SD Racks (Between Arrows)

HDA Racks

SD Racks (Between Arrows)

HDA Racks

UPS

(Inactive)

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

CFD Model Geometry and Boundaries Equipment Rack Exhausts – Red

CRAC Return Intakes - Orange

Cold Air Floor Tiles – Purple

CRAC Supplies - Green

Equipment Rack Inlets – Blue

UPS - Yellow

CRAC 1

CRAC 2

CRAC 3

Cold Aisle Containment Curtains – Dark Blue

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

• Case 1: All Three CRACs operating at equal load and supplying air @ 75°F with

• CRAC flow rate = 6,700 CFM each [Total = 20,100 CFM]

• Case 2: CRAC 1 offline with two CRACs operating at equal load and supplying air @ 75°F

• CRAC flow rate = 10,050 CFM each [Total = 20,100 CFM]

• Case 3: CRAC 2 offline with two CRACs operating at equal load and supplying air @ 75°F

• CRAC flow rate = 10,050 CFM each [Total = 20,100 CFM]

• Case 4: CRAC 3 offline with two CRACs operating at equal load and supplying air @ 75°F

• CRAC flow rate = 10,050 CFM each [Total = 20,100 CFM]

Model Inputs and Process Conditions – Cases 1-4

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

For all cases:

• 53 Racks total:

• 27 Standard (SD) Cabinets @ 160 CFM/kW & 3.5 kW load each

• 4 Main Distribution Area (MDA) Racks @ 160 CFM/kW & 3.5 kW load each

• Additional 2 MDA Racks included, but are assumed passive at 0kW load each

• 6 Horizontal Distribution Area (HDA) Racks @ 160 CFM/kW & 2.8 kW load each

• UPS at 0 kW load

• Total room kW load = 125.3 kW

• Total CFM provided for Room = 20,100 CFM

• Cold Air Floor Tiles are 56% open area

Model Inputs and Process Conditions – Cases 1-4

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

P R

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Case 1 Results 3 CRACs Active

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Velocity Contour, Data Hall, Case 1

Highest velocity flow entering the CRAC units and flowing around cold side containment

Velocities < 8 ft/s filtered out for clarity.

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Temperature Contour, Case 1 Room at held at a constant temperature

Average CRAC Return Temp:

95.0°F

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, 1’ Below Floor, Case 1

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, 4’ Elevation, Case 1

Higher velocity coming in through the floor tiles

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, Mid-Plane, Case 1 High velocity plumes from floor tiles dictate the flow patterns in the cold side containment zones.

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Temperature Profile, 4’ Elevation, Case 1 Room is held at a constant temperature of 95°F

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Rack Inlet Temperatures, Case 1

Avg Rack Inlet Temp = 75.0°F Local Max = 75.0°F

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Pressure Contour, Case 1 Avg CRAC Supply Pressure = 0.083”wc Avg Rack Inlet Pressure = 0.002” wc dP CRACs to Racks = 0.081” wc Avg Rack Outlet Pressure = 0.002” wc Avg CRAC Return Pressure = -0.016”wc dP Rack Outlets to CRAC Returns = 0.018” wc Cold Side dP + Hot Side dP, Avg = 0.099”wc

Highest gradient is from underfloor zone through floor tiles to data hall.

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

• CFD Model Simulation completed for Case 1 case with all 3 CRAC units in service with design IT rack loads

• 37 total Racks, 31 at 3.5kW load, 6 at 2.8kW load [125.3kW total]

• 160 CFM/kW rack flowrate [Required flow = 160*125.3 = 20,048 CFM]

• CRAC flows in Case 1 model case: Design value of 6,700 CFM each at 75°F cold air supply [total =

20,100 CFM]

• Flow patterns predicted exhibit high velocity cold air jets through floor tiles.

• Rack Inlet Temperatures:

• Avg = 75.0°F

• Local Max = 75.0°F

• Avg. CRAC return temperature = 95.0°F

• Avg. CRAC pressure drop from Supply to Return: 0.099” wc [@ flow of 6,700

CFM]

Summary - Case 1

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

P R

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Case 2 Results 2 CRACs Active, CRAC 1 Inactive

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

CFD Model Geometry and Boundaries, Case 2

CRAC 1

(Offline)

CRAC 2

CRAC 3

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Velocity Contour, Data Hall, Case 2

Highest velocity flow entering the CRAC units and flowing around cold side containment

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Temperature Contour, Case 2 Room at held at a constant temperature

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, 1’ Below Floor, Case 2

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, 4’ Elevation, Case 2

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, Mid-Plane, Case 2 High velocity plumes from floor tiles dictate the flow

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Temperature Profile, 4’ Elevation, Case 2 Room is held at a

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Rack Inlet Temperatures, Case 2

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Pressure Contour, Case 2 Avg CRAC Supply Pressure = 0.088”wc Avg Rack Inlet Pressure = -0.01” wc dP CRACs to Racks = 0.098” wc Avg Rack Outlet Pressure = -0.01” wc Avg CRAC Return Pressure = -0.037”wc dP Rack Outlets to CRAC Returns = 0.027” wc Cold Side dP + Hot Side dP, Avg = 0.125”wc

Highest gradient is from

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

• CFD Model Simulation completed for Case 2 case with 2 CRAC units (CRAC 1 Offline) in service with design IT rack loads

• 37 total Racks, 31 at 3.5kW load, 6 at 2.8kW load [125.3kW total]

• 160 CFM/kW rack flowrate [Required flow = 160*125.3 = 20,048 CFM]

• CRAC flows in Case 2 model case: Design value of 10,050 CFM each at 75°F cold air supply [total =

20,100 CFM]

• Flow patterns predicted exhibit high velocity cold air jets through floor tiles.

• Rack Inlet Temperatures:

• Avg = 75.0°F

• Local Max = 75.0°F

• Avg. CRAC return temperature = 95.0°F

• Avg. CRAC pressure drop from Supply to Return: 0.125” wc [@ flow of 10,050

Summary - Case 2

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

P R

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Case 3 Results 2 CRACs Active, CRAC 2 Inactive

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

CFD Model Geometry and Boundaries, Case 3

CRAC 1

CRAC 2

(Offline)

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Velocity Contour, Data Hall, Case 3

Highest velocity flow entering the CRAC units and flowing around cold side containment

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Temperature Contour, Case 3 Room at held at a constant temperature

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, 1’ Below Floor, Case 3

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, 4’ Elevation, Case 3

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, Mid-Plane, Case 3 High velocity plumes from floor tiles dictate the flow

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Temperature Profile, 4’ Elevation, Case 3 Room is held at a

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Rack Inlet Temperatures, Case 3

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Pressure Contour, Case 3 Avg CRAC Supply Pressure = 0.09”wc Avg Rack Inlet Pressure = 0.004” wc dP CRACs to Racks = 0.086” wc Avg Rack Outlet Pressure = 0.003” wc Avg CRAC Return Pressure = -0.022”wc dP Rack Outlets to CRAC Returns = 0.025” wc Cold Side dP + Hot Side dP, Avg = 0.111”wc

Highest gradient is from

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

• CFD Model Simulation completed for Case 3 case with 2 CRAC units in service (CRAC 2 Offline) with design IT rack loads

• 37 total Racks, 31 at 3.5kW load, 6 at 2.8kW load [125.3kW total]

• 160 CFM/kW rack flowrate [Required flow = 160*125.3 = 20,048 CFM]

• CRAC flows in Case 2 model case: Design value of 10,050 CFM each at 75F cold air supply [total =

20,100 CFM]

• Flow patterns predicted exhibit high velocity cold air jets through floor tiles.

• Rack Inlet Temperatures:

• Avg = 75.0°F

• Local Max = 75.0°F

• Avg. CRAC return temperature = 95.0°F

• Avg. CRAC pressure drop from Supply to Return: 0.111” wc [@ flow of 10,050

Summary - Case 3

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

P R

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Case 4 Results 2 CRACs Active, CRAC 3 Inactive

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

CFD Model Geometry and Boundaries, Case 4

CRAC 1

CRAC 2

(Offline)

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Velocity Contour, Data Hall, Case 4

Highest velocity flow entering the CRAC units and flowing around cold side containment

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Temperature Contour, Case 4 Room at held at a constant temperature

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, 1’ Below Floor, Case 4

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, 4’ Elevation, Case 4

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Velocity Profile, Mid-Plane, Case 4 High velocity plumes from floor tiles dictate the flow

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Temperature Profile, 4’ Elevation, Case 4 Room is held at a

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Rack Inlet Temperatures, Case 4

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

3D Pressure Contour, Case 4 Avg CRAC Supply Pressure = 0.1”wc Avg Rack Inlet Pressure = 0.008” wc dP CRACs to Racks = 0.092” wc Avg Rack Outlet Pressure = 0.008” wc Avg CRAC Return Pressure = -0.018”wc dP Rack Outlets to CRAC Returns = 0.026” wc Cold Side dP + Hot Side dP, Avg = 0.118”wc

Highest gradient is from

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

• CFD Model Simulation completed for Case 4 case with 2 CRAC units in service (CRAC 3 Offline) with design IT rack loads

• 37 total Racks, 31 at 3.5kW load, 6 at 2.8kW load [125.3kW total]

• 160 CFM/kW rack flowrate [Required flow = 160*125.3 = 20,048 CFM]

• CRAC flows in Case 2 model case: Design value of 10,050 CFM each at 75°F cold air supply [total =

20,100 CFM]

• Flow patterns predicted exhibit high velocity cold air jets through floor tiles.

• Rack Inlet Temperatures:

• Avg = 75.0°F

• Local Max = 75.0°F

• Avg. CRAC return temperature = 95.0°F

• Avg. CRAC pressure drop from Supply to Return: 0.118” wc [@ flow of 10,050

Summary - Case 4

O

FE

SS

IO

N A

L

EN

G

IN

EE

R

IN

G

S

IM

U

LA

TI

O

N S

C

O N

SU

LT

IN

G

Summary – All Cases

Case 1 (All CRACs Online)

Case 2 (CRAC 1 Offline) Case 3 (CRAC 2 Offline) Case 4 (CRAC 3 Offline)

Avg Rack Inlet Temp 75°F 75°F 75°F 75°F

Max Rack Inlet Temp 75°F 75°F 75°F 75°F

Avg CRAC Return Temp 95°F 95°F 95°F 95°F

Avg CRAC Pressure Drop 0.099” w.c. 0.125” w.c. 0.111” w.c. 0.118” w.c.

Slide 1
Slide 2
Slide 3
Slide 4
Slide 5
Slide 6
Slide 7
Slide 8
Slide 9
Slide 10
Slide 11
Slide 12
Slide 13
Slide 14
Slide 15
Slide 16
Slide 17
Slide 18
Slide 19
Slide 20
Slide 21
Slide 22
Slide 23
Slide 24
Slide 25
Slide 26
Slide 27
Slide 28
Slide 29
Slide 30
Slide 31
Slide 32
Slide 33
Slide 34
Slide 35
Slide 36
Slide 37
Slide 38
Slide 39
Slide 40
Slide 41
Slide 42
Slide 43
Slide 44
Slide 45
Slide 46
Slide 47
Slide 48
Slide 49
Slide 50
Slide 51
Slide 52

File details come from the government source that posted it. Updated .