This is a structural contract document set issued by the Connecticut Department of Transportation for the rehabilitation of Bridge No. 02150 in Stratford, Connecticut, which carries Route 15 over Freeman Brook. The project involves comprehensive repair and restoration of an existing 10-foot by 8-foot box culvert structure, including cleaning the culvert interior, performing concrete repairs to walls, slabs, wingwalls, and footings, crack sealing and curtain wall sealing, concrete invert repair with a 4-inch thick cast-in-place concrete overlay, installation of new sanitary sewer and storm drainage systems with manholes and headwalls, construction of a concrete retaining wall, riprap basin installation, and site restoration including temporary access roads and erosion control measures. The work scope encompasses 201 feet 4 inches of existing culvert requiring rehabilitation, with design specifications based on AASHTO LRFD Bridge Design Specifications (Tenth Edition – 2024), Connecticut Department of Transportation Form 819 specifications, and supplemental specifications dated January 2026. The project utilizes HL-93 live load standards with concrete strength requirements of 4,000 PSI for culvert and wingwall repairs and 3,000 PSI for culvert bottom slab repairs.

The contract specifications detail extensive concrete repair procedures including removal of deteriorated material, reinforcing bar replacement and splicing, installation of embedded galvanic anodes for corrosion protection, welded wire reinforcement in repair areas, and application of penetrating concrete sealer upon completion. Hydraulic design parameters for Freeman Brook establish a 50-year design frequency with 295 cubic feet per second discharge, upstream design water surface elevation of 108.4 feet, and downstream elevation of 89.8 feet. The project includes temporary water handling systems with cofferdam installation, temporary earth retaining systems, and temporary sanitary sewer bypass systems to maintain operations during construction. Environmental considerations include coordination with state and federal wetlands areas, restrictions on unconfined in-stream work limited to June 1 through September 30, and endangered species protection measures including restrictions on tree trimming and removal from April 15 through October 31. Adhesive bonded anchor installation with proof load testing is required for structural repairs, with minimum characteristic bond stress requirements of 1.00 KSI in dry, cracked concrete and 2.5 KSI minimum compressive strength for existing concrete in anchor design.

View the file

Other files

File Type Posted
SB_CB_0138_0252_Bridge02150_Proposed.dgn —
Bidders Checklist.pdf PDF
0138-0252_Nov_5_26_solicitation_doc.pdf PDF
0138-0252_Nov_2_26_solicitation_doc.pdf PDF
0138-0252_Oct_28_26_solicitation_doc.pdf PDF
0138-0252_01_General.pdf PDF
SV_CB_0138_0252_Stratford_Master.dgn —
0138-0252_CTDOT_HIGHWAY_STD.pdf PDF
0138-0252 - Contract Special Provisions.pdf PDF
0138-0252_EEDFileManifest.xlsx XLSX spreadsheet
PROSPECTIVE BIDDERS - 1.pdf PDF
0138-0252_08_Permit Planting.pdf PDF
VendorChangeDetailsReport_0138-0252_v5_Oct_26_26.pdf PDF
0138-0252_Oct_26_26_solicitation_doc.pdf PDF
NTC - Bidx Enhanced Bidding Workflow-Rev April 2026.pdf PDF
SB_CB_0138_0252_Bridge02150_Existing.dgn —
0138-0252_Nov_6_26_solicitation_doc.pdf PDF
0138-0252 Invitation to Bid.pdf PDF
0138-0252_Stratford02150_RevHydraulicLinework.dgn —
0138-0252_02_Revisions.pdf PDF
SB_CB_0138_0252_Master.dgn —
HW_CB_0138_0252_Layout.dgn —
0138-0252_Sep_30_26_solicitation_doc.pdf PDF
PrelimPermitLinework.dgn —
PROSPECTIVE BIDDERS - 5.pdf PDF
0138-0252_Oct_15_26_solicitation_doc.pdf PDF
PROSPECTIVE BIDDERS - 2.pdf PDF
0138-0252_Oct_20_26_solicitation_doc.pdf PDF
PROSPECTIVE BIDDERS - 3.pdf PDF
Electronic Bidding Instructions -Rev April 2026.pdf PDF
HW_CB_0138_0252_Contours.dgn —
NTC - New DBE Requirements - Regular Dealer Affirmation Form.pdf PDF
0138-0252 HazMat Inspection Letter.pdf PDF
HW_CB_0138_0252_ROW_Lines.dgn —
0138-0252_06_Landscape.pdf PDF
0138-0252_03_Highway.pdf PDF
0138-0252_Oct_6_26_solicitation_doc.pdf PDF
0138-0252_Nov_4_26_solicitation_doc.pdf PDF
PROSPECTIVE BIDDERS - 4.pdf PDF
0138-0252_05_Historical_FIO.pdf PDF
HW_CB_0138_0252_Alignment.dgn —
SV_D4_0138_0252_STRATFORD_BR_02150_GRN.dgn —
0138-0252_CTDOT_TRAFFIC_STD.pdf PDF
Bidders Checklist - Rev September 2026.pdf PDF
0138-0252_Nov_3_26_solicitation_doc.pdf PDF
0138-0252_07_Sanitary Sewer.pdf PDF
Online Q and A Instruction.pdf PDF
SB_CB_0138_0252_San_Master.dgn —
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CULVERT REPAIR DETAILS IIIS-10

CULVERT REPAIR DETAILS IIS-09

CULVERT REPAIR DETAILS IS-08

EXISTING STRUCTURE CONDITIONSS-07

LONGITUDINAL SECTION AND ELEVATIONSS-06

SUGGESTED SEQUENCE OF CONSTRUCTION AND WATER HANDLING PLANS-05

SEALER LIMITSS-14BORING LOGSS-04

RETAINING WALL DETAILSS-13GENERAL NOTES AND SCOPE OF WORKS-03

RETAINING WALL PLAN AND ELEVATIONS-12GENERAL PLANS-02

CULVERT REPAIR DETAILS IVS-11STRUCTURE INDEX OF DRAWINGSS-01

DRAWING TITLEDRAWING NUMBERDRAWING TITLEDRAWING NUMBER

INDEX OF DRAWINGS

04 - STRUCTURE

PROJECT TITLE: PROJECT NO.: DRAWING NO.:

SHEET NO.:

7/16/2026

SIGNATURE BLOCK: DRAWING TITLE:

S-01

TOWN(S):

STRATFORD

CARRYING ROUTE 15 OVER FREEMAN BROOK

REHABILITATION OF BRIDGE NO. 02150;

PLOTTED DATE:

V:\Projects\ANY\K6\070461.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0138_0252_S_01_Subset_Cover_Sheet.dgn FILE NAME: 6610 LASTED SAVED BY:

R E

V

D A

T E

R E

V

IS

IO

N

D E

S C

R

IP

T

IO

N

0138-0252

DESIGNER/DRAFTER: CHECKED BY:

STRUCTURE INDEX OF DRAWINGS

TRANSPORTATION

DEPARTMENT OF

CONNECTICUT

DESIGNED BY:

Associates, LLP

Clough, Harbour &

Rocky Hill, CT 06067

400 Capital Boulevard, Suite 301

CEPSJH 04.01

K:

Clough, Harbour & Associates, LLP 400 Capital Boulevard, Suite 301 Rocky Hill, CT 06067

TANGLEWOODROAD

ROUTE 15

N.B.

TO

TRUMBULL

ROUTE 15 EXIT 53

OFF RAMP

ROUTE 15

S.B.

ROW MAP 138-180E SHEET 1A

F R

E E

M A

N B

R O

O K

FR

EE

M A

N

BR

O

O K

(OW)

B-3B-2

B-1

TA

NG

LE

W

O O

D

RO

AD

FND

CHD

FND

CHD

NON ACCESS HIGHWAY LINE

WOOD BEAM RAIL

CONC. PAVEMENT

WOOD BEAM RAIL

CONC. PAVEMENT

CONC. CURB

CONC. CURB

WOOD BEAM RAIL

CONC. CURB

CONC. CURB

WOOD BEAM RAIL

CONC. CURB

CONC. CURB

WOOD BEAM RAIL

WOOD BEAM RAIL

CP-3

CHAIN LINK FENCE

CHAIN LINK FENCE

WOOD FENCE

S T R

U C

T U

R E

' X ' B

O X C

U L

V E

R T

FND

CHD

WOOD BEAM RAIL

WOOD BEAM RAIL

BCLC

BCLC

#4616

SNET

W G

HYD

8" WATER MAIN

APPROX. LOC

W1-6

W1-7

W1-5

W1-8

W1-9

W1-11

W1-12

W1-13

W1-14

W1-15

W1-16

W1-17

W1-18

W1-19

W1-10

W1-20

W1-21

W1-22

W1-23

W1-24

W1-25

W1-26

W1-27

W1-28

W1-29

W1-30

W1-31 W1-32

W1-33

W1-35

W1-36

W1-38

W1-34

W1-37

W1-39

W1-40

W1-41 W1-42

W1-43

W1-44

W1-45

W1-46

W1-48

W1-50

W1-47

W1-49

W1-51

W1-52

W1-53

W1-54

W2-1

W2-2

W2-3

W2-4

W2-5

W2-6

W2-7

W2-8

W2-9

W2-10

W2-11

W2-12

W2-13 W2-14

W2-15

W2-16

W2-17

W2-18

W3-1

W3-2

W3-3

W3-4

W3-5

W3-6

W3-7

W3-8

W1-58

W1-59

W1-60

W1-61

W1-62

W1-68

W1-69

W1-70

W1-71

W1-80

W1-81

W1-82

W1-83

W1-85

W1-86

W1-87

W1-84

WA-23

WA-22

WA-5

WA-4

WA-6

WA-7

WA-8

WA-9

WA-10

WA-11

WA-12

WA-13 WA-14

WA-15

WA-16

WA-17

WA-18

WA-19

WA-20

WA-21

WC-2

WC-3

WC-4

WC-5

WC-6

WC-7

WC-8

WC-9

WC-10

WC-11

WB-4

WB-5

WB-6

WB-7

WB-8

20'

88'

86'

0'

5'

0'

95'

5'

100+00 97+00 98+00 99+00

101+00 102+00 103+00

197+00 198+00 199+00 200+00 201+00 202+00 203+00

220+00 221+00

11+00 12+00

13+00 14+00

HUNTTING

WILLIAM H. III & SHAWNA

N/F

STONE WALLSTONE WALL

OAK

15"

OAK

15"

DOGWOOD

4"

DOGWOOD

4" TRIPLE

" R

C P

" R

C P

" R

C P

" R

C P

18" RCPLOCATED

NOT

INLET

" R

C P

R C

P

" R

C P

S A

N

E

N C

A S E

D

IN

C

O N

C

" S

A N . S

E W

E R

ROW MAP 138-180E SHEET 1A ROW MAP 138-180E SHEET 2A

" R

C P U

N D

E R

D R

A

IN

" S

A N

S A

N

" S

A N

" S

A N . S

E W

E R

E

N C

A S E

D

IN

C

O N

C

(2011)

C O

O R

D

IN

A T E G

R

ID

AD

C O

N N

E C

T

IC

U T

PROJECT TITLE: PROJECT NO.: DRAWING NO.:

SHEET NO.:

7/16/2026

SIGNATURE BLOCK: DRAWING TITLE:

S-02

REHABILITATION OF BRIDGE NO. 02150;

PLOTTED DATE:

V:\Projects\ANY\K6\070461.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0138_0252_S_02_General_Plan.dgn FILE NAME: 7485 LASTED SAVED BY:

R E

V

D A

T E

R E

V

IS

IO

N

D E

S C

R

IP

T

GENERAL PLAN

TRANSPORTATION

PERMANENT ACCESS ROAD

(TYP.)

STATE/FEDERAL WETLANDS

EXISTING BRIDGE NO. 02150 TO REMAIN

SLOPE LIMITS (TYP.) LEDGE IN CHANNEL

AREA OF EXPOSED

REMOVE EXISTING ENDWALL

EXISTING RIGHT OF WAY

STONE UP TO EL. 90 FT

12" DEPTH OF 2" CRUSHED

STANDARD RIPRAP OVER

MATERIAL WASH-IN TO 36"

OF NATURAL STREAMBED

RIPRAP BASIN CONSISTING

2" CRUSHED STONE

OVER 12" DEPTH OF

36" STANDARD RIPRAP

(CALCULATED) (TYP.)

EXISTING 100-YEAR FLOOD

INV. IN = 93.00

STA. 14+62.3, 14.1' LT

PROPOSED HEADWALL

: 9.6 FT/S10MAX V

: 15.5 CFS10MAX Q

INV. OUT = 89.50

STA. 14+82.2, 22.4' RT

ENCASED IN CONC.

PROPOSED OUTLET

36" R.C. PIPE CLASS V

INV. OUT = 90.00

INV IN (N) = 91.75

INV IN. (W) = 90.50

TF = 96.23

STA. 14+69.6, 2.2' LT

TYPE II CATCH BASIN

PROPOSED TYPE "C-L" DOUBLE GRATE

15" R.C. PIPE CLASS V

INV. OUT = 95.25

INV IN. = 97.00

TF = 101.00

STA. 15+14.7, 3.4' LT

PROPOSED MANHOLE

30" R.C. PIPE CLASS V

FOR STORM DRAINAGE PIPE

CONCRETE ENCASEMENT

PIPE (SANITARY SEWER)

15" DIA. POLYVINYL CHLORIDE

EL. 88 FT

BOULDERS WITH TOP

2.5 - 3.5 FT ROUNDED

INSTALL A LINE OF

CHANNEL PROTECTION

STANDARD RIPRAP

APPROX. EDGE OF

STONE CHECK DAM (TYP.)

*REPAIR CULVERT

INVERT WITH 4" THICK

CAST-IN-PLACE

CONCRETE INVERT

ACCESS ROAD (SEE HIGHWAY SUBSET)

LIMITS OF FRENCH MATTRESS BELOW

SEDIMENT CONTROL SYSTEM (TYP.)

(4" MIN.)

MATERIAL

STREAMBED

SUPPLEMENTALWETLAND B

WETLAND C

WETLAND A

UNNAMED

WATERCOURSE 2

UNNAMED WATERCOURSE 3

FENCE

HIGH VISIBILITY

CONCRETE RETAINING WALL NO. 101

MANHOLE (SANITARY SEWER) (TYP.)

REMOVE EXISTING SANITARY SEWER MANHOLEINV. IN = 121.75

STA. 12+40, 8.81' RT

PROPOSED HEADWALL

15" R.C. PIPE CLASS V

INV. OUT = 121.37

STA. 12+40, 10.77' LT

PROPOSED OUTLET

(SEE SANITARY SEWER SUBSET)

RECONSTRUCT SANITARY SEWER MANHOLE

100-YEAR FLOODPLAIN (MAPPED)

4' CHAIN LINK FENCE

18" INTERMEDIATE RIPRAP SWALE

ANTI-TRACKING PAD

12" MODIFIED RIPRAP

12" MODIFIED RIPRAP

18" INTERMEDIATE RIPRAP APRON

18" INTERMEDIATE RIPRAP SLOPE PROTECTION

12" MODIFIED RIPRAP

1" = 20'

HORIZONTAL SCALE

20' 40'

LEGEND

OHW

EDGE OF WATER

ORDINARY HIGH WATER

STATE/FEDERAL WETLANDS

100 YEAR FLOODPLAIN LIMITS (MAPPED)

EXISTING 100-YEAR FLOOD (CALCULATED)100YR

36" STANDARD RIPRAP OVER 12" DEPTH OF 2" CRUSHED STONE

NATURAL STREAMBED MATERIAL WASHED-IN TO

36" STANDARD RIPRAP OVER 12" DEPTH OF 2" CRUSHED STONE

18" INTERMEDIATE RIPRAP SLOPE PROTECTION

EROSION CONTROL MATTING TYPE D

SJH CEP

SEDIMENTATION CONTROL SYSTEM (APPROXIMATE LOCATION)

HIGH VISIBILITY FENCE FOR FREEMAN BROOK.

SEE DRAWING S-03 FOR HYDRAULIC DATA TABLE 2.

EAST OF THIS FENCE IS STRICTLY FORBIDDEN.

AREA OF ENVIRONMENTAL SENSITIVELY. ACCESS

THE AREA EAST OF THE HIGH VISIBILITY FENCE IS AN 1.

:NOTES

NUMBER

RETAINING WALL

DESCRIPTION LOCATION

WALL

RETAINING

CONCRETE

14+75

STATION

BEGIN

12" MODIFIED RIPRAP

N/F

WILLIAM H. III & SHAWNA

HUNTTING

N/F

ROBERT H. & PANTIP

HROMJAK

N/F

NADJA MORENO

DE OLIVERIA ET AL

N/F

ZBIGNIEW J. SLEDZ ET AL

04.02

K:

Clough, Harbour & Associates, LLP

NOTICE TO BRIDGE INSPECTORS

STRUCTURE SHEET REFERENCE

BY THE MANAGER OF BRIDGE SAFETY AND EVALUATION.

MANUALS FOR BRIDGE INSPECTION, UNLESS OTHERWISE DIRECTED

STRUCTURE SHALL BE IN ACCORDANCE WITH THE GOVERNING

THE STRUCTURE). THE FREQUENCY OF INSPECTION OF THIS

IMPORTANCE OF INSPECTION OF ANY OTHER COMPONENT OF

ATTENTION SHALL NOT BE CONSTRUED TO REDUCE THE

DETAILS. (THE LISTING FOR COMPONENTS FOR SPECIFIC

TO INSPECTION THE FOLLOWING SPECIAL COMPONENTS AND

MANUALS FOR BRIDGE INSPECTION. ATTENTION MUST BE GIVEN

APPROPRIATE COMPONENTS INDICATED IN THE GOVERNING

BRIDGE TO BE INSPECTED FOR, BUT NOT LIMITED TO, ALL

THE DEPARTMENT'S BRIDGE SAFETY PROCEDURES REQUIRE THIS

INSPECTION PROCEDURES

FOLLOW NORMAL

COMPONENT OR DETAIL

PROJECT TITLE: PROJECT NO.: DRAWING NO.:

SHEET NO.:

7/16/2026

SIGNATURE BLOCK: DRAWING TITLE:

S-03

REHABILITATION OF BRIDGE NO. 02150;

PLOTTED DATE:

V:\Projects\ANY\K6\070461.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0138_0252_S_03_General Notes.dgn FILE NAME: 7485 LASTED SAVED BY:

R E

V

D A

T E

R E

V

IS

IO

N

D E

S C

R

IP

T

SCOPE OF WORK

GENERAL NOTES AND

TRANSPORTATION

: N/AMASH TEST LEVEL

CONTRACTOR SHALL COORDINATE ALL WORK RELATED TO UTILITY RELOCATION WITH THE TOWN.

PROTECTED DURING CONSTRUCTION: TOWN OF STRATFORD (SANITARY SEWER). THE

: THE FOLLOWING UTILITIES ARE LOCATED WITHIN THE PROJECT LIMITS AND SHALL BE UTILITIES

SUBMITTED FOR REFERENCE BY THE REVIEWER.

MEASUREMENTS ARE SUBMITTED FOR REVIEW, THE FIELD MEASUREMENTS SHALL ALSO BE

FULL RESPONSIBILITY FOR THEIR ACCURACY. WHEN SHOP DRAWINGS BASED ON FIELD

MEASUREMENTS NECESSARY TO ASSURE PROPER FIT OF THE FINISHED WORK AND SHALL ASSUME

DRAWINGS AND ARE NOT GUARANTEED. THE CONTRACTOR SHALL TAKE ALL FIELD

FOR GENERAL REFERENCE ONLY. THEY HAVE BEEN TAKEN FROM THE ORIGINAL DESIGN

: DIMENSIONS OF THE EXISTING STRUCTURE SHOWN ON THESE PLANS ARE EXISTING DIMENSIONS

THE OMITTED DIGITS SHALL BE ASSUMED TO BE ZEROS.

: WHEN DECIMAL DIMENSIONS ARE GIVEN TO LESS THAN THREE DECIMAL PLACES, DIMENSIONS

SPECIFICATIONS.

DETAILS SHEET REFER TO THE GROUP LOADS AS GIVEN IN THE AASHTO LRFD BRIDGE DESIGN

: THE VARIOUS GROUP LOADINGS NOTED ON THE RETAINING WALL FOUNDATION PRESSURES

: N/ABITUMINOUS CONCRETE OVERLAY

: NONEFUTURE PAVING ALLOWANCE

: HL-93LIVE LOAD

: (ASTM A615 GRADE 60)..........fy = 60,000 PSIREINFORCEMENT

PORTLAND CEMENT CONCRETE.

SHALL CONFORM TO THE REQUIREMENTS OF 6.01 - CONCRETE FOR STRUCTURES, AND M.03 -

ABOVE. THE COMPRESSIVE STRENGTH OF THE CONCRETE IN THE CONSTRUCTED COMPONENTS

THE CONCRETE STRENGTH, f’c, USED IN DESIGN OF THE CONCRETE COMPONENTS IS NOTED

CLASS PCC04483 .................................................f'c = 4,000 PSI CLASS PCC03340 .................................................f'c = 3,000 PSI

CONCRETE:

: MATERIAL STRENGTHS

ROADWAY STRUCTURE DESIGN MANUAL (RELEASE 1.1).

AS SUPPLEMENTED BY THE CONNECTICUT DEPARTMENT OF TRANSPORTATION BRIDGE AND

: AASHTO LRFD BRIDGE DESIGN SPECIFICATIONS (TENTH EDITION - 2024), DESIGN SPECIFICATIONS

SUPPLEMENTAL SPECIFICATIONS DATED JANUARY 2026, AND SPECIAL PROVISIONS.

: CONNECTICUT DEPARTMENT OF TRANSPORTATION FORM 819 (2024), SPECIFICATIONS

GENERAL NOTES

BE PERMITTED WITHOUT THE PRIOR APPROVAL OF THE ENGINEER.

: CONSTRUCTION JOINTS, OTHER THAN THOSE SHOWN ON THE PLANS, WILL NOT CONSTRUCTION JOINTS

INCLUDED IN THE ITEM "1/2" CLOSED CELL ELASTOMER".

: FURNISHING AND INSTALLED CLOSED CELL ELASTOMER SHALL BE CLOSED CELL ELASTOMER

PLACING THIS REINFORCEMENT SHALL BE INCLUDED IN THE ITEM "DEFORMED STEEL BARS".

SHALL CONFORM TO THE REQUIREMENTS OF ASTM A615, GRADE 60. THE COST OF FURNISHING AND CONNECTED SHALL BE UNCOATED BAR UNLESS NOTED OTHERWISE. UNCOATED BAR REINFORCEMENT

REINFORCEMENT FOR REPAIR CONCRETE TO WHICH EMBEDDED GALVANIC ANODES WILL BE

THE ITEM "DEFORMED STEEL BARS - HDG".

REQUIREMENTS. THE COST OF FURNISHING AND PLACING THIS REINFORCEMENT SHALL BE INCLUDED IN AND SHALL BE GALVANIZED TO THE REQUIREMENTS OF ASTM A767, CLASS 1, INCLUDING SUPPLEMENTAL GALVANIZED REINFORCEMENT (HDG) SHALL CONFORM TO THE REQUIREMENTS OF ASTM A615, GRADE 60 ENCASEMENT SHALL BE HOT-DIP GALVANIZED AFTER FABRICATION UNLESS NOTED OTHERWISE. HOT-DIP

: REINFORCEMENT FOR NEW RETAINING WALL AND NEW STORM DRAINAGE REINFORCEMENT

OTHERWISE.

: ALL REINFORCEMENT SHALL HAVE 2 INCHES COVER UNLESS DIMENSIONED CONCRETE COVER

OTHERWISE.

" UNLESS DIMENSIONED 4

3" x4

3: EXPOSED EDGES OF CONCRETE SHALL BE BEVELED EXPOSED EDGES

CAST-IN-PLACE STRUCTURE COMPONENTS:

: THE FOLLOWING PAY ITEMS AND CONCRETE CLASS ARE REQUIRED FORCONCRETE CLASSES

: THE USE OF REMAIN-IN-PLACE FORMS ON THIS STRUCTURE IS NOT ALLOWED.REMAIN-IN-PLACE FORMS

CONCRETE NOTES

89.8DOWNSTREAM DESIGN WATER SURFACE ELEV. (FT)

108.4UPSTREAM DESIGN WATER SURFACE ELEV. (FT)

105.7ADF ELEVATION (CALCULATED) (FT)

295DESIGN DISCHARGE (CFS)

50DESIGN FREQUENCY (YR)

0.36DRAINAGE AREA (SQ. MI.)

HYDRAULIC DATA - FREEMAN BROOK

SCOPE OF WORK

INSTALL FENCE; RESTORE ACCESS ROAD; INSTALL VEHICLE BARRIER GATE.14.

AND TEMPORARY EARTH RETAINING SYSTEM.

REMOVE TEMPORARY WATER HANDLING SYSTEM, TEMPORARY BYPASS PIPE/HOSE, 13.

CONSTRUCT RIPRAP BASIN AND LINE OF BOULDERS.12.

APPLY PENETRATING CONCRETE SEALER.11.

(SEE HIGHWAY PLANS).

INSTALL NEW STORM DRAINAGE MANHOLES, PIPES AND HEADWALLS 10.

CULVERT (SEE SANITARY SEWER SUBSET).

SANITARY SEWER MANHOLES AND SANITARY SEWER MAIN DOWNSTREAM OF

RECONSTRUCT SANITARY SEWER MANHOLE AT CULVERT OUTLET. INSTALL NEW 9.

CONSTRUCT CONCRETE RETAINING WALL.8.

DRAINAGE ENDWALL.

SANITARY SEWER OUTSIDE OF THE BOX CULVERT, AND REMOVE EXISTING STORM

REMOVE EXISTING SANITARY SEWER MAIN AND CONCRETE ENCASEMENT FOR THE 7.

REPAIR BOX CULVERT INVERT WITH CONCRETE.6.

HEADWALLS AS NECESSARY AND WHERE DIRECTED BY THE ENGINEER.

UNDERSIDE OF TOP SLAB, WINGWALLS, FOOTINGS, CUTOFF WALLS, AND

PERFORM CONCRETE REPAIRS TO BOX CULVERT SIDE WALLS, BOTTOM SLAB, 5.

WHERE DIRECTED BY THE ENGINEER.

PERFORM CRACK SEALING AND CURTAIN WALL SEALING AT BOX CULVERT WALLS 4.

SEDIMENT, DEBRIS AND BIOLOGICAL GROWTH TO FACILITATE REHABILITATION.

CLEAN INTERIOR OF EXISTING BOX CULVERT BY REMOVING AND DISPOSING ALL 3.

AND TEMPORARY EARTH RETAINING SYSTEM.

INSTALL TEMPORARY WATER HANDLING SYSTEM, TEMPORARY BYPASS PIPE/HOSE, 2.

CLEARING AND GRUBBING; CONSTRUCT ACCESS ROAD (SEE HIGHWAY PLANS)1.

SJH CEP

PCC04483CULVERT AND WINGWALL REPAIRSSURFACE REPAIR CONCRETE

PCC03340CULVERT BOTTOM SLABCONCRETE INVERT

PCC03340

STORM DRAINAGE ENCASEMENT

RETAINING WALL,

ABUTMENT AND WALL CONCRETE

PCC CLASSBRIDGE COMPONENTITEM

#0610001A - “DRILLING HOLES AND BONDING ANCHORS.”

INSTALL ANCHORS, AND INSPECT AND TEST THE ANCHORS SHALL BE PAID FOR UNDER THE ITEM

THE WORK TO FURNISH THE ANCHORS AND ADHESIVE BONDING MATERIAL, DRILL HOLES, 7.

UNLESS OTHERWISE SPECIFIED, THE ENGINEER SHALL RANDOMLY SELECT THE ANCHORS TO BE TESTED.

TABULATED PROOF LOAD:

DETAILS THE MINIMUM NUMBER OF ANCHORS AT EACH LOCATION TO BE FIELD TESTED TO THE

PROCEDURES AND INSTALLED ADHESIVE BONDED ANCHOR STRENGTH. THE FOLLOWING TABLE

THE ANCHOR SHALL BE FIELD TESTED UNDER A PROOF TEST LOAD TO VERIFY THE INSTALLATION 6.

FILLED WITH ADHESIVE BONDING MATERIAL OR NON-SHRINK GROUT.

EXISTING REINFORCEMENT IS NOT PERMITTED. ABANDONED HOLES SHALL BE COMPLETELY

MAINTAINING REQUIRED CONCRETE COVER. THE USE OF CORE DRILLING THROUGH THE

WHEN DRILLING HOLES, IF EXISTING REINFORCEMENT IS ENCOUNTERED, RELOCATE HOLE 5.

ANCHOR CATEGORY OF THE ADHESIVE BONDING MATERIAL SHALL BE AT LEAST CATEGORY 2.

OF 1.00 KSI OR GREATER IN DRY, CRACKED CONCRETE AT TEMPERATURE RANGE A. THE

THE ADHESIVE BONDING MATERIAL SHALL HAVE A MINIMUM CHARACTERISTIC BOND STRESS 4.

"CONCRETE NOTES" ON THIS SHEET.

THE ANCHORS SHALL CONFORM TO THE "REINFORCEMENT" REQUIREMENTS UNDER 3.

ANCHORS WAS 3.732 KSI.

THE COMPRESSIVE STRENGTH OF THE EXISTING BEDROCK IN THE DESIGN OF BONDING ROCK 2.

BONDED ANCHORS WAS 2.5 KSI.

THE COMPRESSIVE STRENGTH OF THE EXISTING CONCRETE IN THE DESIGN OF ADHESIVE 1.

ADHESIVE BONDED ANCHOR NOTES:

35.553#8 ANCHORS

WALL ROCK ANCHORS

#8 BARS - RETAINING

3.463#4 ANCHORS

INTERIOR WALL REPAIRS

#4 BARS - CULVERT

(KIPS)

TEST LOAD

PROOF

TO BE TESTED

ANCHORS

MIN. NUMBER OF

DESCRIPTION

ANCHOR

LOCATION

04.03

K:

Clough, Harbour & Associates, LLP

7/16/2026

SIGNATURE BLOCK: DRAWING TITLE:

S-04

REHABILITATION OF BRIDGE NO. 02150;

PLOTTED DATE:

V:\Projects\ANY\K6\070461.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0138_0252_S_04_Boring_Logs.dgn FILE NAME: 7485 LASTED SAVED BY:

R E

V

D A

T E

R E

V

IS

IO

N

D E

S C

R

IP

T

BORING LOGS

TRANSPORTATION

SJH CEP 04.04

K:

Clough, Harbour & Associates, LLP

(OW)

B-3 B-2

FND

CHD

WOOD BEAM RAIL

CONC. CURB

CONC. CURB

WOOD BEAM RAIL

CONC. CURB

CONC. CURB

WOOD BEAM RAIL

CP-4

CHAIN LINK FENCECHAIN LINK FENCE

S T R

U C

T U

R E

' X ' B

O X C

U L

V E

R T

WOOD BEAM RAIL

20'

88'

86'

90'

101+00 102+00 103+00

201+00 202+00 203+00

220+00 221+00

13+00 14+00

STONE WALL

STONE WALL

" R

C P

" R

C P

" R

C P

" R

C P

S A

N

E

N C

A S E

D

IN

C

O N

C

" S

A N . S

E W

E R

SHEET 1A

ROW MAP 138-180E

ROW MAP 138-180E SHEET 1A ROW MAP 138-180E SHEET 2A

" R

C P U

N D

E R

D R

A

IN

" S

A N

S A

N

" S

A N

" S

A N . S

E W

E R

E

N C

A S E

D

IN

C

O N

C

OHW

(2011)

C O

O R

D

IN

A T E G

R

ID

AD

O

N N

E C

T

IC

T

20' 40'

1" = 20'

HORIZONTAL SCALE

PROJECT TITLE: PROJECT NO.: DRAWING NO.:

SHEET NO.:

7/16/2026

SIGNATURE BLOCK: DRAWING TITLE:

S-05

REHABILITATION OF BRIDGE NO. 02150;

PLOTTED DATE:

V:\Projects\ANY\K6\070461.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0138_0252_S_05_Water_Handling.dgn FILE NAME: 7485 LASTED SAVED BY:

R E

V

D A

T E

R E

V

IS

IO

N

D E

S C

R

IP

T

DESIGNER/DRAFTER: CHECKED BY: WATER HANDLING PLAN

OF CONSTRUCTION AND

SUGGESTED SEQUENCE

TRANSPORTATION

100 YR

MIN. TOP EL. UPSTREAM = 107

COMPLETED MANUALLY (SEE CONSTRUCTION NOTE 5)

TEMPORARY WATER-HANDLING - COFFERDAM TO BE

(DOWNSTREAM)

MIN. TOP EL. = 86

-HANDLING - COFFERDAM

TEMPORARY WATER

BYPASS PIPE

42" DIA. TEMPORARY

FR

EE

M A

N

BRO

O

K

F R

E E

M A

B R

O O

K

ROUTE 15

ROUTE 15

NORTHBOUND

SOUTHBOUND

EXISTING BRIDGE NO. 02150 TO REMAIN

SEDIMENTATION CONTROL SYSTEM (TYP.)

PROPOSED SLOPE LIMITS (TYP.)

TEMP. STORM DRAINAGE BYPASS HOSE

(TYP.) (SEE SANITARY SEWER SUBSET)

SANITARY SEWER MAIN AND MANHOLE

REMOVE EXISTING ENDWALL

(SEE HIGHWAY SUBSET)

STORM DRAINAGE MANHOLE

(SEE HIGHWAY SUBSET)

STORM DRAINAGE PIPE (TYP.)

ACCESS ROAD

(SEE HIGHWAY SUBSET)

STORM DRAINAGE CATCH BASIN

HIGHWAY SUBSET)

ENDWALL (SEE

STATE/FEDERAL WETLANDS (TYP.)

LIMITS (MAPPED)

100-YEAR FLOODPLAIN

BYPASS HOSE

TEMPORARY STORM DRAINAGE

RUNOFF AS NECESSARY

PUMP STORM WATER

TEMPORARY DEWATERING BASIN (TYP.)

MIN. TOP EL. 100

HANDLING - COFFERDAM

TEMPORARY WATER-

CRUSHED STONE

OVER 12" DEPTH OF 2"

36" STANDARD RIPRAP

MATERIAL WASH-IN TO

NATURAL STREAMBED

WITH TOP EL. 88 FT

2.5 - 3.5 FT BOULDERS

INSTALL A LINE OF

TAKING LINE

CONSTRUCTION EASEMENT

LIMITS OF PROPOSED

FENCE

VISIBILITY

HIGH

FLOOD (CALCULATED)

EXISTING 100-YEAR

PUMP STORM WATER RUNOFF AS NECESSARY

UNNAMED WATERCOURSE 3

WETLAND C

WETLAND A

WETLAND B

UNNAMED

WATERCOURSE 2

(SEE SANITARY SEWER SUBSET)

RECONSTRUCT SANITARY SEWER MANHOLE

CLEAN INTERIOR OF EXISTING BOX CULVERT

CONCRETE RETAINING WALL NO 101

RETAINING SYSTEM AS NECESSARY (TYP.)

APPROX. 72 L.F. OF TEMPORARY EARTH

CRUSHED STONE

OVER 12" DEPTH OF 2"

36" STANDARD RIPRAP

RIPRAP SWALE

18" INTERMEDIATE

RIPRAP APRON

18" INTERMEDIATE

12" MODIFIED RIPRAP

LEDGE IN CHANNEL

AREA OF EXPOSED

LEGEND

EDGE OF WATER

ORDINARY HIGH WATER

STATE/FEDERAL WETLANDS

TEMPORARY WATER-HANDLING - COFFERDAM

(SEE CONSTRUCTION NOTE 6)

NON-DRIVEN TEMPORARY EARTH RETAINING SYSTEM

(APPROXIMATE LOCATION)

SEDIMENTATION CONTROL SYSTEM

FLOW

SECTION VIEW

(SEE TEMP. HYDRAULIC TABLE)

TEMP. WATER SURFACE ELEV.

PLASTIC SEAL LINER

MIN. TOP EL. DOWNSTREAM = 86

MIN. TOP EL. UPSTREAM = 107

TEMPORARY WATER-HANDLING - COFFERDAM

BYPASS PIPE

TEMPORARY

(SANDBAGS)

WATER-HANDLING - COFFERDAM CONCEPT

NOT TO SCALE

THROUGH THE WORK AREA.

MINIMIZES NEGATIVE IMPACTS AND SAFELY CONVEYS LARGER FLOWS

FLOWS, PROVIDED THAT THIS INCLUDES A CONTINGENCY PLAN, WHICH

CONSTRUCTION WATER HANDLING PLAN WITH LOWER PUMPING

WEATHER CONDITIONS, THE ENGINEER MAY APPROVE A

BASED UPON FIELD CONDITIONS, WORK DURATION, AND EXPECTED 6.

AREAS SHOWN ON THE WETLAND IMPACT SHEET OF THE PERMIT PLANS.

ALL CONSTRUCTION RELATED ACTIVITIES SHALL NOT EXCEED IMPACT 5.

ENGINEER FOR APPROVAL.

HANDLING SYSTEM SHALL BE SUBMITTED BY THE CONTRACTOR TO THE

SPECIFICALLY PROHIBITED. A MEANS AND METHOD FOR WATER

"HANDLING WATER TYPICAL SCHEMATICS" MAY BE UTILIZED UNLESS

ANY WATER HANDLING SCHEME DEPICTED WITHIN THE DEPARTMENT'S 4.

ENVIRONMENTAL PERMIT(S).

ACTIVITY AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE

CONSTRUCTION AREA, SHALL BE ABLE TO SUPPORT CONSTRUCTION

SAFELY CONVEY WATER FLOWS CONTINUOUSLY THROUGH THE

APPROVED SYSTEM THAT THE CONTRACTOR ELECTS TO USE WHICH WILL

TEMPORARY WATER HANDLING SYSTEM SHALL CONSIST OF AN 3.

(CALCUATLED) ELEVATION.

THE WETLAND LIMITS AND ABOVE THE EXISTING 100-YEAR FLOOD

TEMPORARY DEWATERING BASINS SHALL BE ESTABLISHED OUTSIDE OF 2.

WATER HANDLING SYSTEM AS REQUIRED DURING CONSTRUCTION.

THE CONTRACTOR SHALL MAINTAIN WATER THROUGH THE TEMPORARY 1.

LOW FLOW.

UNCONFINED INSTREAM WORK SHALL BE DONE DURING PERIODS OF -

MINIMIZED TO THE EXTENT POSSIBLE.

DISTURBED AREAS AND THE DURATION OF DISTURBANCE SHALL BE -

TO MINIMIZE TURBIDITY/SEDIMENT TRANSPORT DOWNSTREAM.

BEST MANAGEMENT PRACTICE SHALL BE UTILIZED WHEREVER POSSIBLE -

FOR TEMPORARY AND PERMANENT IMPACT.

DISTURBANCE SHALL BE LIMITED TO AREAS THAT HAVE BEEN APPROVED -

ALL UNCONFINED IN-WATER WORK SHALL BE MINOR IN NATURE.-

PROPOSED SCHEDULE FOR WORK OPERATIONS.-

UNCONFINED IN-WATER WORK WITH CONSIDERATION OF THE FOLLOWING:

THE DEPARTMENT WILL REVIEW AND MAY APPROVE THE METHODS OF 2.

THE CONDITION SHALL APPLY TO PROJECTS IN NON-COASTAL WATERS.

UNLESS OTHERWISE INCLUDED AS A SPECIAL PROVISION OF THE LICENSE,

RESTRICTED TO THE PERIOD FROM JUNE 1 TO SEPTEMBER 30, INCLUSIVE,

ANY UNCONFINED IN-STREAM WORK WITHIN THE WATERCOURSE SHALL BE 1.

UNDER THE ITEM "TEMPORARY EARTH RETAINING SYSTEM" (T.E.R.S.)

DRIVEN TEMPORARY EARTH RETAINING SYSTEM WILL BE PAID FOR

METHOD FOR SUPPORTING THE LIMITS OF EXCAVATION. NON-

CONTRACTOR IS RESPONSIBLE FOR DEVELOPING A MEANS AND

CULVERT AS NECESSARY TO FACILITATE THE WORK. THE

INSTALLED IN THE VICINITY OF THE EXISTING CONCRETE BOX

NON-DRIVEN TEMPORARY EARTH RETAINING SYSTEM MAY BE 6.

THROUGHOUT THE INTERIOR OF THE CULVERT.

THE BOX CULVERT TO PERFORM WORK AT THE INLET AND

METHODS FOR TRANSPORTING MATERIALS AND TOOLS THROUGH

CONTRACTOR SHALL BE REQUIRED TO PROVIDE MEANS AND 5.

INFORMATION.

SANITARY SEWER SUBSET DRAWING NO. SAN-03 FOR ADDITIONAL

CONNECTION TO EXISTING SANITARY SEWER MANHOLES. SEE

RECONSTRUCTION OF THE SANITARY SEWER ENCASEMENT AND

THE CONTRACTOR SHALL COORDINATE WITH THE TOWN DURING 4.

UNDER "HANDLING WATER".

COFFERDAM AND TEMPORARY BYPASS PIPE SHALL BE PAID FOR

WORK ASSOCIATED WITH THE TEMPORARY WATER-HANDLING-3.

FOR ADDITIONAL INFORMATION.

ITEM "WATER POLLUTION CONTROL". SEE SPECIAL PROVISIONS

DRAINAGE. WORK SHALL BE PAID FOR UNDER THE CONTRACT

CONSTRUCTION OPERATIONS WHILE MAINTAINING SURFACE

THE STORM WATER TO PREVENT WASHOUTS DURING

THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONTROLLING 2.

LIMITS NECESSARY TO PERFORM THE CONTRACT WORK.

THE CONTRACTOR IS RESPONSIBLE FOR ACTUAL LOCATION AND 1.

CONSTRUCTION NOTES:

SUGGESTED SEQUENCE OF CONSTRUCTION:

UNCONFINED IN-STREAM WORK BMP NOTES:

WATER HANDLING NOTES:

18" INTERMEDIATE RIPRAP

SCALE: 1"=20'

PLAN

EROSION CONTROL MATTING(CALCULATED)

EXISTING 100-YEAR FLOOD

100 YEAR FLOODPLAIN LIMITS (MAPPED)

SJH CEP

12" DEPTH OF 2" CRUSHED STONE

36" STANDARD RIPRAP OVER

OVER 12" DEPTH OF 2" CRUSHED STONE

WASH-IN TO 36" STANDARD RIPRAP

NATURAL STREAMBED MATERIAL

REMOVE E&S CONTROLS UPON FINAL STABILIZATION.14.

RESTORE SITE; PERFORM FINAL GRADING AND SEEDING.13.

REMOVE TEMPORARY WATER HANDLING.12.

REMOVE TEMPORARY EARTH RETAINING SYSTEM.11.

CONSTRUCT RIPRAP BASIN AND LINE OF BOULDERS.10.

CONSTRUCT CONCRETE RETAINING WALL.9.

INSTALL DRAINAGE R.C. PIPE, ENCASEMENT, AND ENDWALL.8.

SUGGEST SEQUENCE OF CONSTRUCTION NOTES).

NEW SANITARY SEWER (SEE DRAWING NO. SAN-03 FOR ADDITIONAL

INSTALL TEMPORARY SANITARY SEWER BYPASS SYSTEM AND INSTALL 7.

AND INVERT REPAIRS.

AND CURTAIN WALL SEALING REPAIRS; PERFORM CONCRETE SURFACE

CLEAN INTERIOR OF EXISTING BOX CULVERT; PERFORM CRACK SEALING 6.

INSTALL DRAINAGE MANHOLE.5.

INSTALL WATER HANDLING.4.

INSTALL TEMPORARY EARTH RETAINING SYSTEM (T.E.R.S.) AS NECESSARY.

CONSTRUCT PERMANENT ACCESS ROAD AND FRENCH MATTRESS; 3.

PERFORM CLEARING AND GRUBBING.2.

INSTALL EROSION AND SEDIMENTATION (E&S) CONTROLS.1.

84.6 FT

SURFACE ELEVATION DOWNSTREAM

2-YEAR EXISTING WATER

104.0 FT

SURFACE ELEVATION UPSTREAM

2-YEAR EXISTING WATER

84.9 FT

SURFACE ELEVATION DOWNSTREAM

2-YEAR TEMPORARY WATER

105.6 FT

SURFACE ELEVATION UPSTREAM

2-YEAR TEMPORARY WATER

55 CFS

= 2-YEAR FREQUENCY

TEMPORARY DESIGN DISCHARGE

GRAVITY FLOW BYPASS PIPE

5.2 CFS

= 4 x AVERAGE SPRING FLOW

TEMPORARY DESIGN DISCHARGE

LOW FLOW PUMPING

55 CFS2-YEAR FREQUENCY DISCHARGE

1.3 CFSAVERAGE SPRING FLOW

0.7 CFSAVERAGE DAILY FLOW

*TEMPORARY HYDRAULIC DATA

HIGH VISIBILITY FENCE

ENDANGERED SPECIES NOTE:

GREATER FROM APRIL 15 TO OCTOBER 31

OR REMOVAL OF TREES WITH 3" DBH OR

TRI-COLORED BAT - NO TRIMMING, CUTTING,

CHAIN LINK FENCE

12" MODIFIED RIPRAP

T.E.R.S.

NOT TO SCALE

PAYMENT FOR T.E.R.S.

MEASUREMENT OF

VERTICAL LIMITS

V A

R

IE

S

EXCAVATION

BOTTOM OF

OF GRADE

APPROX. TOP

T.E.R.S.

04.05

K:

Clough, Harbour & Associates, LLP

APPROXIMATE TOP OF ROADWAY AT GUTTER LINE

EXISTING CONCRETE HEADWALL

EXISTING CONCRETE BOX CULVERT

APPROX. EXIST. GRADE

REMOVE EXISTING SANITARY SEWER MAIN

OHW EL. 87.2

EL. 89.8

50-YEAR DESIGN

WINGWALL (TYP.)

EXISTING CONC.

WW2B

WW1B

SLOPED EMBANKMENT

MERRITT PARKWAY TIMBER GUIDE RAIL

50-YEAR EXISTING EL. 87.4

(CALCULATED) EL. 87.5

EXISTING 100-YEAR FLOOD

CONCRETE RETAINING WALL

HEADWALL AS REQUIRED (TYP.)

FOOTING, CUTOFF WALL, AND

TO BOX CULVERT, WINGWALLS,

PERFORM CONCRETE REPAIRS

APPROXIMATE FINISHED GRADE (RIPRAP BASIN)

FL = 89.50

APPROXIMATE FINISHED GRADE BEHIND WALL

INV. = 92.47

FOR STORM DRAINAGE

CONCRETE ENCASEMENT

(LEVEL)

EL. 94.9

EL. 94.9±

4' CHAIN LINK FENCE (HIGHWAY ITEM)

APPROXIMATE INV. EL. 93.7

INSTALL WEEP HOLE FILTER SYSTEM

SANITARY MANHOLE

REMOVE EXISTING

10'-0"

EL. 93.5±

CONCRETE LINER

4" THICK CAST-IN-PLACE

REPAIR CULVERT INVERT WITH

15" POLYVINYL CHLORIDE PIPE (SANITARY SEWER)

(SANITARY SEWER)

MANHOLE

APPROXIMATE INV. EL. 95.4

INSTALL WEEP HOLE FILTER SYSTEM

CORNER

JOINT

CONTRACTION

(TYP.)

RETAINING WALL

WEEPHOLE IN

EXISTING CONCRETE HEADWALL

EXISTING CONCRETE BOX CULVERT

WW1A

WW2A

EXISTING 15" DIA. SANITARY SEWER

APPROXIMATE TOP OF ROADWAY AT GUTTER LINE MERRITT PARKWAY TIMBER GUIDE RAIL

50-YEAR EXISTING EL. 108.4

CONCRETE ENCASEMENT AS REQUIRED

PERFORM SURFACE REPAIRS AT EXISTING

WINGWALL (TYP.)

EXISTING CONCRETE

SLOPED EMBANKMENT

50-YEAR DESIGN EL. 108.4

(TYP.)

EXISTING GRADE

APPROXIMATE

AS REQUIRED (TYP.)

CUTOFF WALL, AND HEADWALL

TO BOX CULVERT, WINGWALLS,

PERFORM CONCRETE REPAIRS

OHW EL. 106.9

FOR DETAILS)

(SEE DRAWING S-11

INVERT REPAIR

4" THICK CONCRETE

(CALCULATED) EL. 108.7

100-YEAR FLOOD ELEVEATION

PROPOSED INV. = 102.13

FRONT OF CULVERT INLET

MATERIAL (4" MIN.) IN

SUPPLEMENTAL STREAMBED

10'-0"

EXISTING CONCRETE PAD

2'-0"±

PROJECT TITLE: PROJECT NO.: DRAWING NO.:

SHEET NO.:

7/16/2026

SIGNATURE BLOCK: DRAWING TITLE:

S-06

REHABILITATION OF BRIDGE NO. 02150;

PLOTTED DATE:

V:\Projects\ANY\K6\070461.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0138_0252_S_06_Section_Elevations.dgn FILE NAME: 7485 LASTED SAVED BY:

R E

V

D A

T E

R E

V

IS

IO

N

D E

S C

R

IP

T

AND ELEVATIONS

LONGITUDINAL SECTION

TRANSPORTATION

3' SHDR. 11' 11' 20'

1' SHDR.

11'11'

3' SHDR.

14'

5' SHDR.

SOUTHBOUND

NORTHBOUND

4.8%

CLEAN INTERIOR OF EXISTING CONCRETE BOX CULVERT

CONCRETE BOX CULVERT (TO REMAIN)

201'-4" LF - EXISTING 10' WIDE X 8' HIGH

50-YEAR EXISTING EL. 87.4

(TYP.)

TIMBER GUIDE RAIL

MERRITT PARKWAY

LANE LANE

MEDIAN

GRASS LANE LANE

RAMP

EXIT

APPROXIMATE EXISTING SLOPE EMBANKMENT (TYP.)

APPROXIMATE EXISTING GRADE (TYP.)

ROUTE 15 ROUTE 15

OHW EL. 87.2

ON 12" DEPTH OF 2" CRUSHED STONE

LINE OF 2.5 - 3.5 FT ROUNDED BOULDERS

OHW EL. 106.9

(CALCULATED) EL. 108.7

100-YR FLOOD ELEVATION

50-YEAR EXISTING EL. 108.4

50-YEAR DESIGN EL. 108.4

50-YEAR DESIGN EL. 89.8

(TYP.)

FOOTINGS, CUTOFF WALLS, AND HEADWALLS, AS REQUIRED

BOTTOM SLAB, UNDERSIDE OF TOP SLAB, WINGWALLS,

PERFORM CONCRETE REPAIRS TO BOX CULVERT WALLS,

(RIPRAP BASIN)

APPROXIMATE FINISHED GRADE AT CENTERLINE OF CULVERT

(TO REMAIN) (TYP.)

EXISTING CONCRETE HEADWALL

RIPRAP OVER 12" DEPTH OF 2" CRUSHED STONE

NATURAL STREAMBED MATERIAL WASHED-IN TO 36" STANDARD

CONCRETE LINER

4" THICK CAST-IN-PLACE

REPAIR CULVERT INVERT WITH

EXISTING 100-YEAR FLOOD (CALCULATED) EL. 87.5

MATERIAL (4" MIN.)

SUPPLEMENTAL STREAMBED

POST-INSTALLED WEEP AND FILTER (TYP.)

APPROXIMATE LOCATION OF PROPOSED

OVER 12" DEPTH OF 2" CRUSHED STONE

WASHED-IN TO 36" STANDARD RIPRAP

NATURAL STREAMBED MATERIAL

8.5'±

LONGITUDINAL SECTION

SCALE: 1" = 20'

INLET ELEVATION

SCALE: 1/4"=1'-0"

OUTLET ELEVATION

SCALE: 1/4"=1'-0"

SCALE AS NOTED

CEP

NOTES:

SEE DRAWING NO. S-14 FOR CONCRETE SEALER LIMITS.5.

SEE DRAWING NO. S-13 FOR RETAINING WALL DETAILS.4.

SEE DRAWING NO. S-12 FOR RETAINING WALL PLAN AND ELEVATION.3.

SEE DRAWING NO. S-11 FOR CULVERT INVERT REPAIR DETAILS.3.

SEE DRAWING NO. S-08 THROUGH S-10 FOR CULVERT REPAIR DETAILS.2.

PROVISION "CLEAN EXISTING CULVERT - GREATER THAN 42" DIAMETER".

MEANS AND METHODS AS APPROVED BY THE ENGINEER. SEE SPECIAL

VEGETATION AND BIOLOGICAL GROWTH FROM WITHIN THE STRUCTURE USING

INCLUDE REMOVAL, COLLECTION AND DISPOSAL OF SEDIMENT, DEBRIS,

WITH CLEANING AND PREPARING CONCRETE SURFACES FOR REPAIRS, IS TO

GENERAL CLEANING OF EXISTING BOX CULVERT, THAT IS NOT ASSOCIATED 1.

SJH 04.06

K:

Clough, Harbour & Associates, LLP

201'-4"±

201'-4"±

201'-4"±

PROJECT TITLE: PROJECT NO.: DRAWING NO.:

SHEET NO.:

7/16/2026

SIGNATURE BLOCK: DRAWING TITLE:

S-07

REHABILITATION OF BRIDGE NO. 02150;

PLOTTED DATE:

V:\Projects\ANY\K6\070461.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0138_0252_S_07_Existing_Structure_Conditions.dgn FILE NAME: 7485 LASTED SAVED BY:

R E

V

D A

T E

R E

V

IS

IO

N

D E

S C

R

IP

T

CONDITIONS

EXISTING STRUCTURE

TRANSPORTATION

WW1B

6"L SPALL

WW2B

EXISTING SANITARY SEWER PIPE TO BE REMOVED AND REPLACED

UNDERMINING AT WINGWALL FOOTING

UNDERMINING AT CUTOFF WALL

EXISTING CUTOFF WALL EXPOSED FL x FH

UNDERMINING AT CONCRETE ENCASEMENT

EXISTING SANITARY MANHOLE TO BE REMOVED AND REPLACED 30"L x 8"H x 2"D SPALL

1'x1' HOLLOW AREA

REMAIN

MANHOLE TO

EXISTING SANITARY

OHW EL. 87.2

50-YEAR EXISTING EL. 87.4

100-YEAR FLOOD ELEVATION (CALCULATED) EL. 87.5

10'

GRADE (TYP.)

APPROX. EXISTING

UTILITY PIPE 16'L x 3'W x UP TO 1'H

SPALL IN UTILITY ENCASEMENT ABOVE

ACTIVE LEAKAGE

CONCRETE WITH

UP TO 6"x6" SOFT

WW2A

WW1A

"D SPALL4

3" DIA. x

(TYP.)

EXISTING GRADE

APPROXIMATE

10'

OHW EL. 106.9

50-YEAR EXISTING EL. 108.4

(CALCULATED) EL. 108.7

100-YEAR FLOOD ELEVATION

FACE OF SANITARY SEWER ENCASEMENT

SEVERE SCALE AND ABRASION AT OUTSIDE

EXISTING CONCRETE PAD

FLOW

FLOW

WALL NO. 2

WALL NO. 1

FLOW

FOR SANITARY SEWER

EXISTING CONCRETE ENCASEMENT

BOTTOM SLAB

TOP SLAB

TOP SLAB

BOTTOM SLAB

JOINT 1

POUR

JOINT 13

POUR

JOINT 7

CONSTRUCTION

JOINT 1

POUR

JOINT 7

CONSTRUCTION

JOINT 13

POUR

JOINT 13

POUR

JOINT 7

CONSTRUCTION

JOINT 1

POUR

SPALLS (A.L.)

(3) UP TO 1'H x 9"W x 1"D

24"W x 15"H x UP TO 4"D SPALL

27"W x 7"H x 2"D SPALL (A.L.)

38"W x 9"H x 3"D SPALL (A.L.)

SPALL (A.L.)

15"W x 8"H x 3.5"D

WALL NO. 2

SCALE: 1" = 10'

TOP SLAB (REFLECTED VIEW)

SCALE: 1" = 10'

WALL NO. 1

JOINT 4

POUR

JOINT 10

POUR

JOINT 4

POUR

JOINT 10

POUR

JOINT 10

POUR

JOINT 4

POUR

(A.L.)

x 1"D SPALL x UP TO 3'W

UP TO 3'H

36"H x 4"W x 1"D SPALL (A.L.)

SPALL (A.L.)

7.5'W x 14"H x 6"D

SPALL (A.L.)

45"W x 8"H x 5"D

22"H x 2"W x 1"D SP

24"H x 2"W x 1"D SPALL

20"H x 6"W x 6"D SPALL (A.L.)

20"W x 4"H x 5"D SPALL (A.L.)

SPALL (A.L.)

27"H x 4.5"W x 1.5"D

3'L SHALLOW SPALL

(MOISTURE PRESENT)

26"H x 6"W x 1"D SPALL

SPALLS

(3) 8" DIA. x UP TO 1"D

SCALE: 1" = 10'

HEAVY SCALE

OUTLET

OUTLET

OUTLETINTLET

INTLET

INTLET

SPALL (A.L.)

24"H x 6"W x 1"D

24"H x 12"W HOLLOW AREA

(A.L.)

(2) 12"L x 1.5"D OPEN JOINTS

COVER

SHALLOW

6"H x 6"W x 5"D SPALL (A.L.)

(A.L.)

OPEN JOINT

(A.L.)

OPEN JOINT

HEAVY SCALE

(A.L.)

OPEN JOINT

(3) OPEN JOINTS (A.L.)

(PAST LEAKAGE)

26"H x 4"W x 1"D SPALL

OF PAST LEAKAGE

WITH EVIDENCE

RANDOM HOLES

CONCRETE (A.L.)

12"H x 24"W SOFT

= EFFLORESCENCE PRESENT*

= FULL WIDTHFW

= FULL LENGTHFL

= FULL HEIGHTFH

= EXPOSED REBARER

= ACTIVE LEAKAGEA.L.

SPALL WITH EXPOSED REBAR

SPALL AREA

HOLLOW, OR SCALE, AREA

LIMITS OF DEMOLITION

W A

L L

N O

W A

L L

N O

TOP SLAB

BOTTOM SLAB

LOOKING UPSTREAM

BOX CULVERT DIAGRAM

NOTES:

UP TO FULL WIDTH

AREAS OF SCALE NOTED ON WW2B FOOTING AND WINGWALL UP TO 6'L x -

LENGTH x FULL WIDTH.

- AREAS OF MEDIUM TO HEAVY SCALE ALONG THE CULVERT INVERT FOR FULL

FULL LENGTH x 3" HIGH x 1.5" DEEP.

- SCALE ALONG BOTTOM OF SANITARY SEWER CONCRETE ENCASEMENT FOR

PRESENT AT RANDOM AREAS OF CRACKING.

AREAS OF MAP CRACKING IN TOP SLAB UNDERSIDE THROUGHOUT. MOISTURE

- HAIRLINE CRACKS, SOME OPEN TO 1/16"W, ARE PRESENT THROUGHOUT.

AND SEDIMENT ACCUMULATION.

- SPALLS AND SCALING IN BOTTOM OF WALL NO. 2 EXHIBIT WATER LEAKAGE

INCLUDE, BUT ARE NOT LIMITED TO:

ADDITIONAL CONCRETE DEFICIENCIES NOTED IN THE INSPECTION REPORT 5.

BROUGHT TO THE ATTENTION OF THE ENGINEER.

ANY CRACKS OVER 0.02" WIDE IDENTIFIED DURING CONSTRUCTION SHALL BE

BASED ON FIELD OBSERVATIONS, NO STRUCTURAL CRACKS WERE OBSERVED. 4.

REPAIR DETAILS.

DRAWING NO. S-11 "CULVERT REPAIR DETAILS IV" FOR CONCRETE INVERT

EXISTING CONCRETE BOX CULVERT BOTTOM SLAB NOT SHOWN. SEE 3.

INSTALLED WEEP HOLE WITH FILTER DETAIL.

SEE DRAWING NOS. S-08 THRU S-11 FOR CULVERT REPAIR DETAILS AND POST-2.

PERFORMED ONLY AFTER LIMITS ARE DETERMINED BY THE ENGINEER.

PERFORMS REQUIRED REPAIR WORK. CULVERT REPAIRS SHALL BE

ENGINEER AND THE CONTRACTOR IN THE FIELD BEFORE CONTRACTOR

ONLY. ACTUAL LIMITS AND TYPES OF REPAIRS SHALL BE IDENTIFIED BY THE

INFORMATION SHOWN ON THIS SHEET IS FOR INFORMATIONAL PURPOSES

09/11/2024 AND FIELD VERIFICATION BY CHA ON 10/24/2024. THE

APPROXIMATE BASED ON THE CTDOT BRIDGE INSPECTION REPORT DATED

LOCATIONS AND LIMITS OF DETERIORATED CONCRETE SHOWN ARE 1.

CONCRETE DETERIORATION LEGEND

OUTLET ELEVATION

SCALE: 1/4"=1'-0"

INLET ELEVATION

SCALE: 1/4"=1'-0"

SCALE AS NOTED

SEWER

ENCASED

EXISTING

NOT TO SCALE

THE EXISTING SCOUR HOLE.

DOWNSTREAM OF CULVERT WITHIN

IN OUTLET ELEVATION ARE LOCATED

NOTE: WATER ELEVATIONS SHOWN

SJH CEP 04.07

K:

Clough, Harbour & Associates, LLP

7/16/2026

SIGNATURE BLOCK: DRAWING TITLE:

S-08

REHABILITATION OF BRIDGE NO. 02150;

PLOTTED DATE:

V:\Projects\ANY\K6\070461.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0138_0252_S_08_Culvert_Repair_Details_1.dgn FILE NAME: 7485 LASTED SAVED BY:

R E

V

D A

T E

R E

V

IS

IO

N

D E

S C

R

IP

T

CULVERT REPAIR DETAILS I

TRANSPORTATION

L V

E R

T W

A L

L

C U

L V

E R

T W

A L

L

DETAILS - INJECTION CRACK SEALING FOR ACTIVE LEAKAGE

NOT TO SCALE

EXISTING STEEL REINFORCEMENT

CONCRETE BOX CULVERT

INSIDE FACE OF EXISTING REINFORCED

FLEXIBLE RESIN CRACK INJECTION

ALTERNATE EACH SIDE OF CRACK

MANUFACTURER RECOMMENDATIONS.

DRILL HOLE AT 45° TO THE SURFACE PER

6"±

MOISTURE/LEAKAGE

CRACK WITH ACTIVE

MOISTURE/LEAKAGE

CRACK WITH ACTIVE

EACH SIDE OF CRACK

RECOMMENDATIONS. ALTERNATE

DRILL HOLE PER MANUFACTURER

OUTSIDE FACE OF BOX CULVERT

EXPANDED RESIN ALONG CRACK AT

(TYP.)

INJECTION PORT

(TYP.)

INJECTION PORT

REINFORCED CONCRETE WALL

INSIDE FACE OF EXISTING

INJECTION PORT IS REMOVED

REPAIR HOLE WITH MORTAR AFTER

REINFORCED CONCRETE BOX CULVERT

OUTSIDE FACE OF EXISTING BACKFILL

PLAN SECTION ELEVATION

DETAILS - INJECTION CURTAIN WALL SEALING FOR ACTIVE LEAKAGE

NOT TO SCALE

EXISTING STEEL REINFORCEMENT

CONCRETE BOX CULVERT

INSIDE FACE OF EXISTING REINFORCED

FLEXIBLE RESIN CRACK INJECTION

ALTERNATE EACH SIDE OF CRACK

PER MANUFACTURER RECOMMENDATIONS.

DRILL HOLE PERPENDICULAR TO THE SURFACE

MOISTURE/LEAKAGE

CRACK WITH ACTIVE

(TYP.)

MOISTURE/LEAKAGE

CRACK WITH ACTIVE

MANUFACTURER RECOMMENDATIONS

SPACING AND DRILL HOLES PER

OUTSIDE FACE OF BOX CULVERT

EXPANDED RESIN ALONG

(TYP.)

INJECTION PORT

(TYP.)

INJECTION PORT

REINFORCED CONCRETE WALL

INSIDE FACE OF EXISTING

INJECTION PORT IS REMOVED

REPAIR HOLE WITH MORTAR AFTER

BOX CULVERT

REINFORCED CONCRETE

OUTSIDE FACE OF EXISTING

BACKFILL

PLAN SECTION ELEVATION

S P

A C

IN

G

P E

R M

A N

U F

A C

T U

R E

E C

O M

M E

N D

A T

IO

S

6"± FROM CRACK

APPROXIMATELY

LOCATE PORT

NOTES:

1. INJECTION CRACK SEALING IS INTENDED TO BE USED AT ISOLATED

CRACKS. INJECTION FOR CURTAIN WALL SEALING IS TO BE USED WHERE

MULTIPLE CRACKS MAKE IT DIFFICULT TO SEAL CRACKS INDIVIDUALLY.

SEE REPAIR SEQUENCE FOR ADDITIONAL INFORMATION.

2.LOCATE REINFORCING BEFORE DRILLING TO AVOID DRILLING THROUGH

REINFORCING BARS.

FOR "FLEXIBLE RESIN INJECTION - CURTAIN WALL SEALING"

DASHED LINE IS THE PERIMETER OF THE AREA TO BE MEASURED

BY THE TECHINCAL REPRESENTATIVE

ENGINEER AND AS RECOMMENDED

INJECTION AS ORDERED BY THE

SEAL SURFACE OF CRACK PRIOR TO

CURTAIN WALL INJECTION

OVER THE SPECIFIED AREA (TYP.)

THEN PERFORM CURTAIN WALL INJECTION

INDIVIDUAL CRACKS 0.01" WIDE OR MORE,

PRIOR TO CURTAIN WALL INJECTING, INJECT

REPAIR SEQUENCE FOR STRUCTURE CONCRETE:

1. INJECTION CRACK SEALING:

PERFORM THIS WORK TO PREVENT LEAKAGE THROUGH INDIVIDUAL CRACKS WIDER

THAN 0.01". IF NECESSARY, SEAL EXPOSED SURFACE OF CRACKS WIDER THAN 0.01"

PRIOR TO INJECTION CRACK SEALING TO KEEP THE FLEXIBLE RESIN FROM SPILLING

OUT AS DIRECTED BY THE MANUFACTURERS TECHNICAL REPRESENTATIVE. INSTALL

INJECTION PORTS AT SURACE OF CONCRETE AND SEAL CRACKS PER THE

MANUFACTURER SPECIFICATIONS. ALLOW SUFFICIENT TIME FOR SEALANT TO SET

PRIOR TO INJECTING ADJACENT CRACKS AREAS.

2. INJECTION CURTAIN WALL SEALING:

AFTER INJECTION CRACK SEALING OF INDIVIDUAL CRACKS, PERFORM WORK FOR

INJECTION CURTAIN WALL SEALING. INSTALL INJECTION PORTS AT SURACE OF

CONCRETE AND SEAL OUTSIDE (BURIED) FACE OF WALL PER THE MANUFACTURER

SPECIFICATIONS UNTIL LEAKAGE STOPS FLOWING THROUGH CRACKS AND SPALLS.

ALLOW SUFFICIENT TIME FOR SEALANT TO SET PRIOR TO INJECTING ADJACENT

WALL AREAS, AND PRIOR TO REPAIRING CONCRETE.

3. SURFACE CONCRETE REPAIRS:

SEE DRAWING NOS. S-09 AND S-10 FOR DETAILS AND NOTES.

4. CONCRETE INVERT REPAIR:

SEE DRAWING NO. S-11 FOR DETAILS AND NOTES.

5. PENETRATING SEALER PROTECTIVE COMPOUND:

AFTER CRACK SEALING AND CONCRETE SURFACE REPAIRS ARE COMPLETE, APPLY

PENETRATING SEALER PROTECTIVE COMPOUND OVER MINOR CRACKS (LESS THAN

0.01" WIDE) AND THEN AGAIN OVER THE BROADER EXPOSED CONCRETE SURFACES

INCLUDING THE CRACKS PER THE MANUFACTURER SPECIFICATIONS.

6. WEEP HOLE WITH FILTER:

SEE DRAWING NO. S-11 FOR DETAIL AND NOTES.

NOTE: INSPECTION REPORTS SHOW PAST AND PRESENT LEAKAGE AT ONE

CULVERT WALL OVER AN APPROXIMATE HEIGHT OF 3' ABOVE THE INVERT

AND FOR AN APPROXIMATE LENGTH OF 100'. ACTUAL CURTAIN WALL

LIMITS WILL BE DETERMINED IN THE FIELD USING TEST HOLES AND OTHER

METHODS RECOMMENDED BY THE CURTAIN WALL CONTRACTOR AND

APPROVED BY THE ENGINEER.

SCALE AS NOTED

SJH CEP

CRACK REPAIR NOTES:

1. CONCRETE CRACKS THAT ARE DETERMINED TO BE OF NO STRUCTURAL CONCERN

AND SHOW NO SIGNS OF WATER LEAKING FROM THE CRACK AND ARE LESS THAN

0.02" WIDE SHALL BE SEALED WITH A PENETRATING SEALER AND SHALL NOT BE

REPAIRED BY INJECTION SEALING. THIS WORK SHALL BE INCLUDED FOR PAYMENT

UNDER ITEM #0819002A - "PENETRATING SEALER PROTECTIVE COMPOUND" AND

WILL NOT BE MEASURED SEPARATELY.

2. CRACKS WHICH ARE 0.01" WIDE OR LARGER ARE TO BE REPAIRED WITH FLEXIBLE

RESIN INJECTION SEALING AND SHALL BE PAID FOR UNDER ITEM #0601955A -

"FLEXIBLE RESIN INJECTION CRACK SEALING".

3. INJECTION CRACK REPAIR AND/OR CURTAIN WALL SEALING TO BE PERFORMED AT

CRACKS, CONSTRUCTION JOINTS AND SPALLS WHERE ACTIVE MOISTURE AND/OR

LEAKAGE IS PRESENT INSIDE THE BOX CULVERT. REPAIR CONCRETE SHALL NOT BE

PLACED IN AREAS OF DETERIORATED CONCRETE WHERE MOISTURE AND/OR

LEAKAGE IS PRESENT UNTIL THE FLEXIBLE RESIN INJECTION SEALANT HAS BEEN

INJECTED AND LEAKAGE STOPS TO ALLOW FOR A DRY WORKING ENVIRONMENT.

4. ALL WORK, TOOLS AND MATERIALS ASSOCIATED WITH CURTAIN WALL INJECTION

SHALL BE PAID FOR UNDER ITEM #0601956A - "FLEXIBLE RESIN INJECTION CURTAIN

WALL SEALING.

04.08

K:

Clough, Harbour & Associates, LLP

7/16/2026

SIGNATURE BLOCK: DRAWING TITLE:

S-09

REHABILITATION OF BRIDGE NO. 02150;

PLOTTED DATE:

V:\Projects\ANY\K6\070461.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0138_0252_S_09_S_10_Culvert_Repair_Details_2_3.dgn FILE NAME: 7485 LASTED SAVED BY:

R E

V

D A

T E

R E

V

IS

IO

N

D E

S C

R

IP

T

CULVERT REPAIR DETAILS II

TRANSPORTATION

1. MECHANICAL SPLICES ARE AN ACCEPTABLE

ALTERNATE IF APPROVED BY THE ENGINEER.

REINFORCEMENT SPLICE NOTE:

MAINTAIN EXISTING CONCRETE COVER (TYP.)

NEW REINFORCING BAR SIZE TO MATCH EXISTING.

REPAIR CONCRETE DETAILS

(TYP.)

EXISTING REINFORCEMENT

SURFACE

CONCRETE

EXISTING

REPAIR CONCRETE

WIRE AS REQUIRED

WITH ANCHORS AND TIE

TO SOUND CONCRETE

REINFORCING BARS AND

SECURED TO EXISTING

REINFORCEMENT*

WELDED WIRE

NOT TO SCALE

MORE LOSS OF DIAMETER

EXISTING BAR WITH 25% OR

16.0#7

16.0#6

16.0#5

16.0#4

LENGTH (IN)

MIN. SPLICE

BAR SIZE

SPLICE LENGTHS

OF 1" BEHIND REINFORCING BARS

REMOVE CONCRETE TO A MINIMUM

NOT TO SCALE

REINFORCEMENT SPLICE DETAIL

PERIMETER OF REPAIR AREA

SAWCUT 1" DEEP AROUND

EXISTING REINFORCEMENT (TYP.)

REINFORCEMENT

SECURE WELDED WIRE

CONCRETE AS REQUIRED TO

INSTALL ANCHORS INTO SOUND

(TYP.)

GALVANIC ANODE

PROPOSED EMBEDDED

SUPPLEMENTAL WELDED WIRE REINFORCEMENT*

REPAIR CONCRETE

BARS ARE AVAILABLE TO SECURE THE

REINFORCEMENT WHEN INSUFFICIENT

INSTALL 4"x4" - W2.9xW2.9 WELDED WIRE

SECTION - OVERHEAD SURFACE REPAIR

SECTION - VERTICAL SURFACE REPAIR

1" DEEP SAWCUT

SEE "EMBEDDED GALVANIC ANODE DETAILS" SHEET

PROPOSED EMBEDDED GALVANIC ANODE (TYP.)

2" MIN. COVER

AT ANODES (TYP.)

(TYP.)

REINFORCEMENT

EXISTING REPAIR CONCRETE

WIRE AS REQUIRED

WITH ANCHORS AND TIE

TO SOUND CONCRETE

REINFORCING BARS AND

SECURED TO EXISTING

REINFORCEMENT*

WELDED WIRE

ANODE DETAILS" SHEET

SEE "EMBEDDED GALVANIC

GALVANIC ANODE (TYP.)

PROPOSED EMBEDDED

AT ANODES (TYP.)

2" MIN. COVER

1" MIN. COVER

AT ANODES (TYP.)

EXISTING CONCRETE SURFACE

SECTION - VERTICAL SURFACE REPAIR WITH BUMP-OUT

REPAIR CONCRETE

45° BEVEL

(TYP.)

REINFORCEMENT

EXISTING

REMOVE CONCRETE TO

A MINIMUM OF 1" BEHIND

REINFORCING BARS

EXISTING CONCRETE SURFACE

WIRE AS REQUIRED

WITH ANCHORS AND TIE

TO SOUND CONCRETE

REINFORCING BARS AND

SECURED TO EXISTING

REINFORCEMENT*

WELDED WIRE

ANODE DETAILS" SHEET

SEE "EMBEDDED GALVANIC

GALVANIC ANODE (TYP.)

PROPOSED EMBEDDED

AT ANODES

2" MIN. COVER

1" MIN. COVER

1" MIN. COVER

1" MIN. COVER

AT ANODES (TYP.)

1" MIN. COVER

AT ANODES (TYP.)

1" MIN.

COVER

AT ANODES

(TYP.)

SECTION - DEPTH OF REMOVAL REQUIREMENTS

(TYP.)

REINFORCEMENT

EXISTING

1" DEEP SAWCUT (TYP.)

GALVANIC ANODE (TYP.)

PROPOSED EMBEDDED

REMOVE CONCRETE TO

A MINIMUM OF 1" BEHIND

REINFORCING BARS

EXISTING CONCRETE SURFACE

REMOVE CONCRETE

TO A MINIMUM OF 1"

BEHIND PROPOSED

GALVANIC ANODE

REMOVE CONCRETE TO

A MINIMUM OF 1" BEHIND

REINFORCING BARSAS REQUIRED

REMOVE SOUND CONCRETE

REMOVE DETERIORATED CONC.

(TYP.)

REMOVAL AND PAY LIMIT LINES

APPROX. LIMITS OF CONCRETE

SOUND CONCRETE TO 1" DEPTH

SAW CUT EDGES OF PATCH IN

REQUIRED*

REINFORCEMENT AS

WELDED WIRE

(TYP.)

REINFORCEMENT

EXISTING

BY THE ENGINEER

CONCRETE AS DETERMINED

LIMITS OF UNSOUND

(TYP.)

GALVANIC ANODE

PROPOSED EMBEDDED

ELEVATION

6" MIN.

NOTE 12)

REPAIR CONCRETE

(SEE CULVERT BARS

AND REINFORCING

* REINFORCEMENT

WELDED WIRE

2" MIN. COVER OVER

2" MIN. COVER OVER

WELDED WIRE

REINFORCEMENT* AND

REINFORCING BARS

(SEE CULVERT REPAIR

CONCRETE NOTE 13)

2" MIN. COVER OVER

WELDED WIRE

REINFORCEMENT* AND

REINFORCING BARS

JRH / JLPSJH

LIMITS OF

SECTION LOSS

SEE TABLE FOR MINIMUM SPLICE LENGTH.

THE BARS SHALL BE WIRED TOGETHER FOR

THE FULL LENGTH OF THE SPLICE (TYP.)

1. PRIOR TO REMOVAL OF EXISTING CONCRETE, THE CONTRACTOR SHALL PROVIDE ACCESS TO THE

ANTICIPATED WORK AREAS SO THAT THE INSPECTOR AND THE CONTRACTOR MAY TOGETHER

DETERMINE AND DELINEATE THE EXACT LIMITS AND LOCATIONS OF THE WORK. THE METHOD USED

TO DELINEATE AREAS OF CONCRETE TO BE REPAIRED SHALL NOT PERMANENTLY MARK THE

CONCRETE, LEAVE ANY RESIDUE AFTER REMOVAL, OR REQUIRE HARSH CHEMICALS TO REMOVE.

2. IF THE REMOVAL DEPTH EXCEEDS MORE THAN 1

2" BEHIND MAIN REINFORCEMENT, THE

CONTRACTOR SHALL CEASE REMOVAL OPERATIONS AND NOTIFY THE ENGINEER IMMEDIATELY.

3. REPAIR DETAILS APPLY TO SPALLED, SCALED, AND HOLLOW AREAS WHERE REQUIRED AND NOTED

ON DRAWINGS AND AS DIRECTED BY THE ENGINEER.

4. SURFACE PREPARATION, PROPORTIONING AND MIXING OF MATERIALS, APPLICATION OF

MATERIALS, AND REPAIR PROCEDURES SHALL BE IN ACCORDANCE WITH STANDARD

SPECIFICATION SECTION 6.01 "CONCRETE FOR STRUCTURES".

5. WELDED WIRE REINFORCEMENT USED IN REPAIR AREAS WILL NOT BE MEASURED FOR PAYMENT BUT

WILL BE INCLUDED IN THE COST UNDER ITEM #0601072 - "SURFACE REPAIR CONCRETE".

6. CORRODED, MISSING OR BROKEN REINFORCING STEEL SHALL BE REPLACED AND WILL BE

MEASURED FOR PAYMENT UNDER ITEM #0602000 - "DEFORMED STEEL BARS". BARS TO BE LEFT IN

PLACE THAT ARE DAMAGED BY THE CONTRACTOR SHALL BE REPLACED TO THE SATISFACTION OF

THE ENGINEER AND AT THE EXPENSE OF THE CONTRACTOR.

7. BONDING COMPOUND SHALL NOT BE USED PRIOR TO OR DURING THE PLACEMENT OF THE REPAIR

CONCRETE MATERIAL.

8. REPAIR CONCRETE MATERIAL SHALL BE CLASS PCC04483, OR APPROVED EQUAL.

9. THE SURFACE OF CONCRETE REPAIR AREAS SHALL MATCH THE SURFACE PROFILE OF EXISTING

CONCRETE SURFACES UNLESS NOTED OTHERWISE.

10. AREAS DISTURBED BY CONSTRUCTION SHALL BE RESTORED TO THEIR ORIGINAL CONDITION UNLESS

OTHERWISE NOTED OR AS DIRECTED BY THE ENGINEER AT NO ADDITIONAL COST TO CTDOT.

11. PENETRATING SEALER TO BE PAID FOR UNDER THE ITEM #0819002A - "PENETRATING SEALER

PROTECTIVE COMPOUND", SEE SPECIAL PROVISIONS.

12. IF CONCRETE COVER OVER EXISTING REINFORCING AND WELDED WIRE REINFORCEMENT IS LESS

THAN 1" PROVIDE A BUMP-OUT TO ENSURE A MINIMUM COVER OF 2" AND ADJUST THE DEPTH OF

SAW CUT TO AVOID CUTTING INTO BARS.

CULVERT REPAIR CONCRETE NOTES:

REPAIR DETAIL APPLIES TO AREAS OF REINFORCED CONCRETE WHERE THERE IS EXPOSED REINFORCING

AFTER REMOVAL OF LOOSE AND DETERIORATED CONCRETE.

1. REMOVE DETERIORATED MATERIAL TO SOUND CONCRETE LEAVING NO OFFSET OR ABRUPT

CHANGES IN CONTOUR. CONCRETE SHALL BE REMOVED TO 1" BELOW THE EXISTING

REINFORCING. REMOVAL OF SOUND CONCRETE MAY BE REQUIRED.

2. CONTRACTOR SHALL USE FIFTEEN (15) POUND HAMMERS MAXIMUM OR OTHER METHODS

ACCEPTED BY THE ENGINEER.

3. PRIOR TO APPLYING REPAIR CONCRETE MATERIAL, CLEAN EXISTING REINFORCING STEEL AND

CONCRETE (NEWLY EXPOSED) BY SANDBLASTING, SEE SPECIFICATIONS. MISSING OR

DETERIORATED REINFORCING STEEL SHALL BE REPLACED AS SHOWN IN DETAIL AND AS DIRECTED

BY THE ENGINEER.

4. AFTER SANDBLASTING AND CLEANING ALL DUST AND DEBRIS, INSTALL GALVANIC ANODES AND

WELDED WIRE REINFORCEMENT AS REQUIRED. AFTER SANDBLASTING AND BEFORE PLACING

REPAIR CONCRETE, DUST AND DEBRIS SHALL BE REMOVED COMPLETELY.

5. ENSURE THAT CONCRETE SUBSTRATE IS WETTED (SSD) BEFORE PLACING REPAIR CONCRETE.

6. FORM, WHEN APPLICABLE, AND PLACE REPAIR CONCRETE. CONCRETE FOR OVERHEAD REPAIRS

SHALL BE PUMPED INTO THE EXCAVATED SPACE, USING VENT TUBES AS NECESSARY TO ENSURE

THAT NO AIR IS TRAPPED IN THE PATCH.

7. IMMEDIATELY FOLLOWING CURING AND STRIPPING OF FORMS, THE NEWLY PLACED REPAIR

CONCRETE SURFACE WITHIN REPAIR AREAS SHALL BE HAMMER-TAPPED FOR SOUNDNESS. SOUND

PATCH AREAS SHALL RECEIVE A GROUT CLEAN-DOWN FINISH. ADJACENT AREAS SHALL NOT

RECEIVE SUCH A FINISH.

8. AFTER REPAIRS HAVE BEEN ACCEPTED, APPLY PENETRATING SEALER TO THE REPAIRED AREAS AS

WELL AS CONTIGUOUS AREAS TO THE REPAIR OR AS DIRECTED BY THE ENGINEER.

9. MINOR SPALLS AND SCALING LESS THAN 1/2" DEEP WITH NO REINFORCING EXPOSED AND WITH

SOUND CONCRETE REMAINING MAY BE SEALED WITH PENETRATING SEALER WITH NO REPAIR

REQUIRED UNLESS DIRECTED OTHERWISE BY THE ENGINEER.

CULVERT REPAIR CONCRETE PROCEDURE:

*REQUIREMENTS FOR WELDED WIRE REINFORCEMENT:

1.REQUIRED WHEN INSUFFICIENT BARS ARE AVAILABLE TO SECURE THE REPAIR CONCRETE.

A. FOR VERTICAL APPLICATIONS, REPAIR CONCRETE SHALL BE SECURED BY DEFORMED

STEEL BARS AT A 12" SPACING OR LESS, OR BY WELDED WIRE REINFORCEMENT

SECURED ON A 6" GRID BY TIE WIRES AND APPROVED ANCHORS INTO SOUND

CONCRETE.

B. FOR OVERHEAD APPLICATIONS WHERE BAR SPACING EXCEEDS 6", ADD WELDED

WIRE REINFORCEMENT SECURED TO SOUND CONCRETE AND REINFORCING ON A

6" GRID.

2.ACCEPTABLE ALTERNATIVES TO WELDED WIRE REINFORCEMENT TO SUPPLEMENT

REINFORCING INCLUDE NON-METALLIC MESH AND #3 FRP OR GALVANIZED STEEL

BARS.

NOTE: REMOVAL DETAILS SHOWN FOR VERTICAL

SURFACE, SIMILAR FOR OVERHEAD REMOVAL

(SEE REPAIR CONCRETE NOTE 13)

NOT TO SCALE

04.09

K:

Clough, Harbour & Associates, LLP

7/16/2026

SIGNATURE BLOCK: DRAWING TITLE:

S-10

REHABILITATION OF BRIDGE NO. 02150;

PLOTTED DATE:

V:\Projects\ANY\K6\070461.000\16_Custom_Client\CT Connect\Bridge\Contract_Plans\BR_CP_0138_0252_S_09_S_10_Culvert_Repair_Details_2_3.dgn FILE NAME: 7485 LASTED SAVED BY:

R E

V

D A

T E

R E

V

IS

IO

N

D E

S C

R

IP

T

CULVERT REPAIR DETAILS III

TRANSPORTATION

NOTE: IF EXISTING REINFORCING SPACING IS DIFFERENT THAN INDICATED

IN THIS TABLE, CONTACT ENGINEER FOR MAXIMUM ANODE SPACING.

SECTION - CULVERT WALL REPAIR TYPE I

SCALE: 1

2" = 1'-0"

ANCHOR

AND BOND

DRILL HOLE

(LENGH VARIES)

#4 BENT BAR

EXISTING STEEL REINFORCEMENT

BOX CULVERT SIDE WALL

INTERIOR FACE OF EXISTING

JOINT

CONSTRUCTION

EXISTING

M

IN

S P

L

IC

E

12"

L

IM

IT

S

O F

D E

T E

R

IO

R A

T E

D C

O N

C R

E T

E

L

IM

IT

S

O F

R E

P A

IR

C

O N

C R

E T

E

S E

E N

O T

E

OF REPAIR AREA

AROUND PERIMETER

SOUND CONCRETE

1" DEEP SAWCUT IN

(SEE REPAIR NOTE 1)

ANODE (TYP.)

EMBEDDED GALV.

DETAIL - CULVERT WALL REPAIR TYPE IA

SCALE: 1

2" = 1'-0"

#4 BAR (LENGTH VARIES)

EXISTING CONSTRUCTION JOINT

EXTENDS TO THIS SURFACE

SURFACE IF DETERIORATION

CONCRETE ALONG SLOPED

1" DEEP SAWCUT IN SOUND

#4 BAR (LENGTH VARIES)

(SEE REPAIR NOTE 1)

REMOVAL

LIMITS OF CONCRETE

AND HAUNCH)

(BOTTOM SLAB

CULVERT INVERT

ENGINEER

DIRECTED BY THE

CORRODED BAR AS

REMOVE PORTION OF

(SEE REPAIR NOTE 1)

REMOVE DETERIORATED CONCRETE

REQUIRED (SEE REPAIR NOTE 1)

REMOVE SOUND CONCRETE AS

PLAN - NARROW STRIP

DEEP"2

SAW CUT EDGES OF PATCH

IN EMBEDDING MORTAR

TYPE I ANODE INSTALLED

OF SAWCUT LINE (TYP.)

SOUND CONCRETE OUTSIDE

*CONCRETE COVER REQUIREMENTS:

1" MAY BE REDUCED TO

4" IF NEAT

PATCHING MORTAR IS USED

REINFORCING BARS (TYP.)

BLAST CLEAN EXPOSED

EMBEDDING MORTAR

SURFACE REPAIR CONCRETE

2" COVER

AT ANODE

1" *MIN.

DEEP"2

SAW CUT EDGES OF PATCH

TO REINFORCING BAR

TIE ELECTRODE FROM ANODE

SURFACE REPAIR CONCRETE

REINFORCING BARS (TYP.)

BLAST CLEAN EXPOSED

IN EMBEDDING MORTAR

TYPE I ANODE INSTALLED

EMBEDDING MORTAR

TO REINFORCING BAR (TYP.)

TIE ELECTRODE FROM ANODE

DEEP"2

PATCH

SAW CUT EDGES OF

OF SAWCUT LINE (TYP.)

SOUND CONCRETE OUTSIDE

REINFORCING BARS (TYP.)

BLAST CLEAN EXPOSED

SURFACE REPAIR CONCRETE

TYPE I ANODE

DEEP"2

SAW CUT EDGES OF PATCH

STEEL TIE WIRE

SURFACE REPAIR CONCRETE

REINFORCING BARS (TYP.)

BLAST CLEAN EXPOSED

IN EMBEDDING MORTAR

SLIM ANODE INSTALLED

GALVANIZED FUSION T2

EMBEDDING MORTAR

PARTIALLY FILL WITH

IN CONCRETE AND

" DIA. HOLE 8

DRILL 1

COPPER LEAD WIRE

SEALED BUTTON CONNECTOR

TYPE I ANODE

FUSION T2 SLIM ANODE

FUSION T2 SLIM ANODE

SEALED BUTTON CONNECTOR

STEEL TIE WIRE

COPPER LEAD WIRE

EMBEDDING MORTAR

ANODE INSTALLED IN

GALVANIZED FUSION T2 SLIM

EMBEDDING MORTAR

PARTIALLY FILL WITH

CONCRETE AND

" DIA. HOLE IN 8

DRILL 1

PLAN - SMALL PATCH

DEEP"2

PATCH

SAW CUT EDGES OF

LINE (TYP.)

OUTSIDE OF SAWCUT

SOUND CONCRETE

BARS (TYP.)

REINFORCING

EXPOSED

BLAST CLEAN

CONCRETE

SURFACE REPAIR

CONNECTOR

SEALED BUTTON

STEEL TIE WIRE

COPPER LEAD WIRE

IN EMBEDDING MORTAR

SLIM ANODE INSTALLED

GALVANIZED FUSION T2

EMBEDDING MORTAR

PARTIALLY FILL WITH

IN CONCRETE AND

" DIA. HOLE 8

DRILL 1

FUSION T2 SLIM ANODE

NOT TO SCALE

NOT TO SCALE

SECTION - NARROW STRIP

PLAN - LARGE RECTANGULAR PATCH

DEEP"2

SAW CUT EDGES OF PATCH

IN EMBEDDING MORTAR

TYPE I ANODE INSTALLED

OF SAWCUT LINE (TYP.)

SOUND CONCRETE OUTSIDE

REINFORCING BARS (TYP.)

BLAST CLEAN EXPOSED

RESISTIVETY > 15,000 OHM-CM

ANODES WHEN REPAIR CONCRETE

PLACE EMBEDDING MORTAR AT

CONCRETE

SURFACE REPAIR

TO REINFORCING BAR (TYP.)

TIE ELECTRODE FROM ANODE

SECTION - LARGE RECTANGULAR PATCH

2" COVER

AT ANODE

1" *MIN.

DEEP"2

SAW CUT EDGES OF PATCH

TO REINFORCING BAR

TIE ELECTRODE FROM ANODE

SURFACE REPAIR CONCRETE

(TYP.)

BLAST CLEAN EXPOSED REINFORCING BARS

EMBEDDING MORTAR

TYPE I ANODE INSTALLED IN

RESISTIVITY > 15,000 OHM-CM

ANODES WHEN REPAIR CONCRETE

PLACE EMBEDDING MORTAR AT

NOT TO SCALE

NOT TO SCALE

INVERT (HAUNCH)

EXIST. CULVERT

NOT TO SCALE

1" MIN.

12"

REMOVAL BELOW TOP OF HAUNCH

ON DWG. S-09

SPLICE DETAIL

SEE REINFORCEMENT

2"

MAX.

SPLICE BAR)

(1" MIN. BEYOND

SOUND CONCRETE

REMOVE TO

28"28"#4 @24" & #4 @18"WINGWALL

#4@14" & #4@12"BACK FACE

19"25"

#4@14" & #4@12"FRONT FACE

CULVERT HEADWALL

#4 @18" & #7 @4"BOTTOM FACE

13"17"

#4 @18" & #5 @6"TOP FACE

CULVERT TOP SLAB

#4 @18" & #6 @6"OUTSIDE FACE

15"20"

#4 @18" & #5 @12"INSIDE FACE

CULVERT WALL

TYPE 2TYPE 1

MAX. ANODE SPACING

LONGITUDINAL / TRANSVERSE

EXISTING REINFORCING

ELEMENT

MAXIMUM ANODE SPACING TABLE

JRH / JLPSJH

1. SEE "CONCRETE REPAIR DETAILS I" SHEET FOR ADDITIONAL INFORMATION.

2. STEEL REINFORCEMENT FOR SURFACE CONCRETE REPAIR TYPE I AND TYPE IA

TO BE UNCOATED BLACK BAR. SEE DRAWING NO. S-03 "CONCRETE NOTES"

FOR ADDITIONAL INFORMATION.

CONCRETE REPAIR NOTES:

1. ANODES NOTED AS "TYPE 1" ARE TYPICALLY EMBEDDED WITHIN WET

CONCRETE REPAIRS. WHEN THE RESISTIVITY OF THE REPAIR CONCRETE IS

GREATER THAN 15 K-OHM-CM, EMBEDDING MORTAR IS REQUIRED.

"TYPE 2" DESCRIBES ANODES THAT ARE TYPICALLY PLACED IN DRILLED

HOLES IN HARDENED CONCRETE WITH EMBEDDING MORTAR PLACED IN

THE HOLE BEFORE THE ANODE IS PLACED. GALVASHIELD FUSION T2 SLIM

ANODES ARE A PRE-QUALIFIED TYPE 2 ANODE LISTED IN THE SPECIAL

PROVISION. FUSION ANODES ARE DETAILED IN THESE PLANS TO BE

INSTALLED WITH EMBEDDING MORTAR IN…