This document is a technical specification for resilient base, stair treads, and sheet rubber flooring (Section 09 65 13). The specification details requirements for installing 3mm thick rubber or vinyl base, rubber stair treads with skid-resistant nosing, and sheet rubber flooring, primarily for interior applications. Key technical specifications include using low-pollutant emitting materials, achieving 90% recycled content for sheet rubber flooring, and adhering to ASTM standards for installation. Installation requirements mandate specific environmental conditions (21-27 degrees C), precise substrate preparation, and careful adhesive application to ensure proper bonding and performance. The specification provides detailed guidelines for installation methods, including joint placement, adhesive application, and finishing techniques for base, stair treads, and sheet rubber flooring.

View the file

Other files

File Type Posted
Experience information Sheet.pdf PDF
092900 Gypsum - Copy.docx DOCX document
260526 Grounding and Bonding - Copy.docx DOCX document
283100 Fire Detection and Alarm - Copy.doc DOC document
38 LS - Copy.pdf PDF
Building 38 - As Built_Drawings - Copy.pdf PDF
013323 Shop Drawings - Copy.docx DOCX document
022113 Site Surveys - Copy.docx DOCX document
081710 Integrated Door Assemblies - Copy.docx DOCX document
092216 Non Structural Metal Framing - Copy.docx DOCX document
260533 Raceways and Boxes - Copy.docx DOCX document
38 32 Main Opening - Copy.pdf PDF
Bldg 32 Arch As Builts - Copy.pdf PDF
PAST AND PRESENT PERFORMANCE QUESTIONNAIRE.docx DOCX document
WD-FL20260208 01-02-26.pdf PDF
013526 Safety Requirements Tampa Specific - Copy.docx DOCX document
015719 Temporary Environmental Controls - Copy.docx DOCX document
081400 Interior Wood Doors - Copy.docx DOCX document
090600 Schedule for Finishes - Copy.docx DOCX document
260511 Requirements for Electrical Installations - Copy.docx DOCX document
280500 Common Results Electronics Safety Security - Copy.docx DOCX document
014535 Special Inspections - Copy.docx DOCX document
015816 Temporary Interior Signage - Copy.docx DOCX document
096519 Resilient Tile Flooring - Copy.docx DOCX document
01321616 Network Analysis Schedule DB - Copy.docx DOCX document
014500 Quality Control - Copy.docx DOCX document
017419 Construction Waste Management - Copy.docx DOCX document
024100 Demolition - Copy.docx DOCX document
fire-38gfloor-Floor - Ansi C - Copy.pdf PDF
014219 Reference Standards - Copy.docx DOCX document
081113 Hollow Metal Doors and Frames - Copy.docx DOCX document
fire-32gfloor-Ansi C - Copy.pdf PDF
Schematic Design - Copy.pdf PDF
Base Offer Price Breakdown - 1 page.xlsx XLSX spreadsheet
260513 Medium Voltage - Copy.docx DOCX document
262726 Wiring Devices - Copy.docx DOCX document
010000 TIL General Specification - Tampa Specific - Copy.docx DOCX document
095100 Acoustical Ceiling - Copy.docx DOCX document
099100 Painting - Copy.docx DOCX document
260519 Low Voltage - Copy.docx DOCX document
262921 Enclosed Switches and Circuit Breakers - Copy.docx DOCX document
280513 Conductors and Cables for Electronic Safety Security - Copy.docx DOCX document
EMR 1 page.pdf PDF
36C24826Q0188_1.docx DOCX document
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

01-01-21

SECTION 09 65 13

RESILIENT BASE AND ACCESSORIES

SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project.

GENERAL

SUMMARY

Section Includes:

Resilient base (RB) adhered to interior walls and partitions.

Resilient stair treads (RST) adhered to interior stair treads.

Sheet rubber flooring (SRF) adhered to interior stair landings.

RELATED REQUIREMENTS

Sheet Flooring Integral Base: Section 09 65 16, RESILIENT SHEET FLOORING.

Rubber Tile Flooring at Landings: Section 09 65 19, RESILIENT TILE FLOORING.

SPEC WRITER NOTE: Update and retain references only when specified elsewhere in this section.

APPLICABLE PUBLICATIONS

Comply with references to extent specified in this section.

ASTM International (ASTM):

F1344‑15Rubber Floor Tile.
F1859‑14e1Rubber Sheet Floor Covering without Backing.
F1860‑14e1Rubber Sheet Floor Covering with Backing.
F1861‑16Resilient Wall Base.
D4259‑18Preparation of Concrete by Abrasion Prior to Coating Application.

Federal Specifications (Fed. Spec.):

RR‑T‑650E (1994) Treads, Metallic and Non‑Metallic, Skid‑Resistant.

International Concrete Repair Institute (ICRI):

310.2R‑2013 Selecting and Specifying Concrete Surface Preparation for Sealers, Coatings, Polymer Overlays, and Concrete Repair.

SUBMITTALS

Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Manufacturer's Literature and Data:

Description of each product.

Adhesives and primers indicating manufacturer's recommendation for each application.

Installation instructions.

Samples:

Resilient Base: 150 mm (6 inches) long, each type and color.

Resilient Stair Treads: 150 mm (6 inches) long, each type and color.

Sheet Rubber Flooring: 300 mm (12 inches) square, each type and color.

Sustainable Construction Submittals:

SPEC WRITER NOTE: Retain sustainable design submittals appropriate to product.

Recycled Content: Identify post‑consumer and pre‑consumer recycled content percentage by weight.

Low Pollutant‑Emitting Materials:

Stair Treads and Sheet Rubber Flooring: Submit Floor Score label.

Show volatile organic compound types and quantities.

Operation and Maintenance Data:

Care instructions for each exposed finish product.

DELIVERY

Deliver products in manufacturer's original sealed packaging.

Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, production run number, and manufacture date.

Before installation, return or dispose of products within distorted, damaged, or opened packaging.

STORAGE AND HANDLING

Store products indoors in dry, weathertight facility.

Protect products from damage when handling and during construction operations.

FIELD CONDITIONS

Environment:

Product Temperature: Minimum 21 degrees C (70 degrees F) for minimum 48 hours before installation.

Work Area Ambient Temperature Range: 21 to 27 degrees C (70 to 80 degrees F) continuously, beginning 48 hours before installation.

Install products when building is permanently enclosed and when wet construction is completed, dried, and cured.

WARRANTY

SPEC WRITER NOTE: Always retain construction warranty. FAR includes Contractor's one year labor and material warranty.

Construction Warranty: FAR clause 52.246‑21, "Warranty of Construction."

PRODUCTS

PRODUCTS

Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.

Provide each product from one manufacturer and from one production run.

Provide resilient stair treads and sheet rubber flooring from same manufacturer.

SPEC WRITER NOTE: Detailed product requirements are specified in Section 01 18 13.

Sustainable Construction Requirements:

SPEC WRITER NOTE: Specify products containing greatest recycled content practicable to maximize material recovery. See EPA Comprehensive Procurement Guidelines (CPG) for guidance about individual products and available recycled content. Section 01 81 13 sets overall project recycled content requirements.

Sheet Rubber Flooring Recycled Content: 90 percent total recycled content, minimum.

SPEC WRITER NOTES:

1. Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS includes comprehensive product list setting VOC limits for low‑emitting materials.

2. Retain subparagraphs applicable to products specified in this section.

Low Pollutant‑Emitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:

Flooring Adhesives and Sealants.

RESILIENT BASE

Resilient Base: 3 mm (1/8 inch) thick, 100 mm (4 inches) high.

SPEC WRITER NOTE:

1. Allow rubber or vinyl base as option.

2. When vinyl products are specified, seek products with recycled content where possible.

Type: Rubber or vinyl; use one type throughout.

ASTM F1861, Type TP thermoplastic rubber or Type TV thermoplastic vinyl, Group 2 - layered.

Applications:

Carpet Flooring Locations: Style A - Straight.

Other Locations: Style B - Cove.

RESILIENT STAIR TREADS

SPEC WRITER NOTE: Resilient stair treads are suitable for new and existing interior concrete, terrazzo, concrete‑filled steel pan, and wood stairs.

Resilient Stair Treads: Rubber, skid‑resistant abrasive strip nosing, 5 mm (3/16 inch) thick nosing wear surface tapered to 3 mm (1/8 inch) thick at riser.

Fed. Spec. RR‑T‑650, Composition A, Type 2.

SPEC WRITER NOTE:

1. Two 19 - 25 mm (3/4 - 1 inch) wide abrasive strips are standard. For visually impaired, one 51 - 76 mm (2 - 3 inch) wide abrasive strip is required by reference standard Fed. Spec. RR‑T‑650. Identify where access by visually impaired is required.

2. Black is standard color. Other colors must be specified.

Abrasive Strips: Design for access by visually impaired.

SPEC WRITER NOTE: Flexible nosing permits compliance with ADA.

Nosing: Flexible, accommodating angle between tread and riser; shape suiting sub‑tread.

Size: Single piece full stair tread width and depth.

SHEET RUBBER FLOORING

SPEC WRITER NOTE:

1. Delete sheet rubber flooring when rubber tile, specified in Section 09 65 19, RESILIENT TILE FLOORING, is used for landings.

2. Coordinate with Section 09 06 00, SCHEDULE FOR FINISHES to indicate required landing product.

Sheet Rubber Flooring (SRF): ASTM F1859 or ASTM F1860; Rubber, 900 mm (36 inches) wide, 3 mm (1/8 inch) thick, smooth face; color and pattern matching resilient stair treads.

PRIMER (FOR CONCRETE FLOORS)

Primer: Type recommended by adhesive manufacturer.

LEVELING COMPOUND (FOR CONCRETE FLOORS)

Leveling Compound: Provide products mixed with latex or polyvinyl acetate resins.

ADHESIVES

Adhesives: Low pollutant‑emitting, water based type recommended by adhered product manufacturer for each application.

EXECUTION

PREPARATION

Examine and verify substrate suitability for product installation.

Protect existing construction and completed work from damage.

SPEC WRITER NOTE: Include below for renovation projects.

Remove existing // base // stair treads // landing flooring // to permit new installation.

Dispose of removed materials.

Correct substrate deficiencies.

Fill cracks, pits, and depressions with leveling compound.

Remove protrusions; grind high spots.

Apply leveling compound to achieve 3 mm (1/8 inch) in 3 m (10 feet) maximum surface variation.

Clean substrates. Remove contaminants capable of affecting subsequently installed product's performance.

Mechanically clean concrete floor substrate according to ASTM D4259.

Surface Profile: ICRI Guideline No. 310.2R.

Allow substrate to dry and cure.

Perform flooring manufacturer’s recommended bond, substrate moisture content, and pH tests.

INSTALLATION GENERAL

Install products according to manufacturer's instructions.

When instructions deviate from specifications, submit proposed resolution for Contracting Officer consideration.

RESILIENT BASE INSTALLATION

Applications:

Install resilient base in rooms scheduled on Drawings.

Install resilient base on // casework // and // locker toe spaces //, and other curb supported fixed equipment.

Extend resilient base into closets, alcoves, and cabinet knee spaces, and around columns within scheduled room.

Lay out resilient base with minimum number of joints.

Length: 600 mm (24 inches) minimum, each piece.

Locate joints 150 mm (6 inches) minimum from corners and intersection of adjacent materials.

Installation:

Apply adhesive uniformly for full contact between resilient base and substrate.

Set resilient base with hairline butted joints aligned along top edge.

// Field // Factory // form corners and end stops.

V‑groove back of outside corner.

V‑groove face of inside corner and notch cove for miter joint.

Roll resilient base ensuring complete adhesion.

RESILIENT STAIR TREAD INSTALLATION

Install resilient stair treads without joints on each stair tread substrate.

Install full width resilient stair treads on each intermediate and floor landing.

Apply adhesive uniformly for full contact between resilient stair tread and substrate.

Roll resilient stair treads ensuring complete adhesion.

SPEC WRITER NOTE: Delete sheet rubber flooring when rubber tile, specified in Section 09 65 19, RESILIENT TILE FLOORING is used for landings.

SHEET RUBBER FLOORING INSTALLATION

Applications:

Install sheet rubber flooring on intermediate and floor landings where resilient stair treads are installed.

Lay out sheet rubber flooring symmetrically, with minimum number of joints.

Locate floor landing joints centered under doors.

Installation:

Apply adhesive uniformly for full contact between sheet rubber flooring and substrate.

Install sheet rubber flooring with 1 mm (0.04 inch) maximum width seams, perimeter joints, and joints with adjacent flooring.

Scribe sheet rubber flooring tight to interrupting surfaces.

Roll sheet rubber flooring ensuring complete adhesion.

CLEANING

Remove excess adhesive before adhesive sets.

Clean exposed resilient base, resilient stair treads, and // sheet rubber flooring // surfaces. Remove contaminants and stains.

Clean with mild detergent. Leave surfaces free of detergent residue.

SPEC WRITER NOTE: Verify manufacturer's instructions for polishing resilient base.

Polish exposed resilient base to gloss sheen.

PROTECTION

Prohibit traffic on resilient stair treads // and sheet rubber flooring // 72 hours, minimum, after installation.

Protect products from construction traffic and operations.

Cover resilient stair treads // and sheet rubber flooring // with reinforced kraft paper, and plywood or hardboard.

Maintain protection until directed by Contracting Officer's Representative.

Replace damaged products and re‑clean.

Damaged Products include cut, gouged, scraped, torn, and unbonded products.