36C25525R0097 0002.docx

DOCX document 21 KB Posted

Attached to
Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51
Solicitation number
36C25525R0097
Issued by

About this file

This document is an Amendment (A00002) to a Department of Veterans Affairs solicitation for replacing air handling units and chillers in Buildings 1, 24, and 51 at the VA Network Contracting Office in Leavenworth, Kansas. The amendment provides clarifications to potential contractors, including specific details about temporary mobile cooling for the morgue, rental air handling unit (AHU) specifications, and steam trap requirements. Key technical requirements include providing a temporary mobile cooler during morgue HVAC replacement, using specific Trane rental AHUs or equivalent units with detailed electrical and capacity specifications, and installing steam traps at various heating coils and humidifiers.

The solicitation (36C25525R0097) remains on schedule with proposals due on 7/28/2025 at 10:00 AM Central Time. The project involves replacing HVAC equipment across multiple buildings, with contractors required to coordinate electrical connections, verify piping lengths, and seek VA approval for equipment alternatives. The amendment includes attachments such as specification sheets for HVAC insulation, steam traps, and Trane rental services, providing additional technical guidance for potential bidders. No security guard is deemed necessary for this project, and the VA emphasizes the importance of acknowledging all amendments to avoid potential offer rejection.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE

7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer) 07-10-2025

657-23-101JB

36C255 Department of Veterans Affairs Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway Leavenworth

KS

66048 36C255 Department of Veterans Affairs Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway Leavenworth

KS

66048 To all Offerors/Bidders

36C25525R0097

X X X X The purpose of this amendment is to publish additional clarifications from the questions that were published in amendment 0001.

The due date for proposals remains 7/28/2025 at 10:00 AM Central Time.

Failure to acknowledge any and all Amendments issued pursuant to this solicitation may be cause for rejection of the offer.

Jennifer Hill Contracting Officer NCO 15

CONTINUATION PAGE

1. RFI #65. Can the morgue be shut down during construction? Providing temp cooling for that area to the degree required will be between difficult and impossible. If the shutdown is not possible, can you please provide clarification on how temp cooling for that area is to be accomplished so we can properly price this scope? Including the size and placement of temp unit/units that will achieve the appropriate temperatures?

Contractor to provide temporary mobile cooler during downtime of the Morgue. Temporary mobile cooler can be a box truck with cooler; to be parked in the building 1 Dock area for the 2-3 weeks it takes to replace the Morgue HVAC. This way the VA does not have to go on diversion.

1. RFI #70. Sizing the temp units based on a preconstruction TAB report will not enable us to provide the proper pricing for our scope of work. This information needs to be available for us to include the correct pricing at the time of our bid…not after we are awarded the project. Otherwise, it becomes and guess which usually drives the price up.

For:

Rental AHUs listed are Trane units. It is the A/E’s understanding that the site personal has had issues with the Trane specific maintenance crews in the area. Ensure the rental company for the AHUs have their own maintenance personal to service temporary units. Contractor shall seek approval from the VA COR and site engineering for usage of Trane rental / temporary AHUs. Equivalent alternatives are acceptable to A/E with A/E review and approval.

· AHU-01-1 – Trane CSHX0035F3 (OR EQUIVALENT) (with electric heat), 7000 CFM Nominal, 5in Max ESP, 460V 3 Phase, MCA 179.8A, MOP 200A. Note: The contractor shall coordinate required electrical connection with the VA.

· AHU-01-2 – Trane CSHX0035F3 (OR EQUIVALENT) (with electric heat), 7000 CFM Nominal, 5in Max ESP, 460V 3 Phase, MCA 179.8A, MOP 200A. Note: The contractor shall coordinate required electrical connection with the VA.

· AHU-24-1 – Trane CSH0050F4 (OR EQUIVALENT) (with electric heat), 10000 CFM nominal, 5in Max ESP, 460V 3 Phase, MCA 232.2A, MOP 250A. Note: 460V unavailable at building 24. The contractor shall coordinate required electrical connection with the VA.

· AHU-51-1 – Trane RSHX0080 (OR EQUIVALENT) (with electric heat), 12,800 CFM nominal, 4.8in Max ESP, 460V 3 Phase, MCA 329A, MOP 400A Note: 460V unavailable at building 24. The contractor shall coordinate required electrical connection with the VA. If alternate is used, unit must have adequate capacity for DOAS application.

1. RFI #72, 73 & 108. We need the design team to provide the proper information on the steam trap sizing and placement. Including the traps at the units and any drip traps that might be required. This is a complicated issue that would need to be designed….by the design team….not the installing contractor. Drip traps are generally based on the pounds per hour capacity of the main. This information is not available to us.

Steam trap to be placed at the unit steam coil / humidifier.

Anticipated piping lengths do not require steam drip traps. Contractor to verify and report the piping lengths from steam mains.

STEAM TRAP SCHEDULE BASIS OF DESIGN

MANUFACTURER
TRAP NO.
TRAP SIZE
MAX PRESSURE (PSI)
Steam Condensate Load
AHU-1-01 HEATING COIL
SPIRAX SARCO
FT-15
1"
15
217
AHU-1-02 HEATING COIL
SPIRAX SARCO
FT-15
1-1/4"
15
276
AHU-24-01 HEATING COIL
SPIRAX SARCO
FT-15
1-1/4"
15
466
AHU-51-01 HUMIDIFER
SPIRAX SARCO
FT-15
3/4"
15
23

1. RFI #96. Thank you for giving us the spec section number. But can you provide the actual information contained in that spec section? That section is not in the documents.

Spec sheet attached.

1. RFI #97 & RFI#100. Can you provide the as-built drawing? Or a screenshot like you did in the answer to #98. We cannot determine the size of the piping without removing insulation. Is the removal of insulation allowed in the site visits?

This will be answered in a future amendment

1. Is an unarmed security guard necessary?

This is not necessary for this project.

List of Attachments:

1. 23 01 11

2. Spirax-Sarco FT-15 to FT-200 Traps and Repair Parts

3. Trane Rental Services

See attached document: ssc-cat_spirax-sarco-ft-traps.

See attached document: TEMP-PRC001A-EN_06162024.

See attached document: 230711 - HVAC AND BOILER PLANT INSULATION.

Amendment A00002 to Solicitation 36C25522R0097 –FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 s – Project 657-23-101JB