Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51
Closed Solicitation Posted
This opportunity was awarded. See the award notice from .
- Solicitation number
- 36C25525R0097
- Agency
-
Veterans Integrated Service Network 15
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 238220 Plumbing, Heating, and Air-Conditioning Contractors
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 is procuring construction services to replace various air handling units and chillers in Buildings 1, 24, and 51 at the Jefferson Barracks VA Medical Center in St. Louis, Missouri. The project involves replacing four specific HVAC units: two 7,000 CFM Trane air handling units in Building 1, one 10,000 CFM unit in Building 24, and one 12,800 CFM unit in Building 51, along with associated mechanical systems, steam traps, and electrical connections. Contractors must demonstrate experience in hospital construction environments and provide temporary cooling solutions during construction, particularly for critical areas like the morgue. The evaluation will use a best value trade-off process focusing on five factors: prime contractor construction experience, project execution, key personnel experience, safety plan, and past performance, with non-price factors weighted significantly more than price. The solicitation has been amended multiple times, with the current proposal deadline set for August 12, 2025, at 10:00 AM Central Time.
This procurement is designated as a 100% set-aside for certified Service-Disabled Veteran-Owned Small Businesses (SDVOSB) under NAICS code 238220 for Plumbing, Heating, and Air-Conditioning Contractors. The contract value is estimated between $5-10 million with a performance period of 270 calendar days following the Notice to Proceed. No incumbent contractor is identified in the documentation, suggesting this is either a new requirement or the incumbent information was not disclosed. The project includes comprehensive asbestos abatement requirements and infection control measures appropriate for an active healthcare facility, with work requiring coordination with ongoing hospital operations. Performance will occur at the Jefferson Barracks VA Medical Center, with contractors required to maintain appropriate security clearances and coordinate with VA facility management throughout the construction period.
Notice text
4 versions
Update #4 · Latest ·
RFI #65. Can the morgue be shut down during construction? Providing temp cooling for that area to the degree required will be between difficult and impossible. If the shutdown is not possible, can you please provide clarification on how temp cooling for that area is to be accomplished so we can properly price this scope? Including the size and placement of temp unit/units that will achieve the appropriate temperatures?
We don't use the JB morgue too often. Most patients that pass at JB go directly to the funeral home. The morgue is only used with the veteran does not have funeral home plans in place. The backup plan is the patient will be transported to JC morgue until funeral home arrangements are made.
RFI #70. Sizing the temp units based on a preconstruction TAB report will not enable us to provide the proper pricing for our scope of work. This information needs to be available for us to include the correct pricing at the time of our bid not after we are awarded the project. Otherwise, it becomes and guess which usually drives the price up.
AHU-01-1 Trane CSHX0035F3 (OR EQUIVALENT)Â (with electric heat), 7000 CFM Nominal, 5in Max ESP, Â 460V 3 Phase, MCA 179.8A, MOP 200A. Note: The contractor shall coordinate required electrical connection with the VA.
AHU-01-2 Trane CSHX0035F3 (OR EQUIVALENT)Â (with electric heat), 7000 CFM Nominal, 5in Max ESP, Â 460V 3 Phase, MCA 179.8A, MOP 200A. Note: The contractor shall coordinate required electrical connection with the VA.
AHU-24-1 Trane CSH0050F4 (OR EQUIVALENT)Â (with electric heat), 10000 CFM nominal, 5in Max ESP, 460V 3 Phase, MCA 232.2A, MOP 250A. Note: 460V unavailable at building 24. The contractor shall coordinate required electrical connection with the VA..
AHU-51-1 Trane RSHX0080 (OR EQUIVALENT)Â (with electric heat), 12,800 CFM nominal, 4.8in Max ESP, 460V 3 Phase, MCA 329A, MOP 400A Note: 460V unavailable at building 24. The contractor shall coordinate required electrical connection with the VA. If alternate is used, unit must have adequate capacity for DOAS application.
The needs of the station and the temporary units are based on availability. The information provided is to ensure the contractor understands the situation and the need to ensure a maintenance team/ plan is made available by the subcontractor to avoid any issues with the temporary cooling during construction.
Power can be provided to the temporary units as follows:
Building 1: Feed the temporary AHU from 208V panel EMDP . Provide temporary transformer and connections as necessary.
Building 24: Feed the temporary AHU from 208V External Wireway . Provide temporary transformer and connections as necessary.
Building 51: Feed the temporary AHU from 208V switchboard MSB-51A . Provide temporary transformer and connections as necessary.
RFI #72, 73 & 108. We need the design team to provide the proper information on the steam trap sizing and placement. Including the traps at the units and any drip traps that might be required. This is a complicated issue that would need to be designed .by the design team .not the installing contractor. Drip traps are generally based on the pounds per hour capacity of the main. This information is not available to us.
Steam trap to be placed at the unit steam coil / humidifier.
Anticipated piping lengths do not require steam drip traps. Contractor to verify and report the piping lengths from steam mains.
STEAM TRAP SCHEDULE BASIS OF DESIGN
Â
MANUFACTURER
TRAP NO.
TRAP SIZE
MAX PRESSURE (PSI)
STEAM CONDENSATE LOAD
CONSTRUCTION
AHU-1-01 HEATING COIL
SPIRAX SARCO
FT450-4.5
1"
15
217
STAINLESS STEEL
AHU-1-02 HEATING COIL
SPIRAX SARCO
FT450-4.5
1"
15
276
STAINLESS STEEL
AHU-24-01 HEATING COIL
SPIRAX SARCO
FT450-4.5
1-1/2"
15
466
STAINLESS STEEL
AHU-51-01 HUMIDIFER
SPIRAX SARCO
FT450-4.5
3/4"
15
23
STAINLESS STEEL
NOTE: STEAM TRAP CONNECTION SHALL BE RAISED FACE FLANGE.
Additional Information regarding RFIs 97 and 100:
3C06 As builts and site photos:
Condensate pumps in basement mechanical room GC18:
Location of the Steam supply and condensate return riser main connection to horizontal main.
No as-built of the steam condensate pump is available in Building 1, Room GC18. The steam riser main is 2-1/2 and the condensate return riser main is 2 based on as-built drawings available as noted above.
Update #3 ·
Amendment A00002 to Solicitation 36C25522R0079 Install New Boilers Project 589A7-18-302
Update #2 ·
Amendment A00002 to Solicitation 36C25522R0097 FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 s Project 657-23-101JB
Update #1 ·
Project No. 657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51
Files
Show all 22
Notice history
| Notice | Type | Posted |
|---|---|---|
| Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 | Award Notice | |
| This notice | Solicitation | |
| Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 | Pre-Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| Z2DA--FY27 EHRM | 657-21-702JC EHRM Training And Administrative Space Construction - St Louis John Cochran | VA Technology Acquisition Center | Service-Disabled Veteran-Owned Small Business | |
| Z1DA--Modernize Damen (Bldg. 1) Elevators Construction 537-24-101 | Veterans Integrated Service Network 12 | Service-Disabled Veteran-Owned Small Business | |
| Z2DA--657-27-103JB, FCA Replace Building 51 Roof, JB | Veterans Integrated Service Network 15 | Service-Disabled Veteran-Owned Small Business | |
| Z2NZ--Turn Key Chiller Equipment (Purchase and Install) | Veterans Integrated Service Network 16 | Service-Disabled Veteran-Owned Small Business | |
| CON | Z1DA | replace or chillers | 580-23-105 | solicitation | Veterans Integrated Service Network 16 | Service-Disabled Veteran-Owned Small Business |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity